Grant VORTEX Pro Combi Series, VORTEX Pro Combi 21e, VORTEX Pro Combi 26e, VORTEX Pro Combi 36e Installation & Servicing Instructions Manual

Grant VORTEX Pro Internal Combi
Combi 21e, Combi 26e and Combi 36e Condensing Oil Boiler Range
Installation & Servicing Instructions
Part No. DOC 88. Rev 00. May 2012
Commissioning Report
2
Report
GRANT ENGINEERING (UK) LIMITED
Hopton House, Hopton Industrial Estate, Devizes, Wiltshire SN10 2EU Tel: 01380 736920 Fax: 01380 736991 Email: sales@grantuk.com www.grantuk.com
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. © Grant Engineering (UK) Limited 2012. No part of this manual may be reproduced by any means without prior written consent.
For use with Kerosene* only.
After installing the boiler leave these instructions with the User.
This appliance is deemed a controlled service and specific regional statutory requirements may be applicable.
*Operation on Bio-fuel
All Grant Vortex Pro condensing boilers, manufactured since May 2011, are suitable for operation on both standard kerosene (Class C2 to BS2869) and also bio-kerosene – up to a 30% blend (B30K).
All burner settings and nozzle sizes (as detailed in Section 2.3 of this manual) are correct for both standard kerosene and bio-kerosene (B30K).
In order to operate this boiler on bio-kerosene it will be necessary to take the following actions:
a) Use a bio-kerosene (B30K) compatible flexible oil line in place of the oil line supplied with this boiler.
b) Have your oil storage tank and oil supply line (including all pipework, sight gauges, filters, isolating valves, fire valves, de-aeration devices, etc.) checked for their compatibility with bio-kerosene (B30K).
Where necessary some, or all, of these items may have to be replaced with a bio-kerosene compatible alternative.
c) Check the suitability of the flue system with Grant UK.
d) Use only bio-kerosene (B30K) that conforms to OPS24.
IMPORTANT
Under no circumstances should the boiler be used with bio-kerosene without the above actions being taken first.
Date:
Commissioning engineer:
Tel. No:
Boiler model: Boiler output: kW
Fuel type: Kerosene
Nozzle size: Pump pressure:
Air setting: Flue gas % CO
2
:
Net flue gas temp: Smoke No:
System flushed: Yes / No
Corrosion inhibitor added: Yes / No
Antifreeze added: Yes / No
(where there is a Yes / No - please circle appropriate answer)
For sealed systems only:
Expansion vessel size : litres
Expansion vessel change pressure : bar
Sealed system fill pressure (cold) : bar
Service Log
It is recommended that the boiler should be regularly serviced, at least once a year, and the details entered in the Boiler Handbook by the service engineer.
Contents
Contents
3
1 Introduction 4
1.1 How a Condensing Boiler Works 4
1.2 Boiler Description 4
1.3 Boiler Components 5
2 Technical Data 6
2.1 Boiler Technical Data 6
2.2 Burner Settings 7
2.3 Vortex Combi e Boilers using Class C2 Kerosene 7
2.4 Flue Gas Analysis 7
2.5 Boiler Dimensions 8
3 Oil Storage & Supply System 10
3.1 Fuel Supply 10
3.2 Burner Oil Connection 13
4 Boiler Installation Information 14
4.1 Introduction 14
4.2 Boiler Location 14
4.3 Preparation for Installation 14
4.4 Installing the Boiler 14
4.5 Expansion Vessel 14
4.6 Filling and Venting the System 14
4.7 Regulations Compliance Requirements 15
4.8 Completion 15
4.9 Before you Commission 15
4.10 Underfloor Heating Systems 15
4.11 Pipework Materials 15
4.12 Sealed Systems 15
4.13 Underfloor Pipework 15
5 Pipe Connections 16
5.1 Water Connections 16
5.2 Making the Water Connections 16
5.3 Domestic Hot Water System 17
5.4 To use the Water Hardness Kit 17
6 Condensate Disposal 18
6.1 General Requirements 19
6.2 Connections 18
6.3 Pipework 18
6.4 External Pipework 18
6.5 Condensate Soakaway 18
6.6 Condensate Trap 19
6.7 Condensate Disposal Pipework 19
6.8 Inspection and Cleaning of Trap 19
6.9 External Condensate Trap Fitting 19
7 Sealed Systems 21
7.1 System Models 21
8 Electrical 22
8.1 Connecting the Power Supply 22
8.2 Connecting the Controls - Heating Only 24
8.3 Connecting the Controls - Heating and Hot Water 28
8.4 Connecting an External Frost Thermostat 31
9 Flue System & Air Supply 32
9.1 Air Supply 32
9.2 Conventional Flue Systems 33
9.3 Connecting a Conventional Flue 35
9.4 Balanced Flue Systems 35
9.5 Prepare the Wall 39
9.6 High Level and Vertical Balanced Flue 39
10 Commissioning 40
10.1 Boiler Controls 41
10.2 Commissioning the Vortex Pro Combi 21e Riello RDB Burner 41
10.3 Information for the User 42
10.4 Balancing the System 42
10.5 Completion 42
10.6 Air Adjuster Disc - Combi 21 only 43
10.7 Information for the User 43
11 Boiler Servicing 44
11.1 Checking before Servicing 44
11.2 Dismantling Prior to Servicing 44
11.3 Cleaning the Boiler 44
11.4 Cleaning the Burner 46
12 Fault Finding 47
12.1 Initial Checklist - for Installer or Service Engineers 47
12.2 Main Fault Finding Procedures 48
12.3 Poor Hot Water Checklist 51
12.4 Riello RDB Burner Fault Finding 52
13 Spare Parts 53
14 Health & Safety Information 55
14.1 Insulation Materials 55
14.2 Insulation Materials 55
14.3 Kerosene and Gas Oil Fuels (mineral oils) 55
15 EC Declaration of Conformity 56
16 Warranty 56
16.1 The Vortex Oil Boiler Warranty 56
16.2 Extended Warranty 57
1 Introduction
4
Introduction
Warning of possible human injury as a consequence of not following the instructions in the warning.
To ensure maximum efficiency, the boiler return temperature should be 55° C or less, this will enable the latent heat to be condensed out of the flue gases.
The boiler will achieve net thermal efficiencies of 100%.
To achieve maximum performance from the Grant VORTEX Pro Combi e boilers, it is recommended that the heating system is designed so that a temperature differential of 20° C between the flow and return is maintained.
The Vortex Pro Combi e boilers will however still operate at extremely high efficiencies even when it is not in condensing mode and therefore is suitable for fitting to an existing heating system without alteration to the radiator sizes. The boiler is capable of a maximum flow temperature of 78° C.
1.2 Boiler Description
The Vortex Pro Combi e boilers are automatic pressure jet oil boilers designed for use with a sealed central heating system and will provide domestic hot water at mains pressure.
All boilers are supplied with the control panel and burner factory fitted.
All boilers can be connected to either a conventional flue system or a balanced flue system, as required.
The boilers are suitable for use in sealed central heating systems only.
All models are supplied with the control panel and burner factory fitted. The boilers can be connected to either a conventional flue system or a balanced flue system, as required.
For Conventional Flue Applications
Where a chimney is to be lined - Grant recommends the use of the Grant ‘Orange’ flue system, specifically designed for the Vortex range of condensing boilers. Refer to Section 9.2 for further details.
Caution concerning likely damage to equipment or tools as a consequence of not following the instructions in the caution.
The flue system materials and construction MUST be suitable for use with oil-fired condensing boilers. Failure to fit a suitable conventional flue may invalidate the warranty on the boiler.
For Balanced Flue Applications
The following flue kits are available from Grant UK.
Refer to Section 9 for further details.
Yellow System
Standard low level concentric balanced flue - components available:
Low level concentric balanced flue short
Extensions 225mm, 450mm and 675mm
90° extension elbow
45° extension elbow
45° elbow
• Plume Diverter Kit
Green System
Standard external high level/vertical flue starter kit (room sealed) - components available:
• External high level/vertical flue starter kit short (room sealed)
• Extensions 150mm, 250mm, 450mm, 950mm and adjustable 195 to 270mm
• 45° elbow
• High level terminal
• Vertical terminal
Note text. Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader.
1.1 How a Condensing Boiler Works
During the combustion process, hydrogen and oxygen combine to produce heat and water vapour. The water vapour produced is in the form of superheated steam in the heat exchanger. This superheated steam contains sensible heat (available heat) and latent heat (heat locked up in the flue gas). A conventional boiler cannot recover any of the latent heat and this energy is lost to the atmosphere through the flue.
The Grant VORTEX Pro Combi condensing boilers contain an extra heat exchanger which is designed to recover the latent heat normally lost by a conventional boiler. It does this by cooling the flue gases to below 90° C, thus extracting more sensible heat and some of the latent heat. This is achieved by cooling the flue gases to their dew point (approximately 55° C).
!
WARNING
!
CAUTION
!
NOTE
!
NOTE
Where a rigid conventional flue - internal to external - is required, Grant recommends the use of a hybrid system consisting of Grant 'Green' and 'Orange' flue system components. As no flue adaptor is supplied with the boiler it will be necessary to purchase the Grant CF adaptor kit to connect this system to the boiler correctly.
Flue adaptor kit - Ref. CFA15/70 - is used for all models as they all use the 100mm 'Green' and 'Orange' system components to construct a flue of maximum vertical height 8 metres.
This manual is intended to guide engineers in the installation and maintenance of Grant Pro Internal Combi e boilers. A separate manual is available to guide users in the operation of these boilers, and is printed inverted at the end of this manual.
The following special text formats are used in this manual for the purposes listed below:
Introduction
5
White System
High level concentric balanced flue kit ­components available:
• Vertical concentric balanced flue kit.
• Extensions 225mm, 450mm, 950mm and adjustable 275 to 450mm.
• 45° elbow.
Red System (for Combi 21e and 26e only)
A flexible vertical balanced flue system designed to be fitted inside an existing masonry chimney.
Consisting of three sections:
• Concentric white painted flue pipe connected to the boiler.
• Vertical concentric flexible flue (flexible stainless steel flue liner inside a flexible plastic air inlet liner).
• Terminal assembly for chimney top mounting.
Flue extensions and 45° elbows from the White system may be used.
Fitting instructions for the Low level, High level and Vertical balanced flue systems are supplied with the kits.
1.3 Boiler Components
The Vortex Pro Combi e boilers are only suitable for use with Kerosene.
All burners are ready to connect to a single pipe system with a loose flexible fuel line (900mm) and
3
/8" to 1/4" BSP male adaptor supplied with the boiler. If required, an additional flexible fuel line (900mm) and
3
/8" to 1/4" BSP male adaptor are available to purchase from Grant Engineering (UK) Limited, for two-pipe oil supply system, Part No. RBS36.
The temperature of the water leaving the boiler to heat the radiators is User adjustable.
The setting of the boiler thermostat on the Vortex Pro Combi boilers has no effect on the hot water performance.
The boiler is fitted with an overheat thermostat (which allows it to be used on a sealed central heating system) which will automatically switch off the boiler if the heat exchanger exceeds a pre-set temperature of 111°C ± 3°C.
Figure 1-1 shows the components in the Vortex Pro Combi e boilers and the position of the control panel. Figure 1-2 shows the details of the control panel.
The control panel is fitted with an ON/OFF switch, Heating switch, Hot water switch, Indicator lights, Boiler (heating), Pressure gauge and manual reset button for the overheat thermostat.
Figure 1-1: Vortex Pro Combi e boiler with front panel removed
Figure 1-2: Vortex Pro Combi e boiler control panel
Heating (CH) pump
Hot water (DHW) pump
Plug-in programmer position (if fitted)
Heating switch
Hot water switch
Boiler thermostat
Over heat reset button (under black cap)
Boiler On / Off switch
Indicator lights
Pressure gauge
Non return
valve
Non return
valve
Expansion vessel
Condensate trap
Burner lock-out button
2 Technical Data
6
2.1 Boiler Technical Data
Vortex Pro Combi Vortex Pro Combi Vortex Pro Combi
Model 21e 26e 36e
Boiler water content Litres 48.0 48.5 53.5
(including 32 litre primary store) Gal 10.6 10.7 11.8
Weight (dry)* kg 146 188 218
lbs 322 415 481
Connections: Heating flow and return mm 22 22 28
Cold water mains inlet mm 15 15 22
Domestic hot water outlet mm 15 15 22
Pressure relief valve discharge mm 15
Condensate connection 22mm plastic pipe
Flue size (conventional) 100 mm (4 in) diameter
Waterside resistance Flow/Return temp. diff. of 10°C
mbar 28.5 26.0
Waterside resistance Flow/Return temp. diff. of 20°C
mbar 10.0 9.5
Boiler thermostat range °C 65 to 78
Limit (safety) thermostat switch off temp. °C 111°C +0 -3
Maximum heating system pressure (cold) bar 1.0
Minimum heating system pressure (cold) bar 0.5
Pressure relief valve bar 2.5
Expansion vessel (pre-charged at 1 bar) litres 10 12 14
Maximum heating system volume** litres 106 128 148
Maximum operating pressure bar 2.5
Minimum domestic hot water flow rate 3.0 litres/min (0.66 gal/min)
Maximum domestic hot water temperature °C 65 (factory set)
Maximum mains water inlet pressure bar 8.0
Minimum recommended mains water inlet pressure
bar 2.5
Maximum hearth temperature °C Less than 50
Electricity supply 230V ~ 50Hz Fused at 5 Amp
Motor power 90 W max.
Starting current Amp 4.2 2.60
Running current Amp 0.85
Oil connection
1
/4" Male BSP (on end of flexible fuel line)
Conventional flue Minimum flue draught - 8.7 N/m² (0.035 in wg)
Maximum flue draught - 37 N/m² (0.15 in wg)
* Weight includes burner but excludes flue
** Based on expansion vessel charge and initial cold system pressure of 0.5 bar
Technical Data
Technical Data
7
Heat
SEDBUK
Nozzle Oil Smoke Burner Fuel Flue gas CO
2
output
SAP 2009
pressure
number head flow temp
Model Burner type kW Btu/h
%
bar kg/h °C %
21e Riello RDB 2.2 21.0 71,650 89.5 0.60/80ºEH 9.0 0-1 T1 1.83
80 (flue)
12
235 (door)
26e Riello RDB 1 26.0 88,700 90.2 0.75/80ºEH 8.0 0-1 T2 2.16 75 - 80 12
36e Riello RDB 2.2 36.0 123,000 91.6 1.00/80ºEH 9.1 0-1 T5 3.01 78 12
2.2 Burner Settings
Burners are supplied factory set at the outputs shown.
When commissioning, the air damper must be adjusted to obtain the correct CO
2
level and the Installer
must amend the data label.
2.3 Vortex Combi e Boilers using Class C2 Kerosene
Vortex Combi e boilers are only for use with kerosene.
!
NOTE
!
NOTE
The data given below is approximate only and is based on the boiler being used with a low level balanced flue.
The above settings may have to be adjusted on site for the correct operation of the burner.
Gas Oil is not suitable for use with a Grant Vortex Pro Combi e boiler.
The net flue gas temperatures given above are ± 10%.
When commissioning the air damper must be adjusted to obtain the correct CO
2
level.
The combustion door test point may be used for CO
2
and smoke readings only. Do not use this test point for temperature or efficiency readings.
2.4 Flue Gas Analysis
To allow the boiler to be commissioned and serviced, the boiler is supplied with a combustion test point on the front cleaning door. When this test point is used please note the following:
• The test point is for CO
2
and smoke
readings only.
• The boiler efficiency and temperature must be taken from the flue test point on high level, vertical and conventional flue adaptors.
• Concentric low level flues do not contain a test point. The temperature and efficiency readings must be taken from the flue terminal.
8
Technical Data
Figure 2-1: Vortex Pro Combi Internal 21e and 26e dimensions
2.5 Boiler Dimensions
All dimensions in the diagram above are in millimetres.
2 Technical Data
Right Side View
Plan View
Left Side View
Rear View
External drain trap
exit (left hand)
Internal drain trap
exit (left hand)
high level
Internal drain trap
exit (left hand)
low level
108
227
441
19
98
35
190190 210
62
90
62
90
15
ø155
ø31
590
295
140
125
697
587
142
98
860
691
Technical Data
9
Figure 2-2: Vortex Pro Combi 36e dimensions
All dimensions in the diagram above are in millimetres.
Right Side ViewLeft Side View
External drain trap
exit (left hand)
Internal drain trap
exit (left hand)
high level
Internal drain trap exit
(left hand) low level
190
60
14
Rear View
182.5182.5 250
62
90
615
554
170
694.5
170
695
900
456
82
86
307.5
Plan View
101
605
ø185
ø31
ø31
10
Oil Storage &
Supply System
3.1 Fuel Supply
Fuel Storage
The tank should be positioned in accordance with the recommendations given in BS 5410:1:1997, which gives details of filling, maintenance and protection from fire.
A steel tank may be used and must be constructed to BS 799:5:1987 and OFS T200.
A galvanised tank must NOT be used.
A plastic tank may be used and must comply with OFS T100.
Plastic tanks should be adequately and uniformly supported on a smooth level surface, across their entire load bearing base area, that is, the area in contact with the ground.
Fuel Pipes
For gravity fuel supply systems, fuel supply pipes should be of copper tubing with an external diameter of at least 10 mm.
Flexible pipes must NOT be used outside the boiler case.
A remote sensing fire valve must be installed in the fuel supply line (outside) where it enters the building, with the sensing head located above the burner.
Recommendations are given in BS 5410:1:1997.
A metal bowl type filter with a replaceable micronic filter must be fitted in the fuel supply line adjacent to the boiler. A shut-off valve should be fitted before the filter, to allow the filter to be serviced.
A flexible fuel line, adaptor and
1
/4" BSP isolation valve are supplied loose with the boiler for the final connection to the burner. If a two pipe system or Tiger Loop system is used, an additional flexible fuel line (900mm) and
3
/8" to 1/4" BSP male adaptor are available from Grant Engineering (UK) Limited (Part No. RBS36).
Metal braided flexible pipes should be replaced annually when the boiler is serviced. Long life flexible pipes should be inspected annually and replaced at least every 60 months.
!
CAUTION
!
CAUTION
Galvanised pipe must not be used.
All pipe connections should preferably use flared fittings. Soldered connections must not be used on oil pipes.
!
CAUTION
!
NOTE
Grant UK recommend that a fire valve with a temperature rating of 95°C be installed on any Grant Vortex Pro Combi.
!
NOTE
3 Oil Storage & Supply System
Oil Storage &
Supply System
11
Single Pipe System
Where the storage tank outlet is above the burner the single pipe system should be used. The height of the tank above the burner limits the length of pipe run from the tank to the burner.
As supplied the burner is suitable for a single pipe system.
Head A Max Pipe Length (m)
(m) ø 8mm ø 10mm
0.5 10 20 12040
1.5 40 80 2 60 100
Figure 3-1: Single pipe system
Two Pipe System
With the storage tank outlet below the burner, a two pipe system should be used. The pipe runs should
be as shown in Figure 3-2. The return pipe should be at the same level in the tank as the supply pipe,
both being 75 to 100 mm above the base of the tank. The pipe ends should be a sufficient distance apart
so as to prevent any sediment disturbed by the return entering the supply pipe.
Avoid the bottom of the tank being more than 3.5m below the burner.
A non-return valve should be fitted in the supply pipe together with the filter and fire valve. A non return valve should be fitted in the return pipe if the top of the tank is above the burner.
The pump vacuum should not exceed
0.4 bar. Beyond this limit gas is released from the oil.
For guidance on installation of top outlet fuel tanks and suction oil supply sizing, see OFTEC technical book 3.
Available at www.oftec.org.uk.
Figure 3-2: Two pipe system
Head A Max Pipe Length (m)
(m) ø 8mm ø 10mm
0 35 100
0.5 30 100 1 25 100
1.5 20 90 21570 3830
3.5 6 20
Fire valve
Fire valve sensor
Vent pipe
Fill pipe
Sludge valve
Shut-off valve
Shut-off valve
Level gauge
Filter
Fuel storage tank
Pump (see section 3.2)
Pump (see section 3.2)
Fire valve
Fire valve sensor
Vent pipe
Fill pipe
Sludge valve
Shut-off valve
Shut-off valve
Shut-off valve
Level gauge
Non return valve
Filter
Fuel storage tank
A
Supply
Return
12
Oil Storage &
Supply System
Fire valve
Supply
Return
Fire valve sensor
Vent pipe
Fill pipe
Sludge valve
Tiger Loop System ­(See Figures 3-3 and 3-4)
When The storage tank is below the burner, an alternative to a two pipe system can be achieved using a 'Tiger Loop' type oil de-aerator. This effectively removes the air from the oil supply on a single pipe lift.
The de-aerator is connected close to the boiler as a two pipe system (omitting the non-return valve) as shown in Fig. 3-
3. Refer to the manufacturers instructions supplied with the de­aerator. The de-aerator must be mounted vertically, as shown in Figures 3-3 and 3-4.
To prevent any possibility of fuel fumes entering the building, the de-aerator must be fitted outside in accordance with BS 5410:1:1997.
!
WARNING
Tankmaster
Fuel storage tank
De-aeration device e.g Tiger Loop see Figure 3-4
Pump (see section 3.2)
Figure 3-3: De-aeration device system
Figure 3-4: Tiger loop de-aeration device
To burner
From burner
From tank
Oil Storage &
Supply System
13
Figure 3-5: Burner pump connections
3.2 Burner Oil Connection
The fuel pump is supplied for use with a single pipe fuel supply system. For use on a two pipe system, it is necessary to fit the By-pass screw into the tapping in the return port. See Figure 3-5.
The By-pass screw is supplied in the boiler accessory pack.
The procedure is as follows:
1. Remove the plastic burner cover (two screws).
2. Remove and discard the blanking plug from the return connection of the pump and fit the By-pass screw using a hexagonal key.
3. Connect the return oil flexible fuel line to the pump.
4. Connect the
3
/8" to 1/4" BSP
adaptor to the flexible fuel line.
Flexible fuel lines and adaptors are available to purchase from Grant Engineering (UK) Ltd.
The burner cover may be left off until the boiler is commissioned.
Oil inlet
connection
Return connection
By-pass screw
Pressure gauge connection
Pressure adjuster
Vacuum gauge connection
Solenoid
Supply to nozzle
The blanking plug supplied in the inlet (suction) port may now be plastic and will not provide an oil tight seal when the pump is running.
Ensure the supply from the tank is connected to this port and the plastic plug is discarded.
!
WARNING
14
Oil Storage &
Supply System
4 Boiler Installation Information
4.1 Introduction
The boiler is supplied already fully assembled in a carton which is carefully packed with packing materials. The installation procedure therefore begins with unpacking and uninstalling of the packed boiler.
4.2 Boiler Location
The boiler must stand on a surface that is firm and level. It does not require a special hearth as the temperature of the boiler base is less than 50°C.
Sufficient clearance must be allowed at the front of the boiler to remove the burner and baffles for servicing.
The Vortex Pro Combi 21e and 26e boilers can be serviced from the front, but it is preferable for any worktop above the boiler to be removable.
The Vortex Pro Combi 36e requires a removable section of worktop above the boiler to provide access to components on top of the boiler and for servicing.
Care should be taken when siting the condensate trap if it is to be fitted outside the boiler. Refer to Section 6.
4.3 Preparation for Installation
Carefully remove the packaging from the boiler and remove it from the transit pallet.
Pull off the boiler front panel and remove the literature pack.
Lift off the two parts of the case top and remove the water connecting fittings.
4.4 Installing the Boiler
You are now ready to install the boiler. The main procedures are as follows:
• Make the water connections - see section 5.2.
• Fit flue terminal - see section 9.
• Check the expansion vessel - see section 4.5 below.
• Connect the power supply.
• Connect the fuel supply - see section 3.
• Fill and vent the system - see section 4.5.
4.5 Expansion Vessel
The expansion vessel fitted is supplied with a charge pressure of 1.0 bar (equivalent to a max. static head of 10.2 metres). The charge pressure must not be less than the actual static head at the point of connection. Do not pressurise the vessel above 1.5 bar.
The central heating system volume, using the expansion vessel as supplied, must not exceed the recommended volumes. Refer to Section 2.1. If the system volume is greater, an extra expansion vessel (complying with BS4841) must be fitted as close as possible to the central heating return connection on the boiler. The charge pressure of the extra vessel must be the same as the vessel fitted in the boiler.
Refer to BS7074:1:1989 for further guidance.
The air charge pressure may be checked using a tyre pressure gauge on the expansion vessel Schraeder valve. The vessel may be re-pressurised using a suitable pump. When checking the air pressure the water in the heating system must be cold and the system pressure reduced to zero.
4.6 Filling and venting the system
The expansion vessel fitted is supplied with a charge pressure of 1.0 bar (equivalent to a max. static head of 10.2 metres). The charge pressure must not be less than the actual static head at the point of connection. Do not pressurise the vessel above 1.5 bar.
Automatic and Manual Air Vents
The boiler is fitted with two Automatic air vents at the top of the boiler, located as follows:
• One on the top of the primary store.
• One on the heating flow pipe.
Refer to Figure 5-1.
Check that the small black plug on the side of each air vent is screwed in fully.
Then unscrew it one complete turn - the cap remains in this position thereafter.
A single manual air vent is also fitted at the top of the boiler - on the return pipe. Unscrew the cap one turn vent air from the pipe during filling and then fully close the cap.
Filling loop
If the flexible filling loop is used to fill the system, ensure it is connected and that the valve connecting it to the boiler is open and the valve at the front is closed.
A valve is open when the operating lever is in line with the valve, and closed when it is at right angles to it.
Ensure that the mains cold water supply valve is open (operating lever in line with the valve), then turn on the mains cold water supply and gradually open the front valve on the filling loop until water is heard to flow.
Vent each radiator in turn, starting with the lowest one in the system, to remove air.
It is important the circulating pumps are properly vented to avoid them running dry and the bearings being damaged.
To gain access to the heating pump in the Vortex Pro Combi e, it is necessary to lower the control panel.
Loosen (but do not remove) the four fixing screws securing the control panel to the side panels, hinge the panel forward to gain access to the pump.
Unscrew and remove the plug from the centre of the pump. Using a suitable screwdriver rotate the exposed spindle about one turn. When water starts to trickle out, replace the plug.
The Hot water pump must also be vented as described above.
Check the operation of the safety valve by turning the head anticlockwise until it clicks. The click is the safety valve head lifting off its seat allowing water to escape from the system. Check that this is actually happening.
Continue to fill the system until the pressure gauge indicates between 0.5 and 1.0 bar. Close the fill point valve and check the system for water soundness, rectifying where necessary. Water may be released from the system by manually operating the safety valve until the system design pressure is obtained.
The air pressure in the vessel must be checked annually.
!
NOTE
Boiler Installation
Information
15
The system design pressure (cold) should be between 0.5 bar and 1.0 bar. The pressure is equivalent to the maximum static head in bar + 0.3 (1 bar = 10.2 metres of water), where the static head is the vertical height from the centre of the expansion vessel to the highest point of the system.
Close the valves either side of the filling loop and disconnect the loop.
4.7 Regulatory Compliance
Requirements
Installation of a Grant VORTEX Pro Combi e boiler must be in accordance with the following recommendations:-
• Building Regulations for England and Wales, and the Building Standards for Scotland issued by the Department of the Environment and any local Byelaws which you must check with the local authority for the area.
• Model and local Water Undertaking Byelaws.
• Applicable Control of Pollution Regulations.
• The following OFTEC requirements:
• OFS T100 Polythene oil storage
tanks for distillate fuels.
• OFS T200 Fuel oil storage tanks
and tank bunds for use with distillate fuels, lubrication oils and waste oils.
Further information may be obtained from the OFTEC Technical Book 3 (Installation requirements for oil storage tanks) and OFTEC Technical Book 4 (Installation requirements for oil fired boilers).
The installation should also be in accordance with the latest edition of the following British Standard Codes of Practice:
• BS 715 Metal flue pipes, fittings, terminals and accessories.
• BS 799:5 Oil storage tanks.
• BS 4543:3 Factory made insulated chimneys for oil fired appliances.
• BS 4876 Performance requirements for oil burning appliances.
• BS 5410:1 Code of Practice for oil firing appliances.
• BS 5449 Forced circulation hot water systems.
4.8 Completion
Please ensure that the OFTEC CD/10 installation completion report (provided with the boiler) is completed in full.
Leave the top copy with the User.
Retain the carbon copy.
Ensure that the User Information pack (supplied with the boiler) is handed over to the Householder.
4.9 Before you Commission
To avoid the danger of dirt and foreign matter entering the boiler the complete heating system should be thoroughly flushed out - before the boiler is connected and then again after the system has been heated and is still hot. This is especially important where the boiler is used on an old system.
For optimum performance after installation, this boiler and its associated central heating system must be flushed in accordance with the guidelines given in BS 7593:1992 'Treatment of water in domestic hot water central heating systems'.
This must involve the use of a proprietary cleaner, such as Betz Dearborn's Sentinel X300 or X400, or Fernox Restorer. Full instructions are supplied with the products, but for more details of Betz Dearborn’s products, view the website www.sentinel­solutions.net and for more details of Fernox products view the website www.fernox.com.
For Long term protection against corrosion and scale, after flushing, it is recommended that an inhibitor such as Betz Dearborn's Sentinel X100 or Fernox MB-1 is dosed in accordance with the guidelines given in BS 7593:1992.
Failure to implement the guidelines will invalidate the warranty.
4.10 Underfloor Heating Systems
In underfloor systems it is essential that the return temperature must be maintained above 40°C to prevent internal corrosion of the boiler water jacket.
4.11 Pipework Materials
In Grant boilers are compatible with both copper and plastic pipe. Where plastic pipe is used it must be of the oxygen barrier type and be of the correct class (to BS 7291:Part 1:2001) for the application concerned.
4.12 Sealed Systems
If plastic pipe is used, the installer must check with the plastic pipe manufacturer that the pipe to be used is suitable for the temperature and pressures concerned.
Plastic pipe must be Class S to BS 7291: Part 1:2001.
4.13 Underfloor Pipework
Plastic pipe may be used on Underfloor systems where the plastic pipe is fitted after the thermostatic mixing valve. Copper tube must be used for at least the first metre of flow and return primary pipework between the boiler and the underfloor mixing/blending valves.
• BS 7593 Code of Practice for treatment of water in heating systems.
• BS 7671 Requirements for electrical installations, IEE Wiring Regulations.
Failure to install and commission appliances correctly may invalidate the boiler warranty.
!
NOTE
Before starting any work on the boiler, or fuel supply please read the health and safety information given in Section 14.
!
WARNING
The first metre of pipework connected to both the heating flow and return connections of the boiler must be made in copper on all types of system - sealed or open-vented.
!
NOTE
The boiler incorporates a low­pressure switch to shut off power to the boiler if the system pressure drops below 0.2 bar.
!
WARNING
5 Pipe Connections
16
Pipe Connections
5.1 Water Connections
Water connections may be from the rear, left or right hand side. If using low level side exit flue, connections must be on the opposite side to the flue.
Flow and return connections - All models are supplied with a push-fit elbow connection for the heating flow and return - 22 mm (Vortex Pro Combi 21e and 26e) or 28 mm (Vortex Pro Combi 36e).
Hot water connections - All models are supplied with push-fit elbow connections for the cold water mains inlet pipe and hot water outlet pipe. These are 15mm for the Vortex Pro Combi 21e and 26e, and 22mm for the Vortex Pro Combi 36e.
5.2 Making the Water
Connections
Flow and return pipework can be routed to either side of the boiler, dependant on the flue system used, from the push-fit elbows (supplied) on the flow and return connection. Refer to Figure 5-1.
Holes are provided in the rear of the casing side panels to allow the condensate pipe to be run through the back of the boiler. It will be necessary to
remove the back panel from the boiler casing to fit this pipework, and to refit the panel before placing the boiler in its final position. See Figure 6-3.
If access will be restricted, make any connections to the boiler before placing it in its final position.
If using a balanced flue system - Install the balanced flue system before connecting the heating system pipework to the boiler.
All Models
A 15 mm discharge pipe must be connected to the safety valve outlet connection. The pipework between the safety valve and the boiler must be unrestricted, that is, no valves. The discharge pipe should be run to the outside of the building and terminate so that it cannot cause injury to persons or property.
A drain tap is provided at the bottom on the front of the boiler (and also on the hot water store on the Vortex Pro Combi e).
All pipes to be fitted into the push-fit connectors provided should be cut using a pipe slicer or pipe cutter - to leave the pipe ends with a slight radius and free from any burrs or sharp edges.
Pipes to be used with these fittings should not be cut square using a hacksaw.
!
CAUTION
Figure 5-1: Vortex Pro Combi e pipe positions
Heating flow connection
Heating circulating
pump
Heating
return
Flow switch
Cold water inlet isolating valve
Cold water inlet
Automatic air vent
Safety valve
Pressure
switch
Manual air vent
Primary return isolating valve
Non return
valve
Automatic
air vents
Boiler flow sensor and overheat thermostat bulb
Safety valve
outlet
Condensate
Disposal
17
5.3 Domestic Hot Water System
To maintain a longer and more consistent hot water temperature, a flow restrictor is factory fitted to all models except the Vortex Pro Combi 36e, to limit the flow rate to approximately 15 litres/minute.
The flow restrictor is located in the outlet side of the cold water inlet isolating valve.
The incoming mains water pressure should be between 1 and 8 bar to ensure efficient operation.
If the pressure is above 8 bar a pressure reducing valve must be fitted.
The boiler may still operate down to a pressure of 1.0 bar but with a reduced flow rate. The minimum flow rate needed for the flow switch to operate is 3 litres/minute.
To ensure economic use, the pipe runs between the boiler and hot taps should be as short as possible and in 15 mm copper pipe or 22 mm for the Vortex Pro Combi 36e only. Where possible the pipework should be insulated to reduce heat loss.
All taps and mixing valves used in the domestic hot water system must be suitable for operating at a mains pressure of up to 8 bar.
If required, a shower may be fitted in the domestic hot water system. It is recommended that thermostatically controlled shower valves are used to protect against a flow of water at too high a temperature. If a fixed head type shower is used, no anti-syphonage devices are required. If a loose or flexible head type shower is used, it must be arranged so that the head cannot fall closer than 25 mm above the top of the bath, thereby preventing immersion in the bath water. If this is not practicable, an anti-syphonage device must be fitted at the point of the flexible hose connection.
The supply of hot and cold mains water direct to a bidet is allowed (subject to local Water Undertaking requirements) provided that the bidet is of the over-rim flushing type. The outlets should be shrouded and unable to have a temporary hand held spray attached. Arrangements for antisyphonage are not necessary.
5.4 To use the Water Hardness
Kit
Fill a clean container with a sample of water from the mains cold water supply to the boiler.
Immerse the test strip in the water for approximately one second, ensuring that all the test zones are fully wetted.
Shake off the surplus water and wait for one minute.
Assess the colouration of the test zones using the following chart.
If the hardness reading is found to be in the medium to very hard range (the shaded area), it is essential that some form of water conditioner or softener is fitted to reduce scale formation within the combination boiler. Failure to do so may invalidate both the manufacturers warranty and any extended warranty covering the appliance.
The water conditioner or softener should be fitted to the cold water supply serving the appliance and in accordance with the manufacturer’s instructions. Grant Engineering (UK) Ltd. cannot be held responsible for any damage or misuse caused by the fitting of any water conditioning device.
Before the mains water supply pipe is connected to the boiler, it should be thoroughly flushed out to avoid the danger of dirt or foreign matter entering the boiler.
The mains water connection to the boiler must be the first connection from the mains supply.
Please protect the domestic hot water system from harmful effects of scale. Problems caused by the build-up of limescale are not covered under the terms of the warranty.
!
CAUTION
A water hardness test kit is supplied with the boiler. Should the total hardness of the water supply exceed 125 ppm, an in-line scale inhibitor should be fitted in the cold water supply to the boiler.
Consult the local Water Undertaking if in doubt.
Do not immerse the test strip in running water and avoid contact.
!
NOTE
Green Areas Violet Areas Hardness Total Hardness mg/l (ppm)
4 0 Very Soft <50 mg/l calcium Carbonate 3 1 Soft <70 mg/l calcium Carbonate 2 2 Medium <125 mg/l calcium Carbonate 1 3 Hard <250 mg/l calcium Carbonate 0 4 Very Hard <370 mg/l calcium Carbonate
Note: (1mg/l = 1 ppm (part per million)
6 Condensate Disposal
18
Condensate
Disposal
6.1 General Requirements
When in condensing mode the Grant Vortex PRO Combi e boilers produce condensate from the water vapour in the flue gases. This condensate is slightly acidic with a ph value of around 3 (similar to vinegar). Provision must be made for the safe and effective disposal of this condensate.
Condensate can be disposed of using one of the following methods of connection:
Internal Connection (preferred option):
• Into an internal domestic waste system (from kitchen sink, washing machine, etc.).
• Directly into the soil stack.
External Connection:
• Into an external soil stack.
• Into an external drain or gulley.
• Into a rainwater hopper (that is part of a combined system where sewer caries both rainwater and foul water).
• Purpose made soakaway.
All condensate disposal pipes must be fitted with a trap - whether they are connected internally or externally to a domestic waste system/soil stack or run externally to a gully, hopper or soakaway.
6.2 Connections
Connections into a rainwater hopper, external drain or gulley should be terminated inside the hopper/ drain/gulley below the grid level but above the water level.
Condensate disposal pipes should not be connected directly into rainwater downpipes or to waste/soil systems connected to septic tanks.
Condensate should not be discharged into ’grey water’ systems that re-use water used in the home (not including water from toilets).
It should be noted that connection of a condensate pipe to the drain may be subject to local Building Control requirements.
6.3 Pipework
Condensate disposal pipework must be plastic (plastic waste or overflow pipe is suitable).
Condensate disposal pipes should have a minimum ‘nominal’ diameter of 22mm (
3
/4”) - e.g. use 21.5mm OD
polypropylene overflow pipe.
Condensate disposal pipes must be fitted with a fall (away from the boiler) of at least 2.5° (~45mm fall per metre run).
Copper or steel pipe is NOT suitable and MUST NOT be used.
For a boiler installed in an unheated area such as an outhouse or garage, all condensate pipework should be considered as an ‘external’.
6.5. Condensate Soakaway
To keep external pipework to a minimum, locate the soakaway as close as possible to the boiler but ensure it is at least 500mm from building foundations and away from other services, e.g. gas, electricity, etc.
The condensate pipe may be run above or below ground level and can enter either the top or side of the soakaway tube. Refer to Figure 6-1.
Ensure that the drainage holes in the soakaway tube face away from the building.
Backfill both the soakaway tube and the hole around it, with 10mm limestone chippings.
Only use a soakaway where the soil is porous and drains easily. Do not use in clay soils or where the soil is poorly drained.
Any damage due to condensate backing up into the boiler due to a high water table, in the case of a soakaway, or flooded drains when the condensate disposal is via a gulley or soil stack, is not covered by the Grant product warranty.
Where it is not possible for the pipe to fall towards the point of discharge
- either internally into a waste system or externally to a gulley (e.g. for boilers installed in a basement), it will be necessary to use a condensate pump.
Condensate disposal pipes should be kept as short as possible and the number of bends kept to a minimum.
Pipes should be adequately fixed to prevent sagging, i.e. at no more than
0.5 metre intervals.
6.4 External Pipework
Ideally, external pipework, or pipework in unheated areas, should be avoided. If unavoidable, external pipework should be kept as short as possible (less than 3 metres) and 32mm waste pipe used to minimise the risk of ice blocking the pipe in freezing conditions.
The number of bends, fittings and joints on external pipes should be kept to a minimum to reduce the risk of trapping condensate.
!
NOTE
!
NOTE
!
NOTE
!
CAUTION
Figure 6-1: Purpose made condensate soakaway
32mm waste pipe
external to the building
Two rows of 3 x 12mm holes at 25mm centres and 50mm from the bottom of the tube. Holes facing away from the property.
Backfill with 10mm limestone chippings
Sealed end
100mm plastic tube
Cement seal
Ground level
2.5° fall
25mm
300mm
400mm min.
Condensate
Disposal
19
6.6 Condensate Trap
Grant Vortex PRO boilers are supplied with a factory-fitted condensate trap to provide the required 75mm water seal in the condensate discharge pipe from the boiler.
This trap incorporates a float (which will create a seal when the trap is empty) and an overflow warning outlet (fitted with a plastic sealing cap). See Figure 6-2.
6.9 External Condensate Trap Fitting
To re-locate the factory-fitted trap outside the boiler casing, use the following procedure:
6.8 Inspection and Cleaning of Trap
The trap must be checked at regular intervals (e.g. on every annual service) and cleaned as necessary to ensure that it is clear and able to operate.
To inspect and clean the trap, perform the following procedure:
1. Disconnect flexible condensate hose from inlet connector.
2. Unscrew the inlet connection nut.
3. Remove the ‘top hat’ inlet connector and nut from trap.
4. Disconnect the condensate disposal pipe from the trap outlet.
5. Remove trap from bracket.
6. Remove float from trap - clean if necessary.
7. Inspect inside of trap and clean as necessary.
8. Re-assemble trap, re-fit to boiler and re-connect flexible hose. Ensure that hose is fully pushed onto the ‘top hat’ inlet connector.
With the trap fitted inside the boiler casing, the sealing cap must be fitted. If the trap is re-located outside the boiler then the following applies:
• If connecting the condensate discharge
- either internally or externally - into a waste system or soil stack - the sealing cap must be fitted in the trap outlet.
• On external discharge systems to a hopper, gully or soakaway, the sealing cap should be removed from the trap outlet.
• If there is any discharge of condensate from the overflow outlet, this could indicate a blockage (possibly due to freezing). Turn off the boiler and investigate the cause. If necessary contact your service engineer for assistance.
6.7 Condensate Disposal
Pipework
The condense trap outlet is at an angle of 48° below the horizontal. This is to automatically gives a 3° fall on any ‘horizontal’ runs of condense disposal pipe. Refer to Figure 6-1 and see trap outlet/pipe.
The outlet of the trap will accept
21.5mm OD to 23mm OD
Polypropylene overflow pipe for the condensate discharge pipe.
This discharge pipe can exit through the left side of the boiler through one of two pre-cut ‘knock-outs’ in the lower part of the left casing panel. Push out the ‘knock-out’ from the required hole taking care not to distort the side panel. Refer to Figure 2-1 for this on the Pro Combi 21e or 26e, or Figure 2-2 for this on the Pro Combi 36e.
The trap is factory-fitted inside the boiler casing - mounted on the inside of the left side panel - in an accessible position to allow for routine maintenance.
A flexible hose connects the outlet of the condensing heat exchanger to the trap inlet. Ensure the straight connector on the hose is fully pushed onto the ‘top hat’ inlet connector of the trap.
Figure 6-2: Condensate trap
If required, this condensate trap may be re-located outside the boiler casing. Refer to procedure given in ‘external condensate trap’. This procedure must be carried out before the boiler is installed.
!
NOTE
The bottom bowl is sealed to the trap body and cannot be removed.
!
NOTE
End cap is sealed to trap body. DO NOT attempt to remove it for cleaning.
!
NOTE
Failure to regularly check and clean the condensate trap may result in damage to the boiler and will not be covered by the Product Warranty.
!
NOTE
Condensate drain pipe from boiler
Unscrew this cap for maintenance access
Overflow warning outlet (with cap)
Condensate trap
Condensate outlet to drain
End cap
Care should be taken when siting the trap such that the overflow outlet is readily visible and that any condensate overflowing from the outlet cannot cause either a hazard to persons or damage to surrounding property or equipment.
!
WARNING
20
Condensate
Disposal
6 Condensate Disposal
Figure 6-3: Gaining access to the
condensate outlet
This procedure must be carried out before the boiler is installed.
!
NOTE
The top of the trap must be below the condensate connection on the boiler.
!
NOTE
The flexible hose must fall continuously from the outlet to the top of the trap.
!
NOTE
1. Remove both the top casing panel(s) from the boiler.
2. Unscrew and remove the screws fastening the left side panel to the rear casing panel of the boiler.
3. Carefully separate the left side and rear panels just enough to gain access to the condensate outlet on the left rear of the condensing heat exchanger (see Figure 6-3).
4. Push out pre-cut ‘knock-out’ from condensate outlet hole in rear of left side casing panel.
5. Remove right angle end of flexible condensate discharge hose from outlet connection on condensing heat exchanger.
6. From front of boiler, remove straight connector end of flexible hose from top of condensate trap.
7. Reverse flexible hose and pass the straight connector end through the new hole in the left hand casing panel. Push the straight connector firmly onto the condensate outlet connection of the condensing heat exchanger as far as possible.
8. Refit the left hand casing panel to the rear panel using the reverse procedure, ensuring all fixing screws are used.
9. Remove the trap from the mounting bracket.
10. Unscrew and remove the trap mounting bracket from the left side panel.
11. Fix the trap mounting bracket to the wall adjacent to the boiler in the required position.
12. Re-fit the trap to the mounting bracket. The mounting bracket supplied with the trap must be used
- the trap should not be supported by the condensate pipework only.
13. Connect the flexible condensate hose to the trap - pushing the right angle hose connector onto the trap inlet connection.
Rear panel
Left hand
side panel
Sealed Systems
21
7 Sealed Systems
7.1 System Models
All Grant Vortex Pro Combi e boilers are supplied for use as part of a sealed system complying with the requirements of BS 5449.
The maximum temperature of the central heating water is 78° C.
• Pressure relief safety valve complying with BS 6759 and set to operate at 2.5 bar. The discharge pipe must be routed clear of the boiler to a drain, in such a manner that it can be seen, but cannot cause injury to persons or property.
• Automatic air vent, fitted to the top of the boiler, ensures the boiler is vented.
• Filling loop. This must be isolated and disconnected after filling the system.
Refer to Section 4.5 for further details of the expansion vessel.
The expansion vessel charge pressure should always be slightly greater than the maximum static head of the system, in bar, at the level of the vessel (1 bar =
10.2 metres of water). See Figure 7-1.
The boilers are supplied with the following items factory fitted:
• A diaphragm expansion vessel complying with BS 4814, pre­charged at 1.0 bar, size as follows:
10 litre for Vortex Pro Combi 21e
12 litre for Vortex Pro Combi 26e
14 litre for Vortex Pro Combi 36e.
System pressure gauge, with an operating range of 1 to 4 bar.
The system fill pressure (cold) should be
0.2-0.3 bar greater than the vessel charge pressure - giving typical system fill pressures of approx 0.5 bar for a bungalow and 1.0 bar for a two-storey house. Refer to the Domestic Heating Design Guide for more information if required.
If thermostatic radiator valves are fitted to all radiators, a system by-pass must be fitted. The bypass must be an automatic type.
Provision should be made to replace water lost from the system. This may be done manually (where allowed by the local Water Undertaking) using the filling loop arrangement supplied with the boiler.
Filling of the system must be carried out in a manner approved by the local Water Undertaking.
Where allowed, the system may be filled via the filling loop supplied (the loop arrangement includes a double check valve assembly).
All fittings used in the system must be able to withstand pressures up to 3 bar.
Radiator valves must comply with the requirements of BS 2767(10):1972.
One or more drain taps (to BS 2879) must be used to allow the system to be completely drained.
The expansion vessel is connected via a flexible hose to allow it to be moved to gain access to the baffle cleaning cover. When replacing the vessel, care should be taken to ensure that the flexible connecting hose is not twisted.
Figure 7-1: Sealed system
Static head of system
Heating flow
Heating return
By-pass if required (automatic type)
350mm
Boiler
Expansion
vessel
If thermostatic radiator valves are fitted, the system must incorporate an adequate by-pass.
When designing a system, the pump head, expansion vessel size, and radiator mean temperature are amongst the factors that must be considered. See Section 4.5.
!
NOTE
Ensure that the expansion vessel is of sufficient size for the system volume (including the volume of the boiler). If necessary a second vessel may need to be fitted to the system. Refer to Section 2.1 for system volume. To determine total vessel volume required refer to BS7074:1:1989 or the Domestic Heating Design Guide.
!
NOTE
Stop valve
Water mains
Domestic hot water
Domestic cold water
Loading...
+ 47 hidden pages