Gree 13-04692, GAE15AB-D3RNB1A user guide manual

PACKAGED TERMINAL
AIR CONDITIONER
OWNER’S MANUAL
Please read this manual carefully before running the unit.
Thank you for choosing a GREE air conditioner. Please read this owner's manual carefully before operating the unit and keep it handy for future reference.
0
0510-14/07/11
©
Copyright, Sunrise Tradex Corp., 2011
MODELS:
13-04690 / GAE09AB-D3RNB1A 13-04704 / GAA09AB-D3RNB1A 13-04691 / GAE12AB-D3RNB1A 13-04705 / GAA12AB-D3RNB1A 13-04692 / GAE15AB-D3RNB1A 13-04706 / GAA15AB-D3RNB1A
WWW.GREE.CA
St-Mathieu-de-Beloeil (Québec) Canada
1-866-680-GREE
CONTENTS
The figures in this manual may differ from the actual objects. Please refer to the actual objects for reference.
This symbol represents the instructions that must be followed.
The figures in this manual may differ from the actual objects. Please refer to the actual objects for reference.
D
o not dispose of this product as unsorted municipal waste.
This product must be disposed of separately for special processing.
1. SAFETY CONSIDERATIONS ...................................................................................................... 1
2. GENERAL INFORMATION ........................................................................................................ 1
3. UNIT FEATURES .................................................................................................................. 2
4. ELECTRICAL DATA ................................................................................................................ 4
5. INSTALLATION .................................................................................................................... 5
6. HOW TO CONNECT ................................................................................................................ 8
7. SYSTEM CONFIGURATION ...................................................................................................... 9
8. AUXILIARY CONTROLS .......................................................................................................... 12
9. OPERATION ........................................................................................................................ 14
10. CARE AND CLEANING .......................................................................................................... 15
11. PREVENTATIVE MAINTENANCE .............................................................................................. 16
12. TROUBLESHOOTING ............................................................................................................ 17
13. WARRANTY ...................................................................................................................... 18
1
GREE packaged terminal air conditioners and heat pumps provide high quality performance, workmanship, durability and appearance, as they heat and cool the living space year round. This manual provides information for installation, operation and maintenance. All models are designed for wall-embedded installation. Separate installation instructions are included with all accessory components.
Read all the instructions carefully.
IMPORTANT: Save these instructions for the local inspectorʼs use. IMPORTANT: Observe all governing codes and ordinances.
Be sure to leave these instructions with the owner.
Keep these instructions for future reference. Be sure to write down the model and serial number of the unit on the space provided on the back page. The model and serial number can be located on the serial number plate attached to unit. These numbers are required for service. (See Fig. 1.)
NOTE: We strongly recommend that any servicing be performed by a qualified individual.
BEFORE YOU BEGIN
NOTE TO INSTALLER
NOTE TO OWNER
SAFETY CONSIDERATIONS
GENERAL INFORMATION
WARNING
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Failure to follow this warning may result in personal injury, death and/or property damage. For your safety, the information in this manual must be followed to minimize the risk of fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
This unit must be properly installed in accordance with the Installation Instructions before it is used.
Immediately repair or replace all electric service cords that have become frayed or otherwise damaged.
Unplug or disconnect the unit at the fuse box or circuit breaker before making any repairs.
This is the safety-alert symbol .When you see this symbol on the unit and in instructions or manuals, be aware that there is the potential for personal injury.
Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol.
• DANGER identifies the most serious hazards that will result in severe personal injury or death.
• CAUTION is used to identify unsafe practices that may result in minor personal injury or product and property damage.
• NOTE is used to highlight suggestions that make the unit easier to install or operate, or that make the unit more reliable.
G
REE ELECTRIC APPLIANCES WWW.GREE.CA MODEL # S
ERIAL #
L
ISTED 3JNY
PACKED TERMINAL AIR CONDITIONER
W
arni ng: Use on Sin gl e Outlet C i r cuit Onl y.
A
lso Verified In Accordance With Energy
S
tandards DDE Test Procedure 10 CFR, Part 430, App. F, Issued 01/01 and CAN/CSA-C368,1-M90
D
ESIGN PRESSURE LOWSIDE 300 P.S.I.
R
ATED VOLTS 1 PHASE 60 HZ
EER COP R410a Z. MFG.DATE
COOLING ELECTRIC HEATING HEATING
BTU/HR BTU/HR BTU/HR
AMPS AMPS AMPS
WATTS WATTS WATTS
F
ig. 1 – Sample data information plate
UNIT FEATURES
2
This premium unit has many exciting features that differ from those of most standard PTAC models. The owner must be familiar with these features in order to fully understand the operation and capability of the unit.
• Intelligence – Your premium unit has a computer that utilizes real-time diagnostics to prolong the life of your unit. There is a LED indicator on the control board, behind the front panel, that flashes an error code if the unit detects a malfunction. In many cases, the unit automatically clears the malfunction and continues operating without interruption. In some cases, the malfunction cannot be cleared and the unit requires service. In those cases, an “Fx” failure mode will appear on the digital display. For a detailed list of all error codes and “Fx” conditions, see Table 6 – Status LED Indicator Definitions.
• Memory – Your premium unit also has memory. If power is lost, all of the control settings (setpoint temperature, mode, fan speed, on/off and configuration) are remembered. So when power is restored, the unit will start back up in the mode (and configuration) it was in when power was lost.
• Premium sound – Not only does the unit have two fan motors and a tangential blower wheel for optimum sound control, the indoor fan always runs at least 10 seconds before the compressor starts, to help reduce noise from when the compressor starts.
• Random compressor restart – To help prevent power surges after a power outage (from several PTACs starting at the same time), the compressor is equipped with a 2:45 to 3:15 random restart delay feature. Whenever the unit is plugged in, or the power has been restarted, a random compressor restart will occur.
• Compressor protection – To prevent the compressor from short cycling and to maximize its life, there is a random start-up delay of three minutes on the compressor and a minimum compressor run time of three minutes.
•Automatic freeze protection – Automatically keeps the room temperature from getting too cold, when water pipes might freeze. If the unit is configured for freeze protection ( the default condition), then whenever power is supplied to the unit, if the unit senses that the temperature is below 40°F, the fan motor and electric heater turn on and warm the room to 50°F. If freeze protection is not required, change the configuration switch to turn the feature off (see section on unit configuration).
• Automatic defrost protection (for heat-pump models only) – When the outdoor temperature gets too cold (approx. 35°F) and the unit can no longer effectively heat with the compressor, the unit automatically switches to electric heating. The unit then heats with electric heat until the outside temperature rises enough (approx. 40°F) for the compressor to be used again.
• Automatic quick warm-up (for heat pump models only) -- If the room temperature falls to 5°F below the set temperature, the reverse-cycle heat turns off and the electric strip heat turns on for one cycle, until heating is satisfied.
•LED indicators and buttons – The touch pad has buttons for MODE, FANSPEED, ON/OFF, SETPOINT UP and SETPOINT DOWN. It also has LED lights that correspond to the mode, fan speed and setpoint operation, to indicate the unitʼs status. The LED lights below MODE, FAN, COOL, and HEAT, indicate the active operating mode. The LED lights below the Fan button, Low, Med and Hi, indicate the selected fan speed. The LED light located in the lower right corner shows whether the unit is on or off. If the unit is ON, the LED will be green. If the unit is OFF, the LED will be red.
• Configure fan to optimize selected application – The unit can optimize a selected application by configuring the fan to run in continuous mode or to cycle on and off with the compressor and electric heater (can be different for both heating and cooling modes). In cycle mode, the fan continues to run after the compressor or electric heater stops in order blow out any residual heat or cool left in the coil.
Fig. 2
UNIT FEATURES CONTINUED
3
• Unit configuration – There are many different possible configurations, set with both DIP switches and the digital keypad, that allow you to configure the unit for your exact needs. See the section on unit configuration for more details. The following are the configuration selections that have not previously been mentioned:
• °F or °C – The unit can display temperatures in either °F or °C.
• Indoor temperature sensor biasing – Optimize the room temperature sensor reading to your exact needs (one for cooling
and another for heating).
• Emergency heat (for heat pump only) – Disable the compressor while the heat mode is running (heat only with electric heat).
• Display setpoint OR room temperature – The unit can be configured to display the room temperature OR the setpoint temperature
only, in the heat and cool modes. See section on unit configuration for more details.
• Limit the setpoint range – The unit can be configured to limit the setpoint range. The display will always show the complete setpoint range, but the controlled setpoint will be limited to the selected minimum and maximum setpoint. See section on unit configuration for more details.
• Energy management – Also known as Front Desk Control, an input is provided so that the unit can be manually disabled from a different location. If the unit detects 24 VAC from this input, it automatically turns itself off. If no voltage is detected from the input, the unit runs normally.
• Wall thermostat control – A wired wall thermostat can be connected to the unit. If this is done, the unit must be configured to disable the keypad. See section on wired inputs and unit configuration for more details.
G A E (A) 07 A B - D (P) 3 RNB1A
P
TAC / TTW
Cooling capacity
Refrigerant R410a
Voltage D 230 / 208 ~ 60Hz P 265V ~ 60Hz
E Electrical + cooling A Electrical + heat pump
Fig. 3 – Catalog number nomenclature
ELECTRICAL DATA
4
• POWER CONNECTION OPTIONS
• ALL UNITS
• VOLTAGE SUPPLY
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage. DO NOT alter cord or plug. DO NOT use an extension cord.
The appropriate power cord accessory kit is determined by the voltage and amperage of the branch circuit. The unit does not come with a power cord (or hard wire kit). A power cord accessory kit must be ordered to connect the unit to the outlet. If the unit is to be hard wired, a hard wire accessory kit must be ordered.
LEGEND
AWG --- American Wire Gauge * Single circuit from main box. † Based on copper wire at 60°C temperature rating.
Table 1—SUGGESTED BRANCH CIRCUITWIRE SIZES*
Wire size Use the recommended wire size provided in Table 1 and install a single branch circuit. All wiring must comply with local and national codes. All units are designed to operate from ONE single branch circuit only.
Grounding
For safety and protection, the unit is grounded through the power cord plug or through a separate ground wire provided on hard-wired units. Be sure that the branch circuit or general purpose outlet is grounded.
Cord-connected units
The 250V field supplied outlet must match the plug for the standard 208/230V units and be within reach of the power cord. The standard cord-connected 265V units require an electrical subbase accessory. Refer to Table 2 for the required receptacle and fuse type.
Power cord protection
The power cord for 230/208V units provides power cord fire protection. Unit power automatically turns off when unsafe conditions are detected. Power to the unit can be restored by pressing the reset button on the plug head.
Check voltage supply at outlet. For satisfactory results, the voltage range must always be within the ranges found on the data information plate.
AWG WIRE SIZE
14 12 10
NAMEPLATE AMPS
7.0 to 12
12.1 to 16
16.1 to 24
Table 2—RECEPTACLES AND FUSE TYPES 250, 265 VOLTS
R
ECEPTACLE
L
EGEND : HACR - - He ating, Air Condition ing, Refrigerat ion.
* M
ay be used for 15 - amp appl ications
A
MPS 15
15
2
0
20*
30
30
1
5
15
2
0
20
3
0
30
RATED VOLTS 250 250 250 265 265 265
TIME — DELAY TYPE FUSE
(or HACR circuit breaker)
Upon completing the unit installation of 230/208V models, an operational check should be performed using the TEST/RESET buttons on the plug head.
NOTE: The 265V models do not include this feature, as they require the electrical subbase accessory.
IMPORTANT: For 265V units, if power cord accessory is selected, the cord is only 18” long and must plug into the electrical 265V subbase receptacle accessory.
Be sure that your outlet matches the plugʼs prong configuration and that the power cord will reach it. All wiring, including installation of the receptacle, must be in accordance with the NEC and local codes, ordinances and regulations. National codes require the use of an arc fault or leakage current detection device on all 208/230V power cords. Be sure to select the correct cord for your installation.
NOTE: Use copper conductors only.
INSTALLATION
5
Units are shipped without a sleeve. In applications where unit is a replacement, it is recommended that a GREE or Carrier sleeve be used.
These units can retrofit General Electric, Amana, Trane, and Friedrich sleeves/grills (be sure outdoor grill is installed on the sleeve). See Table 3 for details. For any sleeve retrofit applications, be sure that the foam seals (factory-installed on the tube sheets) provide a good seal between the grill and outdoor coil tube sheets. These foam seals provide a barrier to separate the air exiting from the outdoor coil and the air coming in (known as air recirculation).
• CHASSIS INSTALLATION
UNIT DAMAGE AND/OR OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation. For retrofit applications, foam seals on outdoor coil tube sheets must make a seal between the coil and the grill or loss of performance and premature damage to the major components can result.
Manufacturer
General Electric
M
e
t
a
l
s
l
e
e
v
e
R
A
B
7
1 Plastic sleeve RAB77 Metal sleeve WS900B
Metal sleeve SLV149
T – Series metal 11 ½ in. Deep wall sleeve*
Standard depth wall sleeve 16 X 42 X 13 ¾ in. PXWS
* FR – SLEEVE – EXT accessory is required for retrofit into Friedrich
(T –Series) wall sleeves.
Trane
Friedrich
Amana
Wall Sleeve Part Number
CAUTION
Table 3—Retrofit Wall Sleeves
INDOOR-AIR
INLET
FILTERS
DISCHARGE
GRILL
WIDE
SCREEN
OUTDOOR
OPENING
COIL TUBE
SHEETS
OUTDOOR
G
RILL
ACCESSORY
WALL
SLEEVE
A
CCESSORY
BASE PAN
INDOOR
COIL
FRONT
PANEL
Fig. 4 – Unit components
Proper installation is the responsibility of the installer. Product failure due to improper installation is not covered under the warranty.
6
• RETRO FIT SLEEVE PREPARATION
Remove any existing foam baffles that are installed on other brandʼs outdoor grill, if present. See Fig. 5.
GE sleeves only GE metal wall sleeve – GE metal sleeve is interchangeable with GREE wall sleeve. See Fig. 6. GE plastic sleeve – Remove bottom seal from plastic sleeve. See Fig. 7.
ELECTRICAL SHOCK HAZARD
• Failure to follow this warning could result in personal injury or death.
• Disconnect all power to the unit to avoid possible electrical shock during installation.
WARNING
INSTALLATION OF A GREE OR CARRIER WALL SLEEVE USING A NON-GREE GRILL
This application has become more common due to pre-manufactured windows with built-in grills or renovations where a GREE or Carrier sleeve is used with an existing non-GREE grill. Use of a GREE or Carrier wall sleeve with a non-GREE grill requires the installation of a baffle accessory kit (see Fig. 8), which ensures a good seal between the unit and the exterior grill to prevent air recirculation. Air recirculation is a large contributor to performance loss and premature damage to major components.
NOTES: The GREE stamped grill is interchangeable with CARRIER'S.
NOTE: Contact your unitʼs supplier to get the kit. It
may differ from the one shown above.
BAFFLES
SLEEVE
BOTTOM SEAL
Fig. 5 – Remove existing outdoor grill baffles
from other brandʼs grill
Fig. 6 – GE metal sleeve
Fig. 7 – Remove bottom seal from GE plastic
sleeve
F
ig. 8 –Baffle accessory kit
IMPORTANT: Inspect wall sleeve thoroughly prior to installation. Manufacturer does not assume responsibility for
costs or damages due to defects in sleeve or improper installation.
• INSTALL UNIT INTO WALL SLEEVE
7
1. Carefully remove the shipping tape from the front panel and vent door. See Fig. 9.
2. Remove the shipping screw from the vent door, if present. See Fig. 10.
3. Remove the front panel. See Fig. 11.
4. Keep the unit level and slide into the wall sleeve until the foam seal rests firmly against the front of the wall sleeve.
5. Secure with four screws (supplied) through the unit flange holes. See Fig. 12.
6. Reinstall the front panel. See Fig. 13.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Failure to remove shipping tape and screw will prevent the fresh air vent door from opening and may result in damage to the vent door cable.
CAUTION
2
Pull out at the bottom to release it from the tabs (1). Then lift up (2).
1
Fig. 11 – Removing front panel
Fig. 9 – Shipping tape location
Place tabs over top rail (1). Push inward at bottom until panel snaps into place (2).
Fig. 13 – Replacing front panel
Fig. 10 – Shipping screw location
Fig. 12 – Securing unit
1
2
Shipping
tape
Remove shipping
screw if present
HOW TO CONNECT
8
ELECTRICAL SHOCK AND/OR UNIT OPERATION AND DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and/or damage to the unit or its operation.
• Follow the National Electrical Code (NEC) or local codes and ordinances.
• For personal safety, this unit MUST BE properly grounded.
• Protective devices (fuses or circuit breakers) acceptable for unit installations are specified on the nameplate of each unit.
• Do not use an extension cord with this unit.
• Aluminum building wiring may present special problems. Consult a qualified electrician.
• When unit is OFF, electricity is still running to the controls.
• Disconnect power to unit before servicing by:
1. Removing the power cord (if it has one) from the wall receptacle.
2. Removing the branch circuit fuses or turning the circuit breakers off at the panel.
WARNING
IMPORTANT: Please read the following electrical safety data carefully.
1. Remove front panel. See Fig. 11.
2. Remove junction box.
• Remove the junction box cover by removing the three screws from the front. Remove the junction box by taking out the top, rear and side screws. See Fig. 14.
3. Connect the power supply cord or hard-wire connector accessory to the unit connector. See Fig. 15.
• Units must be installed using the appropriate power supply kit. See Table 4 - POWER CONNECTION CHART. These connections must be followed.
4. Reinstall the junction box and cover.
• Use a wire clamp to attach the power cord to the base pan. Secure with screws (included). See Fig. 16.
• Replace the junction box and cover with the screws removed in Step 2. Tighten securely.
5. Replace the front panel. See Fig. 13.
6. Connect power to the unit.
Unit connector
Power supply cord
or hard-wire accessory
Junction box
Junction box cover
Wire clamp
Fig. 14 – Junction box location
Fig. 15 – Power connection
Fig. 16 – Wire Clamp
UNIT MODEL
230/208 VOLT
CODE OF POWER SUPPLY KIT
30A 20A 15A
GAE09AB-D3RNB1A
N/A*
PWRCORD-
2
30V - 30A
PWRCORD-
2
30V - 20A
PWRCORD-
230V - 15A
GAA09AB-D3RNB1A GAE12AB-D3RNB1A GAA12AB-D3RNB1A GAE15AB-D3RNB1A GAA15AB-D3RNB1A
Table 4—POWER CONNECTION CHART
*
Using 30A on these units could damage your unit.
9
SYSTEM CONFIGURATION
• VENTILATION CONTROL
• ADJUSTING AIR DIRECTION
To adjust air direction:
1. Remove the front panel. See Fig. 11.
2. Remove the louver screws that the hold the louver insert in place (from back side of front panel). See Fig. 18.
3. Turn the louver insert and rotate 180°. See Fig. 19.
4. Replace the louver insert.
5. Replace the screws and front panel.
• The ventilation control lever is located on the left side of the unit, behind the front panel.
NOTE: The vent door shipping hardware must be removed before using the vent control lever. See Installation Instructions.
• When set at CLOSE, only the air inside the room is circulated and filtered.
• When set at OPEN, some outdoor air will be drawn into room. This will reduce heating or cooling efficiency.
Energy tip: Keep the vent control at CLOSE. Room air will be filtered and circulated.
Open
Close
Vent control
(Pull lever through
label to operate.)
Fig. 17 – Ventilation control location
Fig. 19 – Adjusting louvers
Fig. 18 – Backside of front panel
Louver screws
Louver screws
Air discharge upward
Air discharge outward
(Default)
• DIP SWITCHES
10
• Auxiliary DIP switch controls are located behind the front
panel, through an opening below the control panel. To access, remove the front panel. See Fig. 11.
• DIP switches are accessible without opening the control
box. The unit must be OFF to effectively change their status.
• The factory setting for DIP switches is in the DOWN
position. See Table 5 – DIP Switch Functions for functions of each DIP switch position.
Electric heating only / Emergency heat (for heat pump units only)
This setting is typically used for emergency heating.
Wall thermostat enable
A wired wall thermostat can be connected to the unit. If this is done, this DIP switch must be moved to the wall thermostat enable position, before the wall thermostat can control the unit.
Heat and Cool Fan CON/CYC DIP switches
Allows the fan to operate in continuous or cycle modes while the unit is heating or cooling. CON (Continuous) Fan runs continuously, circulating air even when the temperature setting has been reached. This switch helps to maintain the room temperature closer to the thermostat setting. CYC (Cycle) This setting allows the fan to cycle on and off with the compressor or electric heater. The fan stops a short time after the temperature setting is reached.
Setpoint temperature limits
Provides a restricted range of temperatures.
Room freeze protection
If the unit senses a room temperature below 40°F, the fan motor and electric strip heater will turn on and warm the room to 50°F. The fan stops a short time after the temperature is reached.
DIP switches
DIP switch
Fig. 20 – DIP switch location on unit
Fig. 21 – DIP switches
Up Down
Freeze guard Setpoint Limit 2 Setpoint Limit 1
Fan CON/CYC for cooling Fan CON/CYC for heating
Wall thermostat enable Electric heat only (for heat pumps)
1 234567
No. UP DOWN REMARKS DEFAULT
1 2 3 4
7
5*6
ELECTRIC HEAT ONLY
WALL THERMOSTAT ENABLE
FAN CONTINUOUS RUN FOR HEATING
FAN CYCLE FOR COOL
FAN CYCLE FOR HEAT
FAN CONTINUOUS RUN FOR COOLING
F
REEZE GUARD ENABLEFREEZE GUARD DISABLE
CONTROL PANEL ENABLE DOWN
DOWN DOWN
DOWN
HEAT PUMP
FOR HEAT PUMP UNIT ONLY
DOWN
UP*UP
68 - 75 °F
20 - 24 °C
UP*DOWN
63 - 80 °F 18 - 28 °C
DOWN*UP
65 - 78 °F 19 - 26 °C
DOWN*DOWN
61 - 86 °F 16 - 30 °C
TWO CONFIGURATIONS (5*6)
COMBINE TO SELECT SETPOINT RANGE.
WHEN SETPOINT LIMIT IS
SET, DISPLAY ALWAYS SHOWS FULL RANGE.
DOWN*DOWN
61 - 86 °F
16 - 30 °C
(full range)
Table 5—DIP SWITCH FUNCTIONS
• KEYPAD CONFIGURATION
11
Keypad configuration
Allows further configuration of system to desired application. Changes do not take effect until power to the unit is turned on.
To enter keypad configuration
Turn on the unit. Press and hold the Fan Speed button and the COOLER button for 5 continuous seconds, within 30 seconds of the unit being turned on. If the unit has been on for more than 30 continuous seconds, the keypad configuration cannot be entered. When the keypad configuration mode is first entered, it will default to the Fahrenheit/Celsius display mode.
To scroll through the keypad configuration options
Press and release the Fan Speed button. The stored values will be displayed.
To modify configuration settings
Press and release the Setpoint Up or Setpoint Down buttons.
To exit keypad configuration
Keypad configuration will end on its own 30 seconds after the last time a button is pressed or when the MODE button on the keypad is pressed.
Fahrenheit/Celsius display switch
Change between Fahrenheit and Celsius on the display. “F” indicates Fahrenheit display and “C” indicates Celsius. Default is “F”.
Indoor air temperature sensor bias for COOL mode
Sometimes known as an anticipator, the air temperature sensor bias is used to adjust the room air temperature reading when in the COOL mode. (Not normally required.)
Indoor air temperature sensor bias for HEAT mode
Sometimes known as an anticipator, the air temperature sensor bias is used to adjust the room air temperature reading when in the HEAT mode. (Not normally required.)
Indoor temperature display
Change between showing setpoint only “SP” on the display while in the HEAT or COOL modes or displaying the room temperature “AA” while in the HEAT or COOL modes. “SP” mode is the default mode.
• If the “SP” is selected, only the setpoint temperature will be displayed in the HEAT or COOL modes, regardless of what the real temperature is in the room.
• If the “AA” mode is selected, the room temperature will be displayed in the HEAT, COOL and FAN modes. — If the MODE button has been changed to either HEAT or COOL, the setpoint temperature will be displayed for 10 seconds. After the 10 seconds, the room temperature will again be displayed. — If the on/off button is pressed (when the unit is off) and the last mode was either COOL or HEAT mode, the setpoint temperature will be displayed for 10 seconds before displaying room temperature. — During the HEAT and COOL modes, if either the up or down setpoint key is pressed, the display will show the setpoint temperature until 10 seconds after the last up or down key press. Then the room temperature will be displayed again.
AUXILIARY CONTROLS
12
• WALL THERMOSTAT TERMINAL
IMPORTANT: Only trained, qualified personnel should access the unitʼs electrical panel and install electrical accessories. Please contact your local electrical contractor, dealer, or distributor for assistance.
Thermostat wire routing
The thermostat wire is field supplied. Recommended wire gauge is 18 to 20 gauge solid thermostat wire. NOTE: It is recommended that extra wires be run to the unit in case any are damaged during installation. The thermostat wire should always be routed around or under the wall sleeve, NEVER through it. The wire should then be
routed behind the front panel to the easily accessible terminal connector.
R W Y O Gh Gl C
THERMOSTAT WIRE ROUTING
(UNDER SLEEVE, BEHIND FRONT PANEL)
Fig. 22 – Proper wire routing beneath unit
Fig. 23 – Terminal connector removal
and replacement
Wiring thermostat to unit
Wire wall thermostat input as defined in Fig. 25.
NOTE: Terminal connector can be removed and replaced to simplify the wiring. NOTE: For heat pump models, anytime there is a second-stage call for heating from the wall thermostat, the unit automatically
switches over to electric heating.
Install thermostat wiring
1. Check to be sure power to unit is disconnected.
2. Pull terminal connector to remove.
NOTE: Terminal connector can be removed and replaced to simplify thermostat wiring.
3. Connect wires from the thermostat to terminals on unit terminal connector.
4. Reinstall terminal connector.
5. Ensure that unit is configured for wall thermostat enable. 6
. Replace control panel label with wall thermostat label (included).
7. Restore power to unit.
NOTE: Refer to thermostat installation instructions for details on installing wall thermostat. N
OTE: For thermostats that have only one fan speed output (on or auto), the fan speed is determined by how the terminal
connector is wired. If Low fan is desired, wire the G output from the thermostat to GL on the unitʼs terminal block. If Hi fan is desired, wire the G output from the thermostat to GH on the unitʼs terminal block.
NOTE: If your thermostat is not working properly after proper installation, refer to the Troubleshooting section.
13
• TERMINAL CONNECTIONS
The wall thermostat terminal block is located behind the front panel and is easily accessible from the front of the control panel.
NOTES:
1. Use terminal “O” for heat pump connection only.
2. Terminal “C” (common) is typically only required for digital thermostats.
NOTE: Any illegal input combinations will be captured as thermostat wiring
failures and will light the STATUS LED indicator on main board (see Intelligent Self – Checking Control section)
• ENERGY MANAGEMENT INPUT (FRONT DESK CONTROL)
The controller can handle a switch signal from remote energy management input, called EM signal or front desk control. Input must be 24 VAC. If system receives a 24 VAC signal, it will turn the unit off; otherwise, the unit runs normally. This function will be disabled when the freeze guard protection is enabled. See Fig. 24 and Fig. 25 for terminal connections.
• INTELLIGENT SELF-CHECKING CONTROL
Your GREE PTAC has a computer that continuously checks key components of the unit to ensure they are operating properly. Under normal operation, the unit status indicator (STATUS, on main PCB), light is always ON. If there is a major problem, the unit will shut down and display a diagnostic failure code on the unitʼs display screen. If it is only a minor failure and the unit corrects the fault by itself, the diagnostic code will flash on the LED status display and can easily be seen when the front panel is removed (see Fig. 24). Failure STATUS codes are defined in the table below:
STATUS LED
Energy management terminal connections
Wall thermostat
terminal connections
TERMINAL BLOCK
TYPICAL WALL THERMOSTAT
Energy Management
(24 VAC in)
Common
See Note 1
See Note 2
R
W
Y O
GH
GL
C
Fig. 24– Terminal connector and LED location
UNIT DAMAGE HAZARD
•Failure to follow this caution may result in equip ment damage or improper operation.
•Improper wiring may damage unit electronics. Common busing is not permitted. Damage or erratic operation may result.
CAUTION
TERMINAL DESIGNATION
R
W
Y
O GH GL
C
24 VAC Electric heat Compressor
Reversing valve
High fan
Low fan
Common
Fig. 25 – Wiring connections
7 – segment display ʻF1ʼ, with STATUS light flashes 1 time, off 2 seconds 7 – segment display ʻ
F2ʼ, with STATUS light flashes 2 times, off 2 seconds
7 – segment display ʻF4ʼ, with STATUS light flashes 4 times, off 2 seconds 7
– segment display
ʻFPʼ
S
TATUS light flashes 9 times and off 3 sec, repeats STATUS light flashes 8 times and off 3 sec, repeats STATUS light flashes 7 times and off 3 sec, repeats STATUS light flashes 6 times and off 3 sec, repeats STATUS light flashes 5 times and off 3 sec, repeats
1 2 3 4 5 6 7 8 9
Indoor air temp sensor open/short Indoor coil sensor open/short Outdoor coil sensor open/short Freeze guard protection Thermostat wiring error Indoor coil high temp protection D
efrost (heat pump type) Outdoor coil high temp protection I
ndoor coil freeze protection
Table 6—STATUS LED Indicator Definitions
NOTE: When status light is flashing, it will be ON for 0.5 seconds and OFF for another 0.5 seconds.
OPERATION
14
IMPORTANT: When unit is first started, high humidity conditions can cause condensation to form on discharge grill. Keep doors and windows closed. Room humidity will decrease and moisture will evaporate.
2 1
TEMP CONTROL FAN, MODE& OPERATION
Fig. 26 – PTAC CONTROLS
• ABOUT THE CONTROLS ON YOUR UNIT
NOTE: In case of a power failure, the unit will remember the last programmed settings and will revert to those settings when restarted.
1. TEMP CONTROL
Temp Control is used to maintain room temperature. The compressor will cycle on and off to keep the room at the requested level of comfort.
COOLER – Lowers the temperature. (Minimum temperature setting is 61°F/16°C) WARMER – Raises the temperature. (Maximum temperature setting is 86°F/30°C)
2. FAN SPEED, MODE & ON/OFF FAN SPEED – Sets the fan operation to HI, MED, or LO speed. MODE-COOL – For cooling. MODE-HEAT – For heating.
NOTE: If the unit is a heat pump, raising the heat setting 5°F will cause unit to use its electric heating elements for one cycle
in order to reach the new requested temperature quickly.
M
ODE-FAN – For fan only.
ON/OFF – Turns the unit on or off.
NOTE: The LED light above the ON/OFF button will be green when unit is ON and red when the unit is OFF.
A
ll other LEDs are off when unit is set to OFF mode.
NOTE: Power remains connected to unit.
CARE AND CLEANING
15
• FRONT PANEL AND CASE
Turn unit off and disconnect power supply. To clean, use water and a mild detergent. DO NOT use bleach or abrasives. Some commercial cleaners may damage the plastic parts.
• OUTDOOR COIL
Coil on outdoor side of unit should be checked regularly. Unit will need to be removed to inspect dirt build-up that will occur on the inside of the coil. If clogged with dirt or soot, coil should be professionally cleaned.
NOTE: Never use a high-pressure spray on coil.
• BASE PAN
In some installations, dirt or other debris may be blown into unit from outside and settle in base pan (bottom of unit). In some areas of the United States, a gel-like substance may be seen in the base pan. Check base pan periodically and clean, if necessary.
• AIR FILTERS
UNIT DAMAGE HAZARD
•Failure to follow this caution may result in equipment damage or improper operation.
•Airflow restriction may cause damage to the unit.
CAUTION
Coils Grill
Clean inside and outside of outdoor coils regularly.
Fig. 27 – Outdoor coil
IMPORTANT : TURN UNIT OFF BEFORE CLEANING
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Do not operate unit without filters in place. If a filter becomes torn or damaged, it should be replaced immediately. Operating without filters in place or with damaged filters will allow dirt and dust to reach indoor coil and reduce cooling, heating, airflow and efficiency of unit. Airflow restriction may cause damage to unit.
CAUTION
The most important thing you can do to maintain unit efficiency is to clean the filters at least every 30 days (or more often depending on application). Clogged filters reduce cooling, heating and airflow.
Keeping filters clean will:
• Decrease operating costs
• Save energy
• Prevent clogged indoor coil
• Reduce risk of premature component failure
To clean air filters:
• Vacuum off heavy dirt.
• Run water through filters.
• Dry thoroughly before replacing.
Dirty filter-
Needs cleaning
Clogged filter - Greatly reduces
cooling, heating and airflow
Fig. 28 – Identifying clogged filter
Pull up
Push down
2 Air filters
Removing air filter Replacing air filter
Fig. 29 – Removing and replacing air filter
PREVENTATIVE MAINTENANCE
16
Preventative maintenance is essential to proper unit operation, efficiency and longevity. To ensure that the equipment works properly, it must be properly maintained. Equipment should be checked and verified several times during the year. During regular unit inspection and maintenance, follow the guidelines below:
• Clean both sides of outdoor coil. (Never use high pressure spray on coils.)
• Clean base pan and outdoor vent filter.
• Clean outdoor opening and fan.
• Clean indoor coil. (Never use high pressure spray on coils.)
• Clean indoor fan, wire screen and front panel.
• Clean or install new indoor air-inlet filter(s).
• Clean wall sleeve and outdoor grill.
• Inspect cord and receptacle.
• Secure electrical connections.
• Ensure front panel is properly mounted and not damaged.
• Ensure wall sleeve is installed properly.
• Ensure heat and cool cycles operate properly.
TROUBLESHOOTING
17
NOTES:
1. If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician.
2. If unit is installed where condensation drainage could drip in an undesirable location, a drain accessory kit should be installed and connected to drain system.
UNIT DOES NOT START
• Unit may have become unplugged
• Fuse may have blown
• Circuit breaker may have been tripped.
• Unit may be off or in wall thermostat mode. Check section on DIP switch settings to verify DIP switches are set properly.
• Unit may be in a protection or diagnostic failure mode. See section on Intelligent self–checking control.
UNIT NOT COOLING/HEATING ROOM
• Unit air discharge section is blocked
• Temperature setting is not high or low enough Note: Setpoint limits may not allow the unit to heat or cool the room to the temperature desired. Check section on DIP switch settings.
• Unit air filters are dirty.
• Room is excessively hot or cold when unit is started.
• Vent door left open
• Unit may be in a protection or diagnostic failure mode. Check section on Intelligent self–checking control.
• Compressor is in time delay. There is a protective time delay (approx. three minutes) when starting the compressor after a power outage (or restarting after it has been turned off), to prevent tripping of the compressor overload.
DISPLAY HAS STRANGE NUMBERS/CHARACTERS ON IT
ICE OR FROST FORMS ON INDOOR COIL
• Low outdoor temperature
• Dirty filters
COMPRESSOR PROTECTION
• Power may have cycled, so compressor is in restart protection.
Random compressor restart – Whenever the unit is plugged in, or
power has been restarted, a random compressor restart will occur. After a power outage, the compressor will restart after approximately t
hree minutes.
Compressor protection – To prevent the compressor from short
cycling, there is a random startup delay of three minutes and a minimum compressor run time of three minutes.
• When outdoor temperature is approximately 55°F or below, frost may form on the indoor coil when unit is in COOL mode. Switch unit to FAN operation until ice or frost melts.
• Remove and clean filters.
WATER DRIPPING OUTSIDE
UNIT MAKES NOISES
WATER DRIPPING INSIDE
• Wall sleeve is not installed level
• The unit may be in a diagnostic condition. Check Intelligent self–checking control section to determine if unit has had a failure.
• The unit may be set for °C (instead of °F), see the keypad configuration section
• If a drain kit has not been installed, condensation runoff during very hot and humid weather is normal. See Note 2. If a drain kit has been installed and is connected to a drain system, check gaskets and fittings around drain for leaks and plugs.
• Clicking, gurgling and whooshing noises are normal unit is running.
• Wall sleeve must be installed level for proper drainage of condensation. Check that installation is level and make any necessary adjustments.
• Make sure that curtains, blinds or furniture are not restricting or blocking unit airflow.
• Reset to a lower or higher temperature setting.
• Remove and clean filters.
• Allow sufficient amount of time for unit to heat or cool the room. Start heating or cooling early before outdoor temperature, cooking heat or gatherings of people make room uncomfortable.
• Close vent door.
• Check DIP switch settings for desired comfort.
Wait approximately three minutes for compressor to start.
• Check that plug is plugged securely in wall receptacle. Note: Plug has a test/reset button on it. Make sure that the plug has not tripped.
• Replace the fuse. See Note 1.
• Reset circuit breaker. See Note 1.
• Turn unit on (bottom right button on keypad). Note: If the unit turns on, the LED will be green. If the unit is off, the LED will be red. If there is no LED on, there is a problem with power or damage to the control.
POSSIBLE CAUSES SOLUTIONS
LIMITED WARRANTY
This air conditioner is covered by a warranty against defects in materials and workmanship including the compressor, if used for the applications specified in this ownerʼs manual, for a period of FIVE (5) YEARS from the date of original purchase in Canada.
Note : The internal compressor is covered by a 5-YEAR limited warranty.
During the warranty period, if this air conditioner fails under normal use, GREE will, at its option, either repair the unit or replace it, free of charge, within a reasonable period of time after the air conditioner is returned.
As a condition to any warranty service obligation, the customer must present this warranty certificate along with the proof of purchase.
THIS WARRANTY DOES NOT COVER :
1. Damage, accidental or otherwise, to the air conditioner that are not caused by materials or workmanship defect.
2. Damage caused by misuse, tampering or failure to follow the operating and maintenance instructions provided in this
ownerʼs manual.
3. Damage to the finish of the unit enclosure or to other outer features caused by wear.
4. Filter.
5. Damage caused by repairs or modifications to the air conditioner made by any person not duly authorized by GREE
6. Insurance and freight costs for the warranty service.
ALL IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, ARE LIMITED TO A FIVE YEAR (5) PERIOD COVERED BY THIS EXPRESS LIMITED WARRANTY. GREE DISCLAIMS ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES AND, IN NO EVENT, SHALL GREE. LIABILITY EXCEEED THE RETAIL VALUE OF THIS AIR CONDITIONER FOR BREACH OF ANY WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THIS AIR CONDITIONER.
Keep this ownerʼs manual along with your proof of purchase in a safe place for future reference. You must provide proof of purchase for warranty service.
Enter the following information on your air conditioner; it will help you upon getting assistance or service if you ever need it. You will have then to provide the model and serial numbers of the air conditioner – these data are detailed on the rating plate of the unit.
Dealer name :
Address :
M
odel number:
Serial number  :
Date of purchase  :
WARRANTY
18
Loading...