Grant Vortex Pro, Vortex Pro Series, Vortex Pro 15/21, Vortex Pro 15/26, Vortex Pro 26/36 Installation & Servicing Instructions Manual

...
Part No. Doc 52 Rev.06 May 2012 D314
Grant Vortex Pro
External Module Condensing Oil Boiler Range
Installation & Servicing Instructions
2
Date: ______________________________
Tel. No: ____________________________
Boiler model: _______________________ Boiler output: _______________ kW
Fuel type: Kerosene / Bio-Kerosene
Nozzle size: ________________________ Pump pressure: _________________
Air setting: _________________________ Flue gas % CO
2
: ________________
Net flue gas temp: __________________ Smoke No: _____________________
System flushed: yes / no Corrosion inhibitor added: yes / no
Antifreeze added: yes / no
For Sealed systems only:
Expansion vessel size: _____________________ litres
Expansion vessel charge pressure: __________ bar
Sealed system fill pressure (cold): ____________ bar
Commissioning
Report
Commissioning Report
For use with Kerosene* only.
After installing the boiler leave these instructions with the User.
This appliance is deemed a controlled service and specific regional statutory requirements may be applicable.
*Operation on Bio-fuel
All Grant Vortex Pro condensing boilers, manufactured since May 2011, are suitable for operation on both standard kerosene (Class C2 to BS2869) and also bio-kerosene – up to a 30% blend (B30K).
All burner settings and nozzle sizes (as detailed in Section 2.3 of this manual) are correct for both standard kerosene and bio-kerosene (B30K).
In order to operate this boiler on bio­kerosene it will be necessary to take the following actions:
a) Use a bio-kerosene (B30K)
compatible flexible oil line in place of the oil line supplied with this boiler.
b) Have your oil storage tank and oil
supply line (including all pipework, sight gauges, filters, isolating valves, fire valves, de-aeration devices, etc.) checked for their compatibility with bio-kerosene (B30K).
Where necessary some, or all, of these
items may have to be replaced with a bio-kerosene compatible alternative.
c) Check the suitability of the flue system
with Grant UK.
d) Use only bio-kerosene (B30K) that
conforms to OPS24.
IMPORTANT
Under no circumstances should the boiler be used with bio-kerosene without the above actions being taken first.
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. © Grant Engineering (UK) Limited 2012. No part of this manual may be reproduced by any means without prior written consent.
GRANT ENGINEERING (UK) LIMITED
Hopton House, Hopton Industrial Estate, Devizes, Wiltshire SN10 2EU Tel: 01380 736920 Fax: 01380 736991 Email: sales@grantuk.com www.grantuk.com
Service Log
It is recommended that the boiler should be regularly serviced, at least once a year, and the details entered in the Boiler Handbook by the service engineer.
3
1 Introduction 4
1.1 How a condensing boiler works 4
1.2 Boiler description 4
1.3 Boiler components 5
2 Technical Data 6
2.1 Boiler technical data 6
2.2 Sealed system data 6
2.3 Vortex boiler using Class C2 kerosene 7
2.4 Water connections 7
2.5 Flue gas analysis 7
2.6 Boiler dimensions 8
3 Oil Storage & Supply System 10
3.1 Fuel supply 10
3.2 Burner oil connection 11
4 Boiler Installation Information 13
4.1 Introduction 13
4.2 Boiler location 13
4.3 Preparation for installation 13
4.4 Installing the boiler 14
4.5 Regulations compliance 14
4.6 Completion 14
4.7 Before you commission 14
4.8 Heating system design considerations 15
4.9 Underfloor heating systems 15
4.10 Pipework materials 15
4.11 Sealed systems 15
4.12 Underfloor pipework 15
5 Pipe Connections 16
5.1 Water connections 16
6 Condensate Disposal 17
6.1 General requirements 17
6.2 Connections 17
6.3 Pipework 17
6.4 External pipework 17
6.5 Condensate soakaway 17
6.6 Condensate trap 18
6.7 Condensate disposal pipework 18
6.8 Inspection and cleaning of trap 18
7 Sealed Systems 19
7.1 Sealed system installation 19
7.2 15/21 Sealed system kit 19
7.3 15/26 Sealed system kit 20
7.4 26/36, 36/46 Sealed system kit 21
7.5 Fit the expansion vessel 22
7.6 Fill the sealed system 22
7.7 Vent the pump 22
7.8 Pressure relief safety valve 22
Contents
8 Electrical 23
8.1 Connecting the power supply 23
8.2 Frost protection 23
8.3 Control system wiring diagrams 24
8.4 Boiler control panel wiring diagrams 26
9 Flue System and Air Supply 27
9.1 Low level discharge 27
9.2 Grant green system 27
9.3 Grant hybrid system 29
9.4 Grant horizontal system 30
9.5 Conventional flue systems 30
9.6 Air supply 30
10 Commissioning 31
10.1 Before switching on 31
10.2 Switching on 31
10.3 Running the boiler 32
10.4 Balancing the system 32
10.5 Completion 32
10.6 Air adjuster disc - 15/21 only 32
11 Boiler Servicing 33
11.1 Check before servicing 33
11.2 Dismantling prior to servicing 33
11.3 Cleaning the boiler 33
11.4 Cleaning the burner 34
12 Fault Finding 37
12.1 Boiler fault finding 37
12.2 Burner fault finding 38
13 Spare Parts 39
13.1 Boiler spares 39
13.2 Burner heads 39
13.3 Riello RDB1, 2, 2.2 burner spares 40
13.4 Riello RDB3.2 burner spares 42
14 Health & Safety Information 44
14.1 Insulation materials 44
14.2 Sealant materials 44
14.3 Kerosene and gas oil fuels (mineral oils) 44
15 EC Declaration of Conformity 45
16 Warranty 46
17 Notes 48
Contents
4
This manual is intended to guide engineers in the installation and maintenance of Grant VORTEX Pro External modules. A User guide for the operation of this boiler is attached to the reverse of this manual.
The following special text formats are used in this manual for the purposes listed below:
Warning of possible human injury as a consequence of not following the instructions in the warning.
Caution concerning likely damage to equipment or tools as a consequence of not following the instructions in the caution.
Note text. Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader.
1.1 How a Condensing Boiler Works
During the combustion process, hydrogen and oxygen combine to produce heat and water vapour. The water vapour produced is in the form of superheated steam in the heat exchanger. This superheated steam contains sensible heat (available heat) and latent heat (heat locked up in the flue gas). A conventional boiler cannot recover any of the latent heat and this energy is lost to the atmosphere through the flue.
The Grant VORTEX Pro condensing boiler contains an extra heat exchanger which is designed to recover the latent heat normally lost by a conventional boiler. It does this by cooling the flue gases to below 90°C, thus extracting more sensible heat and some of the latent heat. This is achieved by cooling the flue gases to their dew point (approximately 55°C).
1 Introduction
NOTE
!
CAUTION
!
WARNING
!
To ensure maximum efficiency, the boiler return temperature should be 55°C or less, this will enable the latent heat to be condensed out of the flue gases.
• The boiler will achieve net thermal
efficiencies of 100%.
To achieve maximum performance from the Grant Vortex Pro boiler, it is recommended that the heating system is designed so that a temperature differential of 20°C between the flow and return is maintained. The use of modulating circulating pumps (now widely available) and effective control systems should be considered.
The Grant VORTEX Pro boiler will however still operate at extremely high efficiencies even when it is not in condensing mode and therefore is suitable for fitting to an existing heating system without alteration to the radiator sizes. The boiler is capable of a maximum flow temperature of 75°C.
1.2 Boiler Description
Grant VORTEX Pro External modules ha v e an in su l at e d we a th e rp roo f enclosure made of galvanised steel with a powder coated finish, and are designed for external installation, either against a wall or free standing some distance away from the property, as required.
The External modules are part of the Grant range of automatic pressure jet oil boilers which have been designed for use with a fully pumped central heating system with indirect domestic hot water cylinder. They are not suitable for use with either a direct cylinder or a 'primatic' cylinder or gravity hot water.
The boilers are suitable for use on open vented or sealed central heating systems.
All models are supplied with the control panel and burner factory fitted.
The factory fitted low level discharge flue system can be adjusted on site for either rear, left hand or right hand flue outlet position as required.
Introduction
An external conventional flue (Green) system (Figure 9-3) is also available from Grant UK. Refer to Section 9.2 for further details.
A Hybrid flue (Green/Orange) system (Figure 9-1) is also available which allows the External module to utilise an existing chimney stack. Refer to Section 9.2 for further details.
Where an existing chimney is to be lined - Grant recommends the use of the Grant ‘Orange’ flue system, specifically designed for the Vortex range of condensing boilers. Refer to Section 9.2 for further details.
Where a rigid conventional flue is required, Grant recommends the use of the Grant 'Green' and 'Orange' flue system components. As no flue adaptor is supplied with the boiler it will be necessary to purchase the correct Grant Starter Elbow in order to connect this system to the boiler. Refer to Section for further details.
The 'Green' and 'Orange' system components can be used to construct a flue of maximum vertical height 19 metres.
The flue system materials and construction MUST be suitable for use with oil-fired condensing boilers. Failure to fit a suitable conventional flue may invalidate the warranty on the boiler.
A horizontal system - see Figure
9-4, is also available up to 3 metres ­components available:
• Straight starter
• Extensions 150 mm, 250 mm, 450 mm
and 950
mm
• Adjustable extension 195 to 270 mm
• 45° elbow
• Straight terminal
NOTE
!
5
Green system
Standard external high level/vertical flue starter kit - components available:
• External starter kit, straight or elbow
• Extensions 150 mm, 250 mm, 450 mm,
950 mm
• Adjustable extension 195 to 270 mm
• 45° elbow
• High level terminal
• Vertical terminal
1.3 Boiler Components
All burners are pre-set for use with kerosene and are supplied ready to connect to a single pipe fuel supply system with a loose flexible fuel hose and 3/8" to 1/4" BSP male adaptor supplied with the boiler.
An optional indoor programmer is available to purchase from Grant UK which allows the User to set the operating times for central heating and hot water, Part No. EPKIT.
To access the controls remove the front panel by turning the handle at the bottom and withdrawing the cover forwards at the bottom.
Introduction
Figure 1-1: Boiler controls for External modules
PRO EXTERNAL
BOILER ON/OFF SWITCH ISOLATES PUMP(IF WIRED INTO BOILER CONTROL PANEL) & BURNER ONLY. THIS COVER ISTO BE REMOVED BYQUALIFIED PERSONNELONLY DO NOTREMOVE COVER WITHOUTISOLATING SWITCHED LIVEAND FROST'STAT PERMANENTLIVE TESTSWITCH OVERIDES SYSTEM CONTROLSTO OPERATE BOILER
‘Lock-out’ reset button
Boiler front
panel removed
Control Panel
DANGER
THERE IS MORE THAN ONE LIVE SUPPLY TO THIS CONTROL PANEL
BOILER
OFF
OVERHEAT
RESET
TEST
SWITCH
OFF
HEATING
THERMOSTAT
ON ON
REFER TO WIRING DIAGRAM IN MANUAL
Overheat thermostat
reset button
(under screw cover)
Boiler
thermostat
Boiler
On/Off switch
Test
switch
DANGER
THERE IS MORE THAN ONE LIVE SUPPLY TO THIS CONTROL PANEL
BOILER
OFF
OVERHEAT
RESET
TEST
SWITCH
OFF
HEATING
THERMOSTAT
ON ON
REFER TO WIRING DIAGRAM IN MANUAL
If required, an additional flexible fuel line (900 mm) and 3/8" to 1/4" BSP male adaptor are available to purchase from Grant UK, for two-pipe oil supply systems, Part No. RBS36.
The temperature of the water leaving the boiler to heat the radiators and hot water cylinder is User adjustable.
The boiler is fitted with an overheat thermostat (which allows it to be used on a sealed central heating system) which will automatically switch off the boiler if the heat exchanger exceeds a pre-set temperature of 111°C ± 3°C.
The boiler control panel is fitted with an ON/OFF switch, boiler thermostat control knob and the manual reset button for the overheat thermostat.
6
* Weight includes burner but excludes flue. ** 125 mm diameter required for flexible flue liner (Orange system). For rigid flue system (e.g. Green system) 100 mm diameter flue required.
Refer to Section 9 Flue System and Air Supply for further details.
* Based on vessel charge and system cold fill pressure of 0.5 bar
2 Technical Data
Technical Data
2.1 Boiler Technical Data - Vortex Pro
2.2 Sealed System Data - External modules
Heating system pressure (cold)
Operating pressure of pressure relief valve
Expansion vessel size (pre-charged at 1 bar)
Max heating system volume (including boiler)*
Cold water mains connection
Pressure relief valve discharge connection
Circulating pump head
15/21, 15/26, 26/36, 36/46
Maximum 1.0 bar, Minimum 0.5 bar
2.5 bar
10 litres (15/21), 12 litres (15/26), 16 litres (26/36, 36/46)
106 litres (15/21), 128 litres (15/26), 170 litres (26/36, 36/46) - approx.
15 mm copper pipe
15 mm copper pipe
6 m (15/21, 15/26), 7 m (26/36, 36/46)
22 mm (only connect plastic pipe)
28
1
65 to 75
111 ± 3
Less than 50
230/240 V ~ 50 Hz Fused at 5 Amp
0.85
¼" BSP Male (on end of flexible fuel hose)
Minimum 8.7 - Maximum 37
Minimum 0.035 - Maximum 0.15
2.5
2.5
90
150
6.4
100 mm (4 in)
28.5
10.0
125 mm (5 in)**
External module
15/26
19
4.2
157
345
26
88 700
22 mm
22 mm
2 200
1 100
2.6
26/36
21
4.7
174
383
36
122 840
28 mm
28 mm
3 000
1 500
2.6
36/46
21
4.7
174
383
46
157 000
28 mm
28 mm
4 000
2 000
4.2
46/58
50
11
335
738
58
197 896
1¼"BSP
1¼"BSP
5 200
2 600
58/70
50
11
339
747
70
238 840
1¼"BSP
1¼"BSP
6 000
3 000
15/21
16.5
3.6
99
218
21
71 650
22 mm
22 mm
1 800
900
4.2
Model
Water content
* Weight (dry)
Max. heat output (kerosene)
Flow connection
Return connection
Min. flow rate (T=10°C) l/h
Min. flow rate (T=20°C) l/h
Condensate connection
Flue diameter (conventional)
Waterside resistance T=10°C
Waterside resistance T=20°C
Maximum static head
Minimum circulating head
Boiler thermostat range
Limit (safety) stat shut off temp
Max. hearth temperature
Electricity supply
Motor power
Starting current
Running current
Oil connection
Conventional flue draught
Max operating press - sealed sys
Max operating press - open sys
litre
gal
kg
lb
kW
Btu/h
l/h
l/h
mbar
mbar
m
m
°C
°C
°C
Watts
Amps
Amps
N/m²
in wg
bar
bar
26.0
9.5
7
Notes:
1 The data given above is approximate only. 2 The above settings may have to be adjusted on site for the correct operation of the burner. 3 Gas Oil is not suitable for use with the Grant VORTEX Pro boiler range. 4 The net flue gas temperatures given above are ± 10%. 5 When commissioning the air damper must be adjusted to obtain the correct CO2 level. 6 * Factory settings: 15/21 - 21 kW, 15/26 - 23 kW, 26/36 - 31.5 kW, 36/46 - 41.5 kW, 46/58 - 52.0 kW, 58/70 - 64.0 kW. 7 The combustion door test point may be used for CO2 and smoke readings only. Do not use this test point for temperature or efficiency readings. 8 When setting the 15/21 to 15 kW output the burner air adjuster disc requires repositioning. Refer to Section 10 Commissioning. When setting the 15/26 to 15 or 20 kW output the combustion head must be changed. Refer to Section 11.4 Cleaning the burner. When setting the 58/70 to 70 kW output the combustion head setting must be changed. Refer to Section 11.4 Cleaning the burner. 9 The installer must amend the boiler data label if the output is changed.
Technical Data
2.3 Vortex Pro Boilers using Class C2 Kerosene
2.4 Flue Gas Analysis
To allow the boiler to be commissioned and serviced, the boiler is supplied with a combustion test point on the front cleaning door. When this test point is used please note the following:
• The test point is for CO
2
and smoke readings only.
• The boiler efficiency and temperature must be taken from the flue test point on high level, vertical and conventional flue adaptors.
• Concentric low level flues do not contain a test point. The temperature and efficiency readings must be taken from the flue terminal.
2.5 Water Connections
15/21 External module
15/26 External module
26/36 External module
36/46 External module
46/58 External module
58/70 External module
22mm pipe
22mm pipe
28mm pipe
28mm pipe
1¼" BSP
1¼" BSP
Compression straight
Compression elbow
Compression straight
Tectite straight
Female socket
Female socket
in fittings kit
in fittings kit
in fittings kit
in fittings kit
fitted
fitted
22mm pipe
22mm pipe
28mm pipe
28mm pipe
1¼" BSP
1¼" BSP
SizeFitting FittingSupplied Supplied
Boiler model
Flow connection
Return connection
Size
(Btu/h)
51 200
62 400
71 650
51 180
68 240
78 475
88 700
88 700
107 500
123 000
123 000
142 000
157 000
156 952
177 424
197 896
197 896
218 368
238 840
(kW)
15.0
18.3
21.0
15.0
20.0
23.0
26.0
26.0
31.5
36.0
36.0
41.5
46.0
46.0
52.0
58.0
58.0
64.0
70.0
15/21
Riello RDB2.2
15/26
Riello RDB1
26/36
Riello RDB2
36/46
Riello RDB2.2
46/58
Riello RDB3.2
58/70
Riello RDB3.2
Nozzle
0.50/80°EH
0.55/80°EH
0.60/80°EH
0.50/80°EH
0.60/80°EH
0.65/80°EH
0.75/80°EH
0.75/80°EH
0.85/80°EH
1.00/80°EH
1.00/80°EH
1.20/80°S
1.25/80°S
1.25/80°S
1.35/80°S
1.65/80°S
1.65/80°S
1.65/80°S
1.75/80°S
Oil
press.
(bar)
7.0
7.5
9.0
7.0
8.0
8.5
8.0
8.0
9.0
9.1
9.0
8.0
8.0
8.0
9.5
8.0
8.0
9.5
9.5
Smoke
No.
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
Fuel flow
rate
(kg/h)
1.29
1.56
1.83
1.25
1.67
1.94
2.16
2.18
2.57
3.01
3.01
3.56
3.90
4.01
4.47
5.05
5.05
5.58
6.01
Flue gas
temp.
(° C)
66
73
80
60 - 65
65 - 70
70 - 75
68
68
70
78
78
80
88
75 - 80
75 - 80
75 - 80
75 - 80
75 - 80
75 - 80
CO
2
(%)
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
Burner
head type
T1
T1
T1
T1
T1
T2
T2
T3
T3
T3
T5
T5
T5
GIB
GIB
GIB
GIB
GIB
GIB
Heat OutputModel and
burner type
SEDBUK 2009
efficiency
(%)
91.2
91.9
93.3
90.7
91.7
91.4
Disc setting B
Disc setting C
Disc setting C
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Head setting 0
Head setting 0
Head setting 0
Head setting 0
Head setting 0
Head setting 4
Burner
head/disc
setting
*
*
*
*
*
*
Compression
Compression
Compression
Compression
Female socket
Female socket
fitted
fitted
fitted
fitted
fitted
fitted
8
Technical Data
2.6 Boiler Dimensions
Figure 2-2: 15/26, 26/36, 36/46 External module dimensions
Figure 2-3: 46/58, 58/70 External module dimensions
All dimensions in the diagrams above are in millimetres
Figure 2-1: 15/21 External module dimensions
4 pre-cut holes 50 mm dia. in sidesboth
879
637
768
517
307
187
99
Pre-cut hole for side flue exit if required
385
943
734
248
Plan View
112
122
122
=
=
3 pre-cut holes 76 mm dia. in base of boiler enclosure
Pre-cut hole for side flue exit if required
4 pre-cut holes 50 mm dia. in sidesboth
1005
509
797
269
908
117
50
757
A
660
418
179
15/26 A = 804 26/36, 36/46 A = 824
Plan View
132
180
180
=
=
3 pre-cut holes 76 mm dia. in base of boiler enclosure
Pre-cut hole for side flue exit if required
4 pre-cut holes 50 mm dia. in sidesboth
1153
584
945
233
50
1000
1140
816
418
179
1234
Plan View
64
191
191
=
=
3 pre-cut holes 76 mm dia. in base of boiler enclosure
9
Oil Storage & Supply
System
3.1 Fuel Supply
Fuel Storage
The tank should be positioned in accordance with the recommendations given in BS 5410:1:1997, which gives details of filling, maintenance and protection from fire.
A steel tank may be used and must be constructed to BS 799:5:1987 and OFS T200.
A galvanised tank must not be used.
A plastic tank may be used and must comply with OFS T100.
Plastic tanks should be adequately and uniformly supported on a smooth level surface, across their entire base area, that is, the area in contact with the ground.
Fuel Pipes
Fuel supply pipes should be of copper tubing with an external diameter of at least 10 mm.
Galvanised pipe must not be used.
All pipe connections should preferably use flared fittings. Soldered connections
must not be used on oil pipes.
Flexible hoses must NOT be used outside the boiler case.
A remote sensing fire valve must be installed in the fuel supply line, with the sensing head located above the burner. Recommendations are given in BS 5410:1:1997.
A metal bowl type filter with a replaceable micronic filter must be fitted in the fuel supply line adjacent to the boiler. A shut-off valve should be fitted before the filter, to allow the filter to be serviced.
A flexible fuel line, adaptor and ¼" BSP isolation valve are supplied loose with the boiler for the final connection to the burner. If a two pipe system or 'Tiger Loop' type de-aerator is used, an additional flexible fuel hose (900 mm) and
3
/8" to 1/4" BSP male adaptor are available to purchase from Grant UK, Part No. RBS36.
Metal braided flexible hoses should be replaced annually when the boiler is serviced. Long life flexible hoses should be inspected annually and replaced at least every 60 months.
Single pipe system - (See Figure 3-1)
With the storage tank outlet above the burner a single pipe system should be used. The height of the tank above the burner limits the length of pipe run from the tank to the burner.
As supplied the burner is suitable for a single pipe system
Two pipe system - (See Figure 3-2)
With the storage tank outlet below the burner, a two pipe system should be used. The pipe runs should be as shown in Figure 3-2. The return pipe should be the same level in the tank as the supply pipe, both being 75 to 100 mm above the base of the tank. The pipe ends should be a sufficient distance apart so as to prevent any sediment disturbed by the return entering the supply pipe.
Avoid the bottom of the tank being more than 3.5 m below the burner.
A non-return valve should be fitted in the supply pipe together with the filter and fire valve. A non-return valve should be fitted in the return pipe if the top of the tank is above the burner.
To be used with a two-pipe system, the burner must be fitted with an additional flexible fuel hose - a flexible fuel hose (900 mm) and
3
/8" to 1/4" BSP male adaptor are available to purchase from Grant UK), Part No. RBS36.
The pump vacuum should not exceed
0.4 bar. Beyond this limit gas is released from the oil.
For guidance on installation of top outlet fuel tanks and suction oil supply sizing, see OFTEC Technical Book 3. Available from OFTEC.
3 Oil Storage & Supply System
CAUTION
!
CAUTION
!
NOTE
!
Figure 3-1: Single pipe system
Filter
Fire valve
Shut-off valve
Shut-off valve
A
Sludge valve
Fill pipe
Vent pipe
Level gauge
Fuel storage tank
Head A
(m)
Maximum pipe run (m)
0.5
1.0
1.5
2.0
10 mm OD pipe
10 20 40 60
12 mm 0D pipe
20 40 80
100
Fire valve sensor
Pump
1 m
10
Oil Storage & Supply
System
Figure 3-3: De-aeration device system
Figure 3-2: Two pipe system
Fire valve
Tankmaster
See
Section 3.2
Sludge valve
Fill pipe
Vent pipe
Fuel storage tank
De-aeration device
e.g. Tiger Loop See Figure 3-4
Fire valve sensor
Supply
1 m
Return
Filter
Fire valve
Shut-off valve
Shut-off valve
See
Section 3.2
A
Return
Supply
Head A
(m)
Maximum pipe run (m)
0
0.5
1.0
1.5
2.0
3.0
3.5
10 mm OD pipe
35 30 25 20 15
8 6
12 mm OD pipe
100 100 100
90 70 30 20
Non return valve
Fire valve sensor
Sludge
valve
Fill pipe
Vent pipe
Level gauge
Fuel storage tank
1 m
11
Oil Storage & Supply
System
Tiger Loop system ­(See Figures 3-3 and 3-4)
When The storage tank outlet is below the burner, an alternative to a two pipe system can be achieved using a 'Tiger Loop' type oil de-aerator. This effectively removes the air from the oil supply on a single pipe lift.
The de-aerator is connected close to the boiler as a two pipe system (omitting the non-return valve) as shown in Figure 3-3. Refer to the manufacturers instructions supplied with the de-aerator.
The de-aerator must be mounted vertically. See Figure 3-3 and 3-4.
To be used with a de-aerator, the burner must be fitted with an additional flexible fuel hose - a flexible fuel hose (900 mm) and
3
/8" to 1/4" BSP male adaptor are available to purchase from Grant UK, Part No. RBS36.
3.2 Burner Oil Connection
The burner fuel pump is supplied for use with a single pipe fuel supply system.
For use on a two pipe system, it is necessary to fit the By-pass screw, as shown in Figure 3-5, into the tapping in the return port.
The By-pass screw is supplied in the boiler accessory pack.
On all models except 46/58 and 58/78:
Remove the plastic burner cover (secured by two screws).
On 46/58 and 58/70 models only:
Remove the plastic burner cover (secured by three screws).
For ease of access to the fuel pump, to fit the by-pass screw and connect the oil lines, the burner can be removed from the boiler. To do this, unscrew the single nut at the top of the burner (using a 13 mm spanner) and withdraw the burner from the boiler.
Remove and discard the blanking plug from the return connection of the pump and fit the By-pass screw using an hexagonal key.
Connect the return oil flexible fuel hose to the pump.
Connect the
3
/8" to 1/4" BSP adaptor to
the flexible fuel hose.
Flexible fuel hoses and adaptors are available to purchase from Grant UK.
1/4" BSP female
connections
Tiger Loop
SUPPLY
TO PUMP
RETURN
FROM PUMP
SUPPLY
FROM TANK
Figure 3-4: Tiger loop de-aeration device
1
2
3
4
5
6
7
8
Figure 3-5: Riello RDB pump
Description
Inlet (suction) port
Return port
By-pass screw
Pressure gauge port
Pressure adjustment
Vacuum gauge port
Solenoid Nozzle outlet
Item
1
2
3
4
5
6
7
8
The blanking plug supplied in the inlet (suction) port may now be plastic and will not provide an oil tight seal when the pump is running.
Ensure that the supply from the tank is connected to this port and that the plastic plug is discarded.
WARNING
!
12
Oil Storage & Supply
System
Figure 3-6: Riello RDB burner components
Main Burner Components
It may be necessary to remove the burner from the boiler to access connections in the fuel pump.
Remove the single nut at the top of the burner (using a 13 mm spanner) and withdraw the burner from the boiler.
Remove the factory fitted air inlet spigot adaptor (item) 6 in Figure 3-6 from the air intake on the top right hand side of the burner and fit the grey plastic air inlet grille in its place.
7
8
1
23
5
4
6
Burner Connection
If a two pipe system is to be used refer to Section 3.2.
Remove and discard the blanking plug from the inlet (suction) port of the pump. Refer to Figure 3-5.
Connect the elbow of the flexible fuel hose supplied with the boiler to the inlet port.
Connect the other end of the flexible fuel hose to the rigid supply line using the adaptor supplied. The supply enters the enclosure through one of the holes in the bottom of the side panels.
Description
Oil pump
Control box
Reset button with lock-out lamp
Flange with gasket (do not remove from boiler)
Air damper adjustment screw
Air supply tube connection (balanced flue)
Pump pressure adjustment screw
Pressure gauge connection
Item
1
2
3
4
5
6
7
8
NOTE
!
13
Boiler Installation
Information
4.1 Introduction
All models are supplied fully assembled with the flue terminal guard supplied loose inside the boiler.
4.2 Boiler location
1. The External module must stand on a solid, level surface capable of supporting the weight of the boiler when full of water, e.g. a prepared concrete standing, paving slabs bedded down on sand/cement, or similar.
2. The module can be installed either against the building or 'free standing' some distance away from the building.
3. The module must be positioned such that the required clearances from the low level flue outlet, as shown in Figure 9-4, are achieved.
4. Adequate clearance must be left around the module for servicing. In particular, a minimum clearance of 600 mm above the module for removal of the top panel and 600 mm at the opposite end to the flue outlet for access to the burner.
Sufficient clearance is required at
the rear of the boiler to allow the rear panel to be removed for access to the condensate trap.
4.3 Preparation for Installation
1. Carefully remove the packaging from the boiler and remove it from the transit pallet.
2. Remove the case top panel (four screws) and also the front and rear panels, as required.
3. The flue may exit the boiler from the left, right or rear of the casing. Carefully press out the pre-cut section on the side or rear casing panel to provide the opening in the required position for the flue to pass through the casing.
15/21, 15/26, 26/36 and 36/46
models - Fit the cover panel (with the round flue exit hole) over the square flue opening in the casing. Fit the circular rubber sealing grommet, provided, into the circular hole in the cover panel before fitting the flue terminal section.
46/58 and 58/70 models - Fit the
circular rubber sealing grommet, provided, into the circular hole in the side/rear caing panel before fitting the flue terminal section.
4. Slacken the wing nuts holding the flue elbow and rotate the elbow to the required direction for the flue to exit the casing.
4 Boiler Installation Information
5. Push the end of the flue terminal section (with the red seal) through the sealing grommet in the casing panel. The terminal section has been factory lubricated. Take care not to dislodge or damage the red flue seal.
6. Carefully insert the terminal into the flue elbow until the bend of the terminal contacts the outer casing, then, pull the terminal forward approximately 25 mm and rotate the bend so that the outlet is horizontal.
Rear Exit - The flue must
discharge away from the building.
Side Exit - The flue should discharge
towards the rear of the casing to prevent flue gases re-entering the boiler casing through the air inlet vents on the casing front door.
The flue terminal must be fitted
horizontally to prevent dripping from the end of the terminal.
7. Tighten the wing nuts holding the flue elbow and fit the stainless steel flue guard using the two screws provided.
8. The top panel of the casing has been designed so that it may be fitted to create a slight slope away from the side positioned against the wall. To tilt the top panel, loosen the four top panel casing screws, one at each corner and push down on the side furthest from the wall. Tighten the screws. See Figure 4-1.
Figure 4-1: Standard low level flue
14
4.4 Installing the Boiler
1. If the boiler is to be fitted against the wall, prepare the wall to accept the heating system pipework. To mark the wall for drilling, refer to Section
2.6 for the positions of the pipework openings in the enclosure sides.
Pipework should be insulated
where it passes through the wall into the boiler enclosure.
If the boiler is to be installed 'free
standing' (i.e. away from a wall) and the pipework run underground, push out the 'knock-outs' to open the required pipe openings in the base of the boiler enclosure. Using a sharp knife, cut through the polystyrene in the base, around the edge of the holes, to allow the flow and return pipes to enter the enclosure.
2. The electrical supply to the boiler should be routed through the wall in a suitable conduit, such that it enters the boiler enclosure via one of the unused pipework openings. The cable can be routed to the front of the boiler, for connection to the boiler control panel, either over the top or beneath the boiler heat exchanger. Heat resistant PVC cable, of at least 1.0 mm² cross section should be used within the boiler enclosure.
3. The oil supply line should be installed up to the position of the boiler. Refer to Section 3.1 for details. The final connection into the boiler enclosure can be made with 10 mm soft copper, routed along the base of the enclosure (either between the enclosure and wall or in front of the enclosure) to enter through one of the holes located in the bottom edge side panel, at the front (burner) end.
Boiler Installation
Information
4.5 Regulations Compliance
Installation of a Grant VORTEX Pro boiler must be in accordance with the following recommendations:-
• Building Regulations for England and Wales, and the Building Standards for Scotland issued by the Department of the Environment and any local Byelaws which you must check with the local authority for the area.
• Model and local Water Undertaking Byelaws.
• Applicable Control of Pollution Regulations.
• The following OFTEC requirements:-
- OFS T100 Polythene oil storage
tanks for distillate fuels.
- OFS T200 Fuel oil storage tanks
and tank bunds for use with distillate fuels, lubrication oils and waste oils.
Further information may be obtained from the OFTEC Technical Book 3 (Installation requirements for oil storage tanks) and OFTEC Technical Book 4 (Installation requirements for oil fired boilers).
The installation should also be in accordance with the latest edition of the following British Standard Codes of Practice:-
• BS 715 Metal flue pipes, fittings, terminals and accessories.
• BS 799:5 Oil storage tanks.
• BS 1181 Clay flue linings and flue
terminals.
• BS 4543:3 Factory made insulated chimneys for oil fired appliances.
• BS 4876 Performance requirements for oil burning appliances.
• BS 5410:1 Code of Practice for oil firing appliances.
• BS 5449 Forced circulation hot water systems.
• BS 7593 Code of Practice for treatment of water in heating systems.
• BS 7671 Requirements for electrical installations, IEE Wiring Regulations.
Failure to install and commission appliances correctly may invalidate the boiler warranty.
Before starting any work on the boiler, or fuel supply please read the health and safety information given in
Section 14.
4.6 Completion
Please ensure that the OFTEC CD/10 installation completion report (provided with the boiler) is completed in full.
Leave the top copy with the User.
Retain the carbon copy.
Ensure that the User Information pack (supplied with the boiler) is handed over to the Householder.
4.7 Before you Commission
To avoid the danger of dirt and foreign matter entering the boiler the complete heating system should be thoroughly flushed out - before the boiler is connected and then again after the system has been heated and is still hot. This is especially important where the boiler is used on an old system.
For optimum performance after installation, this boiler and its associated heating system must be flushed in accordance with the guidelines given in BS 7593:1992 'Treatment of water in domestic hot water central heating systems'.
This must involve the use of a proprietary cleaner, such as BetzDearborn's Sentinel X300 or X400, or Fernox Restorer. Full instructions are supplied with the products, but for more details of BetzDearborn's products, view the website www.sentinel-solutions.net and for more details of Fernox products view the website www.fernox.com.
NOTE
!
WARNING
!
NOTE
!
15
Boiler Installation
Information
For long term protection against corrosion and scale, after flushing, it is recommended that an inhibitor such as Betzdearborn's Sentinel X100 or Fernox MB-1 is dosed in accordance with the guidelines given in BS 7593:1992.
Failure to implement these guidelines will invalidate the warranty.
We recommend that both antifreeze and corrosion inhibitor be used in the primary water system.
4.8 Heating System Design Considerations
To achieve the maximum efficiency possible from the Grant VORTEX Pro boiler, the heating system should be designed to the following parameters:
Radiators:-
• Flow temperature 70°C
• Return temperature 50°C
• Differential 20°C
Underfloor:-
• Flow temperature 50°C
• Return temperature 40°C
• Differential 10°C
Size radiators with a mean water temperature of 60°C.
Design system controls with programmable ro om t her mo sta ts o r use w eat he r compensating controls to maintain return temperatures below 55°C.
The boiler should not be allowed to operate with return temperatures of less than 40°C when the system is up to operating temperature.
The use of a pipe thermostat is recommended to control the return temperature when using weather compensating controls.
Refer to Section 2.5 for the size and type of the connections and Section 5 for the position of the connections.
4.9 Underfloor Heating Systems
In underfloor systems it is essential that the return temperature must be maintained above 40°C to prevent internal corrosion of the boiler water jacket.
4.10 Pipework Materials
Grant boilers are compatible with both copper and plastic pipe. Where plastic pipe is used it must be of the oxygen barrier type and be of the correct class (to BS 7291:Part 1:2001) for the application concerned.
The first metre of pipework connected to both the heating flow and return connections of the boiler must be made in copper on all types of system
- sealed or open-vented.
NOTE
!
WARNING
!
4.11 Sealed Systems
If plastic pipe is to be used, the installer must check with the plastic pipe manufacturer that the pipe to be used is suitable for the temperature and pressures concerned.
Plastic pipe must be Class S to BS 7291: Part 1:2001.
The system must incorporate a low­pressure switch to shut off power to the boiler if the system pressure drops below 0.2 bar. A suitable low pressure switch kit is available to purchase from Grant UK, Part No. MPCBS 63.
4.12 Underfloor Pipework
Plastic pipe may be used on Underfloor systems where the plastic pipe is fitted after the thermostatic mixing valve. Copper tube must be used for at least the first metre of flow and return primary pipework between the boiler and the underfloor mixing/blending valves.
NOTE
!
WARNING
!
16
5.1 Water Connections
The flow and return pipework can exit the boiler enclosure either through the pre-cut openings provided in both sides (under the movable cover plates) and through the wall when installed against the building, or down and through the pre-cut openings provided in the base of the enclosure for 'free standing' installations. See Section 2.6. Push out the 'knock-out' from the required holes, taking care not to distort the side panel or base.
For condensate disposal pipework refer to Section 6.
1. To gain access to the water connections, remove the two screws securing the bottom of the back panel and remove it by withdrawing it forwards at the bottom. Remove the top casing panel.
2. If required, fit the Grant sealed system kit. Refer to Section 7.
3. Carefully manoeuvre the boiler in position to line up with pipework through the wall. Complete the water connections.
Note: Check that the baffles are in position and that the
cleaning cover is correctly fitted and a good seal made.
4. If the boiler is installed against a wall, fit the wall flashing strip. Position the strip with the bottom edge of the wider flange 20 mm above the enclosure top panel, with the narrow flange (with the three fixing holes) flat against the wall. The strip should overhang the top panel by an equal amount at each end.
5. Mark the position of the three fixing holes onto the wall, drill and plug the wall and secure the strip with suitable screws (not supplied).
15/21, 15/26, 26/36, 36/46 Flow connection: A pipe (22 mm for 15/21, 15/26 or 28 mm for 26/36, 36/46) is provided for the flow connection. This is located on the top of the boiler. The pipe will need to be vented, as it is the highest point on the primary heat exchanger.
15/21, 15/26, 26/36, 36/46 Return connection: A pipe (22 mm for 15/21, 15/26 or 28 mm for 26/36, 36/46) is provided for the return connection. This is located on the top of the boiler. The pipe will also need to be vented at some point, as it is the highest point on the secondary heat exchanger.
46/58, 58/70 Flow connection: A 1¼" BSP socket is provided for the flow connection. This is located on the top of the boiler. This flow pipe will need to be vented, as it is the highest point on the primary heat exchanger.
46/58, 58/70 Return connection: A 1¼" BSP socket is located on top of the boiler. This return pipe will also need to be vented at some point, as it is the highest point on the secondary heat exchanger.
All pipes to be fitted into the push-fit connectors provided should be cut using a pipe slicer or pipe cutter - to leave the pipe ends with a slight radius and free from any burrs or sharp edges. Pipes to be used with these fittings should not be cut square using a hacksaw.
Pipe Connections
5 Pipe Connections
Figure 5-1: 15/26 water connections
Heating return
Heating flow
Thermostat phials
Heating flow
Thermostat phials
Heating return
Heating return
Thermostat phials
Heating flow
Figure 5-2: 15/21, 26/36, 36/46 water connections
Figure 5-3: 46/58, 58/70 water connections
NOTE
!
17
6.1 General Requirements
When in condensing mode the Grant VORTEX Pro boilers produce condensate from the water vapour in the flue gases. This condensate is slightly acidic with a ph value of around 3 (similar to vinegar). Provision must be made for the safe and effective disposal of this condensate.
Condensate can be disposed of using one of the following methods of connection:
Internal connection (preferred option):
• into an internal domestic waste
system (from kitchen sink, washing machine, etc.)
• directly into the soil stack
External connection:
• into an external soil stack
• into an external drain or gulley
• into a rainwater hopper (that is part
of a combined system where sewer carries both rainwater and foul water)
• purpose made soakaway
All condensat e disposal pipes must be fitted with a trap - whether they are connected internally or externally to a domestic waste system/soil stack or run externally to a gully, hopper or soakaway.
6.2 Connections
Connections into a rainwater hopper, external drain or gulley should be terminated inside the hopper/drain/gulley below the grid level but above the water level.
Condensate disposal pipes should not be connected directly into rainwater downpipes or to waste/soil systems connected to septic tanks.
Condensate should not be discharged into 'grey water' systems that re-use water used in the home (not including water from toilets).
It should be noted that connection of a condensate pipe to the drain may be subject to local Building Control requirements.
6.3 Pipework
Condensate disposal pipework must be plastic (plastic waste or overflow pipe is suitable).
IMPORTANT: Copper or steel pipe is NOT suitable and MUST NOT be used.
Condensate disposal pipes should have a minimum 'nominal' diameter of 22 mm (¾") - e.g. use 21.5 mm OD polypropylene overflow pipe.
Condensate disposal pipes must be fitted with a fall (away from the boiler) of at least 2.5° (~45 mm fall per metre run).
Where it is not possible for the pipe to fall towards the point of discharge ­either internally into a waste system or externally to a gulley (e.g. for boilers installed in a basement), it will be necessary to use a condensate pump.
Condensate disposal pipes should be kept as short as possible and the number of bends kept to a minimum.
Pipes should be adequately fixed to prevent sagging, i.e. at no more than 0.5 metre intervals.
6.4 External Pipework
Ideally, external pipework, or pipework in unheated areas, should be avoided. If unavoidable, external pipework should be kept as short as possible (less than 3 metres) and 32 mm waste pipe used to minimise the risk of ice blocking the pipe in freezing conditions.
The number of bends, fittings and joints on external pipes should be kept to a minimum to reduce the risk of trapping condensate.
Condensate
Disposal
6 Condensate Disposal
NOTE
!
NOTE
!
NOTE
!
Figure 6-1: Purpose made condensate soakaway
For boiler installed in an unheated area such as an outhouse or garage, all condensate pipework should be considered as an ‘external’.
6.5 Condensate Soakaway
To keep external pipework to a minimum, locate the soakaway as close as possible to the boiler but ensure it is at least 500 mm from building foundations and away from other services, e.g. gas, electricity, etc.
The condensate pipe may be run above or below ground level and can enter either the top or side of the soakaway tube. Refer to Figure 6-1.
Ensure that the drainage holes in the soakaway tube face away from the building.
Backfill both the soakaway tube, and the hole around it, with 10 mm limestone chippings.
Only use a soakaway where the soil is porous and drains easily. Do not use in clay soils or where the soil is poorly drained.
Any damage due to condensate backing up into the boiler due to a high water table, in the case of a soakaway, or flooded drains when the condensate disposal is via a gulley or soil stack, is not covered by the Grant product warranty.
CAUTION
!
Ground level
32 mm waste pipe external to the building
Minimum 2.5 fall
O
25 mm
300 mm
400 mm
min.
Two rows of 3 x 12 mm holes at 25 mm centres and 50 mm from the bottom of the tube. Holes facing away from the property.
Cement seal
100 mm plastic tube
Sealed end Backfill with 10 mm
limestone chippings
Loading...
+ 39 hidden pages