Dimension of Carton Box (LXWXH)inch42 1/2X19X3342 1/2X19X33
Dimension of Package (LXWXH)inch42 21/32X19 13/64X33 21/3242 21/32X19 13/64X33 21/32
Net Weight Ib154.4 161.0
Gross WeightIb165.4 172.0
Refrigerant R410AR410A
Refrigerant Chargeoz84.6691.71
Lengthft24 39/6424 39/64
Gas Additional Chargeoz/ft0.20.5
Outer Diameter Liquid PipeinchΦ1/4Φ1/4
Outer Diameter Gas PipeinchΦ5/8Φ5/8
Max Distance Heightft32 3/1632 3/16
Max Distance Lengthft98 27/6498 27/64
Note:The connection pipe applies metric diameter.
inch
(GUANGZHOU)COMPRESSOR
CO. LTD
2-1/16
MITSUBISHI ELECTRIC
(GUANGZHOU)COMPRESSOR
CO. LTD
2-1/16
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information
7
2.2 Operation Characteristic Curve
CoolingHeating
)O
Capacity ratio (%)
24K
120
Current(A)
Service Manual
Cooling
14
12
10
8
6
4
2
Conditio
Indoor:DB 80°F
n
WB66
°F
Indoor air flow: Super High
Pipe length:24 39/64ft
0
020406080100120
Compressor Frequency(Hz)
Heating
14
12
10
8
6
Current(A)
4
Condition
Indoor:DB 70°F
2
Indoor air flow: Super High
Pipe length:24 39/64ft
0
020406080100
Compressor Frequency(Hz)
2.3 Capacity Variation Ratio According to Temperature
105
100
95
90
85
80
75
70
65
60
55
50
9095100105110
Conditions
Indoor:
DB 80°F
Indoor air flow: Super High
Pipe length :
WB66
24 39/64ft
°F
Outdoor temp. (˚F
110
100
90
80
70
60
Capacity ratio (%)
50
40
-4514
Conditions
Indoor:DB
Indoor air flow:Super High
Pipe length:
70°F
24 39/64ft
23324150
utdoor temp. (˚F)
8
Technical Information
Service Manual
Noise/dB(A)
2.4 Noise Curve
Indoor side noise Outdoor side noise
60
50
40
30
36K
30K
LM
Indoor fan motor rating speed
HSH
80
75
70
65
60
Noise dB(A)
55
50
45
203040 5060 708090 100
Compressor frequency(Hz)
36K
30K
2.5 Cooling and Heating Data Sheet in Rated Frequency
Cooling:
Rated cooling
condition(°F) (DB/WB)
IndoorOutdoor P (PSIG) T1 (°F)T2 (°F)
80/6695/-30K130~14546.8 to 52.8127 to 96.8Super HighHigh67
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Compressor
revolution
(rps)
80/66
95/-36K
Heating:
Rated heating
condition(°F) (DB/WB)
IndoorOutdoor P (PSIG) T1 (°F)T2 (°F)
70/-20/1930K507~550134.4 to 10236 to 39Super HighHigh61
70/-20/1936K507~550134.4 to 10236 to 39Super HighHigh58
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 24.6ft.
Model
130~145
Pressure of gas pipe
connecting indoor and
outdoor unit
46.8 to 52.8127 to 96.8
Inlet and outlet pipe
temperature of heat
exchanger
Super HighHigh
Fan speed of
indoor unit
Fan speed of
outdoor unit
60
Compressor
revolution
(rps)
Technical Information
9
1 37/64
3. Outline Dimension Diagram
3.1 Indoor Unit
Service Manual
12 53/64
13 25/321029 3/8
Φ2 3/4
11 19/32
3.2 Outdoor Unit
14 37/64
53 9/64
36 2/9
3 1/2
10
Φ2 3/4
Unit:inch
10
15 9/16
39 1/2
24
31 7/64
16 13/16
Unit:inch
Technical Information
Service Manual
4. Refrigerant System Diagram
30K:
Cooling only model
Indoor unit
Heat
exchanger
(evaporator)
Outdoor unit
Gas pipe
side
Valve
Discharge
Suction
Compressor
Accumlator
Heat
exchanger
Liquid pipe
(condenser)
side
Valve
Electron
expansion
valve
Capillary
Strainer
COOLING
Cooling and heating model
Indoor unit
Heat
exchanger
(evaporator)
Gas pipe
side
Valve
Liquid pipe
side
Valve
Discharge
Suction
Compressor
Strainer
Outdoor unit
4-Way valve
Accumlator
Heat
exchanger
(condenser)
Electron
expansion
valve
Capillary
Strainer
COOLING
HEATING
Technical Information
11
36K:
Indoor unit
Outdoor unit
Cooling only model
Service Manual
Gas pipe
side
Valve
Heat
exchanger
(evaporator)
Cooling and heating model
Indoor unit
Liquid pipe
side
Valve
Gas pipe
side
Valve
Discharge
Suction
Compressor
Accumlator
Electron
expansion
valve
Outdoor unit
Heat
exchanger
(condenser)
Strainer
COOLING
4-Way valve
12
Heat
exchanger
(evaporator)
Connection pipe specication:
Liquid pipe:1/4 inch
Gas pipe:5/8 inch
Liquid pipe
side
Valve
Discharge
Suction
Compressor
Strainer
Accumlator
Electron
expansion
valve
Heat
exchanger
(condenser)
Strainer
COOLING
HEATING
Technical Information
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Instruction
SymbolSymbol Color SymbolSymbol Color SymbolName
WHWhiteGNGreenCAPJumper cap
YEYellowBNBrownCOMPCompressor
RDRedBUBlueGrounding wire
YEGNYellow/GreenBKBlack//
VTVioletOGOrange//
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
The above data is subject to change without notice. Please refer to the nameplate of the unit.
<(*1
*
*
<(*1
*
14
Technical Information
Service Manual
5.2 PCB Printed Diagram
Indoor Unit
● Top view
5
6
● Bottom view
1
2 2 2
3 3
4
17 18 19 20 21
16
No.Name
1Power supply live wire
2Fuse
Interface of neutral wire for health
3
function
15
4Power supply neutral wire
5Interface of communication
14
13
6Power switch
7High-frequency transformer
8Interface of fan motor
9Buzzer
12
11
10Interface of display
11Interface of display
Indoor tube temperature sensor
12
interface
Ambient temperature sensor
13
interface
14Interface of wired controller
10
7
8
9
Interface of left and right swing
15
terminal
Interface of up and down swing
16
terminal
17Auto button
18Interface of BMS
19Jumper cap
20Interface of wired controller
Interface of live wire for health
21
function
Technical Information
15
Outdoor Unit
12345 6
10
12
13
● Top view
Service Manual
1415
No.NameNo.NameNo.Name
1 High-frequency transformer T16 High pressure protection terminal HPP111 Terminal of neutral wire
Overload protection terminal of
2
compressor OVC-COMP
3 Terminal of temp sensor CN28 Electric heater band of chassis HEAT2-L13 Terminal of ground wire
High pressure protection terminal
4
HPP
Electronic expansion valve terminal
5
EV
7 Terminal of 4-way valve12 Protective tube FU101
Electric heater band of compressor
9
HEAT1-L
10 Terminal of live wire15
14 Choke L 101 and L102
Terminal of outdoor fan
OFAN-DC
7
8
9
11
● Bottom view
16
Technical Information
Service Manual
6. Function and Control
6.1 Remote Controller Introduction
1
2
4
7
9
11
3
5
6
8
10
1
ON/OFF button
2
MODE button
3
FAN button
4
SWING button
5
TURBO button
6
▲/ button
7
SLEEP button
8
TEMP button
9
I FEEL button
▲
12
Introduction for icons on display screen
I feel
Operation mode
Auto mode
Cool mode
Dry mode
Fan mode
Heat mode
Clock
Sleep mode
Light
:Set temp.
:Outdoor ambient temp.
Temp. display type
:Indoor ambient temp.
10
LIGHT button
11
CLOCK button
TIMER ON / TIMER OFF
12
button
Set fan speed
Send signal
Turbo mode
8℃ heating function
WIFI(This unit without WiFi fuction)
Set temperature
Set time
TIMER ON / TIMER OFF
Child lock
Up & down swing
Introduction for buttons on remote controller
Note:
● After putting through the power, the air conditioner will give out a sound. Operation indictor " " is ON (red indicator). After that,
you can operate the air conditioner by using remote controller.
●
Under on status, pressing the button on the remote controller, the signal icon " "
and the air conditioner will give out a “de” sound, which means the signal has been sent to the air conditioner.
● Under off status, set temperature and clock icon will be displayed on the display
of remote controller (If timer on, timer off and light functions are set, the corre- sponding icons will be displayed on the display of
remote controller at the same
time); Under on status, the display will show the corresponding set function icons.
Technical Information
on the display of remote controller will blink once
17
Service Manual
1. ON/OFF button
Press this button can turn on or turn off the air conditioner. After turning on the air conditioner, operation indicator " "on indoor unit’s
display is ON (green indicator. The colour is different for different models), and indoor unit will give out a sound.
2. MODE button
Press this button to select your required operation mode.
AUTO
● When selecting auto mode, air conditioner will operate automatically according to ex-factory setting. Set temperature can’t be adjusted and
will not be displayed as well. Press "FAN" button can adjust fan speed. Press "SWING" button can adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator " "on indoor unit is ON. Press "▲" or " ▲ " button
to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator " " on indoor unit is ON. Under dry
mode, fan speed can’t be adjusted. Press "SWING" button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating. All indicators are OFF. Press "FAN" button to
adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode. Heat indicator " " on indoor unit is ON. Press "▲" or " ▲ "
button to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle. (Cooling only
unit won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor
ambient temperature).
● Set temperature range from remote controller: 16~30℃ (60.8~86.0OF); Fan speed: auto, low speed, medium speed, high speed.
3. FAN button
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium( ), high( ).
COOL
DRYHEAT
FAN
Auto
Caution:
● Under AUTO speed, air conditioner will select proper fan speed automatically according to ex-factory setting.
● Fan speed under dry mode is low speed.
4. SWING button
Press this button can select up&down swing angle. Fan blow angle can be selected circularly as below:
no display
(horizontal louvers stops at current position)
● When selecting " ", air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at maximum angle.
● When selecting " 、 、 、 、 ", air conditioner is blowing fan at xed position. Horizontal louver will stop at the xed position.
● When selecting " 、 、 " , air conditioner is blowing fan at xed angle. Horizontal louver will send air at the xed angle.
● Hold " "button above 2s to set your required swing angle. When reaching your required angle, release the button.
Note:
● " 、 、 " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically.
5. TURBO button
Under COOL or HEAT mode, press this button to turn to quick COOL or quick HEAT mode. " " icon is displayed on remote controller.
Press this button again to exit turbo function and " " icon will disappear.
6. ▲/▲ button
● Press "▲" or "▲" button once increase or decrease set temperature 1℃(33.8OF). Holding "▲" or "▲" button, 2s later, set temperature
on remote controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change
accordingly. (Temperature can’t be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
buttons) When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER
OFF buttons)
18
Technical Information
Service Manual
7. SLEEP button
Under COOL, HEAT or DRY mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this button
again to cancel sleep function and " " icon will disappear.
8. TEMP button
By pressing this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor unit’s
display. The setting on remote controlleris selected circularly as below:
no display
● When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
●
Outdoor temperature display is not available for some models. At that time, indoor
temperature.
● It’s defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display.
● When selecting displaying of indoor or outdoor ambient temperature, indoor temperature indicator displays corresponding temperature and
automatically turn to display set temperature after three or ve seconds.
unit receives " "signal, while it displays indoor set
9. I FEEL button
Press this button to start I FEEL function and " " will be displayed on the remote controller. After this function is set, the remote controller
will send the detected ambient temperature to the controller and the unit will automatically adjust the indoor temperature according to the
detected temperature. Press this button again to close I FEEL function and " " will disappear.
● Please put the remote controller near user when this function is set. Do not put the remote controller near the object of high temperature
or low temperature in order to avoid detecting inaccurate ambient temperature.
10. LIGHT button
Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn on
display light. " " icon is displayed.
11. CLOCK button
Press this button to set clock time. " " icon on remote controller will blink. Press "▲" or "▲" button within 5s to set clock time. Each
pressing of "▲" or "▲" button, clock time will increase or decrease 1 minute. If hold "▲" or "▲" button, 2s later, time will change quickly.
Release this button when reaching your required time. Press "CLOCK" button to conrm the time. " " icon stops blinking.
Note:
● Clock time adopts 24-hour mode.
● The interval between two operation can’t exceeds 5s. Otherwise, remote controller will quit setting status. Operation for TIMER ON/TIMER
OFF is the same.
12. TIMER ON / TIMER OFF button
● TIMER ON button
"TIMER ON" button can set the time for timer on. After pressing this button, " " icon disappears and the word "ON" on remote controller
blinks. Press "▲" or "▲"button to adjust TIMER ON setting. After each pressing "▲" or "▲" button, TIMER ON setting will increase or
decrease 1min. Hold "▲" or "▲" button, 2s later, the time will change quickly until reaching your required time. Press "TIMER ON" to
conrm it. The word "ON" will stop blinking. " " icon resumes displaying. Cancel TIMER ON: Under the condition that TIMER ON is
started up, press "TIMER ON" button to cancel it.
● TIMER OFF button
"TIMER OFF" button can set the time for timer off. After pressing this button," " icon disappears and the word "OFF" on remote
controller blinks. Press "▲" or "▲" button to adjust TIMER OFF setting. After each pressing "▲" or "▲" button,
TIMER OFF setting will increase or decrease 1min. Hold "▲" or "▲" button, 2s later, the time will change quickly until reaching your
required time. Press "TIMER OFF" word "OFF" will stop blinking. " " icon resumes displaying. Cancel TIMER OFF. Under the condition
that TIMER OFF is started up, press "TIMER OFF" button to cancel it.
Note:
● Under on and off status, you can set TIMER OFF or TIMER ON simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
● After starting up TIMER ON or TIMER OFF, set the constant circulating valid. After that, air conditioner will be turned on or turned off
according to setting time. ON/OFF button has no effect on setting. If you don’t need this function, please use remote controller to cancel it.
Technical Information
19
Service Manual
Function introduction for combination buttons
1. Energy-saving function
Under cooling mode, press "TEMP" and " CLOCK" buttons simultaneously to start up or turn off energy-saving function. When energy-saving
function is started up, "SE" will be shown on remote controller, and air conditioner will adjust the set temperature automatically according to
ex-factory setting to reach to the best energy-saving effect. Press "TEMP" and "CLOCK"buttons simultaneously again to exit energy-saving
function.
Note:
● Under energy-saving function, fan speed is defaulted at auto speed and it can’t be adjusted.
●
Under energy-saving function, set temperature can’t be adjusted. Press "TURBO"
● Sleep function and energy-saving function can’t operate at the same time. If energy-saving function has been set under cooling mode,
press sleep button will cancel energy-saving function. If sleep function has been set under cooling mode, start up the energy-saving
function will cancel sleep function.
2. 8 ℃ heating function
Under heating mode, press "TEMP" and "CLOCK" buttons simultaneously to start
started up, " " and "8℃" will be shown on remote controller, and the air conditioner keep the heating status
"CLOCK" buttons simultaneously again to exit 8℃heating function.
Note:
● Under 8℃ heating function, fan speed is defaulted at auto speed and it can’t be adjusted.
● Under 8℃ heating function, set temperature can’t be adjusted. Press "TURBO" button and the remote controller won’t send signal.
● Sleep function and 8℃ heating function can’t operate at the same time. If 8℃heating function has been set under cooling mode, press
sleep button will cancel 8℃ heating function. If sleep function has been set under cooling mode, start up the 8℃ heating function will
cancel sleep function.
● Under ℉ temperature display, the remote controller will display 46℉ heating.
button and the remote controller won’t send signal.
up or turn off 8℃ heating function. When this function is
at 8℃. Press "TEMP" and
3. Child lock function
Press "▲" and "▲" simultaneously to turn on or turn off child lock function. When child lock function is on, " " icon is displayed on remote
controller. If you operate the remote controller, the " " icon will blink three times without sending signal to the unit.
4. Temperature display switchover function
Under OFF status, press "▲" and "MODE" buttons simultaneously to switch temperature display between ℃ and ℉.
5. WIFI fuction (This unit is without WiFi fuction)
Under ON status, press "Mode" and "Turbo" button simultaneously,the "WiFi" icon will be displayed on remote controller.Press
"Mode"and"Turbo" button simultaneously,the "WiFi" icon will disppear.
Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN, HEAT.
3. Press "▲" or "▲" button to set your required temperature. (Temperature can’t be adjusted under auto mode).
4. Press "FAN" button to set your required fan speed: auto, low, medium and high speed.
5. Press "SWING" button to select fan blowing angle.
Replacement of batteries in remote controller
1. Press the back side of remote controller marked with " ", as shown in the g, and then push
out
the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar
are correct.
3. Reinstall the cover of battery box.
signal senderbattery
reinstall
remove
Note:
● During operation, point the remote control signal sender at the receiving window on indoor unit.
● The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is uorescent lamp or wireless telephone; remote controller should be close to
indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the batteries.
● If the display on remote controller is fuzzy or there’s no display, please replace batteries.
20
Cover of battery box
Technical Information
Service Manual
Tpreset +3˚F
6.2 Brief Description of Modes and Functions
1. Temperature Parameters
Indoor preset temperature(Tpreset)
Indoor ambient temperature (Tamb.)
2. Basic Functions
Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory functionis
available, for the rst energization, if the compressor is at stop before de-energization, the compressor will be started withouta 3-minute
lag; if the compressor is in operation before de-energization, the compressor will be started with a 3-minute lag; andonce started, the
compressor will not be stopped within 6 minutes regardless of changes in room temperature;
(1) Cooling Mode
Working conditions and process of cooling
①
When Tamb. ≥ Tpreset, the unit will enter cooling operation, in which case the indoor fan, the outdoor fan and the compressor willwork and
the indoor fan will run at preset speed.
When Tamb. ≤ Tpreset -3.6°F, the compressor will stop, the outdoor fan will stop with a time lag of 60s, and the indoor fan will run atpreset
speed.
When Tpreset-3.6°F < Tamb.< Tpreset+1.8°F, the unit will remain at its previous state.
Under this mode, the four-way valve will be de-energized and temperature can be set within a range from 61°F~86°F. If the compressor is
shut down for some reason, the indoor fan and the swing device will operate at original state.
Start cooling
Original working state
Stop cooling
Protection
②
Tpreset
Compressor
Outdoor fan
Indoor fan
Tamb.
≥ 6 min.≥ 3 min.≥ 6 min.
Set fan speed
Run
Stop
Antifreeze protection
Under cooling and dehumidifying mode, 6 minutes after the compressor is started:
If Tevap ≤ 35.6°F, the compressor will operate at reduced frequency.
If Tevap ≤ 30.2°F is detected for durative 3 minutes, the compressor will stop, and after 60 seconds, the outdoor fan will stop;and under
cooling mode, the indoor fan and the swing motor will remain at the original state.
If Tevap. ≥ 42.8°F and the compressor has remained at OFF for at least 3 minutes, the compressor will resume its original operation state.
Total current up and frequency down protection
If I
≤ 16A, frequency rise will be allowed; if I
total
frequency; and if I
≥ 20A, the compressor will stop and the outdoor fan will stop with a time lag of 60s.
total
≥ 17A, frequency rise will not be allowed; if I
total
≥ 18A, the compressor will run at reduced
total
(2) Dehumidifying Mode
Working conditions and process of dehumidifying
①
If Tamb. > Tpreset+1.8°F, the unit will enter cooling and dehumidifying mode, in which case the compressor and the outdoor fan will
operate and the indoor fan will run at low speed.
If Tpreset -3.6°F ≤ Tamb. ≤ Tpreset+1.8°F, the compressor remains at its original operation state.
If Tamb.< Tpreset-3.6°F , the compressor will stop, the outdoor fan will stop with a time lag of 60s, and the indoor fan will
operate at low speed.
Protection
②
Protection is the same as that under the cooling mode.
(3) Heating Mode
Working conditions and process of heating
①
If Tamb. ≤ Tpreset+3.6°F, the unit enters heating mode, in which case the four-way valve, the compressor and the outdoor fan willoperate
simultaneously, and the indoor fan will run at preset speed in the condition of preset cold air prevention.
If Tamb. ≥ Tpreset+9°F, the compressor will stop, the outdoor fan will stop with a time lag of 60s, and the indoor fan will stop after
60-second blow at low speed.
If Tpreset+3.6°F < Tamb. < Tpreset+9°F, the unit will maintain its original operating status.
Under this mode, the four-way valve is energized and temperature can be set within a range of 61°F~86°F. The operatingsymbol, the
heating symbol and preset temperature are revealed on the display.
Condition and process of defrost
②
Technical Information
21
Service Manual
When duration of successive heating operation is more than 45 minutes, or accumulated heating time more than 90 minutes, andone of the
following conditions is reached, the unit will enter the defrost mode after 3 minutes.
a. Toutdoor amb. ≥ 41°F, Toutdoor pipe ≤ 28.4°F; b. 28.4°F ≤ Toutdoor amb.
After energization, when defrosting for the first time Tcompensation=0°F. If it is not the firstly time for defrosting, the Tcompensation is
determined by the Toutdoor pipe of last time quitting defrosting.
a. Toutdoor pipe > 35.6°F, Tcompensation=0°F; b. Toutdoor pipe ≤ 35.6°F, Tcompensation=5.4° F.
At that time, the indoor fan stops and the compressor stops, and after 60 seconds the outer fan will stop, and then after 30seconds, the fourway valve will stop. After 30 seconds, the compressor is initiated for raising the frequency to defrost frequency.
When the compressor has operated under defrost mode for 10 minutes, or Touter tube ≥ 50°F, the compressor will be converted to 46Hz
operation.After 30 seconds, the compressor will stop. And after another 30 seconds, the four-way valve will be opened, and after60 seconds,
the compressor and the outer fan will be started, the indoor fan will run under preset cold air prevention conditions,and H1 will be displayed
at temperature display area on the display panel. Defrost frequency is 70 Hz.
3.Protection
Cold air prevention
The unit is started under heating mode (the compressor is ON):
In the case of Tindoor amb. < 75°F: if T tube ≤ 104°F and the indoor fan is at stop state, the indoor fan will begin to run at low speed witha
①
time lag of 2 minutes. Within 2 minutes, if T tube > 104°F, the indoor fan also will run at low speed; and after 1 minute operation atlow speed,
the indoor fan will be converted to operation at preset speed. Within 1 minute low speed operation or 2 minute non-operation, if T tube >
108°F, the fan will run at present speed.
In the case of Tindoor amb. < 75°F: if Ttube ≤ 108°F, the indoor fan will run at low speed, and after one minute, the indoor fan will
②
beconverted to preset speed. Within 1 minute low speed operation, if Ttube > 104°F, the indoor fan will be converted to preset speed.Note:
Tindoor amb. indicated in① and②refers to, under initially heating mode, the indoor ambient temperature before the command to start the
compressor is performed according to the program, or after the unit is withdrawn from defrost, the indoor ambient temperature before the
defrost symbol is cleared.
Total current up and frequency down protection
If the total current I
≤ 16A, frequency rise will be allowed; if I
total
≥ 17A,frequency rise will not be allowed; if Itotal18A,the compressorwill run
total
at reduced frequency; and if Itotal20A, the compressor will stop and the outdoor fan will stop with a time lag of 60s.
(4) Fan Mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the four-way valve and the electricheater will
stop.
Under the mode, temperature can be set within a range of 61°F~86°F.
(5) AUTO Mode
Working conditions and process of AUTO mode
①
Under AUTO mode, standard cooling temperature Tpreset is 77°F and standard heating temperature Tpreset is 68°F.
a. Once energized, if Tamb. ≤ 71.6°F, the unit will be started under heating mode; if 71.6°F < Tamb.< 78.8°F, the unit will run under fanmode
and the run indicator will be bright; and if Tamb. ≥ 78.8°F, the unit will be started under cooling mode.
b.Under AUTO mode,if Tamb. ≥ Tpreset +1.8ºF is detected,the unit will select to run under cooling mode,in which case implicit
presettemperature is 77°F; if Tamb. ≤ Tpreset-1.8°F, the compressor will stop, the outdoor fan will stop with a time lag of 1 minute,
andtheindoor fan will run at preset speed; and if Tpreset-1.8°F < Tamb. < Tpreset+1.8ºF, the unit will remain at its original state.
c.Under AUTO mode, if Tamb. ≤ Tpreset+3.6°F is detected, the unit will select to run under heating mode, in which case implicit preset
temperature is 64°F; if Tamb. ≥ Tpreset+9°F, the compressor will stop, the outdoor fan will stop with a time lag of 1 minute,and the indoor
fan will run under the mode of residue heat blowing; and if Tpreset+3.6°F < Tamb.< Tpreset+41°F, the unit will remainatits original state. The
cooling-only unit will run under fan mode.
d.Under AUTO mode, if 71.6°F < Tamb.< 78.8°F, the unit will remain at its original state.
Protection
②
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor willremain unchanged
for at least 6 minutes.
(6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
Overload protection
①
Ttube:measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat ex-changer under
heating mode.
1) Cooling overloada.
a. If Ttube ≤ 126°F, the unit will return to its original operation state.
b. If Ttube ≥ 131°F, frequency rise is not allowed.
22
Technical Information
Service Manual
c. If Ttube ≥ 136°F, the compressor will run at reduced frequency.
d. If Ttube ≥ 144°F, the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a. If Ttube ≤ 126°F, the unit will return to its original operation state.
b. If Ttube ≥ 131°F, frequency rise is not allowed.
c. If Ttube ≥ 136°F, the compressor will run at reduced frequency.
d. If Ttube ≥ 144°F,the compressor will stop and the indoor fan will blow residue heat and then stop.
Exhaust temperature protection of compressor
②
If exhaust temperature ≥ 208°F, frequency is not allowed to rise.
If exhaust temperature ≥ 217°F, the compressor will run at reduced frequency.
If exhaust temperature ≥ 230°F, the compressor will stop.
If exhaust temperature ≤ 194°F, the compressor has stayed at stop for at least 3 minutes, the compressor will resume itsoperation.
Communication fault
③
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justied and the whole system will stop.
Module protection
④
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, thecompressor will
resume its operation. If module protection occurs six times in succession, the compressor will not be startedagain.
Overload protection
⑤
If temperature sensed by the overload sensor is over 239°F, the compressor will stop and the outdoor fan will stop with atime lag of 30
seconds. If temperature is below 203°F, the overload protection will be relieved.
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a timelag of 30 seconds.
When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least3 minutes, the compressor will
resume its operation.
Faults of temperature sensors
⑥
Designation of sensorsFaults
Indoor ambient temperature
Indoor tube temperature
Outdoor ambient temperature
Outdoor tube temperature
Exhaust
Overload
The sensor is detected to be open-circuited or short-circuited for successive 5
seconds
The sensor is detected to be open-circuited or short-circuited for successive 5
seconds
The sensor is detected to be open-circuited or short-circuited for successive 30
seconds
The sensor is detected to be open-circuited or short-circuited forsuccessive 30
seconds, and no detection is performed within 10 minutesafter defrost begins.
After the compressor has operated for 3 minutes, the sensor is detectedto be
open-circuited or short-circuited for successive 30 seconds.
After the compressor has operated for 3 minutes, the sensor is detectedto be
open-circuited or short-circuited for successive 30 seconds.
Technical Information
23
Service Manual
Part
: Installation and Maintenance
Ⅱ
7. Notes for Installation and Maintenance
Safety Precautions:
Important!
Please read the safety precautions carefully before
installation and maintenance.
The following contents are very important for installation
and maintenance.
Please follow the instructions below.
●The installation or maintenance must accord with the
instructions.
●Comply with all national electrical codes and local
electrical codes.
●Pay attention to the warnings and cautions in this
manual.
●All installation and maintenance shall be performed by
distributor or qualied person.
●All electric work must be performed by a licensed
technician according to local regulations and the
instructions given in this manual.
●Be caution during installation and maintenance. Prohibit
incorrect operation to prevent electric shock, casualty and
other accidents.
Warnings
Electrical Safety Precautions:
1. Cut off the power supply of air conditioner before
checking and maintenance.
2. The air condition must apply specialized circuit and
prohibit share the same circuit with other appliances.
3. The air conditioner should be installed in suitable
location and ensure the power plug is touchable.
4. Make sure each wiring terminal is connected rmly
during installation and maintenance.
5. Have the unit adequately grounded. The grounding wire
can’t be used for other purposes.
6. Must apply protective accessories such as protective
boards, cable-cross loop and wire clip.
7. The live wire, neutral wire and grounding wire of power
supply must be corresponding to the live wire, neutral
wire and grounding wire of the air conditioner.
8. The power cord and power connection wires can’t be
pressed by hard objects.
9. If power cord or connection wire is broken, it must be
replaced by a qualied person.
10. If the power cord or connection wire is not long enough,
please get the specialized power cord or connection wire
from the manufacture or distributor. Prohibit prolong the wire
by yourself.
11. For the air conditioner without plug, an air switch must
be installed in the circuit. The air switch should be all-pole
parting and the contact parting distance should be more than
1/8 inch.
12. Make sure all wires and pipes are connected properly and
the valves are opened before energizing.
13. Check if there is electric leakage on the unit body. If yes,
please eliminate the electric leakage.
14. Replace the fuse with a new one of the same specication
if it is burnt down; don’t replace it with a cooper wire or
conducting wire.
15. If the unit is to be installed in a humid place, the circuit
breaker must be installed.
Installation Safety Precautions:
1. Select the installation location according to the requirement of this manual.(See the requirements in installation
part)
2. Handle unit transportation with care; the unit should not
be carried by only one person if it is more than 44.09lb.
3. When installing the indoor unit and outdoor unit, a sufcient xing bolt must be installed; make sure the installation
support is rm.
4. Ware safety belt if the height of working is above 78 3/4
inch.
5. Use equipped components or appointed components during installation.
6. Make sure no foreign objects are left in the unit after nishing installation.
Refrigerant Safety Precautions:
1. Avoid contact between refrigerant and re as it generates
poisonous gas; Prohibit prolong the connection pipe by
welding.
2. Apply specied refrigerant only. Never have it mixed with
any other refrigerant. Never have air remain in the refrigerant
line as it may lead to rupture or other hazards.
3. Make sure no refrigerant gas is leaking out when installation
is completed.
4. If there is refrigerant leakage, please take sufcient measure
to minimize the density of refrigerant.
5. Never touch the refrigerant piping or compressor without
wearing glove to avoid scald or frostbite.
Improper installation may lead to re hazard, explosion,