Owner's Manual Air Conditioners
Thank you for choosing Air Conditioners, please read this owner’s manual carefully before
operation and retain it for future reference.If you have lost the Owner’s Manual, please contact
the local agent or visit www.gree.com or sent email to global@gree.com.cn or electronic version.
GREE reserves the right to interpret this manual which will be subject to any change due to
product improvement without further notice.
GREE Electric Appliances, Inc. of Zhuhai reserves the final right to interpret this manual.
Multi Variable Air Conditioners Compact Cassette Type Indoor Unit
Preface
For correct installation and operation, please read all instructions carefully. Before reading the
instructions, please be aware of the following items:
(1) For the safe operation of this unit, please read and follow the instructions carefully. (2) During operation, total capacity of indoor units should not exceed the total capacity of
outdoor units. otherwise, poor effect of cooling or heating may result. (3) Direct operators or maintainers should well keep this manual. (4) If this unit fails to operate normally, please contact our service center as soon as possible
and provide the following information:
Content on the nameplate(model number,cooling capacity,production code,ex-factory
date.
Malfunction details(before and after the malfunction occurs.
(5) Each unit has been strictly tested and proved to be qualified before ex-factory. In order to
prevent units from being damaged or operating normally because of improper
disassembly. please do not disassemble the unit by yourself. If you need to disassemble and check units, please contact our service center. We will send specialists to guide the disassembly.
(6) Under the standby status, the unit will consume a little power for ensuring reliability of
complete unit, maintaining normal communication and preheating refrigerant. When the
unit won’t be used for a long time, cut off the power of the complete unit. However, please
preheat it when operating the unit next time.
(7)
All graphics in this manual is only for your reference. For sales or production
reasons,these
graphics are subject to change by manufacturer without prior notice.
(8) These instructions shall also be available in an alternative format, e.g. on a website.
User Notice
This appliance can be used by children aged from 8 years and above and persons with
reduced physical ,sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instrction concerning use of the appliance in a safe way and understand the hazards involved .Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Correct Disposal of this product
This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.
R410A(R32/125:50/50):2087.5
Contents
1 Safety Precautions ................................................................................................................ 1
2 Product Introduction .............................................................................................................. 3
2.1 Names of Key Components ......................................................................................... 3
2.2 Rated Working Condition ............................................................................................. 3
2.3 Unit Functions ............................................................................................................. 3
3 Preparations for Installation ................................................................................................... 4
3.1 Standard Fittings.......................................................................................................... 4
3.2 Installation Position Selection ...................................................................................... 4
3.3 Requirements of communication wire selection .......................................................... 5
3.4 Wiring Requirements ................................................................................................... 6
4 Installation Instructions .......................................................................................................... 7
4.1 Indoor unit installation .................................................................................................. 7
4.2 Refrigerant Pipe Connection ....................................................................................... 9
4.3 Drainage Pipe Installation and Drainage System Testing .......................................... 10
4.4 Panel installation ....................................................................................................... 12
4.5 Installation of Wired Controller .................................................................................. 14
5 Wiring Work ......................................................................................................................... 14
5.1 Connection of Wire and Patch Board Terminal .......................................................... 15
5.2 Power Cord Connection ............................................................................................ 16
5.3 Connection of Communication Wire between Indoor Unit and Outdoor Unit (or indoor
unit) ................................................................................................................................. 16
5.4 Connection of Communication Wire for Wired Controller .......................................... 17
5.5 Wiring Instructions of Wired Controller and Indoor Units Network ............................ 17
6 Routine Maintenance .......................................................................................................... 19
6.1 Cleaning of Filter ....................................................................................................... 19
6.2 Maintenance before the Seasonal Use ..................................................................... 19
6.3 Maintenance after the Seasonal Use ........................................................................ 19
7 Table of Error Codes for Indoor Unit ................................................................................... 19
8 Troubleshooting ................................................................................................................... 20
Multi Variable Air Conditioners Cassette Type Indoor Unit
1
1 Safety Precautions
means items that must be forbidden! Otherwise, it may lead to personal injury or
death or serious damage.
means items that must be followed! Otherwise, it may lead to personal injury or
property loss.
Please install the unit according to instructions in this manual. Read this manual carefully before starting up or checking the machine.
Installation should be performed by dealer or qualified technicians. Do not install the product by yourself. Improper installation may result in water leakage, electric shock or fire hazard.
Make sure the local power supply is in accordance with units before installation, and check the power supply carefully.
This air conditioner must be properly grounded through the receptacle to avoid electric shock.The grounding wire shouldn't be connected with gas pipe, water pipe, lightning arrester or telephone line.
Please use specialized accessories or parts to carry out installation,or water leakage, electric shock,fire hazard may resulted.
R410A refrigerant can produce poisonous gas once it meets fire, so please ventilate the room immediately if refrigerant leaks out during installation.
Diameter of power cord must be large enough. Damaged power cord and connecting wire must be replaced by specialized electric cable.
After the power cord is connected, please install the cover of electric box to avoid danger.
Nitrogen must be charged according to technical requirements.
Short circuit is forbidden. Do not cancel the pressure switch in case the unit may be damaged.
For units with wired controller, do not connect power supply until the wired controller is well installed. Otherwise, the wired controller cannot be used.
When the installation is finished, please check and make sure the drain pipe, pipeline and electric wire are all well connected in order to avoid water leakage, refrigerant leakage, electric shock or fire hazard.
Multi Variable Air Conditioners Cassette Type Indoor Unit
2
Do not extend fingers or objects into air outlet or air return grille.
If you use gas heater or petroleum heater in the same room, please open the door or window to maintain good air circulation in case the room may lack of oxygen.
Never start or stop the air conditioner by inserting or removing the power cord.
Do not turn off the air conditioner until it runs for at least 5 minutes. Otherwise, oil-return of the compressor will be affected.
Children are not allowed to operate the air conditioner.
Do not operate the air conditioner with wet hands.
Please turn the unit off and unplug your air conditioner before cleaning. Otherwise, it may cause electric shock or personal injury.
Do not spray water on the air conditioner or it will cause malfunction or electric shock.
Do not expose the air conditioner directly to water or place it in a damp or corrosive environment.
Connect power supply 8 hours before operation. Do not disconnect power if you want to stop the unit in a short period of time, e.g. in one night. (This is for protecting the compressor.)
Volatile liquid like thinner or gasoline will damage the appearance of air conditioner. (Please use soft dry cloth and wet cloth with mild detergent to clean the outer case of air conditioner.)
During Cooling mode, indoor temperature should not be set too low. Keep the difference between indoor temp and outdoor temp within 5°C.
If abnormal condition occurs (e.g. unpleasant smell), please turn off the unit at once and disconnect power supply. Then contact GREE service center. If the air conditioner continues to operate despite of abnormal condition, the unit may be damaged and it may cause electric shock or fire hazard.)
Do not repair the air conditioner by yourself. Improper repair will cause electric shock or fire hazard. Please contact GREE service center and have it repaired by professional technicians.
Multi Variable Air Conditioners Cassette Type Indoor Unit
3
Any personal injury or property loss caused by improper installation, improper debug, unnecessary repair or not following the instructions of this manual should not be the responsibility of Gree Electric Appliances, Inc. of Zhuhai.
2 Product Introduction
2.1 Names of Key Components
Fig 2.1
No.
① ② ③ ④ ⑤
Name
the hanger
bracket
Drainage Pipe
Louver
Connection
Pipe
Air Inlet Grille
(With Filter)
2.2 Rated Working Condition
Indoor Side Condition
Outdoor Side Condition
Dry Bulb Temp℃(℉)
Wet Bulb Temp℃(℉)
Dry Bulb Temp℃(℉)
Wet Bulb Temp℃(℉)
Rated Cooling
27(80.6)
19(66.2)
35(95)
24(75.2)
Rated Heating
20(68.0)
15(59.0)
7(44.6)
6(42.8)
Indoor Unit Working Temperature Range: 16°C~ 32°C.
2.3 Unit Functions
Unit Functions
Wired Controller XK46(Standard)
Wired Controller
XK49(Optional)
Remote Controller YAP1F (Standard)
Remote Controller
YV1L1 (Optional)
Operation Mode (Cooling, Heating, Fan, Dehumidifying)
Fan Speed Adjustment
Temperature Adjustment
X-fan Function
Quiet Function
Sleep Function
Save Function
E-heater Function
Memory Function
Absence Function
Timer Function
Low Temp Dehumidify Function
Multi Variable Air Conditioners Cassette Type Indoor Unit
4
Filter Cleaning Reminding Function
I Feel
Light Function
Swing
Note!
√: included, X: not included. ② Please refer to the user manual of Wired Controller or Remote Controller for function details.
3 Preparations for Installation
Note: this picture is for reference only, please refer to the actual product; the unit of dimension is mm.
3.1 Standard Fittings
Please use the supplied standard fittings listed below as instructed.
No.
Name
Appearance
Q'ty
Usage
1
Drainage hose assembly
1
To connect the drainage pipe
2
Special Nut
1
To be used for connecting the refrigerant pipe
3
Insulation
1
To insulate the gas pipe
4
Insulation
1
To insulate the liquid pipe
5
Sponge 2
To insulate the drain pipe
6
Fastener
4
To fasten the sponge
7
paper pattern for installation
1
Locate the drill hole on ceiling
8
Tapping screw with washer
4
Fix paper pattern
9
Remote controller
1+2
To control the indoor unit
10
Washer fixing plate
4
Prevent the washer from falling off
3.2 Installation Position Selection
(1) The location should be able to withstand the weight of unit. (2) The water can be drained conveniently from drainage pipe.
Multi Variable Air Conditioners Cassette Type Indoor Unit
5
(3) There should be no obstruction near air inlet and air outlet. (4) Follow the installation distance required in the fig below to ensure sufficient space for
maintenance.
(5) The installation location should be far from heat sources, flammable or explosive gas, or
smog spread in the air.. (6) The appliance shall not be installed in the laundry. (7) Appliances are not accessible to general public. (8) The indoor unit, outdoor unit, power cord and connection electricity wire should be at least
1m from television and radio in order to prevent interference and noise. (Even though 1m
distance is ensured, there may be noise if the electric wave is too strong.)
Unit: mm
Fig 3.2
Notes:
The unit shall be installed in accordance with national standards or local regulations. Only qualified personnel can carry out installation work, please contact with local dealer before
installation..
Make sure all the installation work completed before energizing.
3.3 Requirements of communication wire selection
Note!
If air conditioner used under strong electronic-magnetic interference circumstance,
STP(shielded twisted pair) communication cable must be adopted.
3.3.1 Selection of communication wire between indoor unit and wired controller
Fig 3.3.1
Loading...