Grant Spira Series, Spira 6-26, Spira 9-36, Spira 18-72, Spira 12-52 Installation & Servicing Instructions Manual

...
Grant Spira 6-26 kW and 9-36 kW
Condensing Wood Pellet Boiler
Installation & Servicing Instructions
Part No. DOC 42 Rev 01. May 2013
PROVISIONAL COPY
Important Note
2
Important Note for Installers
After installing the boiler leave these instructions with the Appliance. Leave the user manual with the householder.
This appliance is deemed a controlled service and specific regional statutory requirements may be applicable.
GRANT ENGINEERING (UK) LIMITED
Hopton House, Hopton Industrial Estate, Devizes, Wiltshire SN10 2EU Tel: 01380 736920 Fax: 01380 736991 Email: sales@grantuk.com www.grantuk.com
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. © Grant Engineering (UK) Limited 2013. No part of this manual may be reproduced by any means without prior written consent.
Contents
3
Contents
1 Introduction 4
1.1 How the Condensing Wood Pellet Boiler Operates 5
1.2 Boiler Description 5
1.3 Boiler Models 5
1.4 Boiler Components 6
1.5 Boiler Cleaning and Servicing 7
2 Technical data 8
2.1 Boiler & Hopper Technical Data 8
2.2 Boiler Input and Output Data 9
2.3 Flue Gas Analysis 9
2.4 Boiler and Hopper Dimensions and Clearances 10
3 Pellet Specification
& Storage 13
3.1 Pellet Specification 13
3.2 Pellet Storage 14
4 Installation information 16
4.1 Introduction 16
4.2 Boiler Location 16
4.3 Preparation for Installation 16
4.4 Installing the Boiler 16
4.5 Regulations 16
4.6 Heating System Design Considerations 16
4.7 Pipework Materials 16
4.8 Pipe Connections 17
4.9 Wash System Manifold 17
4.10 Fan Box and Flue Starter 17
4.11 Pellet Hoppers 18
4.12 Pellet Feed Auger 18
4.13 Before you Commission 19
4.14 Completion 19
5 Condensate disposal 20
5.1 General Requirements 20
5.2 Connections 20
5.3 Pipework 20
5.4 External Pipework 20
5.5 Condensate Soakaway 20
5.6 Condensate Trap 21
5.7 Inspection and Cleaning of Trap 21
6 Sealed Systems 22
6.1 Sealed System Requirements 22
6.2 Filling the Sealed System 22
6.3 Venting the Pump 23
6.4 Pressure Relief (Safety) Valve Operation 23
7 Flue System and
Air Supply 24
7.1 Air Supply 24
7.2 Flue Position and Clearances 24
7.3 Flue System Assembly 25
7.4 Flue Notice Plate 27
7.5 Carbon Monoxide Alarm 27
7.6 Flue System Components 28
7.7 Flue Component Dimensions 30
7.8 Typical Flue Systems 31
8 Electrical 32
8.1 General Requirements 32
8.2 Hopper Electrical Connections 32
8.3 Boiler Plug Connections 32
8.4 Heating System Controls 33
8.5 Connecting the Power Supply 33
8.6 Wiring Diagrams 34
9 Burner 40
9.1 Burner Operation 40
9.2 Burner Operational Modes 40
9.3 Burner Operational Sequence 41
9.4 Burner Display Screen 42
9.5 Burner Control Buttons 42
9.6 Burner Menu Navigation Chart and Factory Default Setting 43
9.7 Burner Menu 44
10 Commissioning 47
10.1 Equipment Required 47
10.2 Preliminary Inspection 47
10.3 Boiler 47
10.4 Pellet Hopper 48
10.5 Safety Device Checks 48
10.6 Burner Setting 49
10.7 Priming the Pellet Feed Auger 49
10.8 Lighting the Boiler 50
10.9 Combustion Chamber Draught 50
10.10 Flue Gas Analysis 51
10.11 Customer Handover 51
10.12 Commissioning Report Form 52
10.13 Commissioning Check List 52
11 Boiler Servicing 53
11.1 General 53
11.2 Checks Before Servicing 53
11.3 Heating System 53
11.4 Flue System 53
11.5 Combustion Ventilation 54
11.6 Boiler 54
11.7 Burner Brazier 56
11.8 Burner Components 57
11.9 Re-fitting Burner 58
11.10 Condensate Disposal System 58
11.11 Burner Settings 58
11.12 Safety Device Checks 59
11.13 Combustion Checks 59
12 Fault Finding 60
12.1 General 60
12.2 Normal Screen Display 61
12.3 No Screen Display 62
12.4 Boiler Overheat Thermostat 64
12.5 Pellet Tube Thermostat 65
12.6 Failed Pellet Lighting 67
12.7 Servo Motor Blocked 69
12.8 Probe Failure Thermostat 70
12.9 Air Pressure Error 71
13 Spare Parts 72
14 Health & Safety
Information 80
15 EC Declaration of
Conformity 81
16 Warranty 82
Introduction
4
1 Introduction
Grant SPIRA Condensing Wood Pellet Boiler & Intermediate Hopper
Intermediate Hopper
Wood Pellet Boiler
Boiler Controls
Pellet Feed Auger
Pellet Delivery Hose
Pellet Delivery Tube
Burner Controls
Wood Pellet Burner
This manual is intended to guide Installers who have completed the Grant Wood Pellet Boiler Installer training course on the installation, commissioning and servicing of the Grant SPIRA Condensing Wood Pellet Boiler.
A separate manual is available to guide users in the operation of the boiler.
The following special text formats are used in this manual for the purposes listed:
Warning of possible human injury as a consequence of not following the instructions in the “warning”.
Caution concerning likely damage to equipment or tools as a consequence of not following the instructions in the “Caution”.
Note text: Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader.
!
WARNING
!
CAUTION
!
NOTE
Introduction
5
1.1 How the Condensing Wood Pellet Boiler Operates
During the combustion process, hydrogen and oxygen combine to produce heat and water vapour. The water vapour produced is in the form of superheated steam in the heat exchanger. This superheated steam contains sensible heat (available heat) and latent (heat locked up in the flue gas). A conventional boiler cannot recover any of the latent heat and this energy is lost to the atmosphere through the flue.
The Grant SPIRA Condensing wood pellet boiler contains an extra (secondary) heat exchanger which is designed to recover the latent heat normally lost by a conventional boiler. It does this by cooling the flue gases to below 90°C thus extracting more sensible heat and some of the latent heat. This is achieved by cooling the flue gases to their dew point.
The boiler has been independently tested to BS EN303-5 and will achieve the following full load efficiencies when both the boiler and system are correctly set:
To ensure maximum efficiency from the Grant SPIRA boiler, the boiler return
temperature should be 55°C or less (but NOT less than 40°C) at maximum operating temperature.
This will enable the latent heat to be condensed out of the flue gases.
The boiler is capable of a maximum flow temperature of 75°C.
To achieve the required return temperature (55°C or less), it is recommended that the heating system is designed and balanced to operate with a temperature differential of 20°C between flow and return. The use of modulating circulating pumps (now widely available) and effective control systems should be considered.
Grant SPIRA condensing wood pellet boilers will still operate at extremely high efficiencies even when not in condensing mode and are therefore suitable for fitting to an existing heating system without alteration to the radiator sizes.
1.2 Boiler Description
The Grant SPIRA boiler uses a drop feed type burner with modulated heat output. The burner output is determined by varying the feed and pause time of the pellet feed auger supplying pellets to the burner. See Section 8 for details of burner operation.
The boiler is suitable for use on a sealed or open vented central heating system. When commissioned and set correctly, Grant SPIRA condensing wood pellet boilers will operate automatically, using a typical heating control system.
All models are supplied with the control panel and burner factory fitted. The combined fan box & flue starter, pellet feed auger and hopper are supplied separately and are fitted by the installer. See Section 4 for boiler installation.
The boiler needs to be connected to a conventional flue system. There is no provision for connection to a balanced flue system as there is draft stabilizer fitted to the appliance.
The boiler is not designed specifically for operation on a system with a buffer tank/ thermal store, however when used on such a system there is no effect on the boiler performance.
!
NOTE
Model Nominal Reduced
Output Output
SPIRA 6-26 97.4% 96.4%
SPIRA 9-36 93.1% 98.1%
The only flue suitable for use with the Grant SPIRA condensing wood pellet boiler is the Grant ‘Black’ twin-wall insulated conventional flue system. This 125mm (5”) diameter, black powder coated stainless steel flue system is suitable for both 6-26kW and 9-36kW Spira models.
For the 52kW, 62kW and 72kW double boiler installations each boiler must have a separate flue system. Refer to Section 7.
Product Code Model Description
WPS626RH110 6-26 1 x 6-26kW boiler + 110kg right hand hopper
WPS626LH110 6-26 1 x 6-26kW boiler + 110kg left hand hopper
WPS626RH200 6-26 1 x 6-26kW boiler + 200kg right hand hopper
WPS626LH200 6-26 1 x 6-26kW boiler + 200kg left hand hopper
WPS936RH110 9-36 1 x 9-36kW boiler + 110kg right hand hopper
WPS936LH110 9-36 1 x 9-36kW boiler + 110kg left hand hopper
WPS936RH200 9-36 1 x 9-36kW boiler + 200kg right hand hopper
WPS936LH200 9-36 1 x 9-36kW boiler + 200kg left hand hopper
WPS1252 12-52 2 x 6-26kW boilers + 140kg double boiler hopper
WPS1562 15-62 1 x 6-26kW boiler and 1 x 9-36kW boiler
+ 140kg double boiler hopper
WPS1872 18-72 2 x 9-36kW boilers + 140kg double boiler hopper
1.3 Boiler Models
The Grant SPIRA condensing wood pellet boiler is available in eleven different models:
Introduction
6
1 Introduction
1.4 Boiler Components
1.4.1 Burner. The burner is supplied factory-fitted to the boiler. All burners are supplied with factory default settings. During commissioning each burner parameter will need to be checked (see Section 8), and adjusted if necessary as the flue length can have a significant effect on the boiler performance. Refer to commissioning in Section 9.
The Burner is equipped with a self cleaning device to prevent a build up of ash and clinker in the burner brazier.
The burner output is determined by the feed / pause times of the pellet feed auger supplying the burner. See Section 8 for full burner operation details.
1.4.2 Boiler. The SPIRA condensing boiler is supplied with a combined primary and secondary heat-exchanger. Both heat exchangers are equipped with a self cleaning system.
1.4.3 Boiler controls. The set-point temperature of the boiler is user adjustable via two push buttons on the burner control panel - see Section 8.4 for details.
The boiler control panel (See Figure 1.1.) is located at the top of the boiler and is fitted with three controls, as follows:
ON/STAND-BY switch – to switch off the burner when required, by interrupting the switched live supply to the burner. This switch does not isolate the electrical supply to the burner.
OVERHEAT thermostat - this allows the boiler to be used on a sealed central heating system and will automatically switch off the boiler if the pre-set temperature of 110°C is exceeded.
CLEANING switch - when pressed and held in the TEST position, it allows the cleaning system to be manually operated and tested. When released it will automatically return to the default AUTO position to allow the boiler cleaning system to perform automatically. Only operate the cleaning switch when the boiler is in ‘WAIT BOILER THERMOSTAT’.
1.4.4 Boiler Pellet Hoppers. All single boilers (Spira 6-26 and 9-26 models) come with a pellet hopper. Two sizes of hopper are available for use with single boilers, as follows:
110 kg hopper – for storing a maximum of 110kg (170 litres) of wood pellets
200kg hopper – for storing a maximum of 200kg (308 Litres) of wood pellets.
There are two versions of both the 110kg and 200kg pellet hopper available for use with a single boiler:
Left hand hopper – to be positioned on the left hand side of the boiler. This is the ‘standard’ option and will be automatically supplied with the boiler unless specified otherwise.
Right hand hopper – to be positioned on the right hand side of the boiler. This is the ‘non-standard’ option and must be specified when ordering the boiler.
Both hoppers are supplied with a single
1.2m pellet feed auger, to be fitted to
the hopper on site by the installer.
All ‘double boiler’ installations (Spira 12-52, 15-62 and 18-72 models) come with one 'double' hopper to feed both boilers. This hopper is positioned between the two boilers and stores a maximum of 140 kg (215 litres).
ALL the Grant pellet hoppers are for indoor use only and must be positioned in a dry environment.
Hopper contents switch
All hoppers are fitted with a contents switch. This detects when the level of pellets in the hopper falls to a pre-set minimum value and triggers the operation of either a bulk store auger, or vacuum system, to delivery pellets from the bulk pellet store.
If no bulk store is used, the contents switch will stop the burner operating when the minimum pellet level is reached.
Topping up the hopper with more pellets will automatically operate the contents switch and the burner will restart (if there is a demand for the boiler to run).
The minimum quantity of pellets required to restart the boiler is 20kg for the single boiler hoppers and 3kg for the double boiler hoppers.
All boiler pellet hoppers are for indoor use only and MUST be positioned in a dry environment free from dampness. They must be located
on the same floor level as the boiler, or boilers, they are supplying.
All hoppers are mounted on four castors (with the two front castors lockable) to allow it to be easily moved when required. Allow sufficient area in front of the hopper for it to be moved out and away from the boiler(s) during servicing.
The electrical connections to the boiler(s) are all made to the 4-way electrical plug on one of the three factory-fitted ‘flying leads’ at the rear of the hopper. Refer to Section 7 for details.
After the burner has been switched off (either manually by the switch on the control panel, or automatically by the boiler control stat, or the heating system controls) the burner needs to burn-down the remaining pellets in the brazier. Do not open the front combustion chamber access door until the burner display reads “WAIT BOILER THERMOSTAT”.
!
WARNING
Figure 1-1: Boiler control panel
Introduction
7
All hoppers are supplied with a rectangular blanking plate fitted on the top rear panel. This can be removed, as required, to allow the fitting of the Grant SPIRA-VAC pellet feed system. Refer to Installation Instructions supplied with the Grant SPIRA-VAC system for further details.
This blanking plate has a single round ‘knock-out’ to provide an entry into the hopper from an auger supplying pellets from a bulk hopper system. This knockout is positioned to ensure the pellets drop into the hopper and operate the hopper contents switch. Only this opening MUST be used as making another opening in the intermediate hopper could affect the operation of the contents switch.
Electrical connection for either a bulk auger or Grant SPIRA-VAC system, if required, is made using the 6-way electrical plug and flying lead supplied factory-fitted at the rear of the hopper. Refer to Section 7 for connection details.
Always ensure that the door and top panel of the boiler hopper are fitted to ensure no foreign debris enters the hopper. If a bulk system with an auger is fitted, ensure that the bulk auger does not impede the opening of the hopper door.
1.4.5 Pellet Feed Auger. All Grant hoppers are supplied with either one or, on double boiler hoppers, two 1.2m pellet feed augers. These are set at a fixed angle of 45° to maintain a consistent feed. If the pellet feed auger angle is altered the input to the boiler will also be altered.
The pellet feed auger is a hollow spiral type. Its function is to deliver the pellets from the hopper to the burner. The output of the boiler is determined by varying the on/off periods of the pellet feed auger motor. Refer to Section 2.2 for pellet feed data.
1.5 Boiler Cleaning and
Servicing
Grant SPIRA condensing wood pellet boilers are equipped with an automatic cleaning system for each of the two heat exchangers and also for the burner brazier.
Care must be taken to avoid contact with hot surfaces.
Always wait for the boiler to cool down before opening the combustion chamber door and removing the ash pan.
The boiler MUST be serviced either ANNUALLY or when a service is indicated on the burner control panel display, whichever comes first.
Servicing should only be carried out by a Grant Approved Installer and details of each service should be recorded in the Service Log in the back of the User Operating Manual.
!
WARNING
The ash pan (located inside the combustion chamber) will need to be periodically emptied. This simple task must be carried out by the user at MONTHLY intervals for the FIRST THREE MONTHS. Thereafter, the ash pan should be emptied regularly, on at least a monthly basis, or as indicated by the amount of ash found during the first three months. Two carrying handles are supplied with the boiler to allow removal of the ash pan when hot.
!
CAUTION
The amount of ash produced varies between the different pellet brands and this will affect the frequency of cleaning and maintenance required.
!
NOTE
Technical Data
8
2 Technical Data
2.1 Boiler & Hopper Technical Data
Spira Model
Model Number Units 6-26 9-36
Maximum heat Output kW 26 36
Btu/hr 88,700 122,800 Flow connection - 1" BSP (Female) 1 1/4" BSP (Female) Return connection - 1" BSP (Female) 1 1/4" BSP (Female) Water content Litres 51.5 60 Waterside resistance ΔT = 10°C mbar 26.0 Waterside resistance ΔT = 20°C mbar 9.5 Mains water (cleaning system) bar 1 bar operating pressure Condensate connection - 11/4" BSP (Female) Conventional flue - 125mm (5") Black system Combustion chamber draught requirement mbar 0.10 to 0.15 (running) Maximum static head m 25 Minimum circulating head m 1 Boiler temperature set point range °C 55° to 75°C Boiler temperature cut out point °C 65° to 80°C Minimum return temperature °C 40°C Water system overheat cut-out temp. °C 110°C Burn-back overheat thermostat cut-out °C 60°C Electricity supply - 230V~50Hz Max operating pressure - sealed system bar 2.5 bar Max operating pressure - open system bar 2.5 bar Maximum auger length (bulk hopper) metres 6.0 Maximum auger speed (bulk hopper) rpm 30 Minimum flue length m 2.0 Maximum flue length m 12.0 Heating element rating Watts 450 Intermediate auger motor power Watts 55 Intermediate auger motor starting current Amps 0.64 Intermediate auger motor running current Amps 0.64 Intermediate auger speed rpm 8.1 Flue fan motor power Watts 32 Flue fan motor starting current Amps 0.27 Flue fan motor running current Amps 0.13 Cleaning solenoid power Watts 10 Cleaning solenoid current Amps 0.087 Burner fan motor power Watts 56 Total burner start current amp 2.5 Total burner run current amp 0.60
Model MAX Flame MIN Flame
Pellet Burner setting Heat Heat Draught CO2Burner Heat
feed Output Input Setting Output
Auger TIME TIME kW kW Full Input mbar % TIME kW
angle LOAD PAUSE (Btu/h) (Btu/h) Eff. kg/hr* (in.wg) PAUSE (Btu/h)
MAX MIN
SPIRA 45° 0025 0025 26.3 27.1 97.4 5.70 0.1–0.15 10–12 0140 6.5
6-26 (2.5sec) (2.5sec) (89,735) (92,500) (0.04-0.06) (14.0sec)) (22,100)
SPIRA 45° 0065 0025 36 38.7 93.1 7.78 0.1–0.15 10–12 0250 9
9-36 (6.5sec) (2.5 sec) (122,832) (132,000) (0.04-0.06 (25sec) (30,700)
in.wg)
1. *Heat input is based on a calorific value of 4.81 kWh/kg.
2. Heat input and output data given above is approximate only.
Technical Data
9
2.2 Boiler Input and Output Data
The settings in the table below are based on the boiler using the Grant fixed angle pellet feed auger at 45° with an auger motor fixed speed of 8.1 rpm.
Only ENplus A1 (EN14961-2) pellets MUST be used with the Grant SPIRA boilers. These pellets must be bark and sand free AND approved by Grant UK BEFORE being used in the Spira boilers. Failure to use approved pellets will invalidate the product warranty.
2.2.1 Burner settings
All burner settings must be checked as part of commissioning and servicing. Refer to Section 9.6 for full details of the burner settings and how to access, check and, where necessary, how to adjust them.
Boiler and Hopper Weights
2.3 Flue Gas Analysis
As part of both the commissioning and servicing procedures, the CO
2
content of the flue gases must be checked. To enable this to be done, the boiler is supplied with a combustion test point in the top rear cleaning door. Refer to Figure 10-17.
To gain access to this test point, first remove the top casing panel from the boiler. The test point should be at the back left corner of the rear cleaning door. If it is located at the front right corner of the cleaning door, then remove the door and refit it with the test point in the correct position.
Spira Model
Model Number Units 6-26 9-36
Weight boiler – less burner and fan box (empty) kg 201 231 Weight burner kg 25.5 25.5 Weight fan box kg 5 5 Total weight of boiler (empty) kg 231.5 261.5 Total weight of boiler (full) kg 283 321.5 Weight 110kg pellet hopper (empty) – incl. auger kg 41.35 41.35 Weight 110kg pellet hopper (full) – incl. auger kg 151.35 151.35 Weight 200kg pellet hopper (empty) – incl. auger kg 77 77 Weight 200kg pellet hopper (full) – incl. auger kg 277 277 Weight of auger kg 8.35 8.35 Weight 140kg double pellet hopper (empty)
– incl. 2 augers
kg 42 42
Weight 140kg double pellet hopper (full) – incl. 2 augers
kg 182 182
To ensure correct combustion, the burner settings given in the table above must NOT be changed unless instructed to do so by Grant UK.
!
CAUTION
Do not sample the flue gases through either the draught stabiliser, or from within the flue, as they will have been diluted with air entering through the draught stabiliser.
Only use the combustion test point in the top rear access door to check the CO
2
content of the flue gases.
See Fg. 10-17.
!
CAUTION
!
NOTE
Use only a calibrated flue gas analyser with a ‘Wood Pellet’ fuel setting. Setting the fuel to anything other than wood pellets will give an incorrect reading.
Technical Data
10
2 Technical Data
2.4 Boiler and Hopper Dimensions and Clearances
2.4.1 Single Boiler with Left Hand Hopper
Figure 2-1: Boiler and hopper dimensions and clearances – single boiler with left hand hopper
Front View Side View
Rear View
Plan View
Spira Wood Pellet Boiler Dimensions Model A B C D E F G H
6-26 110kg left hand hopper 1056 518 513 177 96 661 1160 1120 6-26 200kg left hand hopper 1256 618 713 125 44 713 1160 1120 9-36 110kg left hand hopper 1056 518 513 277 196 661 1260 1220 9-36 200kg left hand hopper 1256 618 713 225 144 713 1260 1220
If the measurement from the flue centre line to the rear wall is increased (shown as 134 in the plan view), then the dimensions D, E & G will have to be increased by the same increment. All units in millimeters
 










 
 
 
 





  





Technical Data
11
2.4.2 Single Boiler with Right Hand Hopper
Figure 2-2: Boiler and hopper dimensions and clearances – single boiler with right hand hopper
Front View Side View
Rear View Plan View
Spira Wood Pellet Boiler Dimensions Model A B C D E F G H
6-26 110kg right hand hopper 1056 518 513 177 96 661 1160 1120 6-26 200kg right hand hopper 1256 618 713 125 44 713 1160 1120 9-36 110kg right hand hopper 1056 518 513 277 196 661 1260 1220 9-36 200kg right hand hopper 1256 618 713 225 144 713 1260 1220
If the measurement from the flue centre line to the rear wall is increased (shown as 134 in the plan view), then the dimensions D, E & G will have to be increased by the same increment. All units in millimeters





 


 
 
 


  

 
 




 




Rear View
Plan View
Front View
Side View
Spira Wood Pellet Boiler Dimensions Model A B C D E F G H
12-52 with double hopper 1792 616 697 224 141 616 1160 1120 15-62 with double hopper 1792 616 697 324 241 616 1260 1220 18-72 with double hopper 1792 616 697 324 241 616 1260 1220
If the measurement from the flue centre line to the rear wall is increased (shown as 134 in the plan view), then the dimensions D, E & G will have to be increased by the same increment. All units in millimeters
Technical Data
12
2 Technical Data
2.4.3 Double Boiler with Central Hopper
Figure 2-3: Boiler and hopper dimensions and clearances – double boiler with central hopper






 
 


 
 
 
 


 
 
  

 
 
 
 
 
 
 



Pellet Specification,
Storage & Delivery
13
3 Pellet Specification, Storage & Delivery
3.1 Pellet Specification
Grant SPIRA boilers are designed to run on EN Plus A1 wood pellets that comply with EN 14961 and meet the following of criteria:
The following terms are commonly used when describing the properties of wood pellets:
Additives Additives are used to improve the stability of the pellets. If manufactured correctly, and of a sufficiently low
moisture content, quality pellets will require no additives.
Ash Ash represents the non-combustible content of the pellet. Higher ash content reduces the calorific value of
the pellet and requires the appliance to be cleaned more frequently.
Average Length To provide a predictable flow of fuel into the burner, the recommended length of a pellet is deemed greater
than 5mm and less than 5 times the diameter.
Bulk Density Bulk density is the ratio between the weight of the pellet and the amount of space they take up. A good
quality pellet will have a density of 650 kg/m3.
Chlorine High levels of chlorine in the flue gases emissions can give rise to corrosion.
Diameter The most common diameter is 6mm with some 8mm also available. This boiler is designed for 6mm only.
Fines Pellets are made from compressed wood. As pellets rub together they can break down slightly, producing
dust or fines. Too many fines indicate a poor quality pellet and can impede pellet flow in addition to causing dust problems when delivering and storing the pellets.
Mechanical Durability This is a measure of how stable the pellet is and how likely it is to produce fines from normal handling.
A high durability percentage is an indicator of a good quality pellet.
Moisture Content Moisture affects the calorific value of the pellet. Low moisture content guarantees constant and predictable
combustion efficiency. Higher moisture contents can result in pellet breakdown.
Net Calorific Value This is the useful energy contained in a kilogram of fuel. This value is affected by the amount of non-
combustible materials (ash) and the moisture content of the pellet. Typical values range from 4.8 kWh/kg to 5.2 kWh/kg.
Nitrogen High levels of nitrogen in the flue gases emissions can give rise to corrosion.
Sulphur High levels of sulphur in the flue gases emissions can give rise to corrosion.
Key Parameter Limits Category as per
EN 14961
Diameter 6mm
Average length L<5 x diameter D06,
Minimum and maximum length 3.15 to 40mm
Moisture Content <10% S0.05
Mechanical durability >97.5% DU 97.5
Amount of fines <1.0% F1.0
Additives None
Nitrogen <0.3% N0.3
Nett calorific value 4.8 to 5.2 kWh/kg
Bulk density 650 kg/m
3
Chlorine <0.03% CL 0.03
Pellet Specification,
Storage & Delivery
14
3 Pellet Specification, Storage & Delivery
3.2 Pellet Storage
3.2.1 Pellet Hoppers & Pellet Feed Auger
All Grant SPIRA boilers are supplied with a pellet hopper. Refer to Section
1.4.4 for further details of the hoppers.
All Grant hoppers are supplied with either one or, on a double boiler hopper, two 1.2 m pellet feed augers, to deliver the pellets from the hopper to the boiler. Refer to Section 1.4.5.
The pellet hopper, along with the boiler (or boilers) it is supplying, MUST be installed in a dry indoor environment free from dampness. The hopper and boiler(s) must be located on the same floor level.
If a bulk hopper is to be used, there are two methods of transferring the pellets from the bulk store to the intermediate hopper:
a) Via a bulk pellet feed auger
b) Via the Grant SPIRA-VAC vacuum
pellet feed system
All boiler pellet hoppers are supplied to accept either of these two pellet supply systems, as required. Refer to Section
1.4.4 for further details on the hoppers.
The electrical connections to the boiler(s) are all made to the 4-way electrical plug on one of the three factory-fitted ‘flying leads’ at the rear of the hopper. Refer to Section 7 for details.
Electrical connection for either a bulk auger or Grant SPIRA-VAC system, if required, is made using the 6-way electrical plug and flying lead supplied factory-fitted on the hopper.
3.2.2 Bulk Hopper
It is advisable to fit a bulk pellet store to take advantage of the lower cost of pellets purchased in bulk.
The pellet hopper must still be used, situated between the bulk hopper and the boiler, as the auger fitted to the hopper delivers the precise quantity of pellets required by the burner.
The pellet hopper also allows any problems with bulk pellet quality to be isolated and the intermediate hopper can be used temporarily as the source of pellets for the boiler.
It is essential to only use a bulk storage unit that is:
a) Waterproof
b) Specifically designed to store wood
pellets
c) Supplied with appropriate
connections for pellet delivery, which are within the drivers reach
d) Fitted with a vent connection (for
dust extraction) during filling
e) Permanently vented (if located
outside) or unvented (if installed indoors)
f) Fitted with a rubber arrester mat
(or similar) to limit pellet damage during filling
g) Is electrically earthed
A range of suitable bulk pellet stores are available from Grant UK. These are supplied flat packed for on-site assembly. Refer to assemble instructions supplied with each kit. For details of capacities and dimensions contact Grant UK.
The use of a self constructed wood pellet storage facility should be pre­approved by the fuel supplier before any pellets are delivered and must meet relevant building and fire regulations.
The ONORM M7137 standard should be used as a guideline for DIY bulk storage units.
A storage unit should not be positioned where it would result in a fire risk.
The store should be located on a suitable base (e.g. concrete) capable of supporting the weight of the store when full of pellets.
Figure 3-1: Bulk auger inlet in hopper
Pellet Specification,
Storage & Delivery
15
To determine the length of auger required the following factors must be determined
a) Difference in height between the
ground/floor level (on which the store will stand) and the floor level (on which the hopper will stand).
b) Horizontal distance between the
back of the hopper and the store.
If the store is to be situated outside this will be
a) the distance from the rear of the
hopper to the inner face of the wall
b) the thickness of the wall
c) the distance to the store from the
outside face of the wall.
Refer to Figure 3-3 for further details.
Using the following table select the required length of auger based on the above dimensions. Always select the next size up of auger.
3.2.3 Bulk Pellet Feed Auger
When installing a bulk pellet store with a bulk pellet feed auger, consideration must be given to the position of the store in relation to the hopper as this will dictate the length of the auger.
The length of the pellet feed auger, supplying pellets from the bulk store, is limited to a maximum of 6 metres in length, as a longer auger can damage the pellets.
Grant UK offer a range of eight bulk pellet augers, from 2.5m to 6m in length in 0.5m steps, as given in the table below:
!
NOTE
Each bulk pellet supplier has clear guidelines on the requirements of a bulk storage hopper used to store their pellets, together with requirements on positioning, access, and minimum deliveries.
ALWAYS check with the pellet supplier you wish to use BEFORE installing a bulk storage system.
Figure 3-2: Bulk hopper feeding intermediate hopper
Figure 3-3: Bulk store and auger
dimensions
Product Bulk Auger Auger Code Length m Weight kg
WPAUG25 2.5m 21.3
WPAUG30 3.0m 24.1
WPAUG35 3.5m 26.9
WPAUG40 4.0m 29.7
WPAUG45 4.5m 32.5
WPAUG50 5.0m 35.3
WPAUG55 5.5m 38.1
WPAUG60 6.0m 40.9
New dimensioned diagram of store & hopper here showing key dimensions
New table of store and bulk auger dimensions here
Boiler Installation
Information
16
4 Boiler Installation Information
4.1 Introduction
For the 6-26 and 9-36 models, the appliance comes supplied on two pallets
a) Pallet 1 contains the intermediate
hopper and auger
b) Pallet 2 contains the boiler, burner,
and combined fan box & flue starter.
For the 12-52, 15-62 and 18-72 models (‘double boiler’ installations), the appliance comes supplied on two pallets
a) Pallet 1 contains the intermediate
hopper and augers
b) Pallet 2 contains both boilers, each
with burner and combined fan box & flue starter.
An accessories box is packed with each boiler and this contains the following:
a) fan box (which comes complete
with exhaust fan and draught stabiliser),
b) condensate drain trap items
c) wash pipe manifold assembly
d) auger feed tube
Check the packing list (supplied in the accessories carton) to ensure all items have been delivered.
The Grant ’Black’ flue system comes separately and its configuration will depend on the installation requirements.
4.2 Boiler Location
The boiler must be installed in a damp free environment.
Refer to Section 2.4 for boiler and hopper clearances. These clearances are to allow for access during servicing. Also if fitting a bulk hopper system refer to Section 3.2.2 as the location of the bulk hopper can influence the boiler location.
4.3 Preparation for Installation
With the units on the pallet, remove all outer packaging from the units. Unpack the accessories box supplied with the boiler and check the packing list against all items present.
4.4 Installing the Boiler
The boiler and hopper must be positioned on a level, solid, non­combustible base of at least 125mm thick. This must also extend past the boiler and hopper by 225mm at the front and 150mm on the remaining sides. The boiler position must comply with clearances shown in Section 2.4.
4.5 Regulations
Installation of a Grant SPIRA wood pellet boiler and hopper must be in accordance the following recommendations:
National Building Regulations and any local Byelaws which you must check with the local authority for the area.
Model and local Water Undertaking Byelaws.
The installation should also be in accordance with the latest edition of the following standards and codes of Practice;
BS 715:2005 Metal flue pipes, fittings, terminals and accessories.
BS EN 12828:2003. Heating systems in buildings. Design for water-based heating systems
BS EN 12831:2003. Heating systems in buildings. Method for calculation of the design heat load.
BS EN 14336: 2004. Heating systems in buildings. Installation and commissioning of water based heating systems.
BS 7593:2006 Code of Practice for treatment of water in heating systems.
BS 7671:2008 Requirements for electrical installations, IEE wiring regulations.
ONORM M7137 standard should be used as a guideline for DIY bulk storage units.
4.6 Heating System Design Considerations
To achieve the maximum efficiency possible from the Grant SPIRA wood pellet boiler, the heating system should be designed to the following parameters:
Radiators
Flow temperature 70°C
Return temperature 50°C
Differential 20°C
Size the radiators using a mean water temperature of 60°C.
Design system controls with programmable room thermostats, or use weather compensating controls, to maintain return temperatures below 55°C.
The use of a pipe thermostat is recommended to control the return water temperature when using weather compensating controls.
Underfloor Heating
Flow temperature 50°C
Return temperature 40°C
Differential 10°C
In underfloor systems it is essential that the return temperature must be maintained at or above 40°C to prevent internal corrosion of the boiler water jacket.
4.7 Pipework Materials
Grant SPIRA boilers are compatible with both copper and plastic pipe. Where Plastic pipe is used it must be of the oxygen barrier type and be the correct class (to BS 7291: Part 1:2001) for the application concerned.
!
NOTE
Failure to install and commission the appliance correctly will invalidate the boiler warranty.
!
NOTE
The boiler should not be allowed to operate with a return temperature of less than 40°C when the system is up to operating temperature.
Before starting any work on the boiler or fuel supply please read the Health & Safety information given in Section 13.
!
WARNING
Boiler Installation
Information
17
Sealed Systems
If plastic pipe is to be used, the installer must check with the plastic pipe manufacturer that the pipe to be used is suitable for the temperature and pressures concerned.
Plastic pipe must be Class S to BS 7291:Part1:2001.
Underfloor Pipework
Plastic pipe may be used on underfloor floor systems where the plastic pipe is fitted after the thermostatic mixing valve.
Copper tube must be used for at least the first metre of flow and return primary pipework between the boiler and the underfloor mixing/blending valves.
4.8 Pipe Connections
Flow and return connections:
The flow and return connection are at the rear of the boiler (see Section 2.4) and the sizes are as follows;
SPIRA 6-26 Flow 1” BSP Female
Return 1” BSP Female
SPIRA 9-36 Flow 1” ¼ BSP Female
Return 1” ¼ BSP Female
Drain Cock:
Fit the ½” drain cock to the bottom rear ½” BSP connection. Fit the air vent assembly into the ½” connection on the rear of the boiler (this is to vent the secondary unit only), the flow pipe from the boiler must be vented.
Condensate Connection:
The1¼” BSP female condensate outlet connection is located at the rear of the boiler. Refer to Section 5 for details on condensate connection and disposal pipework.
4.9 Wash System Manifold
The boiler is supplied with a cleaning manifold system to wash the condensing unit of any ash build up in the tubes.
The wash system manifold pipe is factory fitted through the right hand side of the boiler. This manifold pipe can be fitted in either one of two different positions, depending on the location of the pellet hopper, as follows:
With hopper located on the left side of the boiler - the wash system
manifold if fitted from the right-hand side of the boiler, through the holes provided in the right hand side panel of the boiler and both sides of the heat exchanger chamber.
With hopper located on the right side of the boiler - the wash system
manifold if fitted from the left-hand side of the boiler. A semi-pierced hole (provided in the left hand side panel of the boiler) must be pushed out to allow the manifold to be fitted from this side.
With hopper located between two boilers (in a ‘double boiler’ installation)
- the right hand boiler will have the
wash system manifold fitted from the right hand side and the left hand boiler will have the wash manifold fitted from the left hand side.
In all cases, ensure adequate clearance (minimum 400mm) is present for removal of the wash system during servicing. Refer to Section 2.4 for clearance dimensions.
The remainder of the washdown cleaning system consists of the pressure gauge and solenoid valve assembly, flexible hose, isolating valve (with integral check valve).
Fit the gauge/valve assembly to the end of the manifold pipe using the 22mm compression elbow.
Connect the mains water supply to the 15mm compression connection on the isolating/check valve inlet. Fit the flexible hose between the outlet of the isolating/check valve outlet and the inlet to the solenoid valve and leave in place.
4.10 Fan Box and Flue Starter
Fit the fan box to the flanged flue outlet on the back of the boiler so that the flue starter outlet is at the top.
Remove the nuts and washers from the four studs around the fan box inlet. With the neoprene gasket in place on the fan box, locate the four studs through the corresponding holes in the boiler flue outlet flange. Secure the fan box using the nuts and washers previously removed.
Ensure that the fan box is vertical and the neoprene gasket is evenly compressed to give an adequate seal between the fan box and the boiler flange.
Fit the solenoid head (fitted to the same 5-way plug as the lead from the flue fan motor) on to the solenoid valve shaft and secure with the steel clip provided.
Fit the 5-way plug from the flue fan /solenoid valve into the socket at the top right rear of the boiler. Ensure that the plug is fully pushed home. See Figure 4-1.
On either sealed or open-vented systems; where plastic pipe is used a minimum of ONE metre of copper pipe MUST be connected between both the boiler flow and return connections and the plastic pipe. DO NOT CONNECT PLASTIC PIPE DIRECTLY TO THE BOILER.
Grant UK do not accept any responsibility for any damage, however caused, to plastic piping or fittings.
!
WARNING
The system MUST incorporate a low­level pressure switch to shut off power to the boiler if the system pressure drops below 0.2 bar. A suitable low pressure switch kit is available to purchase from Grant UK – Part No. MPCBS62.
Refer to Figure 8.11 for the electrical connection details on this switch.
!
WARNING
!
NOTE
A minimum running (dynamic) pressure of 0.8 to 1.0 bar pressure (as shown on the gauge when the system is operating) is required to maintain an adequate supply for cleaning purposes.
!
NOTE
In hard water areas an anti-scale device should be fitted on the cold water supply to the wash system to prevent scale build-up in the manifold pipe and jets.
Boiler Installation
Information
18
4 Boiler Installation Information
Figure 4-1: Flue fan/solenoid valve plug
connection
Figure 4-2: Pellet feed auger fixing Figure 4-3: Auger plug connection
4.11 Pellet Hoppers
4.11.1 Single Boiler Installation
Position the pellet hopper on the same firm level surface as the boiler, on either the left-hand or right-hand side of the boiler (depending on hopper type used), with the top access door facing forwards. Refer to Figure 2-1 or 2-2 as required, for clearance dimensions.
4.11.2 Double boiler installation
Position the pellet hopper on the same firm level surface as, and in between, the two boilers, with the top access door facing forwards. Refer to Figure 2-3 for clearance dimensions.
Failure to adhere to these measurements can cause blockage of the pellets in the pellet delivery hose or can prevent access for servicing at a later date. The hopper is supplied with castors which allows the hopper be moved during servicing. Once in the correct position, engage the brakes on the front casters to maintain this position.
4.12 Pellet Feed Auger
4.12.1 Single Boiler Hoppers
The pellet feed auger is supplied packed with the hopper but not factory­fitted to it.
To fit, unpack the hopper and auger. Remove the M5 screw fitted below the auger opening on the front of the hopper. Fit the end of the auger into opening in the front of the hopper as far as it will go and secure by fitting the M5 screw through the auger fixing flange and tighten. See Figure 4-2.
4.12.2 Double Boiler Hoppers
Both augers on the ‘double boiler’ Intermediate hoppers are supplied factory-fitted to the hopper.
To connect the hopper to the boiler, fit one end of the pellet delivery hose onto the pellet feed auger outlet and the other end onto the burner feed tube. The pellet delivery hose may need to be cut if too long. A sachet of lubricant is supplied in the accessories carton; apply the lubricant to the joint to ensure the pellet delivery hose is easily fitted. Ensure the pellet delivery hose is not kinked in any way.
Fit the 6-way plug (No.3), from the pellet feed auger motor, into the corresponding 6-way socket on the left side of the burner. Ensure that the plug is fully pushed home until the small catch it clicks into place. See Figure 4-3. Refer to Section 8.3 for all boiler plug connections.
Auger Fixing Flange
Ensure the pellet delivery hose forms an air tight seal at each end and that the pellet delivery hose is not damaged. Leakage of air could cause increased temperature in the pellet delivery hose and result in the pellet feed tube (burn back) thermostat operating and shutting down the burner.
!
WARNING
Boiler Installation
Information
19
4.13 Before you Commission
To avoid the danger of dirt and foreign matter entering the boiler the complete heating system should be thoroughly flushed out – both before the boiler is connected and then again after the system has been heated and is still hot.
This is especially important where the boiler is to be installed on an old system.
For optimum performance after installation, the boiler and the associated heating system must be flushed in accordance with the guidelines given in BS 7593:1992 'Treatment of water in domestic hot water central heating systems'. This must involve the use of a proprietary cleaner, such as Betz Dearborn's Sentinel x300 or x400, or Fernox Restorer. Full instructions are supplied with the products butfor more details visit either www.sentinel-solutions.net for Betz Dearborn products or www.fernox.com for Fernox products.
After flushing the system, an inhibitor such as Sentinel X100 or Fernox MB-1 should be used in accordance with the guidelines given in BS 7593:1992 for long term protection against corrosion and scale,
Grant UK strongly recommend that a magnetic in-line filter is fitted in the heating system pipework. A magnetic in-line filter must be fitted in the heating system pipework. This
should be installed and serviced in accordance with the filter manufacturer’s instructions.
4.14 Completion
Please ensure that the Grant SPIRA Commissioning form (supplied with the boiler) is completed in full and that it is signed by the householder/user.
Leave the White copy with the user, retain the Pink copy for your own records, and return the Yellow copy to Grant UK to register the installation of the boiler.
Ensure that the User Information pack (supplied with the boiler) is handed over to the householder along with this Installation and Servicing manual.
Condensate
Disposal
20
5 Condensate Disposal
5.1 General Requirements
When in condensing mode the Grant SPIRA condensing wood pellet boilers produce condensate from the water vapour in the flue gases. This condensate is slightly acidic with a ph value of around 6. Provision must be made for the safe and effective disposal of this condensate.
Condensate can be disposed using one of the following methods:
a) Into a soil stack – either directly or
via an existing waste system.
b) Into an external gulley.
c) Into a purpose made soakaway.
All condensate disposal pipes must be fitted with a trap whether they are
connected internally or externally to a domestic waste system/soil stack or run externally to a gully, hopper or soakaway. Every Grant SPIRA boiler is supplied with a trap and this MUST be used. Refer to Section 5.6 for trap details.
5.2 Connections
Connections into a rainwater hopper, external drain or gulley should be terminated inside the hopper/drain/ gulley below the grid level but above the water level.
Condensate disposal pipes must not be connected directly into rainwater downpipes or to waste/soil systems connected to septic tanks.
Condensate must not be discharged into ‘grey water’ systems that re-use water used in the home (not including water from toilets).
It should be noted that connection of a condensate pipe to the drain may be subject to local Building Control.
5.3 Pipework
Condensate disposal pipework must be plastic. Copper or steel pipe is not
suitable and must NOT be used.
All condensate disposal pipes connected to a Grant SPIRA boiler must have a minimum ‘nominal’ diameter of 38mm (1 ½”) plastic pipe.
Condensate disposal pipes should be kept as short as possible and the number of bends kept to a minimum.
Pipes should be adequately fixed to prevent sagging, i.e. at no more than
0.5 metre intervals.
Condensate disposal pipes must be fitted with a fall (away from the boiler) of at least 2.5° (~45mm fall per metre run).
5.4 External Pipework
Ideally, external pipework, or pipework in unheated areas, should be avoided. If unavoidable, external pipework should be kept as short as possible (less than 3 metres) and 38mm (1½”) waste pipe used to minimise the risk of ice blocking the pipe in freezing conditions.
The number of bends, fitting and joints on external pipes should be kept to a minimum to reduce the risk of trapping condensate.
5.5 Condensate Soakaway
To keep external pipework to a minimum, locate the soak away as close as possible to the boiler but ensure it is at least 1 metre from building foundations and away from other services, for example gas, electricity or other services.
The condensate pipe may be run above or below ground level and can enter either the top or side of the soakaway tube. Refer to Figure 5.1.
Ensure that the drainage holes in the soakaway tube face away from the building.
Backfill the soakaway tube, and the hole around it, with 10mm limestone chippings.
Only use a soakaway where the soil is porous and drains easily.
When using a condensate pump and holding tank, the burner settings for ‘TIME CLEAN PERIOD’ (time boiler cleaning is in operation) must not be set greater than 600 (60 seconds) and the ‘TIME CLEAN BOILER’ (time between boiler cleaning operations) must not be set less than 180 minutes, as modifying these times could result in larger and more frequent wash down of the boiler which could exceed the capabilities of the tank and condensate pump. Refer to Section 8 for further details of the burner settings.
!
WARNING
!
NOTE
Where it is not possible for the pipe to fall towards the point of discharge –either internally into a waste system or externally to a gulley (e.g. for boilers installed in a basement), it will be necessary to use a condensate pump.
When using a condensate pump with a Grant SPIRA boiler, a condensate holding tank of at least 40 litres is required. This is to ensure that when the boiler cleaning cycle has operated the holding tank can collect the total volume of the water used in the wash down and the condensate pump can then discharge the waste water effectively.
A boiler interlock should be fitted to shut off the boiler in the event of a malfunction of the condensate pump.
!
NOTE
For a boiler installed in an unheated area such as an outhouse or garage, all condensate pipework should be considered as an ‘external’.
Condensate
Disposal
21
5.6 Condensate Trap
Grant SPIRA condensing boilers are supplied with condensate trap. This trap must be used. No alternative trap should be used in place of the trap supplied with the boiler. The 1¼” BSP female condensate outlet connection is located at the rear of the boiler.
Fit the 1¼” 311 fitting (supplied) into this connection. Using the elbow and pipe (supplied), connect the trap to the condensate outlet on the boiler, as shown in Figure. 5-2.
A condensate discharge pipe with a minimum diameter of 38mm (1½”) must be fitted to the outlet connection at the base of the trap.
In all cases the overflow pipe (see Figure 5-2) must be fitted to the trap and the end left open. This will protect the boiler from becoming blocked with condensate in the event of the condensate discharge pipe blocking or frozen.
If connecting the condensate discharge into a waste system or soil stack, either internally or externally, a second trap must be fitted in the condensate discharge pipe. This trap
must provide the required 75mm water seal. It must be located between the boiler condense trap and the connection to the soil stack, in a position accessible for checking and cleaning.
5.7 Inspection and Cleaning
of Trap
The boiler condensate trap (and any second trap fitted) must be checked at regular intervals (e.g. on every annual service) and cleaned as necessary to ensure it is clear and able to operate.
Figure 5-1: Purpose made condensate soakaway
Figure 5-1: ????
All condensate pipework must be adequately protected against freezing, however if the condensate pipe is frozen, water will build up and discharge through the overflow on the trap.
!
CAUTION
Failure to regularly check and clean the condensate trap (or traps) may result in damage to the boiler and this will not be covered by the product warranty.
!
CAUTION
32mm waste pipe externasl to the building
Cement seal
Ground level
100mm plastic tube
Sealed end
Backfill with 10mm limestone chippings
Four rows of 3x12mm holes at 25mm centres and 50mm from bottom of the tube. Holes facing away from the property
25
2.5˚ fall
400
Sealed Systems
22
6 Sealed Systems
6.1 Sealed System Requirements
All Grant Spira boilers are suitable for use with sealed systems complying with the requirements of BS5449.
The system must be provided with the following items:-
Diaphragm expansion vessel complying with BS 4814.
Pressure gauge.
Pressure relief (safety) valve.
Approved method for filling the system.
Expansion vessel
The expansion vessel can be fitted in either the return or flow pipework in any of the recommended positions as shown in Figure 6-1. To reduce the operating temperature of the expansion vessel diaphragm, position it below the pipe to which it is connected.
The expansion vessel may be positioned away from the system, providing the connecting pipe is not less than 13 mm diameter. If the expansion vessel is connected via a flexible hose, care must be taken to ensure that the hose is not twisted.
The pressure gauge must have an operating range of 0 to 4 bar.
It must be located in an accessible place next to the filling loop for the system
Safety Valve
The safety valve (provided with the boiler) is set to operate at 2.5bar. It should be fitted in the flow pipework near to the boiler.
The pipework between the safety valve and boiler must be unrestricted, i.e. no valves. The safety valve should be connected to a discharge pipe which will allow the discharge to be seen, but cannot cause injury to persons or property.
Filling Loop
Provision should be made to replace water lost from the system. This can be done manually (where allowed by the local water undertaking) using an approved filling loop arrangement incorporating a double check valve assembly.
The filling loop must be isolated and disconnected after filling the system.
Heating System
The maximum temperature of the central heating water is 75°C. Refer to Section 1.1.
An automatic air vent should be fitted to the highest point of the system.
If thermostatic radiator valves are fitted to all radiators, a system by-pass must be fitted. The by-pass must be an automatic type.
All fittings used in the system must be able to withstand pressures up to 3 bar. Radiator valves must comply with the requirements of BS 2767(10):1972.
One or more drain taps (to BS 2879) must be used to allow the system to be completely drained.
6.2 Filling the Sealed System
Filling of the system must be carried out in a manner approved by the local Water Undertaking.
Figure 6-1: Sealed heating system components
Figure 6-2: Heating system Pressure Gauge
Only ever fill or add water to the system when it is cold and the boiler is off. Do not overfill.
!
WARNING
!
NOTE
Ensure that the expansion vessel used is of sufficient size for the system volume. Refer to BS 7074:1:1989 or The domestic Heating design Guide for sizing the required vessel.
Sealed Systems
23
The procedure for filling the sealed system is as follows:
1. Check the air charge pressure in the expansion vessel BEFORE filling the system.
The expansion vessel charge pressure should always be slightly greater than the maximum static head of the system, in bar, at the level of the vessel (1 bar = 10.2 metres of water). See Figure 6-2.
The charge pressure must not be less than the actual static head at the point of connection.
2. Check that the small cap (or screw) on all automatic air vents (including the one fitted at the left rear of the boiler) is open at least one turn. The cap (or screw) remains in this position from now on.
3. Ensure that the flexible filling loop is connected and that the double check shut off valve connecting it to the water supply is closed. A valve is open when the operating lever is in line with the valve, and closed when it is at right angles to it.
3. Open the fill point valve.
4. Gradually open the double check valve from the water supply until water is heard to flow.
5. When the needle of the pressure gauge is between 0.5 and 1.0 bar, close the valve.
6. Vent each radiator in turn, starting with the lowest one in the system, to remove air.
7. Continue to fill the system until the pressure gauge indicates between
0.5 and 1.0 bar. Close the fill point valve. The system fill pressure (cold) should be 0.2 - 0.3 bar greater than the vessel charge pressure – giving typical system fill pressures of approx 0.5 bar for a bungalow
and 1.0 bar for a two storey house. Refer to the Domestic Heating Design Guide for further information if required.
8. Repeat steps 5 and 6 as required until system is full of water at the correct pressure and vented.
9. Water may be released from the system by manually operating the safety valve until the system design pressure is obtained.
10. Close the fill point and double check valves either side of the filling loop and disconnect the loop.
11. Check the system for water soundness, rectifying where necessary.
6.3 Venting the Pump
It is important that the pump is properly vented to avoid an air lock and also prevent it running dry and damaging the bearings.
Unscrew and remove the plug from the centre of the pump motor.
Using a suitable screwdriver, rotate the pump spindle about one turn.
Replace the plug in the motor. Do not overtighten.
6.4 Pressure Relief (Safety) Valve Operation
Check the operation of the pressure relief (safety) valve as follows:
1. Turning the head of the valve anticlockwise until it clicks. The click is the safety valve head lifting off its seat allowing water to escape from the system.
2. Check that the water is escaping from the system.
3. Top-up the system pressure, as necessary.
!
NOTE
The expansion vessel air pressure, system pressure and operation of the pressure relief valve must be checked on an annual service. Refer to Section 11.
!
NOTE
The air charge pressure may be checked using a tyre pressure gauge on the expansion vessel Schraeder valve. The vessel may be re­pressurised, when necessary, using a suitable pump. When checking the air pressure, the water in the heating system must be cold and the system pressure reduced to zero.
Flue System and
Air Supply
24
7 Flue System and Air Supply
7.1 Air Supply
The Grant SPIRA wood pellet boiler draws air for combustion from the room in which it is located.
Any such room or space containing an appliance must have sufficient permanent air supply to the boiler
a. To ensure correct combustion of
the fuel and effective operation of the flue system (i.e. to discharge of combustion products to the open air).
b. To supply enough free air to the
draught stabiliser.
The ventilation area provided must be in accordance with the requirements of The Building Regulations Approved Document J – Section 2: Appliances burning solid fuel.
For a boiler with a draught stabiliser, a permanent air vent with a total free area of at least 850mm
2
per kW of appliance rated output is required. To achieve this, the following minimum vent opening areas are required:
If a bulk pellet store is fitted internally, refer to the manufacturer’s instructions for any ventilation requirements.
7.2 Flue Position and Clearances
The Grant Spira wood pellet boilers have high operating efficiencies and low flue gas temperatures. Only the Grant
‘BLACK’ insulated twin-wall flue system must used with the Grant SPIRA boilers.
The flue terminal should be located
in a downdraught free area, i.e. above the roof, where it can discharge freely and not present a fire hazard whatever the wind conditions.
The flue outlet positions shown in Figure 7-1 (taken from Approved Document J – Section 2) can meet the above requirement.
The heights and separation distances shown in Figure 7-1 may have to be increased in particular cases, e.g. where high wind exposure, surrounding tall buildings, or adjacent trees can cause adverse wind effects.
The boiler flue cannot terminate into an existing brick or clay lined chimney. All masonry flues must be lined using the Grant Black system stainless steel flexible flue liner.
No other appliance can be connected to the boiler flue.
The minimum clearance between the outer flue surface and any combustible material is 60mm.
Any condensate in the flue can run back into the boiler. A condensate drain at the base of the flue system is not required.
The above clearances are as specified in Building Regulations Approved Document J. Also refer to Approved Document J of either the England and Wales or Irish building regulations for further requirements on the installation of flue systems for solid fuel appliances.
Minimum Vent
Boiler Model Open Area
Grant SPIRA 6-26 221cm² (35in²)
Grant SPIRA 9-36 306cm² (48in²)
Grant SPIRA 12-52 442cm² (70in²)
Grant SPIRA 15-62 527cm² (83in²)
Grant SPIRA 18-72 612cm² (96in²)
Point where flue passes through weather surface (Note 1,2) Clearance to flue outlet
A At or within 600mm of the ridge At least 600mm above the ridge
B Elsewhere on a roof (whether At least 2300mm horizontally from the
pitched or flat) nearest point on the weather surface and;
a; at least 1000mm above the highest point of intersection of the chimney and the weather surface; or b; at least as high as the ridge
C Below (on a pitched roof) or At least 1000mm above the top of the
within 2300mm horizontally to opening an openable rooflight, dormer window or other opening (Note 3)
D Within 2300mm of an adjoining At least 600mm above the adjacent
building, whether or not beyond building the boundary (Note 3)
Notes
1) The weather surface is the building external surface, such as its roof, tiles or external walls.
2) A flat roof has a pitch less than 10°.
3) The clearance given for A or B, as appropriate, will also apply.
A
B
C
D
Figure 7-1: Flue terminal positions
Flue System and
Air Supply
25
7.3 Flue System Assembly
7.3.1 Fan Box & Flue Starter
The fan box supplied with the boiler (packed in the accessories carton) incorporates:
Flue exhaust fan
Draught stabiliser
Flue starter connection (to fit Grant ‘Black’ flue system)
Clean out hatch
The fan box is supplied with a neoprene gasket for connection to the boiler. This neoprene gasket is to accommodate the low temperature wet flue system of the Grant SPIRA boilers. Refer to Section 4.15 for fitting details.
The lead for the flue fan (supplied factory-fitted to the fan box) is connected to the same 5-way plug as the lead for the wash system solenoid valve. Refer to Section 4.15 for connection details.
When fitting the flue system to the flue starter connection, on the fan box, the lip seal supplied with the flue component must be fitted to the inner flue liner, and the locking band fitted to secure the joint.
When installed, the draught stabiliser must not be boxed in or obstructed from operation in any way.
The clean out hatch allows access to the inside of the fan box for inspection and, where necessary, removal of any ash that may have dropped down inside the flue system. The clean-out hatch MUST be correctly fitted during normal boiler operation. See Section 10
-Servicing.
A condensate drain at the base of the flue is not required as the flue system is designed to allow the condensate to run back into the boiler.
7.3.2 Flue System
The Grant ‘Black’ flue system is a fully insulated stainless steel twin-wall flue ­finished with a Black Polyester Powder paint finish. This insulated flue system reduces the possibility of the condensate freezing in the flue, and also has a high corrosion resistance suitable for solid fuel.
The 125mm (5in) ‘Black’ twin-wall flue system is suitable for BOTH the SPIRA 6-26 & 9-36 models.
Masonry chimneys MUST be lined using the 125mm stainless steel flexible ‘smoothbore’ liner – available as part of the ‘Black’ system - due to the condensate produced from the boiler.
6.3.3 Joining Components
All the ‘Black’ system twin-wall flue components (with the exception of the elbows) use a ‘twist lock’ jointing system.
The ‘male collar’ end of the flue component MUST always be uppermost when fitted.
To join two components together:
First fit the lip seal supplied into the groove (in the inner flue liner) at the ‘female collar’ end of the flue component to be fitted.
All flue joints must have a lip seal gasket fitted. The lip seal should be fitted dry and the lubricating grease (supplied with the component) applied to the internal surface of the socket into which it is to be fitted.
Loosen the locking band at the ‘female collar’ end. Insert the ‘male collar’ into the ‘female collar’ and twist through 1/6 of a turn to lock in place. Refer to Figure 7-3.
!
NOTE
The Grant BLACK flue system is the ONLY flue system suitable for use with the Grant SPIRA Wood pellet boilers. The use of other flue systems will invalidate the product warranty on the boiler.
Figure 7-2: Male and female flue connections
Male collar
Insulation
Female collar
Stainless steel outer case
Stainless steel inner liner
Capillary break
Flue System and
Air Supply
26
Ensure that the two beaded ends of the flue components are in contact with each other all round. Position the locking band so that it grips the beaded edge of both components and fasten using the spring clip. The locking bands provided MUST be fitted at ALL flue joints. Refer to Figure 7-4.
To temporarily assemble the flue system components, to check component lengths, alignment of connections, etc. DO NOT fit the lip seals. However, for FINAL assembly the lip seals provided MUST be fitted at EVERY joint.
7.3.4 Adjustable Length
The Grant ‘Black’ flue system includes an Adjustable flue extension. Refer to Section 7.6. This allows any of the straight flue extension components to be extended in length by between 75mm to 250mm.
This adjustable extension must be used in conjunction with any straight extension (1000mm, 500mm or 333mm) to achieve the actual straight length required.
To fit the adjustable extension, first remove insulation from between the inner and outer walls of the component, as necessary. Fit the open end over the ‘male collar’ end of the fixed extension and adjust to achieve the required overall length. Secure the two components together using the wide locking band supplied.
7.3.5 Support Components
The weight of the flue system is considerable. It must NOT be carried by the fan box fitted to the appliance, but requires independent support.
Support Plate
On internal systems, the weight can often be supported where the flue passes through an upstairs floor, using the Support Plate with clamp band
(Grant ref. WP/SP). A four-sided square opening, formed by timber stringers between the joists, is required to support the plate. Ensure that the minimum distance of 60mm is achieved between the flue outer surface and the any combustibles (e.g. timber joists).
A Fire Stop plate (Grant ref. WP/FP) is also required to be fixed to the ceiling below.
When passing through a second upstairs floor (in a 3-storey house) either a second support plate can be fitted or only two fire-stop plates (one above and one below) need be fitted as the flue is adequately supported at the first upstairs floor level.
Intermediate Top Plate
Flue systems running up against either an Internal or external wall surface can be supported using the Intermediate Top Plate (Grant Ref. WP/TP). This is mounted on a pair of Wall Support Side Plates (Grant Ref. WP/WS), which are fastened to the wall, to provide support at either the base, or part way up, a vertical section of flue.
The ‘female collar’ (on the underside of the plate) is fitted into the flue below and the ‘male collar’ (on the upper side of the plate) is a twist-lock connection into the flue above. Both joints are secured using the clamp bands provided.
Wall and Roof Brackets
Both the Wall bracket (Grant ref. WP/WB50) and the Adjustable Wall Bracket (Grant ref. WP/WB300) are NOT load bearing and are designed to give lateral support only. Wall brackets should be fitted with a maximum spacing of 3m on straight runs of flue and at any offset to ensure the system is rigidly supported.
Similarly, the Roof Support Band (Grant ref. WP/RS) is not load bearing and is designed to give lateral support only.
Where the flue is free standing above the roof and its height exceeds 1.5m beyond the last support of the roof (e.g. Roof Support Band) a Guy Wire Bracket (Grant ref. WP/GB) MUST be used and at every 1.5m thereafter. Grant do not supply the guy wires or tie rods to use with this bracket.
To allow for alignment, the female collars of the elbows do NOT have the twist lock flutes, but the locking band MUST still be used to secure the two flue components together.
Figure 7-3: Twist lock joint between components
Figure 7-4: Fitting of locking band
7 Flue System and Air Supply
Locking band
All joints in the flue system must be accessible for inspection. No joints should be located within a wall, floor or ceiling spaces or any other inaccessible place.
!
WARNING
!
NOTE
The adjustable section is not load­bearing, therefore adequate support of the flue system MUST be provided immediately above the adjustable extension.
Loading...
+ 58 hidden pages