GreenBrook ACPHF270, ACPHF118, ACPHF258, ACPHF136, ACPHF158 Installation Instructions

...
Installation Instructions
or IP65 Non-corrosive Fluorescent Luminaires
f
Model Numbers: ACPHF118, ACPHF136, ACPHF158,
CPHF170
A
CPHF218
,
A
ACPHFLV158, ACPHFLV258
CPHF236
,
A
CPHF258
,
A
CPHF270
,
A
INSTALLATION & OPERATION
Do not drill the body for mounting purposes.
Drilling the body will invalidate the warranty, ONLY use the fixing
ethods provided. Please ensure that the rated voltage and
m frequency of the luminaire is compatible with the supply.
ixing Procedure:
F
This luminaire should only be mounted by means of the surface
,
fixing clips or suspension loops. Only luminaires bearing the mark symbol are suitable for mounting on combustible surfaces.
. The fixing centre points for this luminaire are located on the
1
mounting bracket. Choose a suitable location and fix the mounting brackets, using the wall plugs, screws and washers provided.
Fixing Centres
Important Safety Instructions
Please read these instructions carefully before installation and keep safe for future reference.
This unit should be installed by a competent person and in accordance with the current IEE Wiring Regulations.
If in doubt, consult a qualified electrician.
Always turn off the supply before commencing work.
This appliance must be earthed.
All luminaires are complete with electronic ballast.
S pecification:
Description
18W 18W 36W 36W 58W 58W 70W 70W
Single Twin Single Twin Single Twin Single Twin
Length
A (mm)
665 475 4
665 475 4 1,270 900 8 1,270 900 8 1,586 965 10 1,586 965 10 1,880 1035 12 1,880 1035 12
Fixing Centres
B (mm) Nominal
Clips
Qty
If suspended the supplied suspension clips must be used with a suitable cable suspension system, capable of bearing the weight of the luminaire. The luminaire can also be wall mounted.
Note: The bracket position can be adjusted to give a minimum and maximum fixing centre measurement.
Max
Ceiling/Surface
Mounting
Min
Wall/Surface
Mounting
Suspension
Mounting Clips
Suspension
Mounting
102mm
98mm
102mm
B
A
Operating Conditions:
These Luminaires are suitable for a temperature range of to -15°C to 30°C.
2. Before fitting the luminaire body to the mounting brackets, fit the toggle clips to the body.
3. Fit the luminaire body to the mounting brackets.
4. Insert the mains cable through the gland then tighten the lock
nut to the luminaire body, making sure there is sufficient cable to reach the terminal block.
Mains Cable
Lock Nut
. Fix the lamp holders into the tray.
5
6. Attach the gear tray safety cable - this stops the gear tray from
falling, leaving both hands free.
7. Connect supply to the terminal block as illustrated, making sure the cable is secure with no bare wires showing, also ensure correct polarity.
Note: Any additional power feed cables should be retained in such a way to prevent contact with the ballast.
11. Close the diffuser by fastening all the toggle clips securely.
A
B
C
12. Switch on the mains power to test.
Complete Assembly
MAINTENANCE
. Regular cleaning of the luminaire, especially diffusers and
1
replacement of lamp(s) are recommended to ensure maximum efficiency. When cleaning use a soft cotton cloth. Do not use chemical solvents.
2. In the case of tube failure, switch off the power of the luminaire and wait for the tube to cool completely. Replacement is a reverse of steps 8, 9 and 10 of these instructions. Always replace with the correct tube for the luminaire. Please ensure the old lamp is carefully disposed of, it may be subject to regulations by the Local Authority or Health and Safety Executive.
N (Neutral)
L (Live)
(Earth)
8. Fully attach the gear tray, making sure the clips of the gear tray fastening mechanism are fully located and secured.
9. Fit the correct size and wattage tubes (not supplied).
TECHNICAL INFORMATION
ACPHF Rated voltage: 230V AC 50Hz ACPHFLV Rated voltage: 110V AC 50Hz IP Rating: IP65 Construction: Polycarbonate body &
Diffuser
Temperature Range: -15°C to 30°C Fluorescent Tube Type: T8 Ballast Type: HF
Note: These diagrams are for illustration only,
and may vary slightly from actual product.
GUARANTEE
Your KingShield IP65 Fluorescent Bulkhead is
guaranteed for 12 months from the date of purchase.
This is in addition to your statutory rights.
10. Fit the diffuser to the body.
PLEASE KEEP THESE
INSTRUCTIONS SAFE
FOR FUTURE REFERENCE
WEST ROAD . HARLOW ESSEX . CM20 2BG . UK
sales@greenbrook.co.uk
W W W.G RE E N BR OO K. CO .U K
Issue no: 703877
Loading...