Active - 30mA
Safety RCD Fused Spur Operating Instructions
The PowerBreaker Single Gang
RCD Fused Spur Unit has been
designed for storage and use
between -5°C and +40°C, and at an
altitude of no greater than 2000m
above sea level. Care must be
taken not to subject the unit to
misuse, such as
abnormal pollution by smoke,
chemical or flammable fumes, salt
laden spray, prolonged
periods of high humidity or other
abnormal conditions.
ains
M
upply
Green/Yellow
Green/Yellow
IMPORTANT:
OF SUPPLY AND LOAD
S
Brown
r Red
o
Blue
r Black
o
Blue or Black
Brown
or Red
Load
NOTE POSITION
INSTALLATION.
Note: Metal back box should be
earthed.
Install RCD spur and connect
wires as shown in diagram.
To fit the load/equipment cable
remove blanking plug in lower
plate. The load cable can now be
passed through hole and wired
according to diagram. Any bare
earth conductors must be sleeved
with green/yellow
sleeving.
Note: Clamp is reversable to cover
wide range of cable diameters.
PLEASE CARRY OUT THIS SIMPLE
TEST PROCEDURE AFTER
INSTALLATION.
1. Press Blue ON button.
2. Window indicator will
illuminate Red.
3. Press Grey TEST button.
4. Red window indicator and
illumination will disappear. This
means that the RCD has tripped
successfully.*
5. To reset – press Blue ON button
and use as normal spur.
Fit BS1362 fuse in accordance
with equipment manufacturers’
specification. Remove this RCD
from circuit before performing
any high voltage insulation tests.
*If indicator fails to work, test
fuse, if unit still fails to work do
not use and return to place of
purchase.
IMPORTANT –
FOR YOUR PROTECTION.
Electricity can be dangerous and
the use of an RCD should not be
regarded as a substitute for
basic electrical safety
precautions.
Always switch off from supply
when working on equipment.
This device will protect against
live and neutral leakage faults
to earth, it will not protect
against electric shock due to
contact with both conductors,
short circuits between live and
neutral, or a fault in the wiring
supplying this device. Should
your PowerBreaker Safety RCD
Fused Spur Unit repeatedly
trip with an appliance
connected or fail to trip when
tested, in accordance with the
instructions, return to place of
purchase.
Note: This is an active device and will need resetting in the event of power loss.
To reset - Press the Blue ON button.
Please keep these instructions safe for future reference