Unitary Side Discharge Split System
24VAC Control
Submittal Data: FLEXX24AH/36HP230V1A 24000 BTU/H (208/230V) HEAT PUMP SYSTEM
Name
Date
To
Designation
FEATURES
-Side Discharge Outdoor Unit
-Zero Lot Line Design
-Match with Gree or Competitive Indoor Unit
-Designed for New Construction or Replacement Market
-Quiet Outdoor Operation - 55 dB(A)
-24VAC Thermostat Compatible
-Acrylic Resin/Anti-Corrosion Fin Coating
-5 yr. Limited Compressor & Parts Warranty (Residential Only)
System Ratings
Rated Capacity (BTU/H)
Capacity Range (BTU/H) 12000Power Input (W)
SEER
EER
Rated Capacity at 47°F (BTU/H)
Capacity Range (BTU/H) 12000Power Input (W)
HSPF
COP
Rated Capacity at 17°
Power Input (W)
COP
Range
Cooling
Heating
Piping Data
Gas Pipe Size - OD (in)
Liquid Pipe Size - OD (in)
Connection Method Flared
FactoryCharge (oz)
AdditionalCharge ( oz/ft)
Pre-Charge Length (ft)
MAX Refrigerant Pipe Length (ft)
MIN Refrigerant Pipe Length (ft) 10
MAX Refrigerant Pipe Elevation (ft)
129°F (46°
5°F (-18°
75°F (24°
-22°F (-30°
Reference
Approval
Construction
No.
AHRI Certified Ref No : 205993849
Indoor Unit Data - FLEXX24HP230V1AH
Motor Output Power (HP)
FLA (A)
CFM
Rated External Static Pressure
External Static Pressure Range (InWg) 0Sound Pressure Level (dB(A))
(pt/hr)
Supply (Dedicated Circuit: Size Per Local Code)
Normal Operational Voltage 208/230 V, 1 Phase, 60
Voltage Range 187 - 253
MCA (A)
Outdoor Unit Data - FLEXX36HP230V1AO
DC Inverter Driven
RLA (A)
Type
Motor
Output Power (HP)
FLA (A)
Heater (W)
Pressure Level - dB(A)
Supply (Dedicated Circuit: Size Per Local Code)
Normal Operational Voltage 208/230
Voltage Range (V) 187 -
MCA (A)
MOCP/Breaker Size (A)

Features Summary
Low FrequencyTorque Control
Factor Correction
TXV Control
Voltage Startup YES
Diagnosis YES
AmbientCooling YES
ThermostatCompatible YES
Fan Type Centrifugal
Fan Speeds 3 Speeds
FLEXX24AH/36HP230V1A
FEATURES
Inverter
YES
YES
Type
Type
Electronic Expansion Valve (EEV)
With Electric Heater
With Electric Heater YES
Fin Coating
Defrosting YES
Preheating YES
Failure Recovery YES
ElectricalHeater Optional
Rotary
R410A
YES
YES
YES
Acrylic Resin

Submittal Data: FLEXX24HP230V1AH
FAN PERFORMANCE CURVES
FLEXX24HP230V1AH Air Flow Volume Curve
1400
1200
1000
800
Airflow
-
600
CFM
Speed 1-CFM
Speed 2-CFM
Speed 3-CFM
400
200
0
Pressure - InWc
0 0.1 0.3 0.4
0.15 0.2
Static Pressure-Inches W.C.
0 0.1 0.15 0.2 0.3 0.4
1-CFM
2-CFM
3-CFM
1050 940 910 850 720 600
1200 1070 1010 950 820 630
1280 1180 1130 1080 970 790

EXTENDED RATINGS
Outdoor Ambient
Temperature (DB)
Outdoor Ambient
Temperature (DB)
FLEXX24AH/36HP230V1A
MAX OUTPUT
COOLING PERFORMANCE
Return Air Temperature
80°F (DB)
TC
(Btu/h)
5°F 24000
10°F 24000
15°F 24000
20°F 24000
25°F 24000
30°F 24000
35°F 24000
40°F 24000
45°F 24000
50°F 24000
55°F 24000
60°F 24000
65°F 24000
70°F 24000
75°F 24000
80°F 25000
85°F 25000
90°F 25000
95°F 25000
100°F 24000
105°F 24000
110°F 24000
115°F 24000
120°F 23000
125°F 22000
129°F 22000
SHR EER
20.69 1160
20.51 1170
20.17 1190
20.00 1200
19.83 1210
19.67 1220
19.20 1250
18.90 1270
18.18 1320
17.52 1370
17.20 1395
16.90 1420
16.55 1450
16.11 1490
15.69 1530
14.71 1700
13.37 1870
12.50 2000
11.63 2150
10.86 2210
10.26 2340
9.60 2500
8.89 2700
8.21 2800
7.67 2870
7.59 2900
HEATING PERFORMANCE
Return Air Temperature
70°F (DB)
MAX OUTPUT
TC
(Btu/h)
-22°F
-20°F
-15°F
-10°F
-5°F
0°F
5°F
10°F
15°F
17°F
20°F
25°F
30°F
35°F
40°F
45°F
47°F
50°F
55°F
60°F
65°F
70°F
75°F
COP
1.40 3920
1.45 3950
1.61 4000
1.65 4100
1.68 4200
1.85 3800
2.10 3350
2.23 3150
2.35 3000
2.43 2900
2.61 2700
2.82 2500
2.99 2350
3.09 2280
3.46 2120
3.58 2050
3.85 1980
3.91 1950
3.96 2000
3.91 2100
4.01 2050
4.11 2000
4.14 1700
W - Watts
DB - Dry Bulb
TC - Total Capacity
SHR - Sensible Heat Ratio
COP - Coefficient of Performance

Submittal Data: FLEXX24HP230V1AH
MINIMUM SPACING REQUIREMENTS
Units:inches
INDOOR
A 24
ALL
0
SIDES
ALWAYS CHECK AND FOLLOW
STATE AND LOCAL CODE
REGULATIONS FOR MINIMUM
SPACING REQUIREMENTS
FLEXX36HP230V1AO
MINIMUM SPACING REQUIREMENTS
Units:inches
OUTDOOR
A 12
B 4
C 4
D 40
E 40
ALWAYS CHECK AND FOLLOW
STATE AND LOCAL CODE
REGULATIONS FOR MINIMUM
SPACING REQUIREMENTS

OPTIONAL HEATER AND GENERAL AIR HANDLER INFORMATION
FLEXX24HP230V1AH
Model Cooling Capacity (ton) Optional Electric Heater KW
FLEXX24HP230V1AH 2.0 FLEXXHTR5KW 5
FLEXX24HP230V1AH 2.0 FLEXXHTR8KW 8
Specifications are subjectto change withoutnoti ce. Manufacturerreserves the right to discontinueor modify specificationsor designs

DIMENSIONAL SPECIFICATIONS
UNIT DIMENSIONS& WEIGHTS
Weight (lbs) 156.5
170
inch
W 21-1/4
D 21-1/4
H 48-1/4
A 11-5/8
B 20
Line Valve 3/8-in OD
Line Valve 3/4-in OD
Connector 3/4 inOD
Weight (lbs) 217.2
UNIT DIMENSIONS & WEIGHTS Units: inch
A 37
B 20-7/8
C 32-1/4
D 24
E 19-1/8
G 18-1/8
Line Valve 3/8-in OD
240
Line Valve 3/4-in OD
Power wiring size must comply with applicablenational and localcodes for both ID and OD dedicatedcircuits.
Test conditionsare based on AHRI 210/240.
© GreeCorporation2021
Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs
without notice or without incurring obligations. All rights reserved.
CAT NO: GREE_FLEXX24AH_36HP230V1A_SUBMITTAL_09272021