Grant Vortex Eco Series, Vortex Eco 26/35, Vortex Eco 15/21, Vortex Eco 21/26 Installation And Servicing Instructions

Page 1
Grant Vortex Eco
External and System Floor Standing Condensing Oil Boiler Range
Installation and Servicing Instructions
UK | DOC 0081 | Rev 3.1 | June 2015
Page 2
Important Note
For use with Kerosene* only.
This appliance is deemed a controlled service and specific regional statutory requirements may be applicable.
*Operation on Bio-fuel
All Grant Vortex Eco condensing boilers, manufactured since May 2011, are suitable for operation on both standard kerosene (Class C2 to BS2869) and also bio-kerosene – up to a 30% blend (B30K).
All burner settings and nozzle sizes (as detailed in Section 2.3 of this manual) are correct for both standard kerosene and bio-kerosene (B30K).
In order to operate this boiler on bio­kerosene it will be necessary to take the following actions:
• Use a bio-kerosene (B30K
compatible flexible oil line in place of the oil line supplied with this boiler.
• Have your oil storage tank and oil
supply line (including all pipework, sight gauges, filters, isolating valves, fire valves, ed-aeration devices, etc.) checked for their compatibility with bio-kerosene (B30K). Where necessary some, or all, of these items may have to be replaced with a bio-kerosene compatible alternative.
• Check the suitability of the flue
system with Grant UK.
• Use only bio-kerosene (B30K) that
conforms to OPS24.
IMPORTANT
Under no circumstances should the boiler be used with bio-kerosene without the above actions being taken first.
Date:______________________________
Commissioning Engineer:_____________________________________________________
Tel. No:____________________________
Boiler model:_______________________ Boiler output:________________ kW
Fuel type: Kerosene / Bio-Kerosene
Nozzle size:________________________ Pump pressure:_____________________
Air setting:_________________________ Flue gas % CO2:____________________
Net flue gas temp:___________________ Smoke No:_________________________
System flushed: yes / no Corrosion inhibitor added: yes / no
Antifreeze added: yes / no
For Sealed systems only:
Expansion vessel size:______________________ litres
Expansion vessel charge pressure:___________ bar
Sealed system fill pressure (cold):____________ bar
Service Log
It is recommended that the boiler should be regularly serviced, at least once a year, and the details entered in the Boiler Handbook by the service engineer.
Declaration of Conformity
We declare that the Grant VORTEX range of Oil Boilers equipped with Riello RDB burners approved to EN 267: 1999 satisfy the requirements of the following European Directives:
1. 89/336/EEC - Electromagnetic Compatibility Directive Referred to the generic standards EN 55014: 1993, EN 50082: 1: 1992
2. 73/23/EEC - Electrical Equipment Safety Regulations Directive Referred to the generic standard NO: 3260: The Electrical Equipment (Safety) Regulations: 1994
3. 92/42/EEC - Hot Water Boiler Efficiency Directive Referred to the generic standard The Boiler (Efficiency) (Amendment) Regulations 1994 (SI 1994/3083)
GRANT ENGINEERING (UK) LIMITED
Hopton House, Hopton Industrial Estate, Devizes
???????
Wiltshire SN10 2EU Tel: +44 (0)1380 736920 Fax: +44 (0)1380 736991 Email: [email protected] www.grantuk.com
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
2
2
© Grant Engineering (UK) Limited 2015. No part of this manual may be reproduced by any means without prior written consent.
Page 3
Contents
1 Introduction 4
1.1 How a condensing boiler 4 works
1.2 Boiler description 4
1.3 Boiler components 5
2 Technical Data 6
2.1 Boiler technical data 6
2.2 Sealed system data - sealed 7 system models
2.3 Vortex boilers using Class 7 C2 kerosene
2.4 Flue gas analysis 7
2.5 Water connections 7
2.6 Boiler dimensions 8
3 Oil Storage and Supply 9 System
3.1 Fuel supply 9
3.2 Burner oil connection 11
4 Boiler Installation 13 Information
4.1 Introduction 13
4.2 Boiler location 13
4.3 Preparation for installation 13
4.4 Installing the boiler 14
4.5 Regulations compliance 14
4.6 Completion 14
4.7 Before you commission 14
4.8 Heating system design 15 considerations
4.9 Underfloor heating systems 15
4.10 Pipework materials 15
4.11 Sealed systems 15
4.12 Underfloor pipework 15
6 Condensate Disposal 17
6.1 General requirements 17
6.2 Connections 17
6.3 Pipework 17
6.4 External pipework 17
6.5 Condensate soakaway 17
6.6 Condensate trap 18
6.7 Condensate disposal 18
pipework
6.8 Inspection and cleaning of 18
trap
7 Sealed Systems 19
7.1 Sealed system installation 19
7.2 System models 20
7.3 Fill the sealed system 20
7.4 Pressure relief safety valve 20
7.5 Circulating pump 21
8 Electrical 23
8.1 Connecting the power 23
supply
8.2 Frost protection 23
8.3 Control system wiring 24
diagrams
8.4 Boiler control panel wiring 25
diagram
9 Flue and Air Supply 26
9.1 Air supply 27
9.2 Low level discharge flue 27
9.3 Horizontal system 27
9.4 Green system 28
9.5 Hybrid system 29
9.6 Coventional flue systems 29
10 Commissioning 30
10.1 Before switching on 30
10.2 Switching on 30
10.3 Running the boiler 31
10.4 Balancing the system 31
10.5 Completion 31
10.6 Air adjuster disc - 15/21 only 31
11 Boiler Servicing 32
11.1 Checking before servicing 32
11.2 Dismantling prior to servicing 32
11.3 Cleaning the boiler 34
11.4 Cleaning the burner 34
12 Fault finding 35
12.1 Boiler fault finding 35
12.2 Burner fault finding 36
12.3 Circulating pump fault 37 diagnosis
13 Spare Parts 38
13.1 Boiler parts list 38
13.2 Burner heads 38
13.3 Riello RDB2.2 burner 39
14 Health and Safety 41 Information
14.1 Insulation materials 41
14.2 Sealant materials 41
14.3 Kerosene and gas oil fuels 41 (mineral oils)
15 Recycling and disposal 42
16 Guarantee 43
5 Pipe Connections 16
5.1 Water connections 16
18 Notes 45
3
Page 4
1 Introduction
This manual is intended to guide Installers who have completed the Grant Wood Pellet Boiler Installer training course on the installation, commissioning and servicing of the Grant Spira Condensing Wood Pellet Boiler.
A separate manual is available to guide users in the operation of the boiler.
The following special text formats are used in this manual for the purposes listed below:
WARNING
!
Warning of possible human injury as a consequence of not following the instructions in the “warning”.
CAUTION
!
Caution concerning likely damage to equipment or tools as a consequence of not following the instructions in the “Caution”.
NOTE
!
Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader.
1.1 How a Condensing Boiler Works
During the combustion process, hydrogen and oxygen combine to produce heat and water vapour. The water vapour produced is in the form of superheated steam in the heat exchanger. This superheated steam contains sensible heat (available heat) and latent heat (heat locked up in the flue gas). A conventional boiler cannot recover any of the latent heat and this energy is lost to the atmosphere through the flue.
The Grant Vortex Eco condensing boiler contains an extra heat exchanger which is designed to recover the latent heat normally lost by a conventional boiler. It does this by cooling the flue gases to below 90°C, thus extracting more sensible heat and some of the latent heat. This is achieved by cooling
4
the flue gases to their dew point (approximately 55°C).
To ensure maximum efficiency, the boiler return temperature should be 55°C or less, this will enable the latent heat to be condensed out of the flue gases.
• The boiler will achieve net thermal efficiencies of 100%.
To achieve maximum performance from the Grant Vortex Eco boiler, it is recommended that the heating system is designed so that a temperature differential of 20°C between the flow and return is maintained. The use of modulating circulating pumps (now widely available) and effective control systems should be considered.
The Grant VORTEX Eco boiler will however still operate at extremely high efficiencies even when it is not in condensing mode and therefore is suitable for fitting to an existing heating system without alteration to the radiator sizes. The boiler is capable of a maximum flow temperature of 75°C.
1.2 Boiler Description
Grant Vortex Eco External modules have an insulated weatherproof enclosure made of galvanised steel with a powder coated finish, and are designed for external installation, either against a wall or free standing some distance away from the property, as required.
The External modules are part of the Grant range of automatic pressure jet oil boilers which have been designed for use with a fully pumped central heating system with indirect domestic hot water cylinder. They are not suitable for use with either a direct cylinder or a ‘primatic’ cylinder or gravity hot water.
The boilers are suitable for use on open vented or sealed central heating systems.
All models are supplied with the control panel and burner factory fitted.
The factory fitted low level discharge flue system can be adjusted on site for either rear, left hand or right hand flue outlet position as required.
An external conventional flue (Green system (Figure 9-2) is also available from Grant UK. Refer to Section 9.2 for further details.
A Hybrid flue (Green/Orange) system (Figure 9-3) is also available which allows the External module to utilise an existing chimney stack. Refer to Section
9.3 for further details.
Where an existing chimney is to be lined - Grant recommends the use of the Grant ‘Orange’ flue system, specifically designed for the Vortex range of condensing boilers. Refer to Section 9.3 for further details.
Where a rigid conventional flue is required, Grant recommends the use of the Grant ‘Green’ and ‘Orange’ flue system components. As no flue adaptor is supplied with the boiler it will be necessary to purchase the correct Grant Starter Elbow in order to connect this system to the boiler. Refer to Section 9 for further details.
The ‘Green’ and ‘Orange’ system components can be used to construct a flue of maximum vertical height 19 metres.
NOTE
!
The flue system materials and construction MUST be suitable for use with oil-fired condensing boilers. Failure to fit a suitable conventional flue may invalidate the guarantee on the boiler.
A horizontal system - see Figure
9-4, is also available up to 4 metres ­components available:
• Straight starter
• Extensions 150 mm, 250 mm, 450 mm and 950 mm
• Adjustable extension 195 to 270 mm
• 45° elbow
• Straight terminal
Page 5
Green system
Standard external high level/vertical flue starter kit - components available:
• External starter kit, straight or elbow
• Extensions 150 mm, 250 mm, 450 mm, 950 mm
• Adjustable extension 195 to 270 mm
• 45° elbow
• High level terminal
• Vertical terminal
1.3 Boiler Components
All burners are pre-set for use with kerosene and are supplied ready to connect to a single pipe fuel supply system with a loose flexible fuel line and 3/8” to 1/4” BSP male adaptor supplied with the boiler.
If required, an additional flexible fuel line (600 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK, for two-pipe oil supply systems (product code: RBS35 and RBS36).
The temperature of the water leaving the boiler to heat the radiators and hot water cylinder is user adjustable.
The boiler is fitted with an overheat thermostat (which allows it to be used on a sealed central heating system)
which will automatically switch off the boiler if the heat exchanger exceeds a pre-set temperature of 111°C ± 3°C.
The boiler control panel is fitted with an ON/OFF switch, boiler thermostat control knob and the manual reset button for the overheat thermostat.
An optional indoor programmer is available to purchase from Grant UK which allows the User to set the operating times for central heating and hot water (product code: EPKIT).
To access the controls remove the front panel by turning the handle at the bottom and withdrawing the cover forwards at the bottom.
Figure 1-1: Boiler controls for external modules
5
Page 6
2 Technical Data
2.1 Boiler Technical Data - Vortex Eco
Model Unit 15/21 21/26 26/35
Water content litre 13 13 19
gal 2.9 2.9 4.2
Weight (dry) * External modules
kg 113 (ex ternal module)
136 ( external system)
113 (external module) 136 ( external system)
142 (external module) 152 ( external system)
lb 249 (ex ternal module)
300 ( external system)
Flow connection 22 mm 22 mm 22 mm
Return connection 22 mm 22 mm 22 mm
Min. flow rate (∆ T=10°C) l/h l/h 1 780 2 200 2 980
Min. flow rate (∆ T=20°C) l/h l/h 890 1 100 1 490
Condensate connection 22 mm (only connect plastic)
Flue diameter (conventional) 100 mm
Waterside resistance ∆T=10°C mbar 28.5
Waterside resistance ∆T=20°C mbar 10
Maximum static head m 28
Minimum circulating head m 1
Boiler thermostat range °C 65 to 75
Limit (safety) stat shut of f temp. °C 111 ± 3
Max. hearth temperature °C Less than 50
Electricity supply 230/240 V ~ 50 Hz fused at 5 Amp
Motor power Watts 90
Starting current Amps 4.2
Running current Amps 0.85
Oil connection ¼ BSP Male (on end of flexible fuel hose)
Conventional flue draught N/m² Minimum 8.7 - Maximum 37
in wg Minimum 0.035 - Maximum 0.15
Maximum operating pressure - sealed system bar 2.0
Maximum operating pressure - open system bar 2.0
Maximum operating pressure - pressure relief valve
bar 2.5
249 (external module) 300 ( external system)
313 (external module) 335 ( external system)
* Weight includes burner but excludes flue.
6
Page 7
2.2 Sealed System Data - Sealed System Models
15/21, 21/26, 26/35
Heating system pressure (cold) Maximum 1.0 bar / Minimum 0.5 bar
Operating pressure of pressure relief valve 2.5 bar
Expansion vessel size (pre-charged at 1 bar) 12 litres
Max. heating system volume (including boiler)* 128 litres - approximately
Cold water mains connection 15 mm copper pipe
Pressure relief valve discharge connection 15 mm copper pipe
Circulating pump head 7 m
* Based on vessel charge and system cold fill pressure of 0.5 bar
2.3 Vortex Eco Boiler Using Class C2 Kerosene
Model
and
burner
type
15/21 Riello
RDB2.2
21/26 Riello
RDB2.2
26/35 Riello
RDB2.2
Notes
1 The data given above is approximate only. 2 The above setting may have to be adjusted on site for the correct operation of the burner. 3 Gas Oil is not suitable for use with the Grant Vortex Eco boiler range. 4 The net flue gas temperatures given above are ± 10%. 5 When commissioning the air damper must be adjusted to obtain the correct CO2 level. 6 * Factory settings: 15/21 - 18.1 kW, 21/26 - 22.7 kW, 26/35 - 30.8 kW. 7 The combustion door test point may be used for CO2 and smoke readings only. Do not use this test point for temperature or efficiency readings. 8 When setting the 15/21 to 15.1 kW output the burner air adjuster disc requires repositioning. Refer to Section 10. When setting the 21/26 to 20.7kW or the 26/35 to 25.6 kW output the combustion head must be changed. Refer to Section 11.4. 9 The installer must amend the boiler data label if the output is changed.
Heat Output SEDBUK
2009
(kW) (Btu/h)
annual
efficiency
Nozzle Oil
press.
(bar)
Smoke
No.
Burner
head
type
Burner
head/disc
setting
Fuel flow
rate
(kg/h)
Flue
gas
temp.
(°C)
(%)
15.1 51 500
* 18.1 61 750 0.55/80°EH 7.5 0 - 1 T1 Disc setting C 1.53 75 - 80 11 - 12
20.7 70 600 0.60/80°EH 8.5 0 - 1 T1 Disc setting C 1.78 80 - 85 11 - 12
20.7 70 600
* 22.7 77 500 0.65/80°EH 8.5 0 - 1 T2 Fixed 1.95 85 - 90 11 - 12
25.6 87 350 0.75/80°EH 8.0 0 - 1 T2 Fixed 2.19 90 - 95 11 - 12
25.6 87 350
* 30.8 105 100 0.85/80°EH 9.1 0 - 1 T3 Fixed 2.65 85 - 90 11 - 12
34.7 118 400 1.00/80°EH 8.0 0 - 1 T3 Fixed 2.93 90 - 95 11 - 12
91.9
91.7
91.4
0.50/80°EH 7.0 0 - 1 T1 Disc setting B 1.29 70 - 75 11 - 12
0.60/80°EH 8.5 0 - 1 T1 Fixed 1.78 85 - 90 11 - 12
0.75/80°EH 8.0 0 - 1 T2 Fixed 2.19 75 - 80 11 - 12
CO
(%)
²
2.4 Flue Gas Analysis
To allow the boiler to be commissioned and serviced, the boiler is supplied with a combustion test point on the front cleaning door. When this test point is used please note the following:
• The test point is for CO2 and smoke readings only.
• The boiler efficiency and temperature must be taken from the flue test point on high level, vertical and conventional flue adaptors.
• Concentric low level flues do not contain a test point. The temperature and efficiency readings must be taken from the flue terminal.
2.5 Water Connections
Boiler model Flow connection Return connection
Size Fitting Supplied Size Fitting Supplied
15/21 22mm pipe Tectite elbow in fittings kit 22mm pipe Compression fitted
21/26 22mm pipe Tectite elbow in fittings kit 22mm pipe Compression fitted
26/35 22mm pipe Tectite elbow in fittings kit 22mm pipe Compression fitted
7
Page 8
2.6 Boiler Dimensions
Figure 2-1: 15/21, 21/26 and 26/35 external module dimensions
8
Page 9
3 Oil Storage and Supply System
3.1 Fuel Supply
Fuel Storage
The tank should be positioned in accordance with the recommendations given in BS 5410-1:2014, which gives details of filling, maintenance and protection from fire.
A steel tank may be used and must be constructed to BS 799-5:2010 and OFS T200.
CAUTION
!
A galavanised tank must not be used.
A plastic tank may be used and must comply with OFS T100.
NOTE
!
Plastic tanks should be adequately and uniformly supported on a smooth level surface, across their entire base area, that is, the area in contact with the ground.
Fuel Pipes
Fuel supply pipes should be of copper tubing with an external diameter of at least 10 mm.
Galvanised pipe must not be used.
All pipe connections should preferably use flared fittings. Soldered connections must not be used on oil pipes.
A remote sensing fire valve must be installed in the fuel supply line (outside) where it enters the building, with the sensing head located above the burner. Recommendations are given in BS 5410-1:2014.
It is recommended that a good quality metal bowl type fuel filter is fitted at the tank and a secondary filter in the fuel supply line adjacent to the boiler (15 µ for Kerosene) to protect the burner pump and nozzle from contamination. If the boiler operates on bio kerosene, a compatible filter should be used.
A flexible fuel line, adaptor and ¼” BSP isolation valve are supplied loose with the boiler for the final connection to the burner. If a two pipe system or ‘Tiger Loop’ type de-aerator is used, an additional flexible fuel hose (900 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK (product codes: RBS35 and RBS36).
Metal braided flexible hoses should be replaced annually when the boiler is serviced. Long life flexible hoses should be inspected annually and replaced at least every 60 months.
Single pipe system (see Figure 3-1)
With the storage tank outlet above the burner a single pipe system should be used. The height of the tank above the burner limits the length of pipe run from the tank to the burner.
Two pipe system (see Figure 3-2)
With the storage tank outlet below the burner, a two pipe system should be used. The pipe runs should be as shown in Figure 3-2. The return pipe should be the same level in the tank as the supply pipe, both being 75 to 100 mm above the base of the tank. The pipe ends should be a sufficient distance apart so as to prevent any sediment disturbed by the return entering the supply pipe.
Avoid the bottom of the tank being more than 3.5 m below the burner.
A non-return valve should be fitted in the supply pipe together with the filter and fire valve. A non-return valve should be fitted in the return pipe if the top of the tank is above the burner.
To be used with a two-pipe system, the burner must be fitted with an additional flexible fuel pipe - a flexible fuel hose (900 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK (product codes: RBS35 and RBS36).
The pump vacuum should not exceed
0.4 bar. Beyond this limit gas is released from the oil.
For guidance on installation of top outlet fuel tanks and suction oil supply sizing, see OFTEC Technical Book 3. Available from OFTEC.
CAUTION
!
Flexible hoses must NOT be used outside the boiler case of Utility models.
Figure 3-1: Single pipe system
As supplied the burner is suitable for a single pipe system
9
Page 10
Figure 3-2: Two pipe system
Figure 3-3: De-aeration device system
10
Page 11
Tiger Loop system ­(See Figures 3-3 and 3-4)
When the storage tank outlet is below the burner, an alternative to a two pipe system can be achieved using a ‘Tiger Loop’ type oil de-aerator. This effectively removes the air from the oil supply on a single pipe lift.
The de-aerator is connected close to the boiler as a two pipe system (omitting the non-return valve) as shown in Figure 3-3.
Refer to the manufacturers instructions supplied with the de-aerator.
The de-aerator must be mounted vertically. See Figure 3-3 and 3-4.
WARNING
!
To prevent any possibility of fuel fumes entering the building, the de-aerator must be fitted outside in accordance with BS 5410-1:2014.
To be used with a de-aerator, the burner must be fitted with an additional flexible fuel hose (a flexible fuel hose (900 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK (product codes: RBS35 and RBS36).
3.2 Burner Oil Connection
The burner fuel pump is supplied for use with a single pipe fuel supply system.
For use on a two pipe system, it is necessary to fit the By-pass screw, as shown in Figure 3-5, into the tapping in the return port.
The By-pass screw is supplied in the boiler accessory pack.
Remove the plastic burner cover (secured by two screws).
For ease of access to the fuel pump, to fit the by-pass screw and connect the oil lines, the burner can be removed from the boiler. To do this, unscrew the single nut at the top of the burner (using a 13 mm spanner) and withdraw the burner from the boiler.
Remove and discard the blanking plug from the return connection of the pump and fit the By-pass screw using an hexagonal key.
Connect the return oil flexible fuel pipe to the pump.
Connect the 3/8” to 1/4” BSP adaptor to the flexible fuel pipe.
Flexible fuel pipes and adaptors are available to purchase from Grant UK.
The blanking plug supplied in the inlet (suction) port may now be plastic and will not provide an oil tight seal when the pump is running.
Figure 3-5: Riello RDB pump
Item Description
1 Inlet (suction) port
2 Return port
3 By-pass screw
4 Pressure gauge port
5 Pressure adjustment
6 Vacuum gauge port
7 Solenoid
8 Nozzle outlet
Figure 3-4: Tiger loop de-aeration device
WARNING
!
Ensure that the supply from the tank is connected to this port and that the plastic plug is discarded.
11
Page 12
Main Burner Components
It may be necessary to remove theburner from the boiler to accessconnections in the fuel pump.
Disconnect the flexible air tube from the burner.
Remove the single nut at the top of the burner (using a 13 mm spanner) and withdraw the burner from the boiler.
NOTE
!
Remove the factory fitted air inlet spigot adaptor (item 6) in Figure 3-6 from the air intake on the top right hand side of the burner and fit the grey plastic air inlet grille in its place.
Burner Connection
If a two pipe system is to be used refer to Section 3.2.
Remove and discard the blanking plug from the inlet (suction) port of the pump. Refer to Figure 3-5.
Connect the elbow of the flexible fuel pipe supplied with the boiler to the inlet port.
Connect the other end of the flexible fuel pipe to the rigid supply line using the adaptor supplied. The supply enters through one of the holes in the casing plinth.
12
Figure 3-6: Riello RDB burner components
Item Description
1 Oil pump
2 Control box
3 Reset button with lock-out lamp
4 Flange with gasket (do not remove from boiler)
5 Air damper adjustment screw
6 Air supply tube connection (balanced flue)
7 Pump pressure adjustment screw
8 Pressure gauge connection
Page 13
4 Boiler Installation Information
4.1 Introduction
All models are supplied fully assembled with the flue terminal guard supplied loose inside the boiler.
4.2 Boiler location
1. The External module must stand on a solid, level surface capable of supporting the weight of the boiler when full of water, e.g. a prepared concrete standing, paving slabs bedded down on sand/cement, or similar.
2. The module can be installed either against the building or ‘free standing’ some distance away from the building.
3. The module must be positioned such that the required clearances from the low level flue outlet, as shown in Figure 9-4, are achieved.
4. Adequate clearance must be left around the module for servicing. In particular, a minimum clearance of 600 mm above the module for removal of the top panel and 600 mm at the opposite end to the flue outlet for access to the burner. Sufficient clearance is required at the rear of the boiler to allow the rear panel to be removed for access to the condensate trap.
4.3 Preparation for Installation
1. Carefully remove the packaging from the boiler and remove it from the transit pallet.
2. Remove the case top panel (four screws) and also the front and rear panels, as required.
3. The flue may exit the boiler from the left, right or rear of the casing. Carefully press out the pre-cut section on the side or rear casing panel to provide the opening in the required position for the flue to pass through the casing. Fit the cover panel (with the round flue exit hole) over the square flue opening in the casing. Fit the circular rubber sealing grommet, provided, into the circular hole in the cover panel before fitting the flue terminal section.
4. Slacken the wing nuts holding the flue elbow and rotate the elbow to the required direction for the flue to exit the casing.
5. Push the end of the flue terminal section (with the red seal) through the sealing grommet in the casing panel. The terminal section has been factory lubricated. Take care not to dislodge or damage the red flue seal.
6. Carefully insert the terminal into the flue elbow until the bend of the terminal contacts the outer casing, then, pull the terminal forward approximately 25 mm and rotate the bend so that the outlet is horizontal. Rear exit - The flue must discharge away from the building. Side exit - The flue should discharge towards the rear of the casing to prevent flue gases re-entering the boiler casing through the air inlet vents on the casing front door.
The flue terminal must be fitted horizontally to prevent dripping from the end of the terminal.
7. Tighten the wing nuts holding the flue elbow and fit the stainless steel flue guard using the two screws provided.
8. he top panel of the casing has been designed so that it may be fitted to create a slight slope away from the side positioned against the wall. To tilt the top panel, loosen the four top panel casing screws, one at each corner and push down on the side furthest from the wall. Tighten the screws. See Figure 4-1.
Figure 4-1: Standard low level flue
13
Page 14
4.4 Installing the Boiler
1. 1. If the boiler is to be fitted against the wall, prepare the wall to accept the heating system pipework. To mark the wall for drilling, refer to Section 2.6 for the positions of the pipework openings in the enclosure sides.
NOTE
!
Pipework should be insulated where it passes through the wall into the boiler enclosure.
If the boiler is to be installed ‘free standing’ (i.e. away from a wall) and the pipework run underground, push out the ‘knock-outs’ to open the required pipe openings in the base of the boiler enclosure. Using a sharp knife, cut through the polystyrene in the base, around the edge of the holes, to allow the flow and return pipes to enter the enclosure.
2. The electrical supply to the boiler should be routed through the wall in a suitable conduit, such that it enters the boiler enclosure via one of the unused pipework openings. The cable can be routed to the front of the boiler, for connection to the boiler control panel, either over the top or beneath the boiler heat exchanger. Heat resistant PVC cable, of at least 1.0 mm² cross section should be used within the boiler enclosure.
3. The oil supply line should be installed up to the position of the boiler. Refer to Section 3.1 for details. The final connection into the boiler enclosure can be made with 10 mm soft copper, routed along the base of the enclosure (either between the enclosure and wall or in front of the enclosure) to enter through one of the holes located in the bottom edge side panel, at the front (burner) end.
4.5 Regulations Compliance
Installation of a Grant VORTEX Eco boiler must be in accordance with the following recommendations:
• Building Regulations for England and Wales, and the Building Standards for Scotland issued by the Department of the Environment and any local Byelaws which you must check with the local authority for the area.
• Model and local Water Undertaking Byelaws.
• Applicable Control of Pollution Regulations.
• The following OFTEC requirements:
• OFS T100 Polythene oil
storage tanks for distillate fuels.
• OFS T200 Fuel oil storage
tanks and tank bunds for use with distillate fuels, lubrication oils and waste oils.
Further information may be obtained from the OFTEC Technical Book 3 (Installation requirements for oil storage tanks) and OFTEC Technical Book 4 (Installation requirements for oil fired boilers).
The installation should also be in accordance with the latest edition of the following British Standard Codes of Practice:-
• BS 715 Metal flue pipes, fittings, terminals and accessories.
• BS 799:5 Oil storage tanks.
• BS 1181 Clay flue linings and flue terminals.
• BS EN 1856-1:2009 Chimneys. Requirements for metal chimneys. System chimney products.
• BS 5449 Forced circulation hot water systems.
• BS 7593 Code of Practice for treatment of water in heating systems.
• BS 7671 Requirements for electrical installations, IET Wiring Regulations.
NOTE
!
Failure to install and commission appliances correctly may invalidate the boiler guarantee.
WARNING
!
Before starting any work on the boiler, or fuel supply please read the health and safety information given in Section 14.
4.6 Completion
Please ensure that the OFTEC CD/10 installation completion report (provided with the boiler) is completed in full.
Leave the top copy with the User.
Retain the carbon copy.
Ensure that the User Information pack (supplied with the boiler) is handed over to the Householder.
4.7 Before you Commission
To avoid the danger of dirt and foreign matter entering the boiler the complete heating system should be thoroughly flushed out - before the boiler is connected and then again after the system has been heated and is still hot. This is especially important where the boiler is used on an old system.
For optimum performance after installation, this boiler and its associated heating system must be flushed in accordance with the guidelines given in BS 7593:2006 ‘Treatment of water in domestic hot water central heating systems’.
This must involve the use of a proprietary cleaner, such as BetzDearborn’s Sentinel X300 or X400, or Fernox Restorer. Full instructions are supplied with the products, but for more details of BetzDearborn’s products, view the website www.sentinel­solutions.net and for more details of Fernox products view the website www. fernox.com.
14
Page 15
For long term protection against corrosion and scale, after flushing, it is recommended that an inhibitor such as Betzdearborn’s Sentinel X100 or Fernox MB-1 is dosed in accordance with the guidelines given in BS 7593:2006.
Failure to implement these guidelines will invalidate the guarantee.
NOTE
!
We recommend that both antifreeze and corrosion inhibitor be used in the primary water system.
4.8 Heating System Design Considerations
To achieve the maximum efficiency possible from the Grant VORTEX Eco boiler, the heating system should be designed to the following parameters:
Radiators:
• Flow temperature 70°C
• Return temperature 50°C
• Differential 20°C
Underfloor:
• Flow temperature 50°C
• Return temperature 40°C
• Differential 10°C
Size radiators with a mean water temperature of 60°C.
Design system controls with programmable room thermostats or use weather compensating controls to maintain return temperatures below 55°C.
The use of a pipe thermostat is recommended to control the return temperature when using weather compensating controls.
Refer to Section 2.5 for the size and type of the connections and Section 5 for the position of the connections.
4.9 Underfloor Heating
Systems
In underfloor systems it is essential that the return temperature must be maintained above 40°C to prevent internal corrosion of the boiler water jacket.
4.10 Pipework Materials
Grant boilers are compatible with both copper and plastic pipe. Where plastic pipe is used it must be of the oxygen barrier type and be of the correct class (to BS 7291-1: 2010) for the application concerned.
WARNING
!
The first metre of pipework connected to both the heating flow and return connections of the boiler must be made in copper on all types of system - sealed or open-vented.
4.11 Sealed Systems
If plastic pipe is to be used, the installer must check with the plastic pipe manufacturer that the pipe to be used is suitable for the temperature and pressures concerned.
Plastic pipe must be Class S to BS 7291-1: 2010.
WARNING
!
The system must incorporate a low pressure switch to shut off power to the boiler if the system pressure drops below 0.2 bar. A suitable low pressure switch kit is available to purchase from Grant UK (product code: MPCBS63).
4.12 Underfloor Pipework
Plastic pipe may be used on Underfloor systems where the plastic pipe is fitted after the thermostatic mixing valve.
Copper tube must be used for at least the first metre of flow and return primary pipework between the boiler and the underfloor mixing/blending valves.
NOTE
!
The boiler should not be allowed to operate with return temperatures of less than 40°C when the system is up to operating temperature.
15
Page 16
5 Pipe Connections
5.1 Water Connections
The flow and return pipework can exit the boiler enclosure either through the pre-cut openings provided in both sides (under the movable cover plates) and through the wall when installed against the building, or down and through the pre-cut openings provided in the base of the enclosure for ‘free standing’ installations. See Section 2.6.
Push out the ‘knock-out’ from the required holes, taking care not to distort the side panel or base.
For condensate disposal pipework refer to Section 6.
1. To gain access to the water connections, remove the two screws securing the bottom of the back panel and remove it by withdrawing it forwards at the bottom. Remove the top casing panel.
2. Carefully manoeuvre the boiler in
position to line up with pipework through the wall. Complete the water connections. Note: Check that the baffles are in position and that the cleaning cover is correctly fitted and a good seal made.
3. If the boiler is installed against a wall, fit the wall flashing strip. Position the strip with the bottom edge of the wider flange 20 mm above the enclosure top panel, with the narrow flange (with the three fixing holes) flat against the wall. The strip should overhang the top panel by an equal amount at each end.
4. Mark the position of the three fixing holes onto the wall, drill and plug the wall and secure the strip with suitable screws (not supplied).
Flow connection: A 22 mm pipe is provided for the flow connection. This
is located on the top of the boiler. The pipe will need to be vented, as it is the highest point on the primary heat exchanger.
Return connection: A 22 mm pipe is provided for the return connection. This is located on the top of the boiler. The pipe will also need to be vented at some point, as it is the highest point on the secondary heat exchanger.
NOTE
!
All pipes to be fitted into the push-fit connectors provided should be cut using a pipe slicer or pipe cutter - to leave the pipe ends with a slight radius and free from any burrs or sharp edges. Pipes to be used with these fittings should not be cut square using a hacksaw.
16
Figure 5-1: Water connections and themostat phial positions (utility models)
Figure 5-2: Water connections and themostat phial
positions (15/21 and 21/26 system models)
Figure 5-3: Water connections and themostat phial positions (26/35 system models)
Page 17
6 Condensate Disposal
6.1 General Requirements
When in condensing mode the Grant VORTEX Eco boilers produce condensate from the water vapour in the flue gases. This condensate is slightly acidic with a ph value of around 3 (similar to vinegar). Provision must be made for the safe and effective disposal of this condensate.
Condensate can be disposed of using one of the following methods of connection:
Internal connection (preferred option):
• into an internal domestic wastesystem (from kitchen sink, washing machine, etc.)
• directly into the soil stack
External connection:
• into an external soil stack
• into an external drain or gulley
• into a rainwater hopper (that is part of a combined system where sewer carries both rainwater and foul water)
• purpose made soakaway
All condensate disposal pipes must be fitted with a trap - whether they are connected internally or externally to a domestic waste system/soil stack or run externally to a gully, hopper or soakaway.
6.2 Connections
Connections into a rainwater hopper, external drain or gulley should be terminated inside the hopper/drain/ gulley below the grid level but above the water level.
Condensate disposal pipes should not be connected directly into rainwater downpipes or to waste/soil systems connected to septic tanks.
Condensate should not be discharged into ‘grey water’ systems that re-use water used in the home (not including water from toilets).
It should be noted that connection of a condensate pipe to the drain may be subject to local Building Control requirements.
Condensate disposal pipes should have a minimum ‘nominal’ diameter of 22 mm (¾”) - e.g. use 21.5 mm OD polypropylene overflow pipe.
Condensate disposal pipes must be fitted with a fall (away from the boiler) of at least 2.5° (~45 mm fall per metre run).
NOTE
!
Where it is not possible for the pipe to fall towards the point of discharge - either internally into a waste system or externally to a gulley (e.g. for boilers installed in a basement), it will be necessary to use a condensate pump.
Condensate disposal pipes should be kept as short as possible and the number of bends kept to a minimum.
Pipes should be adequately fixed to prevent sagging, i.e. at no more than
0.5 metre intervals.
6.4 External Pipework
Ideally, external pipework, or pipework in unheated areas, should be avoided. If unavoidable, external pipework should be kept as short as possible (less than 3 metres) and 32 mm waste pipe used to minimise the risk of ice blocking the pipe in freezing conditions.
The number of bends, fittings and joints on external pipes should be kept to a minimum to reduce the risk of trapping condensate.
NOTE
!
For boiler installed in an unheated area such as an outhouse or garage, all condensate pipework should be considered as an ‘external’.
6.5 Condensate Soakaway
To keep external pipework to a minimum, locate the soakaway as close as possible to the boiler but ensure it is at least 500 mm from building foundations and away from other services, e.g. gas, electricity, etc.
The condensate pipe may be run above or below ground level and can enter either the top or side of the soakaway tube. Refer to Figure 6-1.
Ensure that the drainage holes in the soakaway tube face away from the building.
Backfill both the soakaway tube, and the hole around it, with 10 mm limestone chippings.
Only use a soakaway where the soil is porous and drains easily. Do not use in clay soils or where the soil is poorly drained.
CAUTION
!
Any damage due to condensate backing up into the boiler due to a high water table, in the case of a soakaway, or flooded drains when the condensate disposal is via a gulley or soil stack, is not covered by the Grant product guarantee.
6.3 Pipework
Condensate disposal pipework must be plastic (plastic waste or overflow pipe is suitable).
NOTE
!
IMPORTANT: Copper or steel pipe is NOT suitable and MUST NOT be used.
Figure 6-1: Purpose made condensate soakaway
17
Page 18
6.6 Condensate Trap
Grant VORTEX Eco boilers are supplied with a factory-fitted condensate trap to provide the required 75 mm water seal in the condensate discharge pipe from the boiler.
This trap incorporates a float (which will create a seal when the trap is empty) and an overflow warning outlet (fitted with a plastic sealing cap), see Figure 6-2.
The trap is factory-fitted inside the boiler casing, mounted in the rear of the boiler (opposite end to the burner) on the inside of the side panel, see Figure 6-2.
NOTE
!
Access must be available to allow for routine maintenance.
A flexible hose connects the outlet of the condensing heat exchanger to the trap inlet. Ensure the straight connector on the hose is fully pushed onto the ‘top hat’ inlet connector of the trap.
With the trap fitted inside the boiler casing, the sealing cap must be fitted.
If connecting the condensate discharge (either internally or externally) into a waste system or soil stack - the sealing cap must be fitted in the trap outlet.
On external discharge systems to a hopper, gully or soakaway, the sealing cap should be removed from the trap outlet.
If there is any discharge of condensate from the overflow outlet, this could indicate a blockage (possibly due to freezing). Turn off the boiler and investigate the cause. If necessary contact your service engineer for assistance.
The condensate trap outlet is at an angle of 48° below the horizontal. This is to automatically give a 3° fall on any ‘horizontal’ runs of condensate disposal pipe. Refer to Figure 6-2.
6.7 Condensate Disposal Pipework
The outlet of the trap will accept 21.5 mm to 23 mm OD Polypropylene overflow pipe for the condensate discharge pipe.
Possible routes for disposal pipework
The boiler enclosure has several 50 mm diameter openings in both the sides and base. These are designed to allow pipework to pass through, to suit the installation. These openings can be used to allow the condensate disposal pipe to exit the casing in one of the following ways:
Side outlet – The lower opening on either side of the enclosure can allow the condensate disposal pipe to be installed as follows:
• Connection to an internal stack – passing back through the wall of the house.
• Connection to an external soil stack adjacent to the boiler.
• Discharge into an adjacent (external) drain or gulley.
• Discharge into a soakaway – with pipe either above or below ground level.
Bottom outlet – There are three openings in the base that can allow the condensate disposal pipe to be installed as follows:
• Discharge into a drain or gulley beneath the boiler (e.g. drain built in to the concrete base for the boiler).
• Discharge into a soakaway – with pipe below ground level.
When connecting plastic discharge pipe, ensure that the pipe is fully pushed into the outlet end on the flexible pipe to prevent the possibility of leakage.
6.8 Inspection and Cleaning of Trap
The trap must be checked at regular intervals (e.g. on every annual service) and cleaned as necessary to ensure that it is clear and able to operate.
The bottom bowl is sealed to the trap body and cannot be removed.
To inspect and clean the trap:
1. Disconnect flexible condensate hose from inlet connector.
2. Unscrew the inlet connection nut.
3. Remove the inlet connector and nut from trap.
4. Remove trap from bracket.
5. Remove float from trap – clean if necessary.
6. Inspect inside of trap and clean as necessary.
7. Re-assemble trap, re-fit to boiler and re-connect flexible hose. Ensure that hose is fully pushed onto the trap inlet connector.
CAUTION
!
Failure to regularly check and clean the condensate trap may result in damage to the boiler and will not be covered by the guarantee.
18
Figure 6-2: Condensate trap (rear panel removed)
Page 19
7 Sealed Systems
7.1 Sealed System Installation
See Figure 7-1
All Grant VORTEX Eco boilers are suitable for use with sealed systems complying with the requirements of BS EN 12828:2003, BS EN 12831:2003, BS EN 14336:2004.
The maximum temperature of the central heating water is 75°C.
The system must be provided with the following items:
• Diaphragm expansion vessel complying with BS EN 13831:2007.
• Pressure gauge.
• Safety valve.
• Approved method for filling the system.
Figure 7-1: Sealed system
NOTE
!
Ensure that the expansion vessel used is of sufficient size for the system volume. Refer to BS 7074:1:1989 or The Domestic Heating Design Guide for sizing the required vessel.
The expansion vessel can be fitted in either the return or flow pipework in any of the recommended positions as shown in Figure 7-1. To reduce the operating temperature of the expansion vessel diaphragm, position it below the pipe to which it is connected. The expansion vessel may be positioned away from the system, providing the connecting pipe is not less than 13 mm diameter.
The pressure gauge should have an operating range of 0 to 4 bar.
The safety valve, set to operate at 2.5 bar, should be fitted in the flow pipework near to the boiler.
The pipework between the safety valve and boiler must be unrestricted, i.e. no valves. The safety valve should be connected to a discharge pipe which will allow the discharge to be seen, but cannot cause injury to persons or property.
Provision should be made to replace water lost from the system. This can be done manually (where allowed by the local water undertaking) using an approved filling loop arrangement incorporating a double check valve assembly (as supplied in the Sealed System kit).
An automatic air vent should be fitted to the highest point of the system.
The expansion vessel charge pressure should always be slightly greater than the maximum static head of the system, in bar, at the level of the vessel (1 bar =
10.2 metres of water). See Figure 7-2. The system fill pressure (cold) should
be 0.2 - 0.3 bar greater than the vessel charge pressure – giving typical system fill pressures of approx 0.5 bar for a bungalow and 1.0 bar for a two storey house. Refer to the Domestic Heating Design Guide for further information if required.
If thermostatic radiator valves are fitted to all radiators, a system by-pass must be fitted.
Filling of the system must be carried out in a manner approved by the local Water Undertaking.
Where allowed, the system may be filled via the filling loop supplied (the loop arrangement includes a double check valve assembly).
All fittings used in the system must be able to withstand pressures up to 3 bar.
Radiator valves must comply with the requirements of BS 2767:1991.
One or more drain taps (to BS 2879) must be used to allow the system to be completely drained.
Figure 7-2: Boiler with sealed system kit
19
Page 20
20
7.2 System Models
All System models have the following sealed system components factory fitted (refer to Figure 7-3):-
• A diaphragm expansion vessel complying with BS 4814, pre­charged at 1.0 bar. Refer to Section 2.2.
• System pressure gauge, with an operating range of 1 to 4 bar.
• Pressure relief safety valve complying with BS 6759 and set to operate at 2.5 bar.
• Automatic air vent, fitted to the flow pipe of the boiler, ensures the boiler is vented.
• Filling loop. This must be isolated and disconnected after filling the system.
Refer to Section 2.2 for system volumes and BS 7074: for further guidance and for further details of the expansion vessel.
The expansion vessel fitted, is supplied with a charge pressure of 1.0 bar (equivalent to a maximum static head of
10.2 metres). The charge pressure must
not be less than the actual static head at the point of connection.
CAUTION
!
Do not pressurise the vessel above
1.5 bar.
NOTE
!
The air pressure in the vessel must be checked annually.
The central heating system volume, using the expansion vessel as supplied, must not exceed the recommended value. Refer to Section 2.2. If the system volume is greater, an extra expansion vessel (complying with BS 4841) must be fitted as close as possible to the central heating return connection on the boiler.
The charge pressure of the extra vessel must be the same as the vessel fitted in the boiler.
Refer to either BS 7074:1:1989 or The Domestic Heating Design Guide for the required total expansion vessel volume for the system concerned.
NOTE
!
The air charge pressure may be checked using a tyre pressure gauge on the expansion vessel Schraeder valve. The vessel may be re-pressurised using a suitable pump. When checking the air pressure the water in the heating system must be cold and the system pressure reduced to zero.
7.3 Fill the Sealed System
Automatic air vent(s) are fitted to the top of the boiler (see Figure 7-3). Check that the small cap on the top of each air vent is screwed on fully, then unscrew it one complete turn - the cap remains in this position from now on.
The procedure for filling the sealed system is as follows:
1. Only ever fill or add water to the system when it is cold and the boiler is off. Do not overfill.
2. Ensure that the flexible filling loop supplied with the boiler is connected and that the double check shut off valve connecting it to the water supply is closed. A valve is open when the operating lever is in line with the valve, and closed when it is at right angles to it.
3. Open the fill point valve.
4. Gradually open the double check valve from the water supply until water is heard to flow.
5. When the white needle of the pressure gauge is between 0.5 and
1.0 bar, close the valve.
6. Vent each radiator in turn, starting with the lowest one in the system, to remove air.
7. Continue to fill the system until the pressure gauge indicates between
0.5 and 1.0 bar. Close the fill point valve.
8. Repeat steps 4 and 5 as required.
9. Close the fill point and double check valves either side of the filling loop and disconnect the loop.
7.4 Pressure Relief Safety Valve
Now the pressure relief safety valve operation must be checked and set. The procedure is as follows:
1. Check the operation of the safety valve by turning the head anticlockwise until it clicks. The click is the safety valve head lifting off its seat allowing water to escape from the system
2. Check that the water is escaping from the system.
3. Continue to fill the system until the pressure gauge indicates between
0.5 and 1.0 bar.
4. Close the fill point valve and check the system for water soundness, rectifying where necessary.
5. Water may be released from the system by manually operating the safety valve until the system design pressure is obtained. The system design pressure (cold) should be between 0.5 bar and 1.0 bar.
The pressure is equivalent to the maximum static head in bar + 0.3 (1 bar = 10.2 metres of water), where the static head is the vertical height from the centre of the expansion vessel to the highest point of the system.
Now close the valves either side of the filling loop and disconnect the loop.
Page 21
7.5 Circulating Pump
7.5.1 Pump Specification
Make and model Wilo Yonos PARA RS 15/7.0 RKC FS 130 12
Construction
Pump housing Cast iron (with cataphorisis treatment)
Impellar PP composite with GF 40%
Pump shaft Stainless Ste el
Bearing Carbon, metal impregnated
Protection Class IPx4D
Insulation Class F
Motor Protection Integrated
Performance
Max. delivery head 7.2m @ Q = 0 m3 /h
Max. volume flow 3.3 0 m3 /h
Minimum suction head @ 50/95°C 0.5/4.5m
Power consumption @ 1 - 230V 3-45W
Nominal Motor Power 37W
Current @ 1 - 230V 0.028 - 0.44 A
Energy Efficiency Index (EEI) ≤ 0.20
Speed 800-4650 rpm
Settings ∆P-variable (1-7m head) and Constant Speed (I, II and III)
Application
Maximum Static Pressure PN6
Temperature range @ ma ximum ambient temperatures Ma ximum ambient temperature 57°C: 0 to 95°C
Maximum ambient temperature 59°C: 0 to 90°C Maximum ambient temperature 67°C: 0 to 70°C
Approved Fluids Heating Water
Water/Glycol - Max 1:1 (above 20% check pumping data)
21
Page 22
7.5.2 Pump Control Panel
Wilo Yonos PARA RKC circulating pumps have two possible setting modes:
• Constant speed with three pump
speed settings (I, II and III)
• Variable pressure (∆p-v) with pump
head adjustable between 1 and 7m head
Figure 7-3 shows the pump control panel with the red selector knob.
Constant Speed Mode (I, II, III)
This is the default setting of the pump and as such is recommended by Grant for heating systems. In this mode the pump speed is not automatically regulated (as with the Variable Pressure Mode), but operates at constantly at one of the three possible speeds (set using the red selector knob on the pump control panel).
Variable Pressure Mode (
In this mode the electronic control changes the differential pressure setpoint to be maintained by the pump in a linear fashion between Hs (the value set using the red selector knob on the pump control panel) and ½ Hs. The differential setpoint varies linearly with the volume flow Q.
∆p-v)
7.5.3 Indicator LED
The pump is fitted with an indicator LED. This is located around the circumference of the red selector knob. See Figure 7-3 below. This indicates the operating status of the pump and will be illuminated green when the pump is operating normally. This indicator LED can assist in diagnosing and rectifying faults. Refer to Section 12.3.
7.5.3 Setting the Pump Control Mode
Set the pump to one of the two operating modes as follows:
Constant Speed Mode (I, II, III)
Grant recommends this operating mode for the pump.
To set the pump to the ‘Constant Speed’ mode, the pointer on the red selector knob must be set to the RIGHT of the mid position. Refer to Figure 7-3.
Set it to point at the required speed setting, I, II or III as required, ensuring that there is adequate flow to distribute the heat from the boiler whilst avoiding high water velocities causing noise in the pipework.
Variable Pressure Mode (
To set the pump to the ‘Variable Pressure’ mode the pointer on the red selector knob must be set to the LEFT of the mid position. Refer to Figure 7-3.
The further anticlockwise it is set the greater the pressure head setting of the pump – from 1m to 7m head.
If this mode is to be used, set the selector knob at a pressure that represents the maximum pressure (head) loss for the heating system in question.
∆p-v)
22
Indicator LED
Variable Pressure Mode settings: 1 to 7m head
Red selector knob
Figure 7-3: Control panel with red selector knob and LED indicator
Constant Speed Mode settings: I, II, III
Page 23
8 Electrical
The VORTEX Eco External module requires a 230/240 V ~ 50 Hz supply. It must be protected by a 5 Amp fuse.
Refer to Figures 8-1 to 8-4 for typical control system wiring diagrams.
Refer to Figure 8-3 for boiler internal wiring diagram.
WARNING
!
The VORTEX Eco boiler contains electrical switching equipment and must be earthed.
The supply must be fused at 5 Amp and there must only be one common isolator for the boiler and control system, providing complete electrical isolation.
A fused double pole switch or a fused three pin plug and shuttered outlet socket should be used for the connection.
The power supply cable should be at least 0.75 mm² PVC as specified in BS 6500, Table 16.
All the wiring and supplementary earth bonding external to the boiler must be in accordance with the current IET Wiring Regulations.
Any room thermostat or frost thermostat used must be suitable for use on mains voltage.
The boiler requires a permanent mains supply, do not interrupt it with any external time controls.
In the event of an electrical fault after installation of the boiler, the following electrical system checks must be carried out:
• Short circuit
• Polarity
• Earth continuity
• Resistance to earth
8.1 Connecting the Power Supply
NOTE
!
A test switch is fitted to the control panel (see Figure 1-1) to allow the boiler to be test-fired. When On, the switch by-passes the external control system.
It is recommend that the boiler should be connected to a switched mains power supply from a programmer or control system. If a Grant remote programmer is used, a permanent 240 V mains supply (fused at 5 Amp) must be taken to the boiler. A three core cable is required to connect the boiler terminal block to the live supply. Refer to Figures 8-1 to 8-2 for typical control system wiring diagrams.
The procedure is:
1. Undo the three screws and remove the lefthand cover from the control panel to gain access to the boiler terminal block.
2. Pass the mains power supply cable through the cable grommet in the control panel, through the cable clamp and connect to the terminal block as follows:
Brown to live (terminal 2)
Blue to mains neutral (terminal 3)
Green/Yellow to mains earth
(terminal 4)
3. Refer to Figures 8-1 to 8-2 for a typical control system wiring diagrams.
4. If the circulating pump is to be fitted within the boiler enclosure, the pump live must be connected to terminal 7 of the boiler terminal block.
Pass the pump power supply cable through the cable grommet in the control panel, through the cable clamp and connect to the terminal block as follows:-
Brown to live (terminal 7)
Blue to mains neutral (terminal 9)
Green/Yellow to earth (terminal 10)
Connecting the pump in this way allows it to be isolated using the isolating switch fitted in the boiler control panel, for servicing or maintenance work.
5. Ensure that the cable clamp is tightened and that all cables are secure and all external wiring is adequately supported.
6. Replace the cover on the control panel, with the yellow warning label facing outwards and secure with the three screws.
Do not switch on the electricity supply to the External module at this stage.
8.2 Frost Protection
External Modules are supplied with a factory fitted frost protection thermostat, located inside the boiler control panel
This is pre-wired to the boiler electrical system and factory set to 2°C.
For total system protection against freezing, particularly during extended periods without electrical power, Grant recommend the use of a combined heating system antifreeze and corrosion inhibitor, used in accordance with the manufacturer’s instructions.
23
Page 24
8.3 Control System Wiring Diagrams
Wall Mounted
Programmer ESKIT
Wall Mounted
Programmer ESKIT
Grey Grey
5A
240V
50HZ
L N E
Blue
Brown
Pipe Stat
(If fitted)
Green/Yellow
Cylinder
Room
Stat
2 1 3
Stat
1 C 2
1 2 3 4 5 6 7 8 9 10
N
L 1 2 3 4
OFF OFF ON ON HW HT HW HT
Grant 2-Channel
Link
Brown
Blue
Brown
Blue
Orange Orange
Green/Yellow
Green/Yellow
Wiring Centre
HW
Motor
2-Port Zone Valve
HTG
Motor
2-Port Zone Valve
Green/Yellow
Blue
Brown
Boiler Terminal Block (Remove link 5 to 6 when pipe stat fitted)
E N
Pump
L
E
Green/Yellow
N
L
Blue
Brown
Pump (System boiler only)
10
11
12
13
1
L
2
L
3
N
4
E
5
6
7
8
L
9
N
E
L
N
E
Figure 8-1: CH and HW controlled by two 2-port zone valves
5A
240V 50HZ
L N E
Blue
Brown
Pipe Stat (If fitted)
Green/Yellow
Cylinder
Room
Stat
2 1 3
Stat
1 C 2
1 2 3 4 5 6 7 8 9 10
N
L 1 2 3 4
OFF OFF ON ON
HW HT HW HT
Grant 2-Channel
Link
Orange Grey White
Link
Blue
Green/Yellow
Motor
13k2W270k
0.25W
3-Port Mid Position
Zone Valve
Wiring Centre
Green/Yellow
Blue
Brown
Boiler Terminal Block (Remove link 5 to 6 when pipe stat fitted)
E N L
Pump
Green/Yellow
E N L
Blue
Brown
Pump (System boiler only)
10
11
12
13
1
L
2
L
N
3
4
E
5
6
7
8
L
9
N
E
L
N
E
24
Figure 8-2: CH and HW controlled by 3-port mid position zone valve
Page 25
8.4 Boiler Control Panel Wiring Diagram
Control box
chassis earth
Control box
chassis earth
Earth to
switch cover
Test switch
Mains
Boiler On/Off Switch
Red
Blue
Yellow
5B 2A
Frost Thermostat
4B 1A
Limit
Thermostat
C 2 C 1
Red
Red Red
Red
Control
Thermostat
Red
Yellow
Yellow
Red Red
Yellow
Blue
Green/Yellow
Yellow
Yellow
Red
Blue
Green/Yellow
Red
Blue
Green/Yellow
Green/Yellow
1
L
2
L
3
N
4
E
5
Switched Live
Permanent Live
Mains Neutral
Mains Earth
To CH Valve if required
Yellow
6
Brown
Pump Live
Pump Neutral
}
Pump Earth
Burner Live
Burner Neutral
Burner Earth
Pump factory fitted and wired on system models only
7
8
L
9
N
10
E
11
L
12
N
13
E
Figure 8-3: Control panel wiring
25
Page 26
9 Flue System and Air Supply
Figure 9-1: Clearances for
balanced flue terminals
Permission to reproduce extracts from British Standards is granted by BSI Standards Limited (BSI). No other use of this material is permitted.
Location Appliances *
A Directly below an opening, air brick opening, opening window, etc. 1000
B Horizontally to an opening, air brick opening, opening window, etc. 1000
C Below a gutter, eaves or balcony with protection 1000
D Below a gutter or a balcony without protection 1000
E From vertical sanitar y pipework 300
F From an internal or external corner 300
G Above ground or balcony level 300
H From a surface or boundar y facing the terminal 2500
J From a terminal facing the terminal 1200
K Vertically from a terminal on the same wall 1500
L Horizontally from a terminal on the same wall 750
M Above the highest point of an intersection with the roof 600
N From a vertical structure to the side of the terminal 750
O Above a vertical structure less than 750mm from the side of the terminal 600
P From a ridge terminal to a vertical structure on the roof 1500
Q Above or to the side of any opening on a flat or sloping roof 300
R Below any opening on a sloping roof 1000
* Minimum distances to terminals in millimetres as measured from top of the chimney or the outer edge of a low level discharge opening.
26
NOTE: Vertical structure in N, O and P includes tank or lift rooms, parapets, dormers, etc. NOTE: Terminating positionings A to L are only permitted for appliances that have been approved for low level flue discharge when tested in accordance with BS EN 303-1, OFS A100 or OFS A101.
Terminating positions should be at least 1.8 m from an oil storage tank unless a wall with at least 30 min fire resistance and extending 300 mm higher and wider than the tank is provided between the tank and the terminating position. Where a flue is terminated less than 600 mm away from a projection above it and the projection consists of plastics or has a combustible or painted surface, then a heat shield of at least 750 mm wide should be fitted to protect these surfaces. For terminals used with vaporizing burners, a horizontal distance of at least 2 300 mm should be between the terminal and the roof line. If the lowest part of the terminal is less than 2 m above the ground, balcony, flat roof or other place to which any person has access, the terminal should be protected by a guard. Notwithstanding the dimensions given above, a terminal should not be sited closer than 300 mm to combustible material. In the case of a thatched roof, double this separation distance should be provided. It is also advisable to treat the thatch with a fire retardant material and close wire in the immediate vicinity of the flue. A flue or chimney should not pass through the roof within the shaded area delineated by dimensions Q and R. Where protection is provided for plastics components, such as guttering, this should be to the standard specified by the manufacturer of the plastics components.
Page 27
9.1 Air Supply
A permanent air supply must be provided to the burner, sufficient to ensure proper combustion of fuel and effective discharge of combustion products to open air.
The ventilation openings provided in the upper part of the front door of the boiler casing must not be obstructed at any time.
9.2 Low Level Discharge Flue
The Grant VORTEX Eco External module is supplied with a low level discharge flue (see Section 4).
The minimum dimensions for locating the standard terminal from building features (windows, doors, etc.) are shown in Figure 9-1.
The terminal must be positioned so as to avoid products of combustion accumulating in stagnant pockets around the buildings or entering into buildings. Care should be taken that the plume from the condensed flue gases does not cause a nuisance.
Where it is not practical to use this flue, the external module may be fitted with an alternative flue system available from Grant UK.
9.3 Grant Horizontal System
This option uses the Grant Straight Starter boiler connector, replacing the low level terminal and flue guard supplied with the boiler, along with components from the Grant Green system. See Figure 9-2.
A complete list of Grant Green system flue components are given on page 28.
NOTE
!
Under no circumstances can the external module be installed with an existing flue system. Only Grant flue systems and components suitable for wet flues should be used. Failure to install the correct type of flue system will invalidate the guarantee.
Figure 9-2: Horizontal external flue
27
Page 28
9.4 Grant Green System
This vertical twin wall stainless steel insulated flue system - constructed using components from the Grant Green system - connects to a Grant Starter elbow and may terminate at high level or vertically as required. See Figure 9-3.
The insulated Starter elbow includes the boiler connector, complete with test point, replacing the low level terminal and flue guard supplied with the boiler.
Green System components
Item Part number
External starter elbow GKM90
External starter - straight GKM90C
150 mm extension GX150/90
250 mm extension GX250/90
450 mm extension GX450/90
950 mm extension GX950/90
195-270 mm ajudtable extension GXA250/90
45° elbow GE45/90
High level terminal GTH90
Vertical terminal GTV90
Wall bracket - standard GWB90
Wall bracket - extended GEB90
Twin wall to single wall adaptor GFCON80
Straight terminal - horizontal flue GTL90
28
Figure 9-3: Vertical external conventional flue (Green system)
Page 29
9.5 Grant Hybrid System
This vertical option allows the use of an existing chimney using part of the ‘Green’ system and the flexible liner and terminal of the Grant ‘Orange’ system. See Figure 9-4.
If an existing chimney is to be used, it must be lined with a smooth bore stainless steel liner suitable for use with oil fired condensing boilers. The top and bottom of the annular space must be sealed.
Grant recommends the use of the Grant ‘Orange’ flue system, specifically designed for the VORTEX range of condensing boilers.
The internal flue and liner diameter for all models up to 46 kW output must be 100 mm (4 inch).
The maximum vertical height (from the top of the boiler to the terminal) for the‘Orange’ system is 19 metres.
NOTE
!
The Grant Orange system flexible stainless steel liner is directional.
The arrows marked on the liner MUST be pointing vertically upwards, following the direction of the flue gases. Failure to comply with this instruction could lead to a leakage of condensate from the flue liner.
NOTE
!
In order to correctly connect the Grant hybrid system, it will be necessary to purchase the Grant Starter Elbow.
This insulated Starter elbow includes the boiler connector, complete with test point, replacing the low level terminal and flue guard supplied with the boiler.
9.6 Conventional Flue Systems
All flue components are stainless steel and fully insulated with ‘O’ ring seals and locking bands.
The flue must terminate in a down draught free area, i.e. at least 600 mm above the eves or point of exit through the roof, or preferably above the ridge level.
The condensate may be allowed to run back into the boiler. A condensate drain at the base of the flue system is not required.
The flue terminal must be at least 600 mm from any opening into the building, and 600 mm above any vertical structure or wall less than a horizontal distance of 750 mm from the terminal.
No part of any flue system should be made of an asbestos material; alumin­ium must not be used in any part of the flue.
Only stainless steel flue components should be used.
If the draught conditions are satisfactory, the flue should terminate with a standard cowl.
Refer to the locally applicable Building Regulations, BS 5410:1 and OFTEC Installation Requirements (OFTEC Technical Books 2 and 4) for further guidance on conventional flue systems.
Do not use fire cement. The use of high temperature silicone sealants is recommended.
Figure 9-3: Vertical hybrid flue (Green to Orange system)
CAUTION
!
It is important to ensure that the flue system is sealed and that condensate cannot escape. Up to 1.5 l/h of condensate can be produced in a conventional flue system.
NOTE
!
To comply with the requirements of the Building Regulations Approved Document J - conventional flue systems must have a flue data plate. A suitable data plate is supplied with the Grant Orange flue system and should be displayed next to the boiler or flue.
29
Page 30
10 Commissioning
THERE IS MORE THAN ONE LIVE SUPPLY TO
DANGER
THIS CONTROL PANEL
HEATING
TEST
THERMOSTAT
OVERHEAT
BOILER
SWITCH
RESET
OFF
BOILER ON/OFF SWITCH ISOLATES PUMP(IF WIRED INTO BOILER CONTROL PANEL) & BURNER ONLY. THIS COVER ISTO BE REMOVED BYQUALIFIED PERSONNELONLY DO NOTREMOVE COVER WITHOUTISOLATING SWITCHED LIVEAND FROST'STAT PERMANENTLIVE TESTSWITCH OVERIDES SYSTEM CONTROLSTO OPERATE BOILER
PRO EXTERNAL
OFF
ON ON
REFER TO WIRING DIGRAM IN MANUAL
DANGER
TEST
SWITCH
OFF
ON ON
REFER TO WIRING DIAGRAM IN MANUAL
Control Panel
THERE IS MORE THAN ONE LIVE SUPPLY TO THIS CONTROL PANEL
BOILER
OFF
HEATING
THERMOSTAT
OVERHEAT
RESET
30
Boiler front
panel removed
Figure 10-1: Boiler controls
It is important that the following commissioning procedure is carried out to ensure safe and efficient operation of the boiler.
To access the controls, remove the front panel (turn the handle and withdraw it forwards at the bottom).
The controls are shown in Figure 10-1.
10.1 Before Switching On
1. Ensure the boiler On/Off switch and the test switch are set to OFF.
2. Check that the high limit thermostat and boiler thermostat bulbs are correctly located in their respective pockets. Refer to Figure 5-1. Check condition of thermostat capillaries, not damaged, broken or kinked and not crushed.
3. Remove the nuts and washers securing the front cleaning door. Withdraw the door - take care it is HEAVY!
4. Check that the turbulators are in position and that the ends are vertical.
5. Check that the baffles are in position. Refer to Figures 11-1 or 11-2 as required.
6. Re-fit the cleaning door and check it is fitted correctly and that a good seal is made.
7. Remove and check the burner. Check that the burner head is correct. Refer to Section 2.3.
Test
switch
Boiler
On/Off switch
thermostat
‘Lock-out’ reset button
Check the electrodes are set correctly. Refer to Figure 11-6.
Check the nozzle is correct for the output rating required. Refer to Section
2.3.
NOTE
!
If a 15/21 model is down rated, the burner air adjuster disc must be adjusted to setting B as described in Section 10.6. Refer also to Section 2.3.
If a 21/26 or 26/35 model is down rated, the burner head must be changed to a T1 head. See Section
11.4. Refer also to Section 2.3.
8. Check that the water system has been vented (and pressurised if sealed system) and there are no leaks.
9. Ensure the automatic air vent on the condensing heat exchanger is open.
10. Check that all fuel line valves are open.
11. Remove the plastic burner cover if it was not previously removed.
12. Connect a combined vent manifold and pressure gauge to the pressure gauge connection port on the oil pump. See Figure 3-6. Open the vent screw on the vent manifold to vent the supply while the pump is running.
13. Check that all system controls are calling for heat and turn the boiler thermostat to maximum.
Boiler
Overheat thermostat
reset button
(under screw cover)
10.2 Switching On
1. Switch on the electricity supply.
2. Set the Boiler On/Off switch to ON. A neon in the switch lights when it is in the ON position. The boiler will now light automatically. Note that the neon lights when the boiler is switched on, but does not necessarily indicate the burner is firing.
3. The burner fan should start and the burner should light within about 12 seconds. If the burner does not light and the ‘Lock-out’ reset button lights, wait for about 45 seconds then press the reset button to restart the ignition process. This procedure may have to be repeated several times during first lighting.
4. With the burner alight, check the fuel pressure.
5. Refer to the Technical Information, Section 2.3.
6. Adjust the pressure if necessary ­see Figure 3-6.
NOTE
!
It is important that the oil pressure is correctly set.
7. Operate the boiler until it reaches normal operating temperature. Check oil supply/return pipe for leaks, rectifying where necessary.
Page 31
8. Check the operation of the boiler thermostat. Ensure that by turning it anticlockwise it switches the burner off.
9. With the burner alight, re-check the fuel pressure and re-adjust if necessary. Turn the boiler off, remove the pressure gauge and replace the plug in the pump
10. Ensure that there are no oil leaks, replace the burner cover.
10.3 Running the Boiler
1. Relight the boiler and allow it to run for at least 20 minutes.
2. Check the smoke number, if satisfactory check the CO2. Set the CO2 to the value given in Section
2.3 for the boiler concerned.
NOTE
!
Final combustion readings can only be measured outside through the low level flue terminal (or the test point on the conventional flue starter elbow when used) with all the casing panels fitted.
3. Use the hexagonal key supplied to adjust the burner air damper (see Figure 3-6) as required. Turning the screw anti-clockwise closes the damper and increases CO2 level, turning the screw clockwise opens the damper and reduces CO2 level.
4. Re-check the smoke number if the damper has been moved. Under no circumstances must the smoke number be above 1.
NOTE
!
It is important that the air damper is correctly set.
5. Check the flue gas temperature by placing the combustion analyser in the low level flue terminal (or into the test point on the starter elbow if either the Green system or Hybrid system is used).
10.4 Balancing the System
1. When the boiler has been adjusted and is running satisfactorily, balance the central heating system by adjusting the radiator lock shield valves. Start with the radiator nearest the boiler and adjust the
valves to achieve the required temperature drop across each radiator. If thermostatic radiator valves have been installed, check the system by-pass.
2. Switch off the boiler.
10.5 Completion
1. With the system hot, check again for leaks, rectifying where necessary. Drain the system while it is hot to complete the flushing process. Refill and vent (and pressurise if a sealed system) the system.
2. A suitable central heating system inhibitor must be added to protect the system against the effect of corrosion.
3. A suitable antifreeze should be used to prevent damage to the boiler in areas where electrical power failure can occur in winter months.
4. Replace the top, front and rear panels as necessary.
NOTE
!
After commissioning the boiler complete the Commissioning Report in the front of this manual and the OFTEC CD/11 commissioning report. Leave the top copy with the User and retain the carbon copy.
If the boiler is to be left in service with the User, set the controls and room thermostat (if fitted) to the User’s requirements.
If the boiler is not to be handed over immediately, close the boiler fuel supply valve and switch off the electricity supply.
CAUTION
!
If there is any possibility of the boiler being left during frost conditions, then the boiler and system should be drained. Alternatively, a suitable antifreeze should be used.
To allow the boiler to be commissioned and serviced correctly a combustion test point is provided on the front cleaning door.
The CO2 and smoke test may all be carried out using this test point.
NOTE
!
The test point is not suitable for measuring boiler efficiency or conventional flue draught.
When using the test point on the cleaning cover note that the flue gas temperature reading will be higher than that measured in the flue thus resulting in an inaccurate efficiency reading. To obtain an accurate flue gas temperature and efficiency, the reading can only be measured outside through the low level flue terminal or the test point on the conventional flue starter elbow when fitted - with all the casing panels fitted.
10.6 Air Adjuster Disc - 15/21 only
To adjust the 15/21 air adjuster disc when downrating - See Figure 10-2.
1. Ensure the boiler is isolated from the electrical supply.
2. Remove the burner from the boiler.
3. Undo the two screws and remove the air inlet cover from the side of the burner.
4. The secondary air shutter disc is factory set in position ‘C’ – i.e. with the cut-out marked C located against the die-cast boss on the fan housing - suitable for outputs of 18.3 and 21 kW only. See Figure 10-2.
5. Remove the screw from the centre of the air shutter disc, and re-position the disc such that the cut-out ‘B’ (corresponding to 15 kW output setting – See Section
2.3) is located against the cast boss on the fan housing. Replace the screw in the centre of the air shutter disc and tighten.
6. Re-fit the air inlet cover to the side of the burner and reassemble in reverse order.
Figure 10-2: 15/21 air adjuster disc at position ‘C’
31
Page 32
11 Boiler Servicing
To ensure efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year should be adequate.
Servicing and replacement of parts must only be carried out by a suitably qualified engineer.
CAUTION
!
Details of every service should be entered in the Service Log, in the Boiler Handbook.
This information may be required to validate the Grant extended guarantee.
WARNING
!
Before starting any work on the boiler, or fuel supply please read the health and safety information given in Section 14.
External equipment operated at 230 Volts should not be serviced or repaired under adverse weather conditions.
NOTE
!
A test switch is fitted to the control panel to allow the boiler to be testfired. When On, the switch by-passes the external control system.
11.1 Checking Before Servicing
The following sequential checks should be made before any servicing:
1. Check the flue terminal and ensure it is not blocked or damaged.
2. Run the boiler and check the operation of its controls.
3. Ensure that all water/fuel system connections and fittings are sound. Remake any joints and check the tightness of any fittings that may be leaking.
4. If the boiler is used on a sealed central heating system, check the system pressure, check the operation of the pressure relief valve and check the expansion vessel air charge. See Section 7.2.
5. Refill, vent and re-pressurise the system as necessary. See Section
7.3.
6. Check that the louvres in the front panel are clear.
7. Remove any sludge/water from the fuel tank by opening the sludge valve at the lower end of the tank.
8. With the fuel supply valve closed, clean/replace the filter element and clean the filter bowl.
9. Braided flexible fuel supply hoses (as supplied with the boiler) should be replaced annually. If long-life hoses have been installed, these should be inspected annually. If in doubt replace the hoses. In any event, these hoses must be replaced every five years.
WARNING
!
Before servicing, set the boiler On/Off switch to Off, isolate the electricity supply and close the fuel supply valve.
Allow the boiler to cool. The data label on the inside of the case
side panel will indicate the fuel used and the nozzle fitted.
11.2 Dismantling Prior to Servicing
The procedure for dismantling the boiler is as follows:
1. Remove the front panel by turning the handle and withdrawing it forwards at the bottom.
2. Remove the four screws securing the top panel and carefully lift it off, taking care not to damage the insulation.
NOTE
!
The top panel has been designed to provide a slight fall away from the side positioned against a wall, the side of the top panel with the fixing screws closer to the bottom edge is the highest side and goes against the wall.
2. If a sealed system kit is fitted, carefully lift up and remove the expansion vessel from the front of the boiler. Place the vessel on the floor taking care not to strain the flexible hose.
3. Remove the burner fixing nut (top of mounting flange) and withdraw the burner. If required, disconnect the flexible oil hose(s), use a suitable container
NOTE
!
If two flexible hoses are connected to the burner, identify (mark if necessary) which is the inlet and return if they are to be disconnected.
32
Page 33
Figure 11-1: 15/21 and 21/26 baffles
Figure 11-2: 26/35 baffles
Figure 11-3: Turbulators
33
Page 34
11.3 Cleaning the Boiler
The procedure for cleaning the boiler is as follows:
1. Remove the nuts and washers securing the front cleaning door and withdraw the door. Take care ­it is heavy.
2. Remove the baffles as shown in Figures 11-1 or 11-2.
3. Remove all deposits from the baffle plates and all the boiler internal surfaces using a stiff brush and scraper if necessary.
4. Check the condition of the flue, clean as necessary.
5. Check the condition of the front cleaning door seal, replace if necessary.
6. Replace the baffles, ensuring they are correctly fitted. See Figures 11-1 or 11-2.
7. Pull out the spiral turbulators from the heat exchanger tubes. See Figure 11-3.
8. Clean the turbulators using a stiff brush.
9. Test the heat exchanger condensate drain by pouring water into one of the lower tubes and observe whether the water discharges from the 22 mm condensate outlet. Replace the turbulators.
10. Replace the front cleaning door, ensuring the seal is in good condition and secure it in position with the nuts and washers previously removed. Tighten to form a seal.
11. Remove the condensate trap andcheck that it is not blocked and is operating correctly, i.e. the float is free to move. Clean the trap and float as required. Refer to Section
6.8.
12. Check that the boiler condensate outlet is unobstructed. Clean if necessary.
11.4 Cleaning the Burner
The procedure is as follows:
1. Combustion head: Loosen the two screws securing the combustion head and withdraw the head.
2. Clean the combustion head.
3. Inspect the ignition electrodes: Loosen the electrode clamp screw and withdraw the electrode assembly. Wipe clean and check for any cracks in the ceramic insulation. Replace if necessary.
4. Nozzle: The nozzle should be replaced on an annual service. Check that the nozzle size and type are correct, refer to table in Section
2.3 and boiler data label.
5. With the combustion head removed, loosen the electrode assembly clamp screw and slide the electrodes away from the nozzle.
6. Do not attempt to clean the nozzle.
7. Remove the nozzle using a good fitting spanner (16 mm).
CAUTION
!
The use of an ill-fitting spanner will damage the nozzle and could lead to an incorrect flame pattern.
8. Always check the electrode settings after replacing the nozzle, see Figure 11-4.
Photocell - The photocell is a push-fit in the burner body. Carefully pull it out to clean. Burner fan - With the air intake grille or spigot removed, remove the screws securing the fan housing cover (R/H side of burner) and remove the cover.
Inspect the fan and housing and clean as necessary. Replace the cover.
Pump filter - With the burner cover removed, remove the four screws secur­ing the pump end cover. Remove the filter and wash in kerosene. Replace the filter and end cover, ensure the ‘O’ ring is in position.
Re-assemble in reverse order.
WARNING
!
To ensure safe and efficient operation of the boiler it is important that recommissioning is carried out, especially combustion checks (CO2 level, flue gas temperature and smoke number) after the boiler has been serviced.
Refer to the Commissioning instructions in Section 10.
34
NOTE
!
The condensate trap and condensate outlet must be checked on every service and cleaned as necessary.
Figure 11-4: Electrode assembly
Page 35
12 Fault Finding
12.1 Boiler Fault Finding
Always isolate the electricity supply to the boiler before working on the boiler.
Fault
Boiler will not start:
No fuel supply Ensure that an adequate supply of fuel is available and that the fuel supply valve is
No electricity supply Ensure electricity supply to the boiler is switched on and that all controls are calling
Burner not starting - fuel and electricity sup­plies present
Burner lights but goes to lock-out If the flame is unstable, check the combustion settings.
Boiler works but:
Visible smoke from flue or high smoke number
Burner pulses Insufficient air supply - check the air damper setting and the condition of the fan.
Flame slow to stabilise during start up Insufficient air supply - check the air damper setting and the condition of the fan.
Water temperature low Undersize nozzle and/or low fuel pressure.
Boiler operating on overheat thermostat Faulty boiler thermostat. No circulation, check circulating pump. Check for air lock.
Fumes and puffing during starting (conven­tional flue)
Oil odours Check all fuel line connections, remake as necessary.
Combustion fumes smell Check boiler cleaning cover and seal are correctly fitted.
Remedies
open. Check the condition of the fuel filter, clean if necessary. Ensure fuel supply is reaching burner and vent pump.
for heat. Ensure that the overheat thermostat has not tripped, reset if necessary. Check that a mains supply is present at the burner terminal block. If not, check the boiler and overheat thermostat.
Press the reset button on the burner control box if it is lit. Refer to burner fault finding charts.
Refer to burner fault finding charts.
Insufficient air supply - check the air damper setting and the condition of the fan. Check room ventilation is adequate, see Section 9.1. Check the nozzle size and type. Fuel pressure may be too high - check and adjust.
Check room ventilation is adequate, see Section 9.1. Check the nozzle size and type.
Check room ventilation is adequate, see Section 9.1. Check the nozzle size and type. Fuel pressure may be too low - check and adjust. Insufficient draught - clean boiler heat exchanger and check condition of flue.
Check condition of boiler heat exchanger and clean if necessary. Check the boiler thermostat. Check the combustion settings. Check the condition of the fuel filter.
Check the condition of the chimney, ensure it is not blocked and is high enough to produce the required draught. Check that there is an adequate air supply near the burner and that a kitchen fan is not drawing products out of the burner.
Check burner is correctly fitted onto flange. Check flue is correctly sealed into flue outlet of boiler. Check the condensate pipe and trap are operating correctly
35
Page 36
12.2 Burner Fault Finding - Riello RDB burners
36
Page 37
12.3 Circulating Pump Fault Diagnosis
The indicator LED, located around the circumference of the red control knob, can assit in diagnosing and rectifying a fault with the pump. See the table below.
LED condition Meaning Diagnostic Cause Remedy
Green
Flashes red and
green
Flashes red
LED off
Pump operating Pump runs according to the
red knob setting
Pump is operating but
stoipped
Pump not operating Pump stopped (blocked) Pump does not restar t itself
No power supply No voltage to pump control
Pump restarts itself af ter
fault has disappeared
electronics
Normal operation N/A
Undervoltage
Voltage <160V
OR
Overvoltage
Voltage >253V
Overheating:
temperature inside motor
too high
due to a permanent failure
Pump is not connected to
power supply
LED is damaged Check if pump is running
Electronics are damaged Replace pump
Check supply voltage is
195V<V<253V
Check water and ambient
temperature
Replace pump
Check cable connection
37
Page 38
13 Spares Parts
13.1 Boiler Parts List
Description Part number
Cleaning door nut and washer set EFBS14
Double pole switch EFBS19
Test switch EFBS21
Frost thermostat EFBS23
Baffle set (complete) - 15/21 and 21/26 VBS96
Baffle set (complete) - 26/35 VBS97
Turbulator baffle - single VBS98
Sealed system - Expansion vessel 12 litre MPSS01
Sealed system - Water pressure gauge MPSS02
Sealed system pressure relief valve MPCBS50X
Sealed system - Expansion vessel flexible hose MPSS04
Cleaning door - 15/21 and 21/26 VBS92
Cleaning door - 26/35 VBS69
Cleaning door seal - 15/21 and 21/26 VBS20L
Cleaning door seal - 26/35 VBS15
Overheat thermostat TPBS33
Boiler thermostat TPBS34
Circulating pump - 6 m head (non HE) MPCBS23
Circulating pump - 7 m head (HE) VBS126
White pump cable with plug (for HE pump) VBS126A
Black pump cable with plug (for HE pump) VBS126B
Return connection assembly - 22 mm with automatic air vent VBS61
Automatic air vent MPCBS29
Condensate trap VBS02
Condensate flexible hose VBS104
Stainless steel flue guard FKS70
38
13.2 Burner Heads
Figure 13-1: Burner heads
Page 39
This section gives exploded views of the Riello burners in the Grant VORTEX Eco boilers, and parts lists associated with them.
13.3 Riello RDB2.2 burner
Figure 13-2: Riello RDB2.2 burner components diagram
39
Page 40
Riello RDB2.2 burner parts list
Key number Description Riello part number Grant part number
1 Not applicable - -
2 Flange 3005786 RBS119
3 Combustion head T1 - 15/21 (21/26 - 20.7 kW) 3002507 RBS146
3 Combustion head T2 - 21/26 (26/35 - 25.6 kW) 3002423 RBS147
3 Combustion head T3 - 26/35 3002447 RBS144
4 Electrode assembly 3007513 RBS108
5 Electrode bracket 3006552 RBS29
6 Nozzle holder 3008642 RBS111
7 Collar 3008643 RBS112
8 High voltage lead 3008794 RBS129
9 Air damper assembly 3008647 RBS116
10 Fan - 15/21 3005788 RBS151
10 Fan - 21/26 3005708 RBS39
10 Fan - 26/35 3008645 RBS142
11 Photocell 3008646 RBS115
12 Capacitor 4.5 µF 3002837 RBS149
13 Seal kit 3008878 RBS140
14 Needle valve 3007582 RBS109
15 Regulator 3008651 RBS120
16 Pump seal 3000439 RBS14
17 Pump 3008654 RBS101
18 'O' ring 3007162 RBS08
19 Filter - 'O' ring 3008653 RBS122
20 Connector 3003602 RBS35
21 Flexible hose 3007672 RBS36
22 Tube 3008644 RBS113
23 Pressure gauge connector 3008876 RBS138
24 Drive coupling 3000443 RBS16
25 Solenoid 3008648 RBS117
26 Motor RBS102 3002836 RBS102
27 Cover 3008649 RBS118
28 Control box assembly 3008652 RBS103
29 Solenoid lead 3008851 RBS139
30 Cover 3008879 RBS141
31 Air tube spigot 3062774 RBS143
40
Page 41
14 Health and Safety Information
Under the Consumer Protection Act 1987 and Section 6 of the Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health (COSHH Regulations 1988).
Adhesives, sealants and paints used in the manufacture of the product are cured and present no known hazards when used in the manner for which they are intended.
The following other materials are present in the product:
14.1 Insulation Materials
Material Types: Ceramic fibre board,
mineral wool.
Description: Rigid board, slabs, sleeves, gaskets, ropes.
Known Hazards: May cause temporary irritation or rash to skin. High dust levels may irritate eyes and upper respiratory system.
Precautions: Avoid unnecessary or rough handling, or harsh abrasion of boards. Normal handling and use of material should not produce high dust levels.
Avoid inhalation, and contact with skin and eyes.
After handling always follow normal good hygiene practices.
Protection: Use disposable gloves, face mask and eye protection.
First Aid: Eyes - If irritation occurs, wash eyes with copious amounts of water.
If symptoms persist, seek immediate medical advice.
Skin - If irritation occurs, wash under running water before washing with soap and water.
Inhalation - Remove to fresh air, drink water to clear throat and blow nose to remove dust/fibres.
Ingestion - Drink plenty of water.
14.2 Sealant Materials
Material Types: Silicone elastomer.
Description: Sealant and adhesive.
Known Hazards: Irritation to eyes.
Precautions: Avoid inhalation
of vapour, contact with eyes and prolonged or repeated contact with skin.
After handling always follow normal good hygiene practices.
Protection: Use eye protection. Rubber or plastic gloves should be worn where repeated contact occurs and a face mask worn when working in confined spaces.
First Aid: Eyes - Flush eyes with water for 15 minutes. Seek immediate medical attention.
Skin - Wipe off and wash with soap and water.
Inhalation - Remove to fresh air.
14.3 Kerosene and Gas Oil Fuels (mineral oils)
Known Hazards: The effect of mineral
oils on the skin vary according to the duration of exposure and the type of oil.
The lighter fractions remove the protective grease naturally present on the skin, leaving it dry, liable to crack and more prone to damage by cuts, abrasions and irritant chemicals.
Skin rashes (Oil acne) most often on arms, but also on any part of the body in contact with oil or oily clothing.
Contact with fuel oils can cause dermatitis.
Precautions: Avoid as far as possible any skin contact with mineral oil or with clothing contaminated with mineral oil.
The use of a lanolin-based barrier cream is recommended, in conjunction with regular washing with soap and rinsing with water to ensure all oil is removed from the skin.
Take care to prevent clothing, especially underwear, from becoming contaminated with oil.
Do not put oily rags or tools in pockets, especially trouser pockets.
Have first-aid treatment at once for an injury, however slight.
Do not inhale any vapours from mineral oils.
41
Page 42
15 Recycling and Disposal
In EU Countries
The following information is provided to enable regulatory compliance with the European Union (EU) directives identified and any amendments made to these directives when using electrical or electronic equipment in EU countries.
Disposal of Electrical and Electronic Equipment
European Union (EU) Directive 2002/96/ EC Waste Electrical and Electronic Equipment (WEEE)
Do not dispose of electrical or electronic equipment in landfill sites. In the EU, it is the individual recipient’s responsibility to ensure that discarded electrical or electronic materials are collected and recycled according to the requirements of EU environmental law.
Disposal of Surplus Packaging
European Parliament and Council Directive 94/62/EC Packaging and Packaging Waste
Do not dispose of surplus packaging in landfill sites. In the EU, it is the individual recipient’s responsibility to ensure that packaging materials are collected and recycled according to the requirements of EU environmental law.
In non-EU Countries
In non-EU countries, dispose of electrical and electronic equipment and all surplus packaging in accordance with national and regional regulations.
Complies with EC Low voltage Electromagnetic compatibility and Boiler efficiency Directives.
Circulating Pump
The circulating pump must not be disposed of in normal doimestic waste as most of the materials used in it’s construction can be recycled.
For details on how to responsibly dispose of this pump, please visit: www.wilo.com/recycling
42
Page 43
16 Guarantee
16.1 The Vortex Oil Boiler Guarantee
You are now the proud owner of a Grant Vortex condensing boiler from Grant Engineering (UK) Limited which has been designed to give years of reliable, trouble free, operation.
Grant Engineering (UK) Limited guarantees the manufacture of the boiler including all electrical and mechanical components for a period of twelve months from the date of
installation4, provided that the boiler
has been installed in full accordance with the installation and servicing instructions issued.
This will be extended to a total period of two years if the boiler is registered with Grant Engineering (UK) Limited within
thirty days of installation4 and
serviced at twelve monthly intervals3. See main Terms and Conditions below.
Registering the product with Grant Engineering (UK) Limited
Please register your Grant Vortex condensing boiler with Grant Engineering UK Limited within thirty days of installation. To do so visit www.grantuk.com and follow the links to the ‘Homeowners Zone’, where you can register your boiler for a further
twelve months guarantee (giving two years from the date of installation4).
This does not affect your statutory rights1.
If a fault or defect occurs within the manufacturer’s guarantee period
If your boiler should fail within the guarantee period, you must contact Grant Engineering (UK) Limited who will arrange for the repair under the terms of the guarantee, providing that the boiler has been correctly installed, commissioned and serviced (if the appliance has been installed for more than twelve months) by a competent person and the fault is not due to tampering, running out of oil, oil contamination, debris, system water contamination, misuse, trapped air or the failure of any external components not supplied by Grant Engineering (UK) Limited, e.g. fire valve, motorised valve, etc.
This two year guarantee only applies if the boiler is registered with Grant Engineering (UK) Limited within thirty days of installation4 and is serviced after twelve months3.
In the first instance
Contact your installer or commissioning engineer to ensure that the fault does not lie with the system components or any incorrect setting of the system controls that falls outside of the manufacturer’s guarantee otherwise a service charge could result. Grant Engineering (UK) Limited will not be liable for any charges arising from this process.
If a fault covered by the manufacturer’s guarantee is found
Ask your installer to contact Grant Engineering (UK) Limited Service Department on +44 (0)1380 736920 who will arrange for a competent service engineer to rectify the fault.
Remember - before you contact Grant Engineering (UK) Limited:
• Ensure the boiler has been installed, commissioned and serviced by a competent person in accordance with the installation and servicing instructions.
• Ensure there is oil to supply the burner.
• Ensure the problem is not being caused by the heating system or its controls. Consult the boiler handbook for guidance.
Free of charge repairs
During the two year guarantee period no charge for parts or labour will be made, provided that the boiler has been installed and commissioned correctly in accordance with the manufacturer’s installation and servicing instructions, it was registered with Grant Engineering (UK) Limited within thirty days of installation4 and, for boilers over twelve months old, details of annual service is available3.
The following documents must be made available to Grant Engineering (UK) Limited on request:
• Proof of purchase
• CD10 Installation Completion Form (or equivalent document)
• CD11 Commissioning Report Form (or equivalent document)
• Service documents (CD11 or equivalent document)
Chargeable repairs
A charge may be made (if necessary following testing of parts) if the breakdown is due to any fault(s) caused by the plumbing or heating system, e.g. contamination of parts due to system contamination, sludge, scale, debris or trapped air. See ‘Extent of
manufacturer’s guarantee’.
Extent of manufacturer’s guarantee:
The manufacturer’s guarantee does not cover the following:
• If the boiler has been installed for
over two years.
• If the boiler has not been installed, commissioned, or serviced by a competent person in accordance with the installation and servicing instructions.
• The serial number has been removed or made illegible.
• Fault(s) due to accidental damage, tampering, unauthorised adjustment, neglect, misuse or operating the boiler contrary to the manufacturer’s installation and servicing instructions.
• Damage due to external causes such as bad weather conditions (flood, storms, lightning, frost, snow, or ice), fire, explosion, accident or theft.
• Fault(s) due to incorrectly sized expansion vessel(s), incorrect vessel charge pressure or inadequate expansion on the system.
• Fault(s) caused by external electrics and external components not supplied by Grant Engineering (UK) Limited.
• Problems caused by lack of oil or faults with the oil storage and supply system.
• Fault(s) due to contamination of the oil storage and supply system, e.g. water or debris.
• Bleeding or removing oil storage tank contamination or blockages from oil lines.
• Problems due to the flue system being incorrectly fitted or not installed to meet installation requirements.
• Boiler servicing, de-scaling or flushing.
• Cleaning out condensate traps/ discharge pipes or thawing out frozen condensate pipework.
• Checking and replenishing system pressure.
• Oil supply pipelines, electrical cables and plugs, external controls not supplied by Grant Engineering (UK) Limited.
• Heating system components, such as radiators, pipes, fittings, pumps and valves not supplied by Grant Engineering (UK) Limited.
• Instances where the oil boiler has been un-installed and re-installed in another location.
• Use of spare parts not authorised
43
Page 44
44
by Grant Engineering (UK) Limited.
• Consumable items including, but not limited to, oil nozzles, oil hoses, gaskets.
IMPORTANT
The nozzle and braided oil hose supplied with the boiler are only covered for the period up to the time of the first service (twelve months). Both must be changed on the first service and on every annual service thereafter.
IMPORTANT
Do not wait until the fuel supply runs out before you re-order. Sludge in the bottom of the tank may be drawn into the fuel lines. It is recommended that the boiler is switched off when the new oil supply is delivered and that the fuel is allowed to settle for an hour before restarting the boiler.
Terms of manufacturer’s guarantee:
• The Company shall mean Grant Engineering (UK) Limited.
• The boiler must be installed by a competent installer and in full accordance with the relevant Codes of Practice, Regulations and Legislation in force at the time of installation.
• The boiler is guaranteed for two years from the date of installation4, providing that after twelve months the annual service has been completed3 and the boiler registered with the Company within thirty days of installation. Any work undertaken must be authorised by the Company and carried out by a competent service engineer.
• The shell (heat exchanger) of the oil boiler is also covered by a five year parts only guarantee from the date of installation4. This is subject to the following:
• The boiler is operated
correctly, in accordance with the installation and servicing instructions.
• Proof is provided that the
system has been flushed or chemically cleaned where appropriate (refer to BS 7593) and that the required quantity of a suitable corrosion inhibitor added.
• Proof of annual servicing
(including the checking of any expansion vessels and pressure relief valves) must be provided if and when requested by the Company.
IMPORTANT
Grant Engineering (UK) Limited strongly recommends that a Grant Mag-One in-line magnetic filter/s (or equivalent5) is fitted in the heating system pipework. This should be installed and regularly serviced in accordance with the filter manufacturer’s instructions.
• This guarantee does not cover breakdowns caused by incorrect installation, neglect, misuse, accident or failure to operate the boiler in accordance with the manufacturer’s installation and servicing instructions.
• The boiler is registered with the Company within thirty days of installation. Failure to do so does not affect your statutory rights1.
• The balance of the guarantee is transferable providing the installation is serviced prior to the dwelling’s new owners taking up residence. Grant Engineering (UK) Limited must be informed of the new owner’s details.
• The Company will endeavour to provide prompt service in the unlikely event of a problem occurring, but cannot be held responsible for any consequences of delay however caused.
• This guarantee applies to Grant Engineering (UK) Limited boilers purchased and installed on the UK mainland, Isle of Wight, Channel Islands and Scottish Isles only2. Provision of in-guarantee cover elsewhere in the UK is subject to agreement with the Company.
• All claims under this guarantee must be made to the Company prior to any work being undertaken. Invoices for call out/ repair work by any third party will not be accepted unless previously authorised by the Company.
• Proof of purchase and date of installation, commissioning and service documents must be provided on request.
• If a replacement boiler is supplied under the guarantee (due to a manufacturing fault) the product guarantee continues from the installation date of the original boiler, and not from the installation date of the replacement4.
• The oil boiler must be connected to a mains water supply (installations utilising a private water supply are not covered by this guarantee).
• Breakdown/failure due to lime
scale will not be covered by this guarantee.
• The replacement of a boiler under this guarantee does not include any consequential costs, such as the removal or replacement of worktops, kitchen units, etc.
• The boiler (excluding external modules) must not be sited in a location where it may be subjected to frost.
Hard water advice (for Combi boilers only)
If you live in a hard water area, protection against scaling must be given to the domestic hot water heat exchanger of your combination boiler.
You should fit an appropriate scale inhibitor or water softener as any breakdown caused by water scaling is not covered by the manufacturer’s guarantee. Ask your installer for advice.
Foot notes:
1. Your statutory rights entitle you to a one year guarantee period only.
2. The UK mainland consists of England, Scotland and Wales only. Please note that for the purposes of this definition, Northern Ireland, Isle of Man and Scilly Isles are not considered part of the UK mainland.
3. Your boiler must be regularly serviced as per the installation and servicing instructions, (even when the guarantee has expired) to prolong the lifespan and ensure it is operating safely and efficiently.
4. The guarantee period will commence from the date of installation, unless the installation date is more than six months from the date of purchase, in which case the guarantee period will commence six months from the date of purchase.
5. As measured by gauss. The Mag­One magnetic filter has a gauss measurement of 12000.
Version 1.0
Page 45
18 Notes
45
Page 46
46
Page 47
47
Page 48
GRANT ENGINEERING (UK) LTD
Hopton House, Hopton Industrial Estate, Devizes, Wiltshire. SN10 2EU
Telephone: +44 (0)1380 736920 Fax: +44 (0)1380 736991
Email: [email protected] Website: www.grantuk.com
Loading...