Preface
Gree DC Inverter Multi VRF System, with the most advanced technologies in the world, uses ecofriendly refrigerant R410A as its cooling medium. For correct installation and operation, please read
this manual carefully. Before reading the manual, please note that:
(1) For safety operation, please strictly follow the instructions in this manual.
(2) During operation, the gross rated capacity of working IDU should be within the gross rated
capacity of ODU. Otherwise, IDU’s cooling/heating performance will be reduced.
(3) This manual must be in the hands of direct operators or maintenance men.
(4) In case of malfunction and operation failure, please examine the following items and contact
our authorized service centers as soon as possible.
2) Malfunction status (detail description of conditions before and after malfunction occurs)
(6) All units have been strictly tested and proved to be qualied before ex-factory. To avoid unit
damage or even operation failure which may be caused by improper disassembly, please do
not disassemble units by yourself. If disassembly is needed, please contact our authorized
serve centers for help.
(7) All graphics and information in this manual are only for reference. Manufacturer reserves the
right for changes in terms of sales or production at any time and without prior notice.
This appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been given
supervision or instruction concerning use of the appliance in a safe way and understand the hazards
involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be
made by children without supervision.
DISPOSAL:Donot dispose this product as unsorted municipal waste. Collection of such waste
Refers to things that are not allowed. Incorrect operation may cause personal injury
or death.
refers to things that must be followed. Incorrect operation may cause personal injury
or death.
Installation should be conducted
Follow this instruction to complete
the installation work. Please
carefully read this manual before
unit startup and service.
by dealer or qualied personnel.
Please do not attempt to install the
unit by yourself. Improper handling
may result in water leakage,
electric shock or re disaster etc.
Exclusive
accessory
exclusive
Before installation, please check if
the power supply is in accordance
with the requirements specied on
the nameplate. And also take care
of the power safety.
Be sure to use the exclusive
accessory and part to prevent the
water leakage, electric shock and
re accidents.
Wire size of power cord should
be large enough.The damaged
power cord and connection wire
should be replaced by exclusive
cable.
Make sure the unit can be earthed
properly and soundly after
plugging into the socket so as to
avoid electric shock. Please do
not connect the ground wire to gas
pipe, water pipe, lightning rod or
telephone line.
If refrigerant leakage happens
during installation, please ventilate
immediately. Poisonous gas will
emerge if the refrigerant gas meets
re.
After connecting the power cord,
please x the electric box cover
properly in order to avoid accident.
N2
Never fail to comply with the
nitrigen charge requirements.
Charge nitrogen when welding
pipes.
Please rstly connect the wired
controller before energization,
otherwise wired controller can
not be used.
Never short-circiut or cancel the
pressure switch to prevent unit
damage.
Before using the unit, please check
if the piping and wiring are correct
to avoid water leakage, refrigerant
leakage, electric shock, or re etc.
1
Do not insert fingers or objects
26
C
30
C
into air outlet/inlet grille.
D.C. Inverter Multi-variable Modular
Open the door and window and
keep good ventilation in the room
to avoid oxygen decit when
the gas/oil supplied heating
equipment is used.
Never start up or shut off the air
conditioner by means of directly
plug or unplug the power cord.
Do not allow children
operate this unit.
Turn off the unit or cut off the
power supply before cleaning the
unit, otherwise electric shock or
injury may happen.
Do not expose the unit
to the moist or corrosive
circumstances.
<5Min
24H
Turn off the unit after it runs at
least ve minutes; otherwise it
will inuence oil return of the
compressor.
Do not operate this unit
with wet hands.
Never spray or ush water
towards unit, otherwise
malfunction or electric shock
may happen.
Electrify the unit 8 hours before
operation. Please switch on for
8 hours before operation. Do not
cut off the power when 24 hours
short-time halting (to protect the
compressor).
Volatile liquid, such as diluent
or gas will damage the unit
appearance.Only use soft cloth
with a little neutral detergent to
clean the outer casing of unit.
If anything abnormal happens
(such as burning smell), please
power off the unit and cut off
the main power supply, and
then immerdiately contact Gree
appointed service center.If
abnormality keeps going, the unit
might be damaged and lead to
electric shock or re.
Under cooling mode, please
don't set the room temperature
too low and keep the
temperature difference between
indoor and outdoor unit within
.
5
User is not allowed to repair the
unit. Fault service may cause
electric shock or re accidents.
Please contact Gree appointed
service center for help.
GREE will not assume responsibility of personal injury or equipment damage caused by
improper installation and commission, unnecessary service and incapable of following the rules and
instructions listed in this manual.
2
D.C. Inverter Multi-variable Modular
2 Product Introduction
Gree Multi VRF Modular System adopts inverter compressor technology. According to change
the displacement of compressor, stepless capacity regulation within range of 10%-100% can be
realized. Various product lineup is provided with capacity range from 22.4kW to 180kW, which can be
widely used in working area and especially applicable to the place with variable load change.Gree air
conditioner is absolutely your best choice.
Thank you for choosing Air Conditioners, please read this owner’s manual carefully before
operation and retain it for future reference.
GREE reserves the right to interpret this manual which will be subject to any change due
to product improvement without further notice.
GREE Electric Appliances, Inc. of Zhuhai reserves the nal right to interpret this manual.
1
2
Wiring (match with
resistance)
3Mark (Master )
1
2
Must be connected to the
last IDU of communication
connection
Attach on the wired controller of
master IDU or on the front panel
3.2 Installation Site
Forbidden Items! It indicates that improper operation might lead to human casualty or
sever injury.
Items need to be followed. It indicates that improper operation might lead to personal
injury or property damage.
Install the unit at a place where
is adequate to withstand the
weight of the unit and make
sure the unit would not shake
or fall off.
Never expose the unit under
direct sunshine and rainfall.
Install the unit at a place where
is against dust, typhoon and
earthquake.
Try to keep the unit away
from combustible,inammable
and corrosive gas or exhaust
gas.
Keep the indoor and outdoor
units close to each other as
much as possible so as to
decrease the pipe length and
bends.
Leave some space for heat
exchanging and servicing so
as to guarantee unit normal
operation.
Never allow children to
approach to the unit and take
measures to prevent children
touching the unit.
6
D.C. Inverter Multi-variable Modular
A
3.2.1 When the outdoor unit is totally surrounded by walls, please refer to following
gures for space dimension.
3.2.1.1 Space dimension for single-module unit
Air Outlet
>3000
3.2.1.2 Space dimension for dual-module unit
Air Outlet
>200
>3000
Fig. 3
>1000
>1200
>1000
>1200
>1000>1000
Electrical Box
Outlet on this side
>1000>1000
>200
Electrical Box
Outlet on this side
Fig. 4
3.2.1.3 Space dimension for three-module unit
ir Outlet
>200>200
>3000
Fig.5
>1000
>1200
>1000>1000
>200>200
Electrical Box
Outlet on this side
7
3.2.1.4 Space dimension for four-module unit
e
Crown wall
1000
200
D.C. Inverter Multi-variable Modular
Air Outlet
>1000
>1200
Fig.6
>200>200
>200
>200>200>200
>3000
>1000>1000
Electrical Box
Outlet on this sid
3.2.2 When there is wall (or similar obstruction) above the unit, keep the distance
between the unit top and the wall at least 300mm or above. When the unit is located
in a totally open space with no obstructions in four directions, keep the distance
between the unit top and wall at least 1500mm or above (See Fig.7). When space
is limited within 1500mm or the unit is not set in an open space, air return pipe is
required to be installed in order to keep good ventilation (See Fig.8).
Air Outlet
>1500
>
Fig.7 Fig.8
When the distance is less than
1500mm, connect an air duct
so as to keep good ventilation.
>
8
D.C. Inverter Multi-variable Modular
No limit on the height of wall
Max. 4 sets side by side
No limit on the height of wall
Max. 4 sets side by side
Correct
Incorrect:
In this case,
S
FrontFront
3.2.3 Space dimension for multiple-module unit
For keeping good ventilation, make sure there is no obstructions above the unit.
When the unit is located at a half-open space (front and left/right side is open), install the unit as
per the same or opposite direction.
>200
>200
>200
>200
>1000
>1000
>1200
Fig.9
>1200
Fig.10
>1000
>1200
>200
>200
Back side
Front side
Back side
Front side
Front side
Back side
Back side
Front side
>200
>200
>1000
>1200
>1000
>1200
>1200
>1000
3.2.4 Take seasonal wind into consideration when installing the outdoor unit
the defrosting duration
easonal windSeasonal windSeasonal wind
Front
Front
Return air
Protective cover
Return air
Return air
Fig.11
will be extended.
Seasonal wind
Return air
9
D.C. Inverter Multi-variable Modular
S
Protective cover at
Protective cover at
the return air inlet
(field supplied)
higher than that of the snowfall.
3.2.5 Take snow into consideration when installing the outdoor unit
the supply air outlet
(field supplied)
easonal windSeasonal wind
Correct
The height of the base should
3.3 Piping Work Requirements
Incorrect
Fig.12
There should be no fall among outdoor modules. Refer to the table below for piping work
requirements.
R410A Refrigerant System
Outer Diameter (mm)Wall Thickness (mm)Type
Φ6.35 0.80
Φ9.52 0.80
Φ12.70 0.80
Φ15.9 1.00
Φ19.05 1.01/2H
Φ22.2 1.21/2H
Φ25.40 1.21/2H
Φ28.60 1.21/2H
Φ34.90 1.31/2H
Φ38.10 1.51/2H
Φ41.30 1.51/2H
Φ44.5 1.51/2H
Φ54.1 1.51/2H
10
D.C. Inverter Multi-variable Modular
930765
1
2
Installation hole
4 Installation Instruction
4.1 Physical Dimension of the Outdoor Unit and Mounting Hole
Outline and Physical Dimention of GMV-224WM/B-X and GMV-280WM/B-X unit.
1
Installation hole
7291605
792
Fig.13
22
15
Outline and Physical Dimention of GMV-335WM/B-X, GMV-400WM/B-X and GMV-450WM/B-X
unit.
2
729
1200
1605
1340
Fig.14
22
15
765
11
4.2 Connection Pipe
Oil balance pipe
4.2.1 Schematic Diagram of Piping Connection
D.C. Inverter Multi-variable Modular
Module
No.1
Module
No.2
Outdoor
connection pipe
Connection pipe between
outdoor manifolds
Module
No.3
Module
Manifold between
indoor units
No.4
Manifold between
outdoor units
Gas pipe
Liquid pipe
Connection pipe between outdoor
manifold and the first indoor manifold
Connection pipe between indoor
manifold and indoor units
Indoor unit 1
Connection pipe between
indoor manifolds
Connection pipe between indoor
manifold and indoor units
Indoor unit 2
Connection pipe between
indoor manifolds
Connection pipe between indoor
manifold and indoor units
Indoor unit 3
Connection pipe between
indoor manifolds
Fig.15
12
D.C. Inverter Multi-variable Modular
Liquid pipeGas pipe
Oil checking valve
Liquid pipeGas pipe
Oil checking valve
4.2.2 Schematic Diagram of Piping Sequence
GMV-224WM/B-X and GMV-280WM/B-X
Low pressure
check valve
Oil balance pipe
Fig.16
GMV-335WM/B-X, GMV-400WM/B-X and GMV-450WM/B-X
Low pressure
check valve
Oil balance pipe
Fig.17
13
D.C. Inverter Multi-variable Modular
4.2.3 Allowable pipe length and drop height among indoor and outdoor units
Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is shown
in the gure below.
Remark: Equivalent length of one Y-type manifold is about 0.5m.
Outdoor unit
L1
L2
L11
The 1st
branch section
L6
L3
L4L5
between outdoor unit and the farthest indoor unit
L7L8L9
Height difference between indoor unit and outdoor unit: H
Fig.18
L10: Length from the rst branch to the farthest IDU;
L11: Length from the rst branch to the nearest IDU;
Equivalent length of branch of IDU is 0.5m
Indoor unit
L10
Height difference
R410A Refrigerant System
Total length (actual length) of tting pipe 1000L1+L2+L3+L4+…+L9+a+b+…+i+j
Length of farthest tting
pipe(m)
Difference between the pipe length from the rst branch
of IDU to the farthest IDU and the pipe length from the
rst branch of IDU to the nearest IDU
Equivalent length from the rst branch to the furthest
piping (1)
Actual length 165
Equivalent length 190
14
Allowable
Value
40L10-L11
40L6+L7+L8+L9+j
Fitting Pipe
L1+L6+L7+L8+L9+j
D.C. Inverter Multi-variable Modular
Height difference
Outdoor unit at upper(2) 90——
between outdoor unit and
indoor unit
Outdoor unit at lower 90——
Height difference between indoor units (m) 30——
Maximum length of Main pipe(3) 90L1
From IDU to its nearest branch (4) 10a,b,c,d,e,f,g,h,i,j
Notices:
(1) Normally, the pipe length from the rst branch of IDU to the farthest IDU is 40m. When those
three conditions as below are satised, the length can reached 90cm..
1) Actual length of pipe in total: L1+L2x2+L3x2+L4x2+…+L9x2+a+b+…+i+j≤1000m;
2) Length between each IDU and its nearest branch a, b, c, d, e, f, g, h, i, j≤40m;
3) Difference between the pipe length from the rst branch of IDU to the farthest IDU and the
pipe length from the rst branch of IDU to the nearest IDU: L10-L11≤40m.
(2) When the outdoor unit is at upper side and height difference is more than 50m, please consult
company for the related technical requirement.
(3) When the maximum length of the main pipe from ODU to the rst branch of IDU is≥90m, then
adjust the pipe size of the gas pipe and liquid pipe of main pipe according to the following
table.