Gree MULTI42HP230V1CO Installation Manual

DUCTLESS INVERTER HEAT PUMP INSTALLATION MANUAL
Models:
MULTI18HP230V1CO MULTI24HP230V1CO MULTI30HP230V1CO MULTI36HP230V1CO MULTI42HP230V1CO
Thank you for choosing a Multi21 Ductless Heat Pump for your customer.
Please read this installation manual carefully before installing and starting up the Multi21 System. Take a moment to fill out the product and installation form on the back cover. Retain both the manual and installation record for future reference.
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Suggested Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation Site Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6- 7
Crown Indoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Terra Indoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Vireo Indoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-12
Indoor Unit Installation – Piping Design and Layout . . . . . . . . . . . . . . . . . 13 -15
Outdoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-18
Indoor Unit Installation – Mounting Bracket and Refrigerant Piping . . . . . 19-20
Piping Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21- 26
Power and Wiring Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27- 31
Testing and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-33
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35- 36
Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37- 40
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Back
SAFETY PRECAUTIONS
Please read the following before installation.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
WARNING
CAUTION
NOTICE
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
Notice is used to address practices not related to personal injury.
General Safety Precautions
1. Instructions for installation and use of this product are provided by the manufacturer. For proper operation, the system must be installed in accordance with this installation manual.
2. Installation must be performed in accordance with local laws, regulations and National Electrical Codes (NEC).
3. If refrigerant leaks while work is being carried out, ventilate the area. Do not allow refrigerant to come in contact with a flame as it produces toxic gas.
4. Disconnect all electrical power to the indoor and outdoor units until the system is ready for start-up and checkout.
5. When installing or repairing the system, use only R410A refrigerant. Do not mix refrigerant with other gases. If air or other gas enter the refrigeration system, the pressure inside the system may rise to an abnormally high value and cause damage or injury.
WARNING
This appliance is not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
2
NOMENCLATURE
Outdoor Unit
3
SYSTEM REQUIREMENTS
nit Size (BtuH)
U
ort A 1/4 (6) 3/8 (9.5)
18,000
4,000 Port B 1/4 (6) 3/8 (9.5)
2
30,000
36,000
42,000 Port C 1/4 (6) 3/8 (9.5)
P Port B 1/4 (6) 3/8 (9.5)
Port A 1/4 (6) 3/8 (9.5)
Port C 1/4 (6) 3/8 (9.5) Port A 1/4 (6) 3/8 (9.5)
Port B 1/4 (6) 3/8 (9.5) Port C 1/4 (6) 3/8 (9.5) Port D 1/4 (6) 3/8 (9.5)
Port A 1/4 (6) 3/8 (9.5) Port B 1/4 (6) 3/8 (9.5) Port C 1/4 (6) 3/8 (9.5) Port D 1/4 (6) 3/8 (9.5) Port E 1/4 (6) 3/8 (9.5)
Port A 1/4 (6) 3/8 (9.5) Port B 1/4 (6) 3/8 (9.5)
Port D 1/4 (6) 3/8 (9.5) Port E 1/4 (6) 3/8 (9.5)
Liquid Line
REFRIGERANT PIPE LENGTHS
Unit Size Max Total Pipe
(BtuH) Length ft(m) Pipe Length ft(m) PipeLength ft(m) IND Units ft(m) IND& OTDUnitsft(m)
18,000 65 (20) 10 (3) 33 (10) 33 (10) 33 (10) 24,000 197 (60) 10 (3) 65 (20) 33 (10) 33 (10) 30,000 230 (70) 10 (3) 82 (25) 33 (10) 49 (15) 36,000 246 (75) 10 (3) 82 (25) 33 (10) 49 (15) 42,000 246 (75) 10 (3) 82 (25) 33 (10) 49 (15)
Min
Equivalent Max Equivalent Max Elev btwn Max Elev btwn
REFRIGERANT CHARGE
Unit Size Refrigerant Factory System Max Pipe Length w/out Additional
(BtuH) Type Charge oz(kg) adding Refrig ft(m) Charge oz/ft (g/m)
18,000 R-410A 56.5 (1.6) 33 (10) 0.2 (20) 24,000 R-410A 77.6 (2.2) 98 (30) 0.2 (20) 30,000 R-410A 98.7 (2.8) 131 (40) 0.2 (20) 36,000 R-410A 128.8 (3.65) 131 (40) 0.2 (20) 42,000 R-410A 128.8 (3.65) 131 (40) 0.2 (20)
in(mm)
Suction/Gas Line
in(mm)
ELECTRICAL REQUIREMENTS
Unit Size
(BtuH) Amps (MCA) Protection (MOP) Wire Size (AWG)**
18,000 208/230v - 1ph 60hz 16 25 12 24,000 208/230v - 1ph 60hz 23 30 10 30,000 208/230v - 1ph 60hz 20 30 10 36,000 208/230v - 1ph 60hz 23 35 8 42,000 208/230v - 1ph 60hz 24 40 8
**Main power wire from electrical panel to outdoor unit. AWG based on 240VAC Single Phase, 100 ft. distance 1-way, max. 5% allowable voltage drop.
Voltage
Min Circuit Max Overcurrent Main Power
Notes: 1) System must be on a single dedicated circuit.
2) Main power is supplied to the outdoor unit.
3) Use table above to size over current protection.
4) Follow all local building codes and NEC (National Electrical Code) regulations.
Interconnecting Cable: Recommended cable - 14/4 AWG stranded bare copper conductors THHN 600V unshielded wire Note: Use shield cable if installation is in close proximity of RF and EMI transmitting devices.
4
SUGGESTED TOOLS
• Standard Wrench
• Adjustable/Crescent Wrench
• Torque Wrench
• Hex Keys or Allen Wrenches
• Drill & Drill Bits
• Hole Saw
• Pipe Cutter
• Screw drivers (Phillips & Flat blade)
• Manifold and Gauges
• Level
• R410A Flaring Tool
• Clamp on Amp Meter
• Vacuum Pump
• Safety Glasses
• Work Gloves
• Refrigerant Scale
• Micron Gauge
5
INSTALLATION SITE INSTRUCTIONS
Indoor Unit
Select a site that allows for the following:
1. Ensure the installation complies with the installation minimum dimensions (defined below) and meets the minimum and maximum connecting piping length and maximum change in elevation as defined in the System Requirements section.
2.
Air inlet and outlet will be clear of obstructions, ensuring proper airflow throughout the room.
3. Condensate can be easily and safely drained.
4. All connections can be easily made to outdoor unit.
5. Indoor unit is out of reach of children.
6.
A mounting structure (i.e. wall, ceiling, floor,...) strong enough to withstand four times the full weight and vibration of the unit.
7. Filter can be easily accessed for cleaning.
8. Leave enough free space to allow access for routine maintenance.
9. Install at least 10 ft. (3 m) away from the antenna of TV set or radio. Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak. An amplifier may be required for the affected device.
10. Do not install in a laundry room or by a swimming pool due to the corrosive environment.
Minimum Indoor Clearances - High Wall Units
Ceiling
6 in (0.15m)
6 in
(0.15m)
6 ft (1.8m)
Floor
NOTE:
For minimum clearances of other indoor unit types, refer to
6 in
(0.15m)
the Installation Instructions enclosed with those indoor units.
6
INSTALLATION SITE INSTRUCTIONS
Outdoor Unit
Select a site that allows the following:
1. Install the outdoor unit at a location that is capable of withstanding twice the weight of the unit.
2. Install the outdoor unit where it is convenient to connect refrigerant lines to the indoor units.
3. Install the outdoor unit where the condensate water can be drained unobstructed during the heating mode to a safe location.
4. Do not locate the unit where the noise may be objectionable to neighbors.
5. Provide the space shown below, so that the air flow is not blocked and future service and
maintenance can be performed.
Minimum Outdoor Clearances
12 in
(0.3 m)
20 in
(0.5 m)
20 in
(0.5 m)
39 in
(1.0m)
20 in
(0.5 m)
78 in
(2.0 m)
Air outlet
18K and 24K Unit
20 in
(0.5 m)
78 in
(2.0 m)
Air outlet
30K, 36K and 42K Unit
Air inlet
12 in
(0.3 m)
Air inlet
20 in
(0.5 m)
7
CROWN INDOOR UNIT INSTALLATION
Crown
A
INDOOR UNIT DIMENSIONS – in(mm)
Model ABC
CROWN09HP230V1B CROWN12HP230V1B CROWN18HP230V1B
37.8 (960) 12.6 (320) 8.0 (205)
37.8 (960) 12.6 (320) 8.0 (205)
37.8 (960) 12.6 (320) 8.0 (205)
PIPE SIZE – in(mm)
Unit Size (BtuH) Liquid Line Suction/Gas Line
9,000 1/4 (6) 1/2 (12) 12,000 1/4 (6) 1/2 (12) 18,000 1/4 (6) 5/8 (16)
C
B
Crown Unit Mounting Bracket Diagram (inches)
3.5 27.0 7.1
31/2 27 7 3/8
9K, 12K and 18K Unit
Left
(Rear piping hole)
2.8 2.8
2
2.0
3 1/8
3.1
Right
(Rear piping hole)
8
TERRA INDOOR UNIT INSTALLATION
Terra
A
INDOOR UNIT DIMENSIONS – in(mm)
Model ABC
C
B
TERRA09HP230V1AH
TERRA12HP230V1AH
TERRA18HP230V1BH
TERRA24HP230V1BH
PIPE SIZE – in(mm)
Unit Size (BtuH) Liquid Line Suction/Gas Line
9,000 1/4 (6) 1/2 (12)
12,000 1/4 (6) 1/2 (12)
18,000 1/4 (6) 5/8 (16)
24,000 1/4 (6) 5/8 (16)
34.1 (866) 11.5 (292) 8.2 (208)
34.1 (866) 11.5 (292) 8.2 (208)
40.1 (1018) 12.6 (319) 9.1 (231)
46.4 (1178) 12.8 (325) 10.4 (264)
9
TERRA INDOOR UNIT INSTALLATION
Terra Unit Mounting Bracket Diagrams (inches)
9K and 12K Unit
Left Right
(Rear piping hole) (Rear piping hole)
18K Unit
(Rear piping hole)
24K Unit
(Rear piping hole)
Left
Left
Right
(Rear piping hole)
Right
(Rear piping hole)
10
VIREO INDOOR UNIT INSTALLATION
Vireo
A
INDOOR UNIT DIMENSIONS – in(mm)
Model ABC
VIR09HP230V1B 33.4
VIR12HP230V1B 33.4
VIR18HP230V1B 38.2 (970) 11.8 (300)
VIR24HP230V1B 42.4 (1077) 12.8 (325)
(848)
(848)
11.4 (290)
11.4 (290)
PIPE SIZE – in(mm)
Unit Size (BtuH) Liquid Line Suction/Gas Line
9,000 1/4 (6) 3/8 (9)
12,000 1/4 (6) 1/2 (12)
18,000 1/4 (6)
24,000 1/4 (6) 5/8 (16)
B
5/8 (16)
8.2
8.2
8.8
9.7
C
(208)
(208)
(224)
(246)
11
VIREO INDOOR UNIT INSTALLATION
Vireo Unit Mounting Bracket Diagrams (inches)
9K and 12K Unit
Left
(Rear piping hole)
18K Unit
(Rear piping hole)
Left
4
.6
2.3
1.4
4
2.3
1.5
7.5 5.5
8.1 27
2
1.4
27
2.3
7
2.3
7.3
1.5
7.4
.3
1.4
(Rear piping hole)
Right
(Rear piping hole)
Right
24K Unit
(Rear piping hole)
Left
6.0
2.8
1.6
3.1
2.8
1.6
(Rear piping hole)
Right
12