Multi-Room Ductless heat-pump systems
Submittal Data: MULTI24HP230V1AO
24,000 BTU/H Wall Mounted Heat- Pump System
Job Name Location Date
Purchaser Engineer
Submitted To For
Reference Approval
Construction
Unit Designation Schedule No.
GENERAL FEATURES
-Up to 3 Indoor Units Comfort (3-Port)
-G10 DC Inverter Technology
-Quiet Operation - Both Indoor & Outdoor
-Wireless Remote Controller
-Optional Wired Remote Controller
-Gold Fin Coil Coating
-Intelligent Defrost
-Auto Restart on Power Outages
-Limited 7 yr Compressor & 5 yr Parts Warranty
Cooling Compressor Type DC Inverter Driven Rotary
Rated Capacity 26,000 BTU/H RLA 10.0 A
Capacity Range 7,500-33,000 BTU/H
Power Input (Max) 3,050 W Fan Motor Output Power 60 W
SEER 16 FLA 0.6 A
EER 8.2 Air Flow (Max) 1,530 CFM
Heating at 47° F
Rated Capacity 29,000 BTU/H Sound Pressure
Capacity Range 7,500-35,000 BTU/H Cooling 56 db(A)
Input Power (Max) 2,800 W Heating 56 db(A)
HSPF 8.2
COP 3.0 Dimensions & Weights
Heating at 17° F Unit Dimensions (LxHxD) 37.2 x 27.6 x 15.6 -in
Rated Capacity 17,000 BTU/H Weight (Net/Shipping) 134/146 LBS
Capacity (Max) 23,715 BTU/H
Min. Number of Indoor Units 2
Operating Range
Cooling (Max)
Heating (Max)
(Min)
(Min)
118℉ (48 C)
23℉ (-5 C) Connection Method Flared
80℉ (27 C) Refrigerant Type R410A
5℉ (-15 C) Factory Charge for Total Line Length 98-ft
Max. Number of Indoor Units 3
Additional Charge Per Line Length 0.2-oz/ft
Power Supply Total Refrigerant Pipe Length 230-ft
Normal Operational Voltage
Voltage Range
Main Power Wire Size
Interconnecting Cable Wire Size
MCA
MOCP/Breaker Size
208/230 V, 1 Phase, 60 Hz Max Refrigerant Piping Length to any Indoor Unit 66-ft
187 - 253 V Min Refrigerant Piping Length to any Indoor Unit 10-ft
10-2 AWG Max Elevation between Indoor Units 33-ft
14-4 AWG Max Lift from Outdoor to Indoor Unit 66-ft
20.0 A Max Drop from Outdoor to Indoor Unit 66-ft
30 A
AHRI Certified Ref No: 7084908
Gree Corporation 2014 V2.0 Page 1
©
OUTDOOR UNIT DIMENSIONAL SPECIFICATIONS MULTI24HP230V1AO
Units: inch (mm)
Model # MULTI24HP230V1AO 24,000 BTUH 230V
Port #1 3/8-in OD Flared Port #1
Port #2 3/8-in OD Flared Port #2
Port #3 3/8-in OD Flared Port #3
MINIMUM SPACING REQUIREMENTS
1. Recommended Interconnecting Cable Type Stranded Bare Copper Conductors THHN 600V Unshielded Wire
2. Power wiring cable size must comply with applicable national and local codes.
Suction/Gas Line Port Size
without notice or without incurring obligations. All rights reserved.
Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs
Units: inch (mm)
Notes:
3. Test conditions are based on AHRI 210/240.
© Gree Corporation 2014 V2.0 Page 2