Gree MG30-24/D1(B) Installation And Operation Manual

Page 1
安装使用说明书
Installation and Operation Manual
中央空调 BACnet 网关套件 MG30-24/D1(B)
BACnet Gateway Kit MG30-24/D1(B) for Central Air Conditioners
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
为了正确使用本产品,请在使用前仔细阅读本使用说明书,并妥善保存以供今后参考。
Please read this manual carefully before using this product and keep it properly for future reference.
Page 2
目录
一、功能介绍.................................................................1
1 功能概述 .......................................................................... 1
2 功能特点 .......................................................................... 1
2.1 BACnet/IP 楼宇接口功能 ............................................................... 1
2.2 Web 服务器功能 ....................................................................... 2
二、结构图...................................................................4
1 产品图片 .......................................................................... 4
2 产品尺寸 .......................................................................... 4
3 各个模块安装图 .................................................................... 5
4 产品整体效果图 .................................................................... 6
三、使用说明.................................................................6
1 接口 .............................................................................. 6
1.1 电源接口............................................................................. 6
1.2 模块安装接口......................................................................... 6
1.3 通讯接口............................................................................. 7
2 指示灯 ............................................................................ 7
2.1 电源指示灯........................................................................... 7
2.2 PCD 控制器 (CPU 模块 )PCD3.M6340 指示灯 ................................................ 7
2.3 WEB Server 控制器指示灯 .............................................................. 8
3 工程安装说明 ...................................................................... 9
3.1 BACnet 网关安装在电控柜中侧面示意说明 ................................................ 9
3.2 BACnet 网关安装在电控柜中正面示意说明 ................................................ 9
3.3 BACnet 网关的网络拓扑图 .............................................................. 9
3.4 BACnet 网关与上层 BACnet 通讯设备的连接方式 .......................................... 11
3.5 BACnet 网关与下层通讯模块设备的连接方式 ............................................. 12
四、注意事项................................................................12
Page 3
中央空调 BACnet 网关套件安装使用说明书
1
一、功能介绍
1 功能概述
格力中央空调 BACnet 网关套件 MG30-24/D1(B) 可实现空调机组和 BAS 系统的数据交换,提供标准的 BACnet/IP 楼宇接口,并且支持 Web 服务器功能,实现对机组的远程监测和控制,可满足互联网高速监控空 调信息。
2 功能特点
使用 BACnet/IP 楼宇接口功能时,BACnet 网关的 TCP/IP 默认属性为 IP Address:192.168.1.150、 Subnet Mask:255.255.255.0、Default Router:192.168.1.1。
使用Web服务器功能时,用互联网浏览器访问BACnet网关,登陆的默认地址为http://
192.168.1.150,默认用户名为:admin,密码为空。
BACnet 网关的 TCP/IP 属性能够通过 WEB 界面登陆后,按客户自身需求进行修改配置。
注意:访问 BACnet 网关时,需要调整客户端设备(如 PC 机)的 TCP/IP 属性与 BACnet 网关的 TCP/IP 属性在同一 IP 允许互相访问的网段区域。具体操作示例见英文版附录 A(Appendix A)。
对于 BACnet 网关的 BACnet/IP 楼宇接口和 Web 服务器两种功能的介绍分别描述如下:
2.1 BACnet/IP 楼宇接口功能
BACnet 网关支持符合 ANSI ASHARE Standard 135-2008(BACnet2008)标准的 BACnet/IP 接口协议,并 且通过了 BTL 认证。BACnet 网关的 PICS 声明和协议详述见英文版附录 B(Appendix B)。
支持的空调各种设备类型的参数如下:
空调设备类型 参数名称 空调设备类型 参数名称
GMV 室内机
( 参数说明:
远程屏蔽指所
屏蔽的参数仅
远程监控可控
制;远程锁定
指屏蔽所有参
数,仅远程监
控可控制。)
多联机内机故障总标志
GMV 室外机
多联机外机故障总标志
多联机内机故障码 多联机外机故障码
多联机内机环境温度 多联机外机环境温度
多联机内机温度设定 多联机外机压缩机运行状态
多联机内机模式状态
多联热水机
多联热水机特殊故障标志
多联机内机模式设定 多联热水机特殊故障码
多联机内机开关机状态 多联热水机水箱温度状态
多联机内机开关机设定 多联热水机水箱温度设定
多联机内机风速状态 多联热水机水箱运行状态
多联机内机风速设定 多联热水机水箱运行设定
多联机内机扫风设定 多联热水机水箱模式状态
多联机内机节能设定 多联热水机水箱模式设定
多联机内机远程屏蔽温度设定 多联热水机套管出水温度状态
多联机内机远程屏蔽模式设定 多联热水机地暖供水温度设定
多联机内机远程屏蔽开关机设定 多联热水机消毒运行状态
多联机内机远程锁定设定
多联热水机地板采暖有无状态
水箱控制屏蔽状态码
Page 4
中央空调 BACnet 网关套件安装使用说明书
2
2.2 Web 服务器功能
BACnet 网关的 WEB 服务器功能,是通过 HTML 页面的形式提供 Web 内容,实现监测、控制空调信息, 支持多用户终端同时访问。具有访问权限的用户在标准浏览器上即可访问 Web 界面。详细操作说明见 Web Server 的帮助文档。
2.2.1 使用环境要求:
1)操作系统:windows 操作系统,苹果操作系统,LINUX/UNIX 操作系统;
2)浏览器:支持 JAVA 技术的浏览器,如 IE,CHROME,NETSCAPE,FIREFOX 等;
3)语言支持:简体中文及英文(黑体);
4)Java 虚拟机安装:如果浏览器无法打开网页,请先从 Java 官网 www.java.com 下载 Java 虚拟机, 安装后便可正常使用。
5)最低硬件配置要求:
CPU: Pentium 400 MHz
RAM:128MB
硬盘:10GB
2.2.2 登陆界面和主界面示意如下(具体以实际运行界面为准):
Page 5
中央空调 BACnet 网关套件安装使用说明书
3
Page 6
中央空调 BACnet 网关套件安装使用说明书
4
二、结构图
1 产品图片
格力中央空调 BACnet 网关套件 MG30-24/D1(B) 产品实物图如下:
① PCD 控制器 (CPU 模块 )PCD3.M6340
② PCD 控制器 (WEB SERVER 模件 )PCD3.R600
③ Battery Module 模件 (含纽扣电池,注意电池正极朝外)
④ PCD 控制器 (BACnet 模件 )PCD7.R560
⑤ PCD 控制器 (SD 卡 )PCD7.R-SD1024
1
2
3
4
5
图 2-1 BACnet 网关套件 MG30-24/D1(B) 产品各个模块实物图
2 产品尺寸
格力中央空调 BACnet 网关套件 MG30-24/D1(B) 产品尺寸示意图如下:
(单位:mm)
图 2-2 BACnet 网关套件 MG30-24/D1(B) 产品尺寸图
类型 描述 重量
PCD3.M6340
BACnet 网关主控制器,支持 Web 服务器功能,控制器掉
电时纽扣电池可保护网关数据 1~3 年。
560g
Page 7
中央空调 BACnet 网关套件安装使用说明书
5
3 各个模块安装图
格力中央空调 BACnet 网关套件 MG30-24/D1(B) 产品各个模块安装图如下:
① 装入 PCD 控制器 (WEB SERVER 模件 )PCD3.R600 到 SLOT0 插槽
② 装入 Battery Module 模件(含纽扣电池,注意电池正极朝外)到 Batt Module 插槽
③ 装入 PCD 控制器 (BACnet 模件 )PCD7.R560 到 M1 插槽
④ 标准 RJ45 网络接口,10M/100M 自适应 Ethernet,连接网线到 BAS 系统
⑤ +24VDC、GND 电源线连接
1
2
3
4
5
图 2-3 BACnet 网关套件 MG30-24/D1(B) 产品各个模块安装图
备注:装入 PCD 控制器 (SD 卡 )PCD7.R-SD1024 到 PCD3.R600 中操作示意如下:
1
图 2-4 PCD 控制器 (WEB SERVER 模件 )PCD3.R600 装入 SD 卡图
Page 8
中央空调 BACnet 网关套件安装使用说明书
6
4 产品整体效果图
格力中央空调 BACnet 网关套件 MG30-24/D1(B) 产品整体效果图如下:
图 2-5 BACnet 网关套件 MG30-24/D1(B) 产品整体效果图
三、使用说明
1 接口
1.1 电源接口
如图 2-5 所 示。电源(POWER) 采 用接线端 子 输入,具 体 输入电源 规 格为 24VDC -20/+25% incl.5% ripples 符合 EN/IEC 61131-2,正常 175mA/4.2W,最大 500mA/12W。
注意:24 直流电源输入端子电源线不能接反,否则将会损坏 BACnet 网关设备。
丝印 端子 端子引脚 接口说明
+24V
GND
接线端子 PIN7:+24VDC 24V 直流输入
1.2 模块安装接口
如图 2-5 所示。BACnet 网关左方打开壳盖,可以看到 M1、M2、Batt Module 插口,BACnet 网关右方打开壳盖, 从左到右分为 4 个插口分别为 Slot0、Slot1、Slot2、Slot3,如图所示,已将 PCD3.R600 插入 Slot0。
丝印 端子 端子引脚 接口说明
M1 、M2 插口
Socket M1 或 Socket M2, 选 择 任
一一个端子接入 BACnet 卡件
接入 PCD 控制器 (BACnet 模件 )PCD7.
R560
Batt Module 插口
接 入 主 控 制 器 PCD3.M6340 包 含
Battary Module 卡件
接入 Battary Module,带纽扣电池
Slot0
Slot1
Slot2
Slot3
卡座插口
选择 Slot0 卡座 ( 该卡座最靠近 USB
接 口 ) 接 入 PCD3.R600(SD 卡 PCD7.
R-SD1024 插入该 WEB Server 模件)
选 择 Slot0 接 入 WEB Server 模 件
PCD3.R600
Page 9
中央空调 BACnet 网关套件安装使用说明书
7
1.3 通讯接口
如图 2-5 所示。BACnet 网关正面接线端子处可以看到对应的丝印 D、/D、O、C,网口采用 RJ45 标准接口。
丝印 端子 端子引脚 接口说明
D
/D
接线端子
P1:485 通讯 A
RS485 接口,接机组 MODBUS 设备的监控 / 楼宇接口,
无极性。D——R+/D+( 或 485 + ),/D——R-/D-(
或 485-) 。
P2:485 通讯 B
O
C
开关拨码
Switch position:
“0”(Left)—没有加匹配电阻
“C”(Right)—加匹配电阻
MODBUS 端匹配电阻添加选择按钮,默认拨为 C,
即加匹配电阻。
Ethernet
标准 RJ45
网络接口
Ethernet BACnet 网关与 BAS 系统连接接线端子。
2 指示灯
2.1 电源指示灯
如图 3-1 所示,丝印Power 指示灯为电源指示灯,Power指示灯被点亮红色表示 BACnet 网关电源已连接好, 否则表示 BACnet 网关电源未连接好。
2.2 PCD 控制器 (CPU 模块 )PCD3.M6340 指示灯
图 3-1 电源模块指示灯示意图
CPU 类型 PCD3.Mxxxx 电源模块
LED 电源 运行 停止 故障 颜色 绿 黄 运行
运行指令 ●/○ ○ 故障运行
故障运行指令 ●/○
停止
故障停止
暂停
系统诊断 ●/○ ●/○ ●/○
无电源 / 电压
○ LED 熄灭 ● LED 点亮 ● / ○ LED 闪烁
Page 10
中央空调 BACnet 网关套件安装使用说明书
8
开始 开机或重启后,自动诊断 1 秒钟。
运行
启动后,用户程序正常运行。由于安全原因,当编程器通过 CD8.K11x 连入 PGU 模式时(例
如,PGU 模式中的 PG5), CPU 自动进入停止状态,而非运行状态。
条件运行 条件运行状态。调试器中所设置的运行条件,目前还没有完全满足。
故障运行 同“运行”,但带有故障信息。
故障运行指令 同“条件运行”,但带有故障信息。
停止
以下情况将出现停止状态:
当 CPU 启动时,PGU 模式下有连接编程器
编程器使 PGU 停止运行
“条件运行”设置条件得到满足时
故障停止 同“停止“,但带有故障。
暂停
以下情况下将出现暂停状态:
运行暂停指令
用户程序出现严重故障
硬件故障
没有加载程序
在 S-Bus PGU 或网关主接口上没有通讯模块
系统诊断 如果 PLC 两分钟后没有运行,模块需发回制造商进行维修。
重设
以下情况将出现重设:
电源电压过低
固件没有运行
2.3 WEB Server 控制器指示灯
BCD开关
LED指示灯
闪存卡插槽
开关
图 3-2 PCD 控制器 (WEB SERVER 模件 )PCD3.R600 指示灯示意图
带有 5 个 LED 指示灯的储存卡模块:
LED 说明
User 用户指示灯,根据模块的基址由用户程序进行设置(SET:关,RES: 开)。
Diag 出现故障时,指示灯闪烁。
Write Prot 当检测到“写入保护”时,指示灯亮 ( 只读 SD 开关, BCD 开关或软件 )
Busy 此指示灯亮时,不能移走储存卡模块。
Activity 如硬盘驱动一样工作, 处理数据时,该指示灯闪烁。
Page 11
中央空调 BACnet 网关套件安装使用说明书
9
3 工程安装说明
3.1 BACnet 网关安装在电控柜中侧面示意说明
根据 DIN EN60715 TH35( 即老的 DIN EN50022),PCD3 CPU
和模块底托可固定在 35mm 的顶帽型安装导轨上。
将 PCD3 安装在顶帽型安装导轨上。 ① 将网关外罩的底部按压在安装表面上。 ② 沿安装导轨向上按压网关。 ③ 朝安装表面,向下按压网关外罩的顶部,网关与安装
导轨咬合。
④ 朝顶安装导轨,相下按压网关外罩,确保网关安装牢
固可靠。
拆卸: 拆卸外罩时,将其向上推,然后取出。
3.2 BACnet 网关安装在电控柜中正面示意说明
① 将模块插入正确的安装位置,且朝 CPU 底部或模块底托向下压。 ② 为了安全和防止网关安装不当,可使用导轨。在某些不方便的情况下,网关可使用螺丝钉固定。 螺丝钉型号:自动螺丝 3×8mm, 可从五金店购买。
定位槽
用另外的 螺丝固定
锁扣
图 3-4 BACnet 网关正面示意图
3.3 BACnet 网关的网络拓扑图
网络拓扑结构见下图 3-6。整个系统由两部分通讯网络构成:机组内部网络和 BACnet/IP 网络。两个网
络通过 BACnet 网关桥接,使两个网络的通讯数据可以互相交换。
一个 BACnet 网关能接 4 个通讯模块,也就是能接 4 套多联机机组(支持 64 个内机)。
下述以某一种通讯模块为例,具体以实际通讯模块拨码方式为准。通讯模块内部 8 位拔码开关用来设置 设备地址,在 PCB 板上地址拨码由 SA2 和 SA3 组成,实际使用时,底壳标识为 DIP1。拨码拨到 ON 端表示 0, 拨到数字端表示 1。接入 BACnet 网关时,通讯模块的有效地址范围为地址 1 到地址 4。详细拨码设置需见 通讯模块使用说明书。
图 3-3 BACnet 网关安装和拆卸说明示意图
Page 12
中央空调 BACnet 网关套件安装使用说明书
10
ON
1
2 3 4
ON
5
6 7 8
低位 高位
拨码表
DIP1
ON
1
2 3 4
ON
5
6 7 8
低位 高位
DIP1
拨码表
通讯模块地址 1 有效 通讯模块地址 2 有效
ON
1
2 3 4
ON
5
6 7 8
低位 高位
DIP1
拨码表
ON
1
2 3 4
ON
5
6 7 8
低位 高位
DIP1
拨码表
通讯模块地址 3 有效 通讯模块地址 4 有效
图 3-5 BACnet 网关连接的通讯模块设备有效地址拨码示意图
注:当多联机机组数量大于 4 套时,BMS 系统可以再使用一个网关搭建新的网络。
消防
通风
配电电梯
BMS楼宇自控系统
照明
Internet(BACnet/IP协议)
COM2
COM1
COM2
COM2
COM1
COM2COM2
COM1
COM2
内机1焊接点外机
控制柜
L1
L2L2
L1 L1
L2
内机2
内机16
内机1焊接点外机
内机2
内机16
内机1焊接点外机
内机2
内机16
通讯模块1
通讯模块4
WEB客户端
L3
HUB
L3
Intranet(BACnet/IP协议)
其它BACnet
Gateway
BACnet Gateway BACnet Gateway
图 3-6 BACnet 网关网络拓扑
Page 13
中央空调 BACnet 网关套件安装使用说明书
11
1)此图以某一种通讯模块连接方式为例,通讯模块连接接口 ( 是否为 COM1、COM2 接口 ) 方式以具体实 际通讯模块接口为准;
2)在上述网络中,通讯介质 L3 为 RJ45 网口间通用网线;
3)BMS(BACnet/IP) 系统和 BACnet Gateway 所能提供的 WEB Server 功能可以同时使用。
3.4 BACnet 网关与上层 BACnet 通讯设备的连接方式
3.4.1 网口连接的示意图
1)RJ45 网口平行网线连接方式
2)RJ45 网口交叉网线连接方式
3.4.2 BACnet 网关与 PC 机客户端连接的示意图
1)采用交叉网线,BACnet 网关直接对接 PC 机
10BASE-T 或 100BASE-TX
交叉网线
2)采用平行网线,BACnet 网关通过 HUB,对接 PC 机
10BASE-T 或 100BASE-TX
平行网线
HUB
Page 14
中央空调 BACnet 网关套件安装使用说明书
12
3.5 BACnet 网关与下层通讯模块设备的连接方式
3.5.1 下述以某一种通讯模块为例,具体以实际通讯模块连接接口方式为准
通讯模块侧面图
焊接点
COM2口
RS485+
RS485-
双绞线RS485连接,采用无极性
3.5.2 中继器套件选配
如果 BACnet 网关与通讯模块设备连接距离超过 800m 时,需要选配中继器套件。
中继器之间通讯线最大距离是800m
四、注意事项
1)确保电源适配器的规格,否则 BACnet 网关将不能正常工作甚至被损坏;
2)确保设备装配到正确位置,否则将通讯故障;
3)确保通讯线接入正确的接口,否则将通讯故障;
4)用焊锡加固连接通讯线后,应使用绝缘胶布保护,以免氧化、短路;
5)BACnet 网关正常工作环境要求 : ①温度 : 0~55℃ , ②湿度小于等于 95%: ③安装在室内 ( 推荐安装 在电控柜中 ),避免阳光直晒,雨雪等;
6)警示 : 如果工作环境不满足以上要求,BACnet 网关可能工作异常 !
7)为有效保护客户的访问权限,客户使用 BACnet 网关的 WEB 服务器功能时,需及时修改 WEB 服务器的 访问密码;
8)格力保留产品升级时不另行通知的权利。
Page 15
Gree Electric Appliances,Inc. of Zhuhai
地址:珠海市前山金鸡西路 邮编:
519070
Tel: 4008 365 315 (0756)8617555
(客户服务中心)
http: //www. gree. com
64134100001-01( )
Page 16
Contents
1 Functional Specications ��������������������������������������������������������������������������������� 1
1�1 Brief Introduction �����������������������������������������������������������������������������������������������������������������������1
1�2 Features �������������������������������������������������������������������������������������������������������������������������������������1
2 Product Drawing ���������������������������������������������������������������������������������������������� 4
2�1 Parts Drawing ����������������������������������������������������������������������������������������������������������������������������4
2�2 Dimension Drawing ��������������������������������������������������������������������������������������������������������������������5
2�3 Installation Drawing ��������������������������������������������������������������������������������������������������������������������6
2�4 General Drawing ������������������������������������������������������������������������������������������������������������������������7
3 Operation Instructions ������������������������������������������������������������������������������������� 7
3�1 Interfaces �����������������������������������������������������������������������������������������������������������������������������������7
3�2 Indicating LEDs ��������������������������������������������������������������������������������������������������������������������������8
3�3 Installation Instructions ������������������������������������������������������������������������������������������������������������10
4 Precautions���������������������������������������������������������������������������������������������������� 15
Appendixes ������������������������������������������������������������������������������������������������������ 16
Appendix A TCP/IP Property Setting �����������������������������������������������������������������������������������������16
Appendix B BACnet Protocol ��������������������������������������������������������������������������������������������������������18
Appendix C Indoor Unit Error Codes ��������������������������������������������������������������������������������������������46
Appendix D Outdoor Unit Error Codes �����������������������������������������������������������������������������������������47
Appendix E Specic Error Codes for the GMV Water Heater �������������������������������������������������������49
Appendix F Water Tank Control Shielding Codes ������������������������������������������������������������������������� 50
Page 17
BACnet Gateway Kit for Central Air Conditioners
1
1 Functional Specications
1�1 Brief Introduction
BACnet gateway kit MG30-24/D1(B) is capable of realizing the data exchange between the air
conditioning unit and BAS, supporting the Web server, providing remote monitoring and control to
the air conditioning unit, and also enabling the internet to monitor the information related to the air
conditioning unit at high speed.
1�2 Features
When BACnet/IP BAS interface is put into use, the default properties of BACnet gateway is
shown as below:
IP Address: 192.168.1.150
Subnet Mask:255.255.255.0
Default Router:192.168.1.1
Under the condition that the Web server is put into use, when visiting the BACnet gateway
through the Internet browser:
Web Server Default Login Address: http:// 192.168.1.150
Web Server Default Login Username: admin
Web Server Default Login Password: null
After logging in the Web page, these properties listed above are allowed to be modied.
Note: When visiting the BACnet gateway, it is required to adjust the TCP/IP properties of the client-
side equipment (like, PC) to be compatible with that of the BACnet gateway. See the example
covered in Appendix A for more details.
BACnet/IP BAS interface and BACnet Web server are two major functions for the BACnet gateway.
See the followings for more details.
1�2�1 BACnet BAS Interface
This BTL certificated BACnet gateway supports the standard BACnet/IP interface protocol
which complies with the ANSI ASHRAD standard 135-2008 (BACnet2008). See Appendix B for
PICS of the BACnet gateway and more detailed protocol content.
Page 18
BACnet Gateway Kit for Central Air Conditioners
2
Parameters of the Supported Air Conditioning Units
AC Type Parameters Name
GMV Indoor Units (Note: “Remote temp/mode/On/Off shield mark” indicates the parameter of “temp/mode/On/Off” is disabled to be set through the unit controller but the remote monitoring system; while “Remote lock mark” indicates all parameter are disabled to be set through the unit controller but the remote monitoring system.)
Indoor unit general error mark
Indoor unit error code
Indoor unit environment Temp
Indoor unit Temp(setting)
Indoor unit mode(status)
Indoor unit mode(setting)
On/Off(status)
On/Off(setting)
Fan Speed(status)
Fan Speed(setting)
Swing(setting)
Energy saving(setting)
Remote temp shield mark(setting)
Remote mode shield mark(setting)
Remote On/Off shield mark(setting)
Remote lock mark(all shield)(setting)
GMV Outdoor Units
Outdoor unit general error mark
Outdoor unit error code
Outdoor environment temp
Complete machine compressor state
GMV Water Heater
Specic error mark for the GMV Water Heater
Specic error codes for the GMV Water Heater
Water tank temp(status)
Water tank temp(setting)
Water tank(status)
Water tank(setting)
Water tank mode(status)
Water tank mode(setting)
Double-Tube supply Water Temp
Floor Heating supply Water Setting Temp
Disinfecting
Floor heat power
Water tank control shielding code(setting)
Page 19
BACnet Gateway Kit for Central Air Conditioners
3
1.2. 2 BACnet Web Server
The BACnet is capable of supporting the controller Web server in the form the HTML Web
pages so as to control, monitor and display the data of the air conditioning unit, meanwhile
supporting the multi-user visit at a time. For detailed information see the Help document on the
Web Sever page.
1.2.2.1 Application Conditions:
1) Operation System: Windows, Mac, LINUX/UNIX.
2) Browser: Browsers which support JAVA, like, IE, CHROME, NETSCASPE, FIREBOX, etc.
3) Supportive Language: Simplied Chinese and English
4) Installation of the JAVA virtual machine: when the browser fails to access to the web page,
please download the JAVA virtual machine at rst from the ofcial website:www.java.com, then
install it properly, after that the normal use is available.
5) Minimum Requirements on the Hardware:
CPU: Pentium 400 MHz
RAM: 128MB
Hard Disc: 10GB
1.2.2.2 Login and Main Interface (Always see the actual running interface)
Page 20
BACnet Gateway Kit for Central Air Conditioners
4
2 Product Drawing
2�1 Parts Drawing
See the following real image drawing of each module of the BACnet Gateway MG30-24/D1(B)
① .
CPU Module PCD3.M6340
② .
Web Server Module PCD3.R600
③ .
Battery Module (incl. button cell with the positive electrode outward)
④ .
BACnet Module PCD 7.R560
⑤ .
SD Card PCD 7.R-SD1024
Page 21
BACnet Gateway Kit for Central Air Conditioners
5
1
2
3
4
5
Fig. 2-1 Real Image Drawing of Each Module of BACnet Gateway MG30-24/D1(B)
2�2 Dimension Drawing
See the following drawing for the dimensions of the BACnet Gateway MG30-24/D1(B)
(Unit:mm)
Type Description Weight
PCD3.M6340
PLC with 1 MB of user memory with Run/Stop switch Back up option with PCD7.R500 Flash Card,USB port for PG5 Max.1023 digital I/Os,2 interrupts,Web-Server,RS232,RS485 for Pro-S-Net,CAN interface Data protection 1~3 years with Lithium battery
560g
Fig. 2-2 Dimension Drawing of BACnet Gateway MG30-24/D1(B)
Page 22
BACnet Gateway Kit for Central Air Conditioners
6
2�3 Installation Drawing
See the following drawing for the installation of each module of the BACnet Gateway MG30-24/
D1(B)
① .
Install the Web server PCD3.R600 at slot0.
② .
Install the battery module at the battery module special slot.
③ .
Install the BACnet module PCD7.R560 at M1
④ .
Standard RJ45 interface, 10M/100M self-adaptive to the Ethernet, linked to the BAS
through the communication line.
⑤ .
+24VDC GND, used to connect the power cord.
1
2
3
4
5
Fig.2-3 Installation Drawing of Each Module of the BACnet Gateway MG30-24/D1(B)
Note: See the following drawing for how to install the SD card into the Web server module PCD3.
R600�
1
Fig.2-4 Installation of the SD Card into the Web Server Module PCD3.R600
Page 23
BACnet Gateway Kit for Central Air Conditioners
7
2�4 General Drawing
See the following drawing for the outline of the whole BACnet MG30-24/D1(B)
Fig. 2-5 Outline Drawing of the Whole BACnet MG30-24/D1(B)
3 Operation Instructions
3�1 Interfaces
3�1�1 Power Supply Interface
As shown in Fig.2-5, the power supply is input through the wiring terminal.
Power Supply: 24VDC -20/+25% incl. 5% ripples as per EN/IEC 61131-2, 175mA/4.2W normal,
500mA/12W maximum.
Note: the power cord mustn’t be connected reversely and the power supply mustn’t be beyond
the specied l, otherwise the BACnet gateway would be damaged.
Printed Mark Terminal Pin Description
+24V GND Wiring Terminal
+24VDC 24V DC Input
3.1.2 Module Installation Interfaces
As shown in Fig.2-5, when the left cover is opened, the interfaces of M1, M2 and Batt Module
can be seen; when the right cover is opened, the interfaces from left to right are Slot0, Solt1, Slot2
and Slot3, in which case, PCD3.R600 has been inserted into Slot0.
Printed Mark Terminal Pin Description
M1, M2 Socket / It is used to connect BACnet module PCD7�R560
Batt Module Socket /
It is used to connect battery module PCD3.M6340 (incl. button cell)
Slot0 Slot1 Slot2 Slot3
Socket /
Slot0 (at the side of the nearest USB interface) is used to connect the Web server module PCD3.R600 into which PCD7.R-SD1024 is inserted.
Page 24
BACnet Gateway Kit for Central Air Conditioners
8
3�1�3 Communication Interfaces
As shown in Fig.2-5, the printed marks D, /D, O, and C can be seen in the front of the wiring
terminals of the BACnet gateway, and the RJ45 standard interface is prepared.
Printed
Mark
Terminal Pin Description
D
/D
Wiring
Terminal
P1: 485 A
RS485 Interface, it is used to connect the Modbus device and of no polarity. D——R+/D+(or 485+); /D——R-/D-(or 485-)
P2: 485 B
O
C
DIP
Switch
Switch Setting “0”(Left)—without the matched resistance “C”(Right)—with the matched resistance
It is used to set if the matched resistance is connected or not. It is defaulted to be set to “C”
Ethernet
RJ45
Network
Interface
Ethernet
Communication Interface, used for the communication line which connects the
BACnet gateway and the BAS.
3�2 Indicating LEDs
3�2�1 Power Indicating LED
As shown in Fig. 3-1, the printed mark “Power” represents the power indicating LED. When
it turned to red, it indicates the BACnet gateway is powered on; when it turns off, it indicates the
BACnet gateway is powered off�
3.2.2 CPU Module PCD3.M6340 Indicating LED
Fig. 3-1 Battery Module Indicating LEDs
Page 25
BACnet Gateway Kit for Central Air Conditioners
9
CPU type PCD3.Mxxxx Battery module
LED Batt Run Halt Error
Colour Red Green Red Yellow
Run
Run cond� ●/○
Run with error
Run cond. with error ●/○
Stop
Stop with error
Halt
System diagnostics ●/○ ●/○ ●/○
Batt./Super Cap voltage absent
○ LED off ● LED on ●/○ LED ashing
Start Self-diagnosis for approx. 1 sec. after switching on or after a Restart
Run
Normal processing of the user program after Start. Where a programming unit is connected via a PCD8.K11x in PGU mode (e.g. PG5 in PGU mode), the CPU automatically goes into the Stop state and not the Run state; this is for
safety reasons
Run conditional
Conditional Run state. A condition has been set in the debugger (Run until…), which has not yet been met
Run with error Same as Run, but with an error message
Run cond. with error Same as conditional Run, but with an error message
Stop
The Stop state occurs in the following cases:
• Programming unit in PGU mode connected when the CPU was switched on
• PGU stopped by programming unit
• Condition for a COND.RUN has been met
Stop with error Same as Stop, but with an error message
Halt
The Halt state occurs in the following cases:
• Halt instruction processed
• Serious error in user program
• Hardware fault
• No program loaded
• no communication module on an S-Bus PGU or Gateway Master port
System diagnostics If the PLC doesn‘t go to RUN after 2 minutes, you have to send it for repair
Reset
The RESET state has the following causes:
• Supply voltage too low
• Firmware not starting up
Page 26
BACnet Gateway Kit for Central Air Conditioners
10
3.2.3 WEB Server Module Indicating LED
Fig.3-2 Wed Server Module PCD3.R600 Indicating LED
The memory module is tted with 5 LEDs:
LED Meaning
User
User LED, set by the user program with the base address of the module (SET = off; RES = on)
Diag Flashes when there is an error message
Write Prot
Active when a "write-protected" condition is detected (read-only SD switch, BCD switch or software)
Busy Do not remove the module when this LED is on.
Activity Works as with a hard disk drive; ashes when data being processed
Note:Do not remove the card when the "Busy" LED is on.
3�3 Installation Instructions
3.3.1 Side View of the Installation and Removal of the BACnet Gateway
The PCD3 CPUs and module holders can be snapped onto a 35 mm Top-hat rail according to
DIN EN60715 TH35 (formerly DIN EN50022).
Mounting the PCD3 on the top-hat rail
① .
Press bottom of housing onto the mounting surface
② .
Press upwards against the top-hat rail
③ .
Press top of housing against the mounting surface and snap into place
④ .
Push the housing down onto the top-hat rail to ensure that it is secure
Removal:
To remove the housing, push upwards and pull out.
Page 27
BACnet Gateway Kit for Central Air Conditioners
11
Fig.3-3 Side View of the Installation and Removal of the BACnet Gateway
3.3.2 Front View of the Installation and Removal of the BACnet Gateway
① .
Insert the module into the appropriate module location and press down to the bottom of the
CPU or module holder housing;
② .
For security, a guide way is provided to prevent the module being inserted the wrong way
round. In awkward positions, the modules can also be secured with a screw. Screw type: self-
tapping 3x8mm, standard type obtainable from hardware stores;
Locks
Loaction slots
For additional screw fixing
Fig.3-4 Front View of the Installation and Removal of the BACnet Gateway
3.3.3 Network Topology
See Fig.3-6 for the network topology. The whole system consists of the internal network of
the air conditioning unit and BACnet/IP network through which the communication data can be
exchanged.
One Bacnet gateway can support up to four communication modules, that it, four sets of GMV
units (max. 64 indoor units)
Take a certain module as an example, however, always see the real communication module for
Page 28
BACnet Gateway Kit for Central Air Conditioners
12
the DIP switch setting. Inside the communication module there is 8-poistion switch among which
the SA2 and SA3 are used to set the device address. In the actual application, when the DIP switch
is set to the side “ON”, it represents “0” of the binary system and “1” on the opposite end. Once the
communication module is integrated with the BANnet gateway, its address range is 1 thru 4. See
the Operation Instruction of the Communication Module for more details about the setting of the
DIP switch.
Communication Address 1
Communication Address 2
Communication Address 3
Communication Address 4
Fig.3-5 Address DIP Switch Setting of the Communication Module
Note: when the quantity of the GMV units exceeds 4, it is allowed for the BMS system to build a
new network with another BACnet gateway �
Page 29
BACnet Gateway Kit for Central Air Conditioners
13
Fire
Vent
Electricity
Lift
BMS
Lighting
Internet(BACnet/IP Protocal)
COM2
COM1
COM2
COM2
COM1
COM2COM2
COM1
COM2
ID Unit 1
Soldering
Point
OD Unit
Control Cabinet
L1
L2L2
L1 L1
L2
ID Unit 2
ID Unit 16
ID Unit 1
ID Unit 2
ID Unit 16
ID Unit 1
ID Unit 2
ID Unit 16
Commun-
module
1
Commun-
module
4
WEB Client
L3
HUB
L3
Intranet(BACnet/IP
Protocol)
Other BACnet
Gateway
BACnet
Gateway
BACnet
Gateway
Soldering
Point
Soldering
Point
OD Unit
OD Unit
Fig.3-6 BACnet Network Topology
1) The communication module shown above is just taken as example, and always see the real
communication module for the actual interfaces.
2) As shown in the gure above, “L3” represents the universal communication line between
RJ45 interfaces.
3) The Web Server function provided by BMS(BACnet/IP) and BACnet gateway can be used at
the same time.
3.3.4 Connection between the BACnet Gateway and the Upper Communication Device
3�3�4�1 Interface Connection
RJ45 Interface Connection with Parallel Line
Page 30
BACnet Gateway Kit for Central Air Conditioners
14
RJ45 Interface Connection with Cross Line
3.3.4.2 Connection between the BACnet Gateway and the Client-Side PC
1) Direction Connection with the Cross Communication Line:
10BASE-T or 100BASE-TX Cross Communication Line
2) Indirection Connection via the Hub with the Parallel Communication Line:
10BASE-T or 100BASE-TX Parallel Communication Line
HUB
3.3.5 Connection between the BACnet Gateway and the Lower Communication Device
3.3.5.1 Take some communication module as an example, however, always see the real
interfaces located at the communication module for actual connection.
COM2
Side View of the
Communication Module
Twisted Pair RS485
Communication Line of No Polarity
Soldering
Poin
t
RS485+
RS485-
Page 31
BACnet Gateway Kit for Central Air Conditioners
15
3�3�5�2 Optional Repeater Kit
A RS-422/485 repeater (isolated) is required to amplify the communication signal when the
communication distance exceeds 800m�
Max. distance of communication line between two repeaters is 800m
4 Precautions
1) Be sure the adaptor is proper; otherwise the BACnet gateway would function improperly or
even be damaged.
2) Be sure the communication equipments are located at the proper place; otherwise it would
lead to communication error�
3) Be sure the communication line is connected to the correct interface; otherwise it would lead
to communication error�
4) After secured through soldering, the communication line should be protected with the
insulating tape so as to avoid oxidization and short-circuiting.
5) Working Conditions for BACnet gateway:
Temperature: 0~55 ;
Humidity: equal to or less than 95%;
Located in the room (esp. the electric control cabinet) to avoid direct sunlight, ran and snow etc.
6) WARNING: If the working conditions are beyond what stated above, then BACnet would
function improperly!
7) In order to protect the user’s access authority, when the user is visiting the Web server of the
BACnet gateway, it is strongly advised to modify the login passwords.
8) GREE keeps the right to update the products without advanced notice.
Page 32
BACnet Gateway Kit for Central Air Conditioners
16
Appendixes
Appendix A TCP/IP Property Setting
① .
Choose the ‘“Local Area Connection” on PC�
② .
Click the “Properties”.
③ .
Choose the option Internet Protocol Version 4(TCP/IPv4)
④ .
Choose the “Use the following IP address” and set the TCP/IP properties.
⑤ .
DNS server addresses is not required to be set but keeps the default setting.
⑥ .
Click OK and the setting is nished.
1
2

3
Page 33
BACnet Gateway Kit for Central Air Conditioners
17
4
5
6
Page 34
BACnet Gateway Kit for Central Air Conditioners
18
Appendix B BACnet Protocol
1 Brief Introduction to the BACnet Protocol
1.1 What is BACnet
BACnet - A Data Communication Protocol for Building Automation and Control Networks - see
bacnet.org. BACnet is a standard data communication protocol for Building Automation and Control
Networks. BACnet is an open protocol, which means anyone can contribute to the standard, and
anyone may use it. The only caveat is that the BACnet standard document itself is copyrighted
by ASHRAE, and they sell the document to help defray costs of developing and maintaining the
standard (just like IEEE or ANSI or ISO).
1.2 BACnet Collapsed Architecture
BACnet is based on a four-layer collapsed architecture that corresponds to the physical, data
link, network, and applicationlayers of the OSI model.
BACnet Layers Equivalent OSI Layers
BACnet Application Layer
BACnet Network Layer
ISO 8802-2(IEEE 802.2)
Type 1
MS/TP PTP
LonTalk
BVLL
ISO 8802-
3(IEEE 802.3)
ARCNET EIA-485 EIA-232 UDP/IP
BACnet is dened for several physical layers.
BACnet/IP has only later been added to the original group.
1.3 BACnet device proles
Today 6 device proles are dened with BACnet:
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specic Controller (B-ASC)
BACnet Smart Actuator (B-SA)
BACnet Smart Sensor (B-SS)
Any device that implements all the required BACnet capabilities for a particular device type
and interoperability area may claim to be a device of that particular type.Devices may also provide
additional capabilities and shall indicate these capabilities in their PICS.
Application
Network
Data Link
Physical
Page 35
BACnet Gateway Kit for Central Air Conditioners
19
1.4 BACnet standard objects
ANSI/ASHRAE 135-2008 defines 30 BACnet standard objects as shown in the standard
document�
Clause Description Page Clause Description Page
12�1 Accumulator Object Type 132 12�16 Life Safety Zone Object Type 203
12�2 Analog Input Object Type 140 12�17 Loop Object Type 209
12�3 Analog Output Object Type 145 12�18 Multi-state Input Object Type 216
12�4 Analog Value Object Type 150 12�19 Multi-state Output Object Type 220
12�5 Averaging Object Type 155 12�20 Multi-state Value Object Type 224
12�6 Binary Input Object Type 158 12�21 Notication Class Object Type 229
12�7 Binary Output Object Type 163 12�22 Program Object Type 232
12�8 Binary Value Object Type 169 12�23 Pulse Converter Object Type 237
12�9 Calendar Object Type 174 12�24 Schedule Object Type 244
12�10 Command Object Type 176 12�25 Trend Log Object Type 249
12�11 Device Object Type 180 12�26 Access Door Object Type 257
12�12 Event Enrollment Object Type 188 12�27 Event Log Object Type 264
12�13 File Object Type 193 12�28 Load Control Object Type 270
12�14 Group Object Type 195 12�29 Structured View Object Type 279
12�15 Life Safety Point Object Type 197 12�30 Trend Log Multiple Object Type 281
1.5 BACnet services
BACnet services are divided into ve segments:
1) Alarm and event Services
2) File Access Services
3) Object access Services
4) Remote device management Services
5) Virtual terminal Services
For each device prole certain services are mandatory.
1.6 Description of a service: BIBB
BACnet Interoperability Building Blocks (BIBBs) are collections of one or more BACnet
services. These are prescribed in terms of an "A" and a "B" device. Both of these devices are
nodes on a BACnet internetwork. In most cases, the "A" device will act as the user of data (client),
and the "B" device will be the provider of this data (server). In addition, certain BIBBs may also be
predicated on the support of certain, otherwise optional, BACnet objects or properties and may
place constraints on the allowable values of specic properties or service parameters.
Page 36
BACnet Gateway Kit for Central Air Conditioners
20
1.7 Description of a device type: PICS
PICS protocol implementation conformance statement All devices conforming to the BACnet
protocol shall have a Protocol Implementation Conformance Statement (PICS) that identies all of
the portions of BACnet that are implemented.
A PICS is a written document, created by the manufacturer of a device, that identifies the
particular options specified by BACnet that are implemented in the device. A BACnet PICS is
considered a public document that is available for use by any interested party.
2 BACnet protocol implementation conformance statement(PICS)
Date: 08.08.2011
Vendor Name: Saia-Burgess Controls AG (Vendor ID = 89)
Product Names: BACnet_GMV1_V1.0
stations: PCD3.M6340
Product Model Number: PCD7.R560
Applications Software Version: -
Firmware Revision: BACnetPCD3Mxxx0_PCD2M5xx0_1.08.49.blk
BACnet Protocol Revision: 1.4
2.1 Product Description:
The BACnet gateway applied for GREE GMV units links the unit’s internal network with
the BACnet/IP network , and also provides BACnet BAS interfaces which enable the unit to be seamlessly integrated into the third party’s BAS.
2.2 BACnet Standardized Device Prole (Appendix L):
□ BACnet Operator Workstation (B-OWS)
□ BACnet Building Controller (B-BC)
□ BACnet Advanced Application Controller (B-AAC)
■ BACnet Application Specic Controller (B-ASC)
□ BACnet Smart Sensor (B-SS)
□ BACnet Smart Actuator (B-SA)
2.3 List all BACnet Interoperability Building Blocks Supported (Appendix K):
1) Data Sharing BIBBs
Data Sharing Read-Property-B DS-RP-B
Data Sharing Read-Property-Multiple-B DS-RPM-B
Data Sharing Write-Property-B DS-WP-B
Data Sharing Write-Property-Multiple-B DS-WPM-B
Data Sharing COV-B DS-COV-B
Data Sharing COV-Unsolicited-B DS-COVU-B
Data Sharing COV-Property-B DS-COVP-B
2) Device Management BIBBs
Device Management-Dynamic Device Binding-A DM-DDB-A
Device Management-Dynamic Device Binding-B DM-DDB-B
Device Management-Dynamic Object Binding-B DM-DOB-B
Page 37
BACnet Gateway Kit for Central Air Conditioners
21
Device Management-DeviceCommunicationControl-B DM-DCC-B
Device Management-TimeSynchronization-B DM-TS-B
Device Management-UTCTimeSynchronization-B DM-UTC-B
Device Management-ReinitializeDevice-B DM-RD-B
Device Management-Backup and Restore-B DM-BR-B
Device Management-Restart-B DM-R-B
Device Management-List Manipulation-B DM-LM-B
Device Management-Object Creation and Deletion-B DM-OCD-B
3) Network Management BIBBs
Network Management-Connection Establishment-B NM-CE-B
Network Management-Router Conguration-B NM-RC-B
2.4 Segmentation Capability:
■ Able to transmit segmented messages Window Size 16
■ Able to receive segmented messages Window Size 16
2.5 Standard Object Types Supported:
1) Standard Object Types Supported: Analog-Input-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Device Type Reliability Update_Interval Min_Pres_Value Max_Pres_Value
Resolution
COV_Increment Time_Delay Notication_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Present_Value COV_Increment Time_Delay High_Limit Low_Limit Deadband Limit_Enable Event_Enable
Page 38
BACnet Gateway Kit for Central Air Conditioners
22
2) Standard Object Types Supported: Analog-Value-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Reliability Priority_Array Relinquish_Default COV_Increment Time_Delay Notication_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Present_Value COV_Increment Time_Delay High_Limit Low_Limit Deadband Limit_Enable Event_Enable
3) Standard Object Types Supported: Binary-Input-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Device_Type Reliability Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_
Count
Time_Of_State_Count_
Reset
Elapsed_Active_Time Time_Of_Active_Time_
Reset
Time_Delay Notication_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Present_Value Time_Delay Event_Enable
Page 39
BACnet Gateway Kit for Central Air Conditioners
23
4) Standard Object Types Supported: Binary-Output-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Device_Type Reliability Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_
Reset
Elapsed_Active_Time Time_Of_Active_Time_
Reset
Minimum_Off_Time Minimum_On_Time Time_Delay Notication_Class Feedback_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Present_Value Time_Delay Event_Enable
5)Standard Object Types Supported: Binary-Value-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Reliability Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_
Reset
Elapsed_Active_Time Time_Of_Active_Time_
Reset
Minimum_Off_Time Minimum_On_Time Priority_Array Relinquish_Default Time_Delay Notication_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Present_Value Time_Delay Event_Enable
Page 40
BACnet Gateway Kit for Central Air Conditioners
24
6) Standard Object Types Supported: Multistate-Input-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Device_Type Reliability State_Text Time_Delay Notication_Class Alarm_Values Fault_Values Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Present_Value Time_Delay Alarm_Values Fault_Values Event_Enable
7) Standard Object Types Supported: Multistate-Value-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Reliability State_Text Priority_Array Relinquish_Default Time_Delay Notication_Class Alarm_Values Fault_Values Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Present_Value Time_Delay Alarm_Values Fault_Values Event_Enable
2.6 Data Link Layer Options:
■ BACnet IP, (Appendix J)
□ BACnet IP, (Appendix J), Foreign Device
□ ISO 8802-3, Ethernet (Clause 7)
□ ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
□ ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ____________
□ MS/TP master (Clause 9), baud rate(s):
□ MS/TP slave (Clause 9), baud rate(s):
□ Point-To-Point, EIA 232 (Clause 10), baud rate(s):
□ Point-To-Point, modem, (Clause 10), baud rate(s):
□ LonTalk, (Clause 11), medium: __________
□ Other:
2.7 Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with
Page 41
BACnet Gateway Kit for Central Air Conditioners
25
MS/TP slaves and certain other devices.) □Yes ■ No
2.8 Networking Options:
■ Router, Clause 6 - List all routing congurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP,
etc�
□ Appendix H, BACnet Tunneling Router over IP
□ BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? □ Yes ■ No
2.9 Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported
simultaneously�
■ ANSI X3.4 □ IBM™/Microsoft™ DBCS □ ISO 8859-1
□ ISO 10646 (UCS-2) □ ISO 10646 (UCS-4) □ JIS C 6226
3 BACnet Objects List
3.1 Supported BACnet Object Type
Based on the object type specified in the BACnet standard document, the object type and
name related to the air conditioning unit are listed as follows:
Object
number
Object Type
Hexadecimal
format
Decimal
format
Air conditioner Parameter name
0 Analog Input X’0000 0000’ 0
Indoor unit environment Temp, Water tank temp(status), Double­Tube supply Water Temp, Outdoor environment temp
1 Analog Output X’0040 0000’ 4194304
2 Analog Value X’0080 0000’ 8388608
Indoor unit Temp(setting), Water tank temp(setting), Floor Heating supply Water Setting Temp.
3 Binary Input X’00C0 0000’ 12582912
Indoor unit general error mark, On/ Off(status), Specific error mark for the GMV Water Heater, Disinfecting, Floor heat power, Outdoor unit general error mark , Complete machine compressor state
4 Binary Output X’0100 0000’ 16777216 On/Off(setting)
5 Binary Value X’0140 0000’ 20971520
Swing(setting), Energy saving(setting), Remote temp shield mark(setting), Remote mode shield mark(setting), Remote On/Off shield mark(setting), Remote lock mark(all shield)(setting)
6 Calendar X’0180 0000’ 25165824
7 Command X’01C0 0000’ 29360128
Page 42
BACnet Gateway Kit for Central Air Conditioners
26
8 Device X’0200 0000’ 96468992
9 Event-Enrollment X’0240 0000’ 37748736
10 File X’0280 0000’ 41943040
11 Group X’02C0 0000’ 46137344
12 Loop X’0300 0000’ 50331648
13 Multistate Input X’0340 0000’ 54525952
Indoor unit error code, Indoor unit
mode(status), Fan Speed(status), Specific error codes for the GMV Water Heater, Water tank(status), Water tank mode(status), Outdoor
unit error code
14 Multistate Output X’0380 0000’ 58720256
15 Notication Class X’03C0 0000’ 62914560
16 Program X’0400 0000’ 67108864
17 Schedule X’0440 0000’ 71303168
18 Averaging X’0480 0000’ 75497472
19 Multistate Value X’04C0 0000’ 79691776
Indoor unit mode(setting), Fan Speed(setting), Water tank(setting), Water tank mode(setting), Water tank control shielding code(setting)
20 Trend Log X’0500 0000’ 83886080
21 Life Safety Point X’0540 0000’ 88080384
22 Life Safety Zone X’0580 0000’ 92274688
23 Accumulator X’05C0 0000’ 96468992
24 Pulse Converter X’0600 0000’ 100663296
25 Event Log X’0640 0000’ 104857600
26 Reserve X’0680 0000’ 109051904
27
Trend Log
Multiple
X’06C0 0000’ 113246208
28 load-control X’0700 0000’ 117440512
29 structured-view X’0740 0000’ 121634816
30 access-door X’0780 0000’ 125829120
Page 43
BACnet Gateway Kit for Central Air Conditioners
27
3�2 BACnet Point List
A BACnet Object Identier value shall consist of two components: Object Type and Instance
Number. The BACnet object uses the data eld of the instance number 22 as shown below.
(High)70 70 70 70 (Low)
Object Type (Bits Instance (22 Bits)
XX YYY
ZZ
Bits for the same type object type of each air conditioning unit
1Bit 7Bit
6Bit
Bits for the indoor unit number
8Bit
Bits for the outdoor unit number Always 1 for the VRF units.
The detailed object is explicated as below (table 3.2.1 and table 3.2.2 are two parts of the
whole point list)
Notes:
1) A object name includes XX_YYY_ZZ, and following each parameter represents the air
conditioning unit number. Wherein, XX means Air condition type, like GMV is 01;YYY means
Outdoor Unit's number, like GMV is between 001 and 004 now(this means the communication
module’s address); ZZ means Indoor Unit's number, like GMV is between 01 and 16 now, otherwise
00 means device YYY's Parameters.
For instance:
IndoorUnitModeCommand_01_001_01: On/ Off setting of the GMV outdoor unit 1 and indoor
unit 1�
IndoorUnitModeCommand_01_001_16: On/Off setting point of the GMV outdoor unit 1 and
indoor unit16�
OutdoorUnitErrorMark_01_001_00: General error of the GMV outdoor unit.
WaterTankModeCommand_01_004_00: Want tank mode setting of the GMV outdoor unit 4,
only applicable to the unit which can functions as the water heater.
2) See Appendix C, Appendix D, Append E and Appendix F for more details about alarm codes
and shield mark.
3) GMV water heater includes both the specific parameters of GMV water heater and
parameters of GMV outdoor units.
4) Parameters marked with* are only for the multi GMV water heater with oor heating function.
Page 44
BACnet Gateway Kit for Central Air Conditioners
28
Table 3.2.1
Parameter
number
Parameter name Object name Object ID
Object
Type
Parameters of GMV Indoor Units
1
Indoor unit general error
mark
IndoorUnitErrorMark_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+1 BI
2 Indoor unit error code IndoorUnitErrorCode_XX_YYY_ZZ MI(13)+YYY*8192+ZZ*64+1 MI
3
Indoor unit environment
Temp
IndoorUnitEnvironmentTemp_XX_
YYY_ZZ
AI(0)+YYY*8192+ZZ*64+1 AI
4 Indoor unit Temp(setting)
IndoorUnitTempCommand_XX_YYY_
ZZ
AV(2)+YYY*8192+ZZ*64+1 AV
5 Indoor unit mode(status) IndoorUnitModeStatus_XX_YYY_ZZ MI(13)+YYY*8192+ZZ*64+2 MI
6 Indoor unit mode(setting)
IndoorUnitModeCommand_XX_YYY_
ZZ
MV(19)+YYY*8192+ZZ*64+1 MV
7 On/Off(status) OnOffStatus_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+2 BI
8 On/Off(setting) OnOffCommand_XX_YYY_ZZ BO(4)+YYY*8192+ZZ*64+1 BO
9 Fan Speed(status) FanSpeedStatus_XX_YYY_ZZ MI(13)+YYY*8192+ZZ*64+3 MI
10 Fan Speed(setting) FanSpeedCommand_XX_YYY_ZZ MV(19)+YYY*8192+ZZ*64+2 MV
11 Swing(setting) SwingCommand_XX_YYY_ZZ BV(5)+YYY*8192+ZZ*64+1 BV
12 Energy saving(setting)
EnergySavingCommand_XX_YYY_
ZZ
BV(5)+YYY*8192+ZZ*64+2 BV
13
Remote temp shield
mark(setting)
RemoteTempShieldCommand_XX_
YYY_ZZ
BV(5)+YYY*8192+ZZ*64+3 BV
14
Remote mode shield
mark(setting)
RemoteModeShieldCommand_XX_
YYY_ZZ
BV(5)+YYY*8192+ZZ*64+4 BV
15
Remote On/Off shield
mark(setting)
RemoteOnOffShieldCommand_XX_
YYY_ZZ
BV(5)+YYY*8192+ZZ*64+5 BV
16
Remote lock mark(all
shield)(setting)
RemoteLockCommand_XX_YYY_ZZ BV(5)+YYY*8192+ZZ*64+6 BV
Specic Parameters of GMV Water Heater
17
Specic error mark for the
GMV Water Heater
GMVWaterHeaterSpecicErrorMark_
XX_YYY_ZZ
BI(3)+YYY*8192+ZZ*64+1 BI
18
Specic error codes for the
GMV Water Heater
GMVWaterHeaterSpecificErrorCode
s_XX_YYY_ZZ
MI(13)+YYY*8192+ZZ*64+1 MI
19 Water tank temp(status) WaterTankTempStatus_XX_YYY_ZZ AI(0)+YYY*8192+ZZ*64+1 AI
20 Water tank temp(setting)
WaterTankTempCommand_XX_
YYY_ZZ
AV(2)+YYY*8192+ZZ*64+1 AV
21 Water tank(status) WaterTankStatus_XX_YYY_ZZ MI(13)+YYY*8192+ZZ*64+2 MI
22 Water tank(setting) WaterTankCommand_XX_YYY_ZZ MV(19)+YYY*8192+ZZ*64+1 MV
23 Water tank mode(status) WaterTankModeStatus_XX_YYY_ZZ MI(13)+YYY*8192+ZZ*64+3 MI
Page 45
BACnet Gateway Kit for Central Air Conditioners
29
24 Water tank mode(setting)
WaterTankModeCommand_XX_
YYY_ZZ
MV(19)+YYY*8192+ZZ*64+2 MV
25
Double-Tube supply Water
Temp
DoubleTubeSupplyWaterTemp_XX_
YYY_ZZ
AI(0)+YYY*8192+ZZ*64+2 AI
26
Floor Heating supply
Water Setting Temp.
FloorHeatingSupplyWater
SettingTemp_XX_YYY_ZZ
AV(2)+YYY*8192+ZZ*64+2 AV
27 Disinfecting Disinfecting_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+2 BI
28 Floor heat power FloorHeatPower_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+3 BI
29
Water tank control
shielding code(setting)
WaterTankControlShieldingCodeCom
mand_XX_YYY_ZZ
MV(19)+YYY*8192+ZZ*64+3 MV
Parameters of GMV Outdoor Units
30
Outdoor unit general error
mark
OutdoorUnitErrorMark_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+4 BI
31 Outdoor unit error code OutdoorUnitErrorCode_XX_YYY_ZZ MI(13)+YYY*8192+ZZ*64+4 MI
32
Outdoor environment
temp
OutdoorEnvironmentTemp_XX_YYY_
ZZ
AI(0)+YYY*8192+ZZ*64+3 AI
33
Complete machine
compressor state
CompleteMachineCompressorState_
XX_YYY_ZZ
BI(3)+YYY*8192+ZZ*64+5 BI
Table 3.2.2
Parameter
number
Instance Number Present_Value Units
Min_
Pres_
Value
Max_
Pres_
Value
Resolution
Parameters of GMV Indoor Units
1 YYY*8192+ZZ*64+1 0:without, 1:with
2 YYY*8192+ZZ*64+1 see Alarm codes
3 YYY*8192+ZZ*64+1 -20~100 -20 100 1
4 YYY*8192+ZZ*64+1 16~30
5 YYY*8192+ZZ*64+2
1- Cool, 2- Dehumidify,3- Fan,4-
Heat; Others-0 means nothing, used
insignicance symbol to express, like
"--";
6 YYY*8192+ZZ*64+1
1- Cool,2- Dehumidify,3- Fan,4-
Heat;Others:0 means nothing, used
insignicance symbol to express, like
"--";
7 YYY*8192+ZZ*64+2 0:Off,1:On
8 YYY*8192+ZZ*64+1 0:Off,1:On
9 YYY*8192+ZZ*64+3
0- Auto fan speed,1- Low fan
speed,2- Middle fan speed,3- High
fan speed;
10 YYY*8192+ZZ*64+2
1- Low fan speed,2- Middle fan
speed,3- High fan speed;
11 YYY*8192+ZZ*64+1 0:Off,1:On
Page 46
BACnet Gateway Kit for Central Air Conditioners
30
12 YYY*8192+ZZ*64+2 0:Off,1:On
13 YYY*8192+ZZ*64+3 0:Without shield ,1:Shield
14 YYY*8192+ZZ*64+4 0:Without shield ,1:Shield
15 YYY*8192+ZZ*64+5 0:Without shield ,1:Shield
16 YYY*8192+ZZ*64+6 0:Without shield ,1:Shield
Specic Parameters of GMV Water Heater
17 YYY*8192+ZZ*64+1 0:without, 1:with
18 YYY*8192+ZZ*64+1 see Alarm codes
19 YYY*8192+ZZ*64+1
1) Hot Water, Night, Reserve
modes:35 ~58 (the upper
limit can be adjusted to 65 );
2) Energy saving mode:35 ~50 ;
3) High temp sterilization mode:65
~70 ;
1
20 YYY*8192+ZZ*64+1
1) Hot Water, Night, Reserve
modes:35 ~58 (the upper
limit can be adjusted to 65 );
2) Energy saving mode:35 ~50 ;
3) High temp sterilization mode:65
~70 ;
21 YYY*8192+ZZ*64+2
7-off,8-heat preservation and
standby,9-heating water
22 YYY*8192+ZZ*64+1
7-off,8-heat preservation and
standby,9-heating water
23 YYY*8192+ZZ*64+3
1-energy saving mode mode,2-
reservation mode mode,3-night
mode,4-hot water mode
24 YYY*8192+ZZ*64+2
1-energy saving mode mode,2-
reservation mode mode,3-night
mode,4-hot water mode
25 YYY*8192+ZZ*64+2 -127~255 -127 255 1
26 YYY*8192+ZZ*64+2 30~52
27 YYY*8192+ZZ*64+2 0:No,1:Yes
28 YYY*8192+ZZ*64+3 0:off, 1:on
29 YYY*8192+ZZ*64+3 see shield mark codes
Parameters of GMV Outdoor Units
30 YYY*8192+ZZ*64+4 0:without, 1:with
31 YYY*8192+ZZ*64+4 see Alarm codes
32 YYY*8192+ZZ*64+3 -127~255 -127 255 1
33 YYY*8192+ZZ*64+5 0:off, 1:on
Page 47
BACnet Gateway Kit for Central Air Conditioners
31
3.3 Detailed Descriptions of BACnet Objects
For each communication status, objects related to the unit are treated on the BANnet as
follows:
(1) It is known from the BACnet gateway topology that the BACnet objects related to the
units include those about the GMV outdoor unit and GMV indoor unit. As for the GMV water
heater unit, BACnet objects also include those about the water tank and oor heating device
additionally.
(2) Indoor unit general error mark
Member number:1
Object name:IndoorUnitErrorMark_XX_YYY_ZZ (XX means Air condition type,like GMV is
01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Binary output
Object ID: BI(3)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the general error of the indoor unit.
Present_Value:
ACTIVE:with
INACTIVE:without
Note :
1) When some error occurs to any one of the indoor unit, Present_Value property will turn to
ACTIVE and raise an alarm.
2) Present_Value property is defaulted to be INACTIVE.
(3) Indoor unit error code
Member number:2
Object name:IndoorUnitErrorCode_XX_YYY_ZZ (XX means Air condition type,like GMV is
01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the error code of the indoor unit. For more details see
Appendix C�
Present_Value:
0x00000000-0x000003FF (See Appendix C)
Notes:
1) When some error occurs to the indoor unit, Present_Value property will produce a decimal
numerial� For more details see Appendix C�
2) Multiple error may concur. Each error has a independent error code, e.g. 0x00000008 for
“Outlet Tube Temp Sensor Error”,0x00000010 for “Inlet Tube Temp Sensor Error”. When these
errors just happen together, Present_Value property will be 24 (conversion method: 0x00000008
plus 0x00000010 is 0x00000018, that is equal to the decimal numeral 24).
Page 48
BACnet Gateway Kit for Central Air Conditioners
32
3) When some communication error occurs, it indicates the indoor unit is not well connected
with the communication module. When the message “Indoor Unit/Wired Controller Communication
Error Mark” is sent, it indicates the outdoor unit is not well connected with the indoor unit or the
wired controller�
(4) Indoor unit environment Temp
Member number:3
Object name:IndoorUnitEnvironmentTemp_XX_YYY_ZZ (XX means Air condition type,like GMV
is 01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Analog Input
Object ID: AI(0)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the indoor unit environment temperature.
Present_Value:-20~100
Units: degrees-Celsius or
Min_Pres_Value: -20
Max_Pres_Value: 100
Resolution: 1
Note :
(5) Indoor unit mode(status)
Member number:4
Object name:IndoorUnitModeStatus_XX_YYY_ZZ (XX means Air condition type,like GMV is
01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the running mode of the indoor unit.
Present_Value:
1- Cool,
2- Dehumidify,
3- Fan,
4- Heat;
Others: 0 means nothing, can use insignicance symbol to express, like "--";
Note :
1) The indoor unit running mode takes effective only when the unit is turned on.
(6) Indoor unit mode(setting)
Member number:5
Object name:IndoorUnitModeCommand_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Page 49
BACnet Gateway Kit for Central Air Conditioners
33
Object type: Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the mode setting of the indoor unit.
Present_Value:
1- Cool,
2- Dehumidify,
3- Fan,
4- Heat;
Note :
1) The indoor unit running mode takes effective only when the unit is turned on.
2) For the cooling only unit, the “HEAT” parameter takes ineffective.
3) It is required to judge if the setting parameter sent by the BMS is within the effective range.
(7) On/Off(status)
Member number:6
Object name:OnOffStatus_XX_YYY_ZZ (XX means Air condition type,like GMV is 01;YYY
means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor Units's
number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: It is used to monitor the on/off status of the indoor unit.
Present_Value:
ACTIVE:On
INACTIVE:Off
Note :
1) When the unit runs normally, Present_Value wil reect the real-time on/off status of the unit.
(8) On/Off(setting)
Member number:7
Object name:OnOffCommand_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Binary Output
Object ID: BO(4)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the on/off setting of the unit.
Present_Value:
ACTIVE:On
INACTIVE:Off
Notes:
1) Relinquish default is INACTIVE.
2) In the event that the Present-Value of “Indoor unit mode (status)” is “0”, it will be defaulted to
Page 50
BACnet Gateway Kit for Central Air Conditioners
34
“1” responding to the “On” command.
3) When some error still exists on the unit, the unit may fail to be started prior to the clearance
of the error.
(9) Fan Speed(status)
Member number:8
Object name:FanSpeedStatus_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to monitor the fan speed status of the indoor unit.
Present_Value:
0- Auto fan speed,
1- Low fan speed,
2- Middle fan speed,
3- High fan speed;
Note :
1) When the unit run normally, Present_Value wil reect the real-time fan speed status.
2) Under the “DRY” mode, Present_Value will keep at “1”- “Low fan speed”.
(10) Fan Speed(setting)
Member number :9
Object name:FanSpeedCommand_XX_YYY_ZZ (XX means Air condition type,like GMV is
01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the fan speed setting of the indoor unit.
Present_Value:
1- Low fan speed,
2- Middle fan speed,
3- High fan speed;
Notes :
1) Under the “DRY” mode, Present_Value will keep at “1”- Low fan speed.
2) When Present_Value property is “0”, it indicates the unit runs at the auto fan speed.
However, BACnet species that the MV object can not be set in such a way, therefore it is invalid.
(11) Swing(setting)
Member number :10
Object name:SwingCommand_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Units's number, like GMV is between 001 and 004 now; ZZ means Indoor Units's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Page 51
BACnet Gateway Kit for Central Air Conditioners
35
Object type:Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the Swing setting of the indoor fan.
Present_Value:
ACTIVE:On
INACTIVE:Off
Note:
1) The Present_Value can reect the real-time Swing state of the unit. That is, it varies as the
change of the Swing setting of the wired controller or the wires controller.
(12) Energy saving(setting)
Member number:11
Object name:EnergySavingCommand_XX_YYY_ZZ (XX means Air condition type,like GMV is
01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the energy saving setting of the indoor unit.
Present_Value:
ACTIVE: On
INACTIVE:Off
Notes:
1) the Present_Value can reect the real-time energy saving setting of the unit. That is, it varies
as the change of the energy saving setting of the wired controller or the wires controller.
2) When Present_Value is ACTIVE, under either the “COOL” or “HEAT” mode, the unit will run
among the energy saving temperature limit so as to save more energy.
(13) Remote temp shield mark (setting)
Member number: 12
Object name:RemoteTempShieldCommand_XX_YYY_ZZ (XX means Air condition type,like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Binary Value
Object ID: BV (5)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to enable or disable the wired or wireless controller to set the
room temperature�
Present_Value:
ACTIVE:Shield
INACTIVE: Without shield
Note :
Page 52
BACnet Gateway Kit for Central Air Conditioners
36
1) Present_Value is ACTIVE, the wired or wireless controller is disabled to set the room
temperature�
2) Present_Value is ACTIVE,the BMS is enabled to control the room temperature.
(14) Remote mode shield mark(setting)
Member number :13
Object name:RemoteModeShieldCommand_XX_YYY_ZZ (XX means Air condition type,like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means deviceYYY's
Parameters.)
Object type:Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+4
Instance Number: YYY*8192+ZZ*64+4
Description: this object is used to enable or disable the wired or wireless controller to set the
running mode the unit.
Present_Value:
ACTIVE: Shield
INACTIVE: Without shield
Note :
1) When Present_Value is ACTIVE, the wired or wireless controller is disabled to set the
running mode of the unit.
2) When Present_Value is ACTIVE, the BMS is enabled to control the running mode of the unit.
(15) Remote On/Off shield mark (setting)
Member number :14
Object name:RemoteOnOffShieldCommand_XX_YYY_ZZ (XX means Air condition type,like
GMV is 01;YYY means Outdoor Unit 's number, like GMV is between 001 and 004 now;ZZ means
Indoor Unit's number ,like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+5
Instance Number: YYY*8192+ZZ*64+5
Description: this object is used to enable the wired or wireless controller to start or stop the unit.
Present_Value:
ACTIVE:Shield
INACTIVE:Without shield
Note :
1) When Present_Value is ACTIVE, the wired or wireless controller is enabled to start or stop
the unit.
2) When Present_Value is ACTIVE, the BMS is enabled to control the start or stop of the unit.
(16) RemoteLockCommand_XX_YYY_ZZ
Member number :15
Object name:RemoteLockCommand_XX_YYY_ZZ (XX means Air condition type,like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Page 53
BACnet Gateway Kit for Central Air Conditioners
37
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+6
Instance Number: YYY*8192+ZZ*64+6
Description: this object is used to enable or disable the wired or wireless controller to set any
parameter�
Present_Value:
ACTIVE:Shield
INACTIVE:Without shield
Note :
1) When Present_Value is ACTIVE, the wired or wireless controller is disable to set any
parameter of the unit.
2) When Present_Value is ACTIVE, the BMS controller is enabled to control all functions of the
indoor unit�
(17) Specic error mark for the GMV water heater
Member number :16
Object name:GMVWaterHeaterSpecificErrorMark_XX_YYY_ZZ (XX means Air condition
type,like GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;
ZZ means Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device
YYY's Parameters.)
Object type: Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the special error mark of the GMV water heater unit.
Present_Value:
ACTIVE: with
INACTIVE:without
Note :
1) As for the GMV water heater unit, it includes both the special water heater error and general
error of GMV outdoor unit. When this error occurs, Present_Value property wil turn to ACTIVE and
an alarm will be raised.
2) Present_Value property is defaulted to be INACTIVE.
3) This parameter is only for the GMV water heater.
(18) Specic error codes for the GMV Water Heater
Member number :17
Object name:GMVWaterHeaterSpecificErrorCodes_XX_YYY_ZZ (XX means Air condition
type,like GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;
ZZ means Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device
YYY's Parameters.)
Object type: Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+1
Page 54
BACnet Gateway Kit for Central Air Conditioners
38
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the error code of the GMV water heart. For more
details see Appendix E�
Present_Value:
0x00010000-0x0001FFFF (See Appendix E)
Note :
1) When some error occurs to the GMV water heater, Present_Value property will be a decimal
numeral related to the error code.
2) Multi errors may concur. Each error has a independent error code, e.g. 0x00000040 for “Water
Tank Upper Temp Sensor Error”, 0x00000080 for “Water Tank Lower Temp Sensor Error”. When
these two errors just happen together, Present_Value property will be192 (conversion method:
0x00000040 OR 0x00000080 is 0x000000C0,equal to192).
3) This parameter is only for the GMV water heater.
(19) Water tank temp(status)
Member number :18
Object name:WaterTankTempStatus_XX_YYY_ZZ (XX means Air condition type, like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Analog Input
Object ID: AI(0)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the water tank temperature status of the GMV water
heater..
Present_Value:
① .
Hot Water, Night, Reserve modes:35 ~58 (the upper limit can be adjusted to 65 );
② .
Energy saving mode:35 ~50 ;
③ .
High temp sterilization mode:65 ~70 ; Units: degrees-Celsius or
Resolution: 1
Note :
1) The temperature status of the water tank varies as the change of the running mode of the
water tank.
2) This parameter is only for the GMV water heater.
(20) Water tank temp(setting)
Member number :19
Object name:WaterTankTempCommand_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type:Analog Value
Object ID: AV(2)+YYY*8192+ZZ*64+1
Page 55
BACnet Gateway Kit for Central Air Conditioners
39
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the temperature setting of the water tank of the GMV
water heater.
Present_Value:
① .
Hot Water, Night, Reserve modes:35 ~58 (the upper limit can be adjusted to 65 );
② .
Energy saving mode:35 ~50 ;
③ .
High temp sterilization mode:65 ~70 ; Units: degrees-Celsius or
Notes:
1) The temperature status of the water tank varies as the change of the running mode of the
water tank. This object name is WaterTankModeStatus_XX_YYY_ZZ.
2) This parameter is only for the GMV water heater.
(21) Water tank temp(setting)
Member number :20
Object name:WaterTankTempCommand_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type:Analog Value
Object ID: AV(2)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the temperature setting of the water tank of the GMV
heater water.
Present_Value:
① .
Hot Water, Night, Reserve modes:35 ~58 (the upper limit can be adjusted to 65 );
② .
Energy saving mode:35 ~50 ;
③ .
High temp sterilization mode:65 ~70 ; Units: degrees-Celsius or
Notes:
1) The temperature setting range of the water tank varies as the change of the running mode of
the water tank whose object name is WaterTankModeStatus_XX_YYY_ZZ.
2) This parameter is only for the GMV water heater.
(22) Water tank(status)
Member number :21
Object name:WaterTankStatus_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the status of the water tank of GMV water heater.
Present_Value:
Page 56
BACnet Gateway Kit for Central Air Conditioners
40
7-off;
8-heat preservation and standby;
9-heating water.
Note:
1) This parameter is only for the GMV water heater.
(23) Water tank(setting)
Member number :22
Object name:WaterTankCommand_XX_YYY_ZZ (XX means Air condition type, like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the status setting of the water tank of GMV water
heater.
Present_Value:
7-off;
8-heat preservation and standby;
9-heating water.
Note :
1) Present_Value “7” and “8” can be set successfully only when they comply with the
temperature control logic of the unit.
2) This parameter is only for the GMV water heater.
(24) Water tank mode(status)
Member number :23
Object name:WaterTankModeStatus_XX_YYY_ZZ (XX means Air condition type, like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to monitor the status of the water tank of GMV water heater.
Present_Value:
1-energy saving mode;
2-reservation mode;
3-night mode;
4-hot water mode.
Notes:
1) This parameter is only for the GMV water heater.
Page 57
BACnet Gateway Kit for Central Air Conditioners
41
(25) Water tank mode(setting)
Member number :24
Object name:WaterTankModeCommand_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type:Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the mode setting of the water tank of GMV water
heater.
Present_Value:
1-energy saving mode mode;
2-reservation mode mode;
3-night mode;
4-hot water mode.
Note :
1) Present_Value can reflect the running mode of the water tank. That is, it varies as the
change of the water tank mode setting of the wired controller or the wires controller.
2) This parameter is only for the GMV water heater.
(26) Double-Tube supply Water Temp
Member number :25
Object name:DoubleTubeSupplyWaterTemp_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Analog Input
Object ID: AI(0)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the double-tube supply water temperature of GMV
water heater.
Present_Value:
-127-255
Units: degrees-Celsius or
Min_Pres_Value: -127
Max_Pres_Value: 255
Resolution:1
Note :
1) This parameter is only for the GMV water heater.
(27) Floor Heating supply water setting temp.
Member number :26
Object name:FloorHeatingSupplyWaterSettingTemp_XX_YYY_ZZ (XX means Air condition
Page 58
BACnet Gateway Kit for Central Air Conditioners
42
type, like GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;
ZZ means Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device
YYY's Parameters.)
Object type: Analog Value
Object ID: AV(2)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the setting temperature of oor heating of GMV water
heater.
Present_Value:
30-52
Units: degrees-Celsius or
Note :
1) This parameter is only for the GMV water heater with oor heating device.
(28) Disinfecting
Member number :27
Object name:Disinfecting_XX_YYY_ZZ (XX means Air condition type,like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the disinfecting status of GMV water heater.
Present_Value:
ACTIVE: Yes
INACTIVE:No
Note:
1) This parameter is only for the GMV water heater.
(29) Floor heat power
Member number :28
Object name:FloorHeatPower_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to monitor the on/off status of the oor heating device of GMV
water heater.
Present_Value:
ACTIVE: On
INACTIVE:Off
Note :
1) This parameter is only for the GMV water heater.
Page 59
BACnet Gateway Kit for Central Air Conditioners
43
(30) Water tank control shielding code(setting)
Member number :29
Object name:WaterTankControlShieldingCodeCommand_XX_YYY_ZZ (XX means Air condition
type,like GMV is 01;YYY means Outdoor Units's number,like GMV is between 001 and 004
now;ZZ means Indoor Units's number,like GMV is between 01 and 16 now,otherwise 00 means
deviceYYY's Parameters.)
Object type:Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to enable or disable the wired or wireless controller to control
the water tank of GMV water heater. For more details see Appendix F.
Present_Value:
0x00000001-0x80000000 (See Appendix F)
Note :
1) When Present_Value is “0”, it indicates the wired or wireless controller is enabled to control
the water tank.
2) Multiple functions of the water tank may be disabled to be set through the wired or wireless
controller, e.g. 0x00000001 for “On/Off Shielding State” 0x00000004 for “Setting Temp Shielding
State”. When these two happen together, then Present_Value property will be “5” (conversion
method: 0x00000001 OR 0x00000004 is 0x00000005, equal to 5).
3) When Present_Value is 0x8000000, all disabled functions will be enabled and the Present_
Value property will be “0”.
4) This parameter is only for the GMV water heater.
(31) Outdoor unit general error mark
Member number :30
Object name:OutdoorUnitErrorMark_XX_YYY_ZZ (XX means Air condition type,like GMV is
01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+4
Instance Number: YYY*8192+ZZ*64+4
Description: this object is used to monitor the outdoor unit error.
Present_Value:
ACTIVE: with
INACTIVE:without
Note :
1) When some error occurs to the GMV outdoor unit, Present_Value property will turen to
“ACTIVE” and raise an alarm.
2) Present_Value property is defaulted to be INACTIVE.
(32) Outdoor unit error code
Member number :3
1
Object name:OutdoorUnitErrorCode_XX_YYY_ZZ (XX means Air condition type, like GMV
Page 60
BACnet Gateway Kit for Central Air Conditioners
44
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type:Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+4
Instance Number: YYY*8192+ZZ*64+4
Description: this object is used to monitor the error code of the GMV outdoor unit. For more
details see Appendix D
Present_Value:
0x00000000-0x003FFFFF (For more details see Appendix D)
Note :
1) When some error occurs to the GMV outdoor unit, Present_Value property will be the
decimal numerical� For more details, please see Appendix D�
2) Multiple errors may concur. Each error has a independent error code, e.g. 0x00000001 for
“Outdoor Environment Temp Sensor Error”, 0x00000040 for “High Pressure Transducer Error”.
When these two error do occur together, Present_Value property will be “65”. (conversion method:
0x00000001 OR 0x00000040 is 0x00000041, equal to 65).
(
33) Outdoor environment temp
Member number :32
Object name: Outdoor Environment Temp_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Analog Input
Object ID: AI(0)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to monitor the outdoor environment temperature.
Present_Value:
-127-255
Units: degrees-Celsius or
Min_Pres_Value: -127
Max_Pres_Value: 255
Resolution: 1
Note:
(34) Complete machine compressor state
Member number :33
Object name:CompleteMachineCompressorState_XX_YYY_ZZ (XX means Air condition type,
like GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ
means Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device
YYY's Parameters.)
Object type: Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+5
Page 61
BACnet Gateway Kit for Central Air Conditioners
45
Instance Number: YYY*8192+ZZ*64+5
Description: this object is used to monitor the on/off status of the compressor of the GMV
outdoor unit�
Present_Value:
ACTIVE: On
INACTIVE:Off
Note :
Page 62
BACnet Gateway Kit for Central Air Conditioners
46
Appendix C Indoor Unit Error Codes
Indoor Unit Error Codes
Present_Value
Code
Meaning
B32 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
0x00000001 0 0 0 0 0 0 0 0 0 0 0 1 Indoor Unit Mode Conict Mark
0x00000002 0 0 0 0 0 0 0 0 0 0 1 0 Full Water Protection Mark
0x00000004 0 0 0 0 0 0 0 0 0 1 0 0 Midway Tube Temp Sensor Error
0x00000008 0 0 0 0 0 0 0 0 1 0 0 0 Outlet Tube Temp Sensor Error
0x00000010 0 0 0 0 0 0 0 1 0 0 0 0 Inlet Tube Temp Sensor Error
0x00000020 0 0 0 0 0 0 1 0 0 0 0 0
Environment Temperature
Sensor Error
0x00000040 0 0 0 0 0 1 0 0 0 0 0 0 Auxiliary Heater Protection Error
0x00000080 0 0 0 0 1 0 0 0 0 0 0 0 Freeze Protection
0x00000100 0 0 0 1 0 0 0 0 0 0 0 0 Communication Error
0x00000200 0 0 1 0 0 0 0 0 0 0 0 0
Indoor Unit/Wired Controller
Communication Error Mark
Page 63
BACnet Gateway Kit for Central Air Conditioners
47
Appendix D Outdoor Unit Error Codes
Outdoor Unit Error Codes
Present_Value
Code
Meaning
B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
0x00000001 0 0 0 0 0 0 0 0 0 0 1
Outdoor Environment Temp Sensor
Error
0x00000002 0 0 0 0 0 0 0 0 0 1 0
Outdoor Unit Inlet Tube Temp
Sensor Error
0x00000004 0 0 0 0 0 0 0 0 1 0 0
Outdoor Unit Midway Tube Temp
Sensor Error
0x00000008 0 0 0 0 0 0 0 1 0 0 0
Outdoor Unit Outlet Tube Temp
Sensor Error
0x00000010 0 0 0 0 0 0 1 0 0 0 0
Fixed-Frequency Compressor
Discharge Temp Sensor Error
0x00000020 0 0 0 0 0 1 0 0 0 0 0
Variable-Volume Compressor
Discharge Temp Sensor Error
0x00000040 0 0 0 0 1 0 0 0 0 0 0 High Pressure Transducer Error
0x00000080 0 0 0 1 0 0 0 0 0 0 0
Fixed-Frequency Compressor Oil
Temp Sensor Error
0x00000100 0 0 1 0 0 0 0 0 0 0 0 Low Pressure Transducer Error
0x00000200 0 1 0 0 0 0 0 0 0 0 0
Variable-Volume Compressor Oil
Temp Sensor Error
0x00000400 1 0 0 0 0 0 0 0 0 0 0 High Pressure Protection
Page 64
BACnet Gateway Kit for Central Air Conditioners
48
Outdoor Unit Error Codes
Present_
Value
Code
Meaning
B32 B22 B21 B20 B19 B18 B17 B16 B15 B14 B13 B12
0x00000800 0 0 0 0 0 0 0 0 0 0 0 0 1 0
Low Pressure
Protection/Refrigeration
Insufciency Protection
0x00001000 0 0 0 0 0 0 0 0 0 0 0 1 0 0
Discharge Protection/
Oil Temperature
Protection
0x00002000 0 0 0 0 0 0 0 0 0 0 1 0 0 0
Overcurrent Protection/
Drive Error
0x00004000 0 0 0 0 0 0 0 0 0 1 0 0 0 0 Communication Error
Applicable only to the digital multi GMV system (R22) and digital multi GMV system (R410A) with the capacity of 56 and 60kW
0x00008000 0 0 0 0 0 0 0 0 1 0 0 0 0 0
Subunit Outlet Tube
Temp Sensor Error
0x00010000 0 0 0 0 0 0 0 1 0 0 0 0 0 0
Subunit Midway Tube
Temp Sensor Error
0x00020000 0 0 0 0 0 0 1 0 0 0 0 0 0 0
Subunit Inlet Tube
Temp Sensor Error
0x00040000 0 0 0 0 0 1 0 0 0 0 0 0 0 0
Subunit Oil Temp
Sensor Error (1)
0x00080000 0 0 0 0 1 0 0 0 0 0 0 0 0 0
Subunit Discharge
Temp Sensor Error (2)
0x00100000 0 0 0 1 0 0 0 0 0 0 0 0 0 0
Subunit Discharge
Temp Sensor Error (1)
0x00200000 0 0 1 0 0 0 0 0 0 0 0 0 0 0
Subunit Oil Temp
Sensor Error (2)
Page 65
BACnet Gateway Kit for Central Air Conditioners
49
Appendix E Specic Error Codes for the GMV Water Heater
Specic Error Codes for the GMV Water Heater
Present_
Value
Code
Meaning
B32 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
0x00000001 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Outdoor Unit Inlet Tube Temp
Sensor Error (1)
0x00000002 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0
Outdoor Unit Midway Tube
Temp Sensor Error (1)
0x00000004 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
Outdoor Outlet Tube Temp
Sensor Error (1)
0x00000008 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
Outdoor Unit Inlet Tube Temp
Sensor Error (2)
0x00000010 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0
Outdoor Unit Midway Tube
Temp Sensor Error (2)
0x00000020 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0
Outdoor Outlet Tube Temp
Sensor Error (2)
0x00000040 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0
Water Tank Upper Temp
Sensor Error
0x00000080 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0
Water Tank Lower Temp
Sensor Error
0x00000100 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0
Water Tank Outlet Tube Temp
Sensor Error
0x00000200 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0
Water Tank Inlet Tube Temp
Sensor Error
0x00000400 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 Hydrobox Communication Error
0x00000800 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
Electric Heater Dry Heating
Error
0x00001000 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 Creepage Protection
0x00002000 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 Contact Caking Error
0x00004000 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Water Flow Switch Protection
0x00008000 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Freeze Protection
0x00010000 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Jumper Cap Error
Page 66
BACnet Gateway Kit for Central Air Conditioners
50
Appendix F Water Tank Control Shielding Codes
Water tank control shielding codes
Present_Value
Code
Meaning
B32 B8 B7 B6 B5 B4 B3 B2 B1
0x00000001 0 0 0 0 0 0 0 0 0 1 On/Off Shielding State
0x00000002 0 0 0 0 0 0 0 0 1 0 User Mode Shielding State
0x00000003 0 0 0 0 0 0 0 1 0 0 Setting Temp Shielding State
0x00000004 0 0 0 0 0 0 1 0 0 0 Quick Water-Heating Shielding State
0x00000005 0 0 0 0 0 1 0 0 0 0 Cleaning Shielding State
0x00000006 0 0 0 0 1 0 0 0 0 0 Parameter Viewing Shielding State
0x00000007 0 0 0 1 0 0 0 0 0 0 Priority Control Shielding State
0x00000008 0 0 1 0 0 0 0 0 0 0 Lock State
……
0x80000000 1 0 0 0 0 0 0 0 0 0 All no shield command
Page 67
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 E-mail: gree@gree.com.cn www.gree.com
64134100001