![](/html/a6/a6e9/a6e9381ff76bd29b127b5427e3fb303f85a72e63e1ab32a7684cad8bb659c184/bg1.png)
INSTALLATION AND OPERATION
FOR:
AH – 1000 & 1500 Series
Table of Contents
..… 1
… 2
…… 3
Operation .. 6
7
9
s …………. 12
……….. 15
nance …………… 17
………….. 18
VS.10.13
21
22
23
1
![](/html/a6/a6e9/a6e9381ff76bd29b127b5427e3fb303f85a72e63e1ab32a7684cad8bb659c184/bg2.png)
1. Equipment provided
: Locate all equipment provided with your order. The following
make sure to look at your packing slips and purchase orders
to determine exactly what is included in your system.
Control Panel only (for STS units only)
STS (Split Tank System) Box
Governing humidity sensor
Installation and Maintenance Manual
Location of the humidifier
the location shown by the Design Engineer in the Project drawings. The following
guidelines should be adhered to:
The DTA should be placed in
) feet up stream and downstream with no obstructions, branch take offs or
If a vertical section of duct is chosen make sure to slightly angle the DTA
that all condensate will pitch back to the header tube.
rule applies for obstructions as stated previously.
The Generator should be located in close proximity to the DTA. Locations
ld not be located further than 1
For the STS systems the STS Box should be located as near as possible to
the receiving air duct and DTA. The Control Panel for STS systems may be
located as far away as 40 ft. (please consult with your local Rep or Factory if
er distances are desired)
The controlling humidity sensor, if it is a duct mounted sensor, should be
located in the return air duct as long as it is a dedicated return to the same
then the controlling sensor should be located
a wall mounted humidity sensor.
Service access is very important. Make sure that the Generator unit is
located with adequate clearance around the unit to service it.
The DTA should also be located with good accessibility.
straight section of duct work with at
servicing. If the humidifier has a common retur
in the space being humidified
equipment may be provided –
a. Generator Con
b.
c.
d.
e.
f.
g.
2. Humidifier location:
a.
(2
bends.
b.
upwards so
c.
shou
DTA.
d.
- including hose cuff(s)
(DTA)
including 4 gal. storage tank
, Air flow switch, Hi-limit Switch
and all its components
a
0 ft of equivalent pipin
is critical. Verify
least two
The same
long
e.
zone
is
via
f.
18”
all four sides of the unit.
g.
n
A minimum of
2
![](/html/a6/a6e9/a6e9381ff76bd29b127b5427e3fb303f85a72e63e1ab32a7684cad8bb659c184/bg3.png)
h.
The RO Water system will see the most maintenance as filters need to be
replaced annually. Mount the system on a wall where clear access is
If a High Limit Stat is included, it
Flow Switch should be mounted on the supply side (positive pressure)
I) Generator and DTA Location and Piping:
the Generator and DTA within 1
using the STS system the same rule applies.
installed LEVEL! VERY IMPORTANT!
When installing the DTA make sure it is level or pitching back slightly toward
the supply pipe. Fasten all holes on the DTA flange to the bottom of th
Make sure there are no obstructions
downstream of the DTA for at least 3
Sealant can be used on the flange if desired for complete seal.
Once you have located the Generator in a clear
hose cuffs and begin installing pipe between the Generator and the DTA.
Follow the project plans for piping size but verify that they adhere to the
3000 Series should utilize 4”ID or greater supply pip
1000 Series should utilize
When piping try to avoid creating
the piping. If you cannot avoid doing so then
from such trap locations.
3/8”id pipe/tubing and there should be at least a 3” long nipple of ½” size off
down to create enough “head” to drain the line.
e the drain line to an appropriate drain location. Again be sure not to trap
water. If necessary employ a condensate pump/drain to elevate the drain water
and evacuate it during drain cycles.
Determine whether the system you are installing is a
system (please note that the
designates what type of application, supply side or return side, your system
is. If any questions call the Factory Representative).
If the system is a supply si
feed from a take off up stream of the DTA location (consult your Submittal
drawings for more specific information).
’ ft of equivalent piping distance from
Make sure the STS tank is
and accessible location use the
water “traps” or low points in
Drain line size must be a minimum of
de installation then you must pipe in a supply air
accessible.
i.
of the DTA.
j. The Air
INSTALLATION:
should be located at least
.
’ ft. downstream
A. Locate
each other.
B. When
C.
D.
E.
F.
-
-
-
CAUTION:
the trap pointed
Pip
0
, bends, or branches
’ft in either direction.
utilize 4”ID or greater supply piping
3”ID or greater supply piping
be
(see Fig. 1 )
e duct.
ing.
.
-drain
G.
humidifier schedule column
H.
3
![](/html/a6/a6e9/a6e9381ff76bd29b127b5427e3fb303f85a72e63e1ab32a7684cad8bb659c184/bg4.png)
CAUTION: For supply air locations there must be at least .075” static
static pressure then a return air location may be required.
If you have a return side installation no supply air feed is needed.
When installing the STS Box be sure to leave adequate service
must have ‘pull’ room for the tank to be removed if necessary. The cover for
the STS Box is a ‘Zero’ clearance cover. However standard space
requirements are at least 1.5x the width of the STS Box of space is needed in
II
) RO System Location and Piping:
mountable with simply two screws and can be hung as self supporting. Follow
respective connections. All connections are simple quick connects. It is
recommended that a shut off valve be placed in line after tapping the domestic
water line for the RO System supply.
quipment. This will be the right side as you face the system. The
supply side will consist of Black ¼” tubing.
Locate the Yellow drain line, and place in an appropriate area for
HUMIDIFICATION SEASON IS MONTHS AWAY.
proximity to the RO System.
Make sure to open the valve at the top of the storage tank.
Once installed, allow the system to run for approximately 15
minutes to flush completely. Make sure there are no leaks, parts
can come loose in shipping. Hand tightening may be necessary.
The RO System will run until all the humidifier supply lines and
torage tank are filled and charged to the pressure of the building.
This may take several hours to happen.
WATER SUPPLY TO THE RO SYSTEM.
filling the clear water filter housings on the RO System.
e at the supply feed location. If there is not enough
Water system. These systems are wall
for connecting the colored tubes to their
e product water line that will provide
(provided and taped to the RO
to hook up the product water (blue line) to the
Locate the 2.5 gallon storage/bladder tank in close
(Consult with the Factory
the RO System to the fitting on the side of the
valve off of the building domestic water supply to begin
System. You should notice water immediately
I.
J.
front to service it.
room. You
A. Now install the R
the instructions
1)
e
2)
3)
4)
5)
Osmosis (RO)
domestic water
NOTE: DRAIN MUST BE OPERABLE
– IT MUST BE ON LINE!
lu
. Utilize a “t” connector
frame)
IF PIPED TO A
RO water to the
6)
s
7)
B.
Panel/Generator
C.
the
OTE: 35 PSI MINIMUM REQUIRED
labeled “water in”.
RO
INCOMING
Control
4
![](/html/a6/a6e9/a6e9381ff76bd29b127b5427e3fb303f85a72e63e1ab32a7684cad8bb659c184/bg5.png)
D. Check for leaks.
As stated above The RO System will run until al
supply lines and storage tank are filled and charged to the pressure of the
building. This may take several hours to happen. Again, make sure that the
if the drain line is fed to a condensate pump the pump MUST
The RO System has an automatic shut off valve (ASO) that
is completely mechanical and will only open and pass water to drain when the
pressures are not equalized between the domestic water supply and the
humidifier supply lines. If there are any q
If the system was provided with a controlling humidity sensor then install it
and wire it from the Generator panel at the appropriately labeled locations on
Refer to the Wiring Diagram
unit for proper landing locations and line sizes.
recommended but not required.
Do the same as the above with both the High Limit humidistat and the Air
ovided. Terminal locations are again labeled in the Wiring
Diagram provided with your Unit.
S signal is being provided then connect it to the proper terminal
locations in the Generator as labeled in the
In this case a separate 24VAC signal is required to turn on the
uestions or issues please contact your
Wiring Diagram provided with the
drain is working –
BE OPERABLE!
l the humidifier
III) Accessories:
A.
the terminals.
B.
Flow switch if pr
CAUTION:
dampers.
C. If a BA
Unit.
humidifier.
(see Fig.2 )
Shiel
zone
5
![](/html/a6/a6e9/a6e9381ff76bd29b127b5427e3fb303f85a72e63e1ab32a7684cad8bb659c184/bg6.png)
IV)
A. Building Automation Control (BA
humidifier will first look to the air flow switch (AFS) safety and
the high limit switch (HL) safety before coming on.
efore leaving the RAH in an On
control logic will energize the normally closed water fill solenoid
valve. At the same time the normally opened drain solenoid valve will be closed. The
with water and when the low water safety
system will begin to generate fog
e continuous run time when humidifier is undersized or the space really needs
more humidifiers but the customer elected not to furnish and install them. If your model
has a timer delay relay go to that section in this Manual for more info.
In this configuration the Digital Controller governs the
humidifier. The electronic humidity sensor is wired back to the Control Panel per the
wiring diagram and the Controller will operate the system to maintain the set point.
act relay for activating the AHU Fan when there is a call for
Connecting this relay is at the discretion of the Installer and/or Owner.
Care must be taken to insure that zone dampers are opened as well when this relay is
the Controller determines the humidifier needs to come on to maintain
the humidity level the system will first look to the air flow switch (AFS) safety and the
high limit switch (HL) safety before coming on. Be sure these are installed and
rly before leaving the RAH in an On
control logic will energize the normally closed water fill
solenoid valve. At the same time the normally opened drain solenoid valve will be
l fill with water and when the low water safety float swit
satisfied the system will begin to generate fog (early generations of the RAH had two
low water safeties in series)for humidification. A timer relay may be installed for
essive continuous run time when humidifier is undersized or the space
really needs more humidifiers but the customer elected not to furnish and install them.
If your model has a timer delay relay go to that section in this Manual for more info.
Once the 24VAC signal is sent
Be sure these are installed and
(early generations of the RAH had two low water
A timer relay may be installed for prevention of
Line state. Assuming the two
signal is sent to the RAH-1
the system for output the
operating properly b
above safeties are good
system will fill
safeties in series)
excessiv
B. Local Control:
There is a dry cont
humidification.
energized. Once
S) Control: With BA
-Line state.
float switche(s
24VAC
to
are satisfied the
operating prope
above safeties are good,
closed. The system wil
prevention of exc
-
ch(s) are
6
![](/html/a6/a6e9/a6e9381ff76bd29b127b5427e3fb303f85a72e63e1ab32a7684cad8bb659c184/bg7.png)
SUPPLY SIDE TYPICAL INSTALLATION
1)Componentsoutlinedindashed linesinadditiontoPanelandDTAprovidedbyReensAir,
TYPICAL UNIT
SCALE: 1"=24"
BY: DJR -12/11/08
ISSUE:01 REV: 00
SIDEVIEW
ofcondensate
InstallDTAatslight
anglefordrainback
PANEL
WIREBACK
TOCONTROL
SWITCH
AIRFLOW
SUPPLYAIR
3"ODCOPPER
4"OD
METAL
SHEET
9"
Tube
Assembly
Dispersion
el/Generator
iredbackto
tronicWall
Elec
sensorw
ControlPan
R
0
O
0
T
0
A
1
R
H
E
A
N
R
E
G
completelyopen
InstallGeneratorat
TO
REDUCE
3"ATPANEL
FAN
angleso doorcanswing
HX
FILTER
INTAKE
R
ROMCLOSETDOO
t
FRONTVIEWF
TANK
STATION
STORAGE
isfornotifiationonly.
necessarillyhere. This
Note:water stationlocationis no
NOTES:
all otherpiping,wiring,mounting andinstallationbyothers.
2)Controllingwall mountedsensor,airflowswitch, providedbyReensAir.
3)Donot trapsupplypipingtoDTA- mustdrainbacktoPanel.
7