Grant Vortex Eco Series, Vortex Eco 26/35, Vortex Eco 15/21, Vortex Eco 21/26 Installation And Servicing Instructions

Grant Vortex Eco
External and System Floor Standing Condensing Oil Boiler Range
Installation and Servicing Instructions
UK | DOC 0081 | Rev 3.1 | June 2015
Important Note
For use with Kerosene* only.
This appliance is deemed a controlled service and specific regional statutory requirements may be applicable.
*Operation on Bio-fuel
All Grant Vortex Eco condensing boilers, manufactured since May 2011, are suitable for operation on both standard kerosene (Class C2 to BS2869) and also bio-kerosene – up to a 30% blend (B30K).
All burner settings and nozzle sizes (as detailed in Section 2.3 of this manual) are correct for both standard kerosene and bio-kerosene (B30K).
In order to operate this boiler on bio­kerosene it will be necessary to take the following actions:
Use a bio-kerosene (B30K
compatible flexible oil line in place of the oil line supplied with this boiler.
Have your oil storage tank and oil
supply line (including all pipework, sight gauges, filters, isolating valves, fire valves, ed-aeration devices, etc.) checked for their compatibility with bio-kerosene (B30K). Where necessary some, or all, of these items may have to be replaced with a bio-kerosene compatible alternative.
Check the suitability of the flue
system with Grant UK.
Use only bio-kerosene (B30K) that
conforms to OPS24.
IMPORTANT
Under no circumstances should the boiler be used with bio-kerosene without the above actions being taken first.
Date:______________________________
Commissioning Engineer:_____________________________________________________
Tel. No:____________________________
Boiler model:_______________________ Boiler output:________________ kW
Fuel type: Kerosene / Bio-Kerosene
Nozzle size:________________________ Pump pressure:_____________________
Air setting:_________________________ Flue gas % CO2:____________________
Net flue gas temp:___________________ Smoke No:_________________________
System flushed: yes / no Corrosion inhibitor added: yes / no
Antifreeze added: yes / no
For Sealed systems only:
Expansion vessel size:______________________ litres
Expansion vessel charge pressure:___________ bar
Sealed system fill pressure (cold):____________ bar
Service Log
It is recommended that the boiler should be regularly serviced, at least once a year, and the details entered in the Boiler Handbook by the service engineer.
Declaration of Conformity
We declare that the Grant VORTEX range of Oil Boilers equipped with Riello RDB burners approved to EN 267: 1999 satisfy the requirements of the following European Directives:
1. 89/336/EEC - Electromagnetic Compatibility Directive Referred to the generic standards EN 55014: 1993, EN 50082: 1: 1992
2. 73/23/EEC - Electrical Equipment Safety Regulations Directive Referred to the generic standard NO: 3260: The Electrical Equipment (Safety) Regulations: 1994
3. 92/42/EEC - Hot Water Boiler Efficiency Directive Referred to the generic standard The Boiler (Efficiency) (Amendment) Regulations 1994 (SI 1994/3083)
GRANT ENGINEERING (UK) LIMITED
Hopton House, Hopton Industrial Estate, Devizes
???????
Wiltshire SN10 2EU Tel: +44 (0)1380 736920 Fax: +44 (0)1380 736991 Email: info@grantuk.com www.grantuk.com
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
2
2
© Grant Engineering (UK) Limited 2015. No part of this manual may be reproduced by any means without prior written consent.
Contents
1 Introduction 4
1.1 How a condensing boiler 4 works
1.2 Boiler description 4
1.3 Boiler components 5
2 Technical Data 6
2.1 Boiler technical data 6
2.2 Sealed system data - sealed 7 system models
2.3 Vortex boilers using Class 7 C2 kerosene
2.4 Flue gas analysis 7
2.5 Water connections 7
2.6 Boiler dimensions 8
3 Oil Storage and Supply 9 System
3.1 Fuel supply 9
3.2 Burner oil connection 11
4 Boiler Installation 13 Information
4.1 Introduction 13
4.2 Boiler location 13
4.3 Preparation for installation 13
4.4 Installing the boiler 14
4.5 Regulations compliance 14
4.6 Completion 14
4.7 Before you commission 14
4.8 Heating system design 15 considerations
4.9 Underfloor heating systems 15
4.10 Pipework materials 15
4.11 Sealed systems 15
4.12 Underfloor pipework 15
6 Condensate Disposal 17
6.1 General requirements 17
6.2 Connections 17
6.3 Pipework 17
6.4 External pipework 17
6.5 Condensate soakaway 17
6.6 Condensate trap 18
6.7 Condensate disposal 18
pipework
6.8 Inspection and cleaning of 18
trap
7 Sealed Systems 19
7.1 Sealed system installation 19
7.2 System models 20
7.3 Fill the sealed system 20
7.4 Pressure relief safety valve 20
7.5 Circulating pump 21
8 Electrical 23
8.1 Connecting the power 23
supply
8.2 Frost protection 23
8.3 Control system wiring 24
diagrams
8.4 Boiler control panel wiring 25
diagram
9 Flue and Air Supply 26
9.1 Air supply 27
9.2 Low level discharge flue 27
9.3 Horizontal system 27
9.4 Green system 28
9.5 Hybrid system 29
9.6 Coventional flue systems 29
10 Commissioning 30
10.1 Before switching on 30
10.2 Switching on 30
10.3 Running the boiler 31
10.4 Balancing the system 31
10.5 Completion 31
10.6 Air adjuster disc - 15/21 only 31
11 Boiler Servicing 32
11.1 Checking before servicing 32
11.2 Dismantling prior to servicing 32
11.3 Cleaning the boiler 34
11.4 Cleaning the burner 34
12 Fault finding 35
12.1 Boiler fault finding 35
12.2 Burner fault finding 36
12.3 Circulating pump fault 37 diagnosis
13 Spare Parts 38
13.1 Boiler parts list 38
13.2 Burner heads 38
13.3 Riello RDB2.2 burner 39
14 Health and Safety 41 Information
14.1 Insulation materials 41
14.2 Sealant materials 41
14.3 Kerosene and gas oil fuels 41 (mineral oils)
15 Recycling and disposal 42
16 Guarantee 43
5 Pipe Connections 16
5.1 Water connections 16
18 Notes 45
3
1 Introduction
This manual is intended to guide Installers who have completed the Grant Wood Pellet Boiler Installer training course on the installation, commissioning and servicing of the Grant Spira Condensing Wood Pellet Boiler.
A separate manual is available to guide users in the operation of the boiler.
The following special text formats are used in this manual for the purposes listed below:
WARNING
!
Warning of possible human injury as a consequence of not following the instructions in the “warning”.
CAUTION
!
Caution concerning likely damage to equipment or tools as a consequence of not following the instructions in the “Caution”.
NOTE
!
Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader.
1.1 How a Condensing Boiler Works
During the combustion process, hydrogen and oxygen combine to produce heat and water vapour. The water vapour produced is in the form of superheated steam in the heat exchanger. This superheated steam contains sensible heat (available heat) and latent heat (heat locked up in the flue gas). A conventional boiler cannot recover any of the latent heat and this energy is lost to the atmosphere through the flue.
The Grant Vortex Eco condensing boiler contains an extra heat exchanger which is designed to recover the latent heat normally lost by a conventional boiler. It does this by cooling the flue gases to below 90°C, thus extracting more sensible heat and some of the latent heat. This is achieved by cooling
4
the flue gases to their dew point (approximately 55°C).
To ensure maximum efficiency, the boiler return temperature should be 55°C or less, this will enable the latent heat to be condensed out of the flue gases.
The boiler will achieve net thermal efficiencies of 100%.
To achieve maximum performance from the Grant Vortex Eco boiler, it is recommended that the heating system is designed so that a temperature differential of 20°C between the flow and return is maintained. The use of modulating circulating pumps (now widely available) and effective control systems should be considered.
The Grant VORTEX Eco boiler will however still operate at extremely high efficiencies even when it is not in condensing mode and therefore is suitable for fitting to an existing heating system without alteration to the radiator sizes. The boiler is capable of a maximum flow temperature of 75°C.
1.2 Boiler Description
Grant Vortex Eco External modules have an insulated weatherproof enclosure made of galvanised steel with a powder coated finish, and are designed for external installation, either against a wall or free standing some distance away from the property, as required.
The External modules are part of the Grant range of automatic pressure jet oil boilers which have been designed for use with a fully pumped central heating system with indirect domestic hot water cylinder. They are not suitable for use with either a direct cylinder or a ‘primatic’ cylinder or gravity hot water.
The boilers are suitable for use on open vented or sealed central heating systems.
All models are supplied with the control panel and burner factory fitted.
The factory fitted low level discharge flue system can be adjusted on site for either rear, left hand or right hand flue outlet position as required.
An external conventional flue (Green system (Figure 9-2) is also available from Grant UK. Refer to Section 9.2 for further details.
A Hybrid flue (Green/Orange) system (Figure 9-3) is also available which allows the External module to utilise an existing chimney stack. Refer to Section
9.3 for further details.
Where an existing chimney is to be lined - Grant recommends the use of the Grant ‘Orange’ flue system, specifically designed for the Vortex range of condensing boilers. Refer to Section 9.3 for further details.
Where a rigid conventional flue is required, Grant recommends the use of the Grant ‘Green’ and ‘Orange’ flue system components. As no flue adaptor is supplied with the boiler it will be necessary to purchase the correct Grant Starter Elbow in order to connect this system to the boiler. Refer to Section 9 for further details.
The ‘Green’ and ‘Orange’ system components can be used to construct a flue of maximum vertical height 19 metres.
NOTE
!
The flue system materials and construction MUST be suitable for use with oil-fired condensing boilers. Failure to fit a suitable conventional flue may invalidate the guarantee on the boiler.
A horizontal system - see Figure
9-4, is also available up to 4 metres ­components available:
Straight starter
Extensions 150 mm, 250 mm, 450 mm and 950 mm
Adjustable extension 195 to 270 mm
45° elbow
Straight terminal
Green system
Standard external high level/vertical flue starter kit - components available:
External starter kit, straight or elbow
Extensions 150 mm, 250 mm, 450 mm, 950 mm
Adjustable extension 195 to 270 mm
45° elbow
High level terminal
Vertical terminal
1.3 Boiler Components
All burners are pre-set for use with kerosene and are supplied ready to connect to a single pipe fuel supply system with a loose flexible fuel line and 3/8” to 1/4” BSP male adaptor supplied with the boiler.
If required, an additional flexible fuel line (600 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK, for two-pipe oil supply systems (product code: RBS35 and RBS36).
The temperature of the water leaving the boiler to heat the radiators and hot water cylinder is user adjustable.
The boiler is fitted with an overheat thermostat (which allows it to be used on a sealed central heating system)
which will automatically switch off the boiler if the heat exchanger exceeds a pre-set temperature of 111°C ± 3°C.
The boiler control panel is fitted with an ON/OFF switch, boiler thermostat control knob and the manual reset button for the overheat thermostat.
An optional indoor programmer is available to purchase from Grant UK which allows the User to set the operating times for central heating and hot water (product code: EPKIT).
To access the controls remove the front panel by turning the handle at the bottom and withdrawing the cover forwards at the bottom.
Figure 1-1: Boiler controls for external modules
5
2 Technical Data
2.1 Boiler Technical Data - Vortex Eco
Model Unit 15/21 21/26 26/35
Water content litre 13 13 19
gal 2.9 2.9 4.2
Weight (dry) * External modules
kg 113 (ex ternal module)
136 ( external system)
113 (external module) 136 ( external system)
142 (external module) 152 ( external system)
lb 249 (ex ternal module)
300 ( external system)
Flow connection 22 mm 22 mm 22 mm
Return connection 22 mm 22 mm 22 mm
Min. flow rate ( T=10°C) l/h l/h 1 780 2 200 2 980
Min. flow rate ( T=20°C) l/h l/h 890 1 100 1 490
Condensate connection 22 mm (only connect plastic)
Flue diameter (conventional) 100 mm
Waterside resistance T=10°C mbar 28.5
Waterside resistance T=20°C mbar 10
Maximum static head m 28
Minimum circulating head m 1
Boiler thermostat range °C 65 to 75
Limit (safety) stat shut of f temp. °C 111 ± 3
Max. hearth temperature °C Less than 50
Electricity supply 230/240 V ~ 50 Hz fused at 5 Amp
Motor power Watts 90
Starting current Amps 4.2
Running current Amps 0.85
Oil connection ¼ BSP Male (on end of flexible fuel hose)
Conventional flue draught N/m² Minimum 8.7 - Maximum 37
in wg Minimum 0.035 - Maximum 0.15
Maximum operating pressure - sealed system bar 2.0
Maximum operating pressure - open system bar 2.0
Maximum operating pressure - pressure relief valve
bar 2.5
249 (external module) 300 ( external system)
313 (external module) 335 ( external system)
* Weight includes burner but excludes flue.
6
2.2 Sealed System Data - Sealed System Models
15/21, 21/26, 26/35
Heating system pressure (cold) Maximum 1.0 bar / Minimum 0.5 bar
Operating pressure of pressure relief valve 2.5 bar
Expansion vessel size (pre-charged at 1 bar) 12 litres
Max. heating system volume (including boiler)* 128 litres - approximately
Cold water mains connection 15 mm copper pipe
Pressure relief valve discharge connection 15 mm copper pipe
Circulating pump head 7 m
* Based on vessel charge and system cold fill pressure of 0.5 bar
2.3 Vortex Eco Boiler Using Class C2 Kerosene
Model
and
burner
type
15/21 Riello
RDB2.2
21/26 Riello
RDB2.2
26/35 Riello
RDB2.2
Notes
1 The data given above is approximate only. 2 The above setting may have to be adjusted on site for the correct operation of the burner. 3 Gas Oil is not suitable for use with the Grant Vortex Eco boiler range. 4 The net flue gas temperatures given above are ± 10%. 5 When commissioning the air damper must be adjusted to obtain the correct CO2 level. 6 * Factory settings: 15/21 - 18.1 kW, 21/26 - 22.7 kW, 26/35 - 30.8 kW. 7 The combustion door test point may be used for CO2 and smoke readings only. Do not use this test point for temperature or efficiency readings. 8 When setting the 15/21 to 15.1 kW output the burner air adjuster disc requires repositioning. Refer to Section 10. When setting the 21/26 to 20.7kW or the 26/35 to 25.6 kW output the combustion head must be changed. Refer to Section 11.4. 9 The installer must amend the boiler data label if the output is changed.
Heat Output SEDBUK
2009
(kW) (Btu/h)
annual
efficiency
Nozzle Oil
press.
(bar)
Smoke
No.
Burner
head
type
Burner
head/disc
setting
Fuel flow
rate
(kg/h)
Flue
gas
temp.
(°C)
(%)
15.1 51 500
* 18.1 61 750 0.55/80°EH 7.5 0 - 1 T1 Disc setting C 1.53 75 - 80 11 - 12
20.7 70 600 0.60/80°EH 8.5 0 - 1 T1 Disc setting C 1.78 80 - 85 11 - 12
20.7 70 600
* 22.7 77 500 0.65/80°EH 8.5 0 - 1 T2 Fixed 1.95 85 - 90 11 - 12
25.6 87 350 0.75/80°EH 8.0 0 - 1 T2 Fixed 2.19 90 - 95 11 - 12
25.6 87 350
* 30.8 105 100 0.85/80°EH 9.1 0 - 1 T3 Fixed 2.65 85 - 90 11 - 12
34.7 118 400 1.00/80°EH 8.0 0 - 1 T3 Fixed 2.93 90 - 95 11 - 12
91.9
91.7
91.4
0.50/80°EH 7.0 0 - 1 T1 Disc setting B 1.29 70 - 75 11 - 12
0.60/80°EH 8.5 0 - 1 T1 Fixed 1.78 85 - 90 11 - 12
0.75/80°EH 8.0 0 - 1 T2 Fixed 2.19 75 - 80 11 - 12
CO
(%)
²
2.4 Flue Gas Analysis
To allow the boiler to be commissioned and serviced, the boiler is supplied with a combustion test point on the front cleaning door. When this test point is used please note the following:
The test point is for CO2 and smoke readings only.
The boiler efficiency and temperature must be taken from the flue test point on high level, vertical and conventional flue adaptors.
Concentric low level flues do not contain a test point. The temperature and efficiency readings must be taken from the flue terminal.
2.5 Water Connections
Boiler model Flow connection Return connection
Size Fitting Supplied Size Fitting Supplied
15/21 22mm pipe Tectite elbow in fittings kit 22mm pipe Compression fitted
21/26 22mm pipe Tectite elbow in fittings kit 22mm pipe Compression fitted
26/35 22mm pipe Tectite elbow in fittings kit 22mm pipe Compression fitted
7
2.6 Boiler Dimensions
Figure 2-1: 15/21, 21/26 and 26/35 external module dimensions
8
3 Oil Storage and Supply System
3.1 Fuel Supply
Fuel Storage
The tank should be positioned in accordance with the recommendations given in BS 5410-1:2014, which gives details of filling, maintenance and protection from fire.
A steel tank may be used and must be constructed to BS 799-5:2010 and OFS T200.
CAUTION
!
A galavanised tank must not be used.
A plastic tank may be used and must comply with OFS T100.
NOTE
!
Plastic tanks should be adequately and uniformly supported on a smooth level surface, across their entire base area, that is, the area in contact with the ground.
Fuel Pipes
Fuel supply pipes should be of copper tubing with an external diameter of at least 10 mm.
Galvanised pipe must not be used.
All pipe connections should preferably use flared fittings. Soldered connections must not be used on oil pipes.
A remote sensing fire valve must be installed in the fuel supply line (outside) where it enters the building, with the sensing head located above the burner. Recommendations are given in BS 5410-1:2014.
It is recommended that a good quality metal bowl type fuel filter is fitted at the tank and a secondary filter in the fuel supply line adjacent to the boiler (15 µ for Kerosene) to protect the burner pump and nozzle from contamination. If the boiler operates on bio kerosene, a compatible filter should be used.
A flexible fuel line, adaptor and ¼” BSP isolation valve are supplied loose with the boiler for the final connection to the burner. If a two pipe system or ‘Tiger Loop’ type de-aerator is used, an additional flexible fuel hose (900 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK (product codes: RBS35 and RBS36).
Metal braided flexible hoses should be replaced annually when the boiler is serviced. Long life flexible hoses should be inspected annually and replaced at least every 60 months.
Single pipe system (see Figure 3-1)
With the storage tank outlet above the burner a single pipe system should be used. The height of the tank above the burner limits the length of pipe run from the tank to the burner.
Two pipe system (see Figure 3-2)
With the storage tank outlet below the burner, a two pipe system should be used. The pipe runs should be as shown in Figure 3-2. The return pipe should be the same level in the tank as the supply pipe, both being 75 to 100 mm above the base of the tank. The pipe ends should be a sufficient distance apart so as to prevent any sediment disturbed by the return entering the supply pipe.
Avoid the bottom of the tank being more than 3.5 m below the burner.
A non-return valve should be fitted in the supply pipe together with the filter and fire valve. A non-return valve should be fitted in the return pipe if the top of the tank is above the burner.
To be used with a two-pipe system, the burner must be fitted with an additional flexible fuel pipe - a flexible fuel hose (900 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK (product codes: RBS35 and RBS36).
The pump vacuum should not exceed
0.4 bar. Beyond this limit gas is released from the oil.
For guidance on installation of top outlet fuel tanks and suction oil supply sizing, see OFTEC Technical Book 3. Available from OFTEC.
CAUTION
!
Flexible hoses must NOT be used outside the boiler case of Utility models.
Figure 3-1: Single pipe system
As supplied the burner is suitable for a single pipe system
9
Figure 3-2: Two pipe system
Figure 3-3: De-aeration device system
10
Tiger Loop system ­(See Figures 3-3 and 3-4)
When the storage tank outlet is below the burner, an alternative to a two pipe system can be achieved using a ‘Tiger Loop’ type oil de-aerator. This effectively removes the air from the oil supply on a single pipe lift.
The de-aerator is connected close to the boiler as a two pipe system (omitting the non-return valve) as shown in Figure 3-3.
Refer to the manufacturers instructions supplied with the de-aerator.
The de-aerator must be mounted vertically. See Figure 3-3 and 3-4.
WARNING
!
To prevent any possibility of fuel fumes entering the building, the de-aerator must be fitted outside in accordance with BS 5410-1:2014.
To be used with a de-aerator, the burner must be fitted with an additional flexible fuel hose (a flexible fuel hose (900 mm) and 3/8” to 1/4” BSP male adaptor are available to purchase from Grant UK (product codes: RBS35 and RBS36).
3.2 Burner Oil Connection
The burner fuel pump is supplied for use with a single pipe fuel supply system.
For use on a two pipe system, it is necessary to fit the By-pass screw, as shown in Figure 3-5, into the tapping in the return port.
The By-pass screw is supplied in the boiler accessory pack.
Remove the plastic burner cover (secured by two screws).
For ease of access to the fuel pump, to fit the by-pass screw and connect the oil lines, the burner can be removed from the boiler. To do this, unscrew the single nut at the top of the burner (using a 13 mm spanner) and withdraw the burner from the boiler.
Remove and discard the blanking plug from the return connection of the pump and fit the By-pass screw using an hexagonal key.
Connect the return oil flexible fuel pipe to the pump.
Connect the 3/8” to 1/4” BSP adaptor to the flexible fuel pipe.
Flexible fuel pipes and adaptors are available to purchase from Grant UK.
The blanking plug supplied in the inlet (suction) port may now be plastic and will not provide an oil tight seal when the pump is running.
Figure 3-5: Riello RDB pump
Item Description
1 Inlet (suction) port
2 Return port
3 By-pass screw
4 Pressure gauge port
5 Pressure adjustment
6 Vacuum gauge port
7 Solenoid
8 Nozzle outlet
Figure 3-4: Tiger loop de-aeration device
WARNING
!
Ensure that the supply from the tank is connected to this port and that the plastic plug is discarded.
11
Main Burner Components
It may be necessary to remove theburner from the boiler to accessconnections in the fuel pump.
Disconnect the flexible air tube from the burner.
Remove the single nut at the top of the burner (using a 13 mm spanner) and withdraw the burner from the boiler.
NOTE
!
Remove the factory fitted air inlet spigot adaptor (item 6) in Figure 3-6 from the air intake on the top right hand side of the burner and fit the grey plastic air inlet grille in its place.
Burner Connection
If a two pipe system is to be used refer to Section 3.2.
Remove and discard the blanking plug from the inlet (suction) port of the pump. Refer to Figure 3-5.
Connect the elbow of the flexible fuel pipe supplied with the boiler to the inlet port.
Connect the other end of the flexible fuel pipe to the rigid supply line using the adaptor supplied. The supply enters through one of the holes in the casing plinth.
12
Figure 3-6: Riello RDB burner components
Item Description
1 Oil pump
2 Control box
3 Reset button with lock-out lamp
4 Flange with gasket (do not remove from boiler)
5 Air damper adjustment screw
6 Air supply tube connection (balanced flue)
7 Pump pressure adjustment screw
8 Pressure gauge connection
4 Boiler Installation Information
4.1 Introduction
All models are supplied fully assembled with the flue terminal guard supplied loose inside the boiler.
4.2 Boiler location
1. The External module must stand on a solid, level surface capable of supporting the weight of the boiler when full of water, e.g. a prepared concrete standing, paving slabs bedded down on sand/cement, or similar.
2. The module can be installed either against the building or ‘free standing’ some distance away from the building.
3. The module must be positioned such that the required clearances from the low level flue outlet, as shown in Figure 9-4, are achieved.
4. Adequate clearance must be left around the module for servicing. In particular, a minimum clearance of 600 mm above the module for removal of the top panel and 600 mm at the opposite end to the flue outlet for access to the burner. Sufficient clearance is required at the rear of the boiler to allow the rear panel to be removed for access to the condensate trap.
4.3 Preparation for Installation
1. Carefully remove the packaging from the boiler and remove it from the transit pallet.
2. Remove the case top panel (four screws) and also the front and rear panels, as required.
3. The flue may exit the boiler from the left, right or rear of the casing. Carefully press out the pre-cut section on the side or rear casing panel to provide the opening in the required position for the flue to pass through the casing. Fit the cover panel (with the round flue exit hole) over the square flue opening in the casing. Fit the circular rubber sealing grommet, provided, into the circular hole in the cover panel before fitting the flue terminal section.
4. Slacken the wing nuts holding the flue elbow and rotate the elbow to the required direction for the flue to exit the casing.
5. Push the end of the flue terminal section (with the red seal) through the sealing grommet in the casing panel. The terminal section has been factory lubricated. Take care not to dislodge or damage the red flue seal.
6. Carefully insert the terminal into the flue elbow until the bend of the terminal contacts the outer casing, then, pull the terminal forward approximately 25 mm and rotate the bend so that the outlet is horizontal. Rear exit - The flue must discharge away from the building. Side exit - The flue should discharge towards the rear of the casing to prevent flue gases re-entering the boiler casing through the air inlet vents on the casing front door.
The flue terminal must be fitted horizontally to prevent dripping from the end of the terminal.
7. Tighten the wing nuts holding the flue elbow and fit the stainless steel flue guard using the two screws provided.
8. he top panel of the casing has been designed so that it may be fitted to create a slight slope away from the side positioned against the wall. To tilt the top panel, loosen the four top panel casing screws, one at each corner and push down on the side furthest from the wall. Tighten the screws. See Figure 4-1.
Figure 4-1: Standard low level flue
13
4.4 Installing the Boiler
1. 1. If the boiler is to be fitted against the wall, prepare the wall to accept the heating system pipework. To mark the wall for drilling, refer to Section 2.6 for the positions of the pipework openings in the enclosure sides.
NOTE
!
Pipework should be insulated where it passes through the wall into the boiler enclosure.
If the boiler is to be installed ‘free standing’ (i.e. away from a wall) and the pipework run underground, push out the ‘knock-outs’ to open the required pipe openings in the base of the boiler enclosure. Using a sharp knife, cut through the polystyrene in the base, around the edge of the holes, to allow the flow and return pipes to enter the enclosure.
2. The electrical supply to the boiler should be routed through the wall in a suitable conduit, such that it enters the boiler enclosure via one of the unused pipework openings. The cable can be routed to the front of the boiler, for connection to the boiler control panel, either over the top or beneath the boiler heat exchanger. Heat resistant PVC cable, of at least 1.0 mm² cross section should be used within the boiler enclosure.
3. The oil supply line should be installed up to the position of the boiler. Refer to Section 3.1 for details. The final connection into the boiler enclosure can be made with 10 mm soft copper, routed along the base of the enclosure (either between the enclosure and wall or in front of the enclosure) to enter through one of the holes located in the bottom edge side panel, at the front (burner) end.
4.5 Regulations Compliance
Installation of a Grant VORTEX Eco boiler must be in accordance with the following recommendations:
Building Regulations for England and Wales, and the Building Standards for Scotland issued by the Department of the Environment and any local Byelaws which you must check with the local authority for the area.
Model and local Water Undertaking Byelaws.
Applicable Control of Pollution Regulations.
The following OFTEC requirements:
OFS T100 Polythene oil
storage tanks for distillate fuels.
OFS T200 Fuel oil storage
tanks and tank bunds for use with distillate fuels, lubrication oils and waste oils.
Further information may be obtained from the OFTEC Technical Book 3 (Installation requirements for oil storage tanks) and OFTEC Technical Book 4 (Installation requirements for oil fired boilers).
The installation should also be in accordance with the latest edition of the following British Standard Codes of Practice:-
BS 715 Metal flue pipes, fittings, terminals and accessories.
BS 799:5 Oil storage tanks.
BS 1181 Clay flue linings and flue terminals.
BS EN 1856-1:2009 Chimneys. Requirements for metal chimneys. System chimney products.
BS 5449 Forced circulation hot water systems.
BS 7593 Code of Practice for treatment of water in heating systems.
BS 7671 Requirements for electrical installations, IET Wiring Regulations.
NOTE
!
Failure to install and commission appliances correctly may invalidate the boiler guarantee.
WARNING
!
Before starting any work on the boiler, or fuel supply please read the health and safety information given in Section 14.
4.6 Completion
Please ensure that the OFTEC CD/10 installation completion report (provided with the boiler) is completed in full.
Leave the top copy with the User.
Retain the carbon copy.
Ensure that the User Information pack (supplied with the boiler) is handed over to the Householder.
4.7 Before you Commission
To avoid the danger of dirt and foreign matter entering the boiler the complete heating system should be thoroughly flushed out - before the boiler is connected and then again after the system has been heated and is still hot. This is especially important where the boiler is used on an old system.
For optimum performance after installation, this boiler and its associated heating system must be flushed in accordance with the guidelines given in BS 7593:2006 ‘Treatment of water in domestic hot water central heating systems’.
This must involve the use of a proprietary cleaner, such as BetzDearborn’s Sentinel X300 or X400, or Fernox Restorer. Full instructions are supplied with the products, but for more details of BetzDearborn’s products, view the website www.sentinel­solutions.net and for more details of Fernox products view the website www. fernox.com.
14
For long term protection against corrosion and scale, after flushing, it is recommended that an inhibitor such as Betzdearborn’s Sentinel X100 or Fernox MB-1 is dosed in accordance with the guidelines given in BS 7593:2006.
Failure to implement these guidelines will invalidate the guarantee.
NOTE
!
We recommend that both antifreeze and corrosion inhibitor be used in the primary water system.
4.8 Heating System Design Considerations
To achieve the maximum efficiency possible from the Grant VORTEX Eco boiler, the heating system should be designed to the following parameters:
Radiators:
Flow temperature 70°C
Return temperature 50°C
Differential 20°C
Underfloor:
Flow temperature 50°C
Return temperature 40°C
Differential 10°C
Size radiators with a mean water temperature of 60°C.
Design system controls with programmable room thermostats or use weather compensating controls to maintain return temperatures below 55°C.
The use of a pipe thermostat is recommended to control the return temperature when using weather compensating controls.
Refer to Section 2.5 for the size and type of the connections and Section 5 for the position of the connections.
4.9 Underfloor Heating
Systems
In underfloor systems it is essential that the return temperature must be maintained above 40°C to prevent internal corrosion of the boiler water jacket.
4.10 Pipework Materials
Grant boilers are compatible with both copper and plastic pipe. Where plastic pipe is used it must be of the oxygen barrier type and be of the correct class (to BS 7291-1: 2010) for the application concerned.
WARNING
!
The first metre of pipework connected to both the heating flow and return connections of the boiler must be made in copper on all types of system - sealed or open-vented.
4.11 Sealed Systems
If plastic pipe is to be used, the installer must check with the plastic pipe manufacturer that the pipe to be used is suitable for the temperature and pressures concerned.
Plastic pipe must be Class S to BS 7291-1: 2010.
WARNING
!
The system must incorporate a low pressure switch to shut off power to the boiler if the system pressure drops below 0.2 bar. A suitable low pressure switch kit is available to purchase from Grant UK (product code: MPCBS63).
4.12 Underfloor Pipework
Plastic pipe may be used on Underfloor systems where the plastic pipe is fitted after the thermostatic mixing valve.
Copper tube must be used for at least the first metre of flow and return primary pipework between the boiler and the underfloor mixing/blending valves.
NOTE
!
The boiler should not be allowed to operate with return temperatures of less than 40°C when the system is up to operating temperature.
15
Loading...
+ 33 hidden pages