Boiler Installation
Information
16
4 Boiler Installation Information
4.1 Introduction
For the 6-26 and 9-36 models, the
appliance comes supplied on two
pallets
a) Pallet 1 contains the intermediate
hopper and auger
b) Pallet 2 contains the boiler, burner,
and combined fan box & flue
starter.
For the 12-52, 15-62 and 18-72
models (‘double boiler’ installations), the
appliance comes supplied on two
pallets
a) Pallet 1 contains the intermediate
hopper and augers
b) Pallet 2 contains both boilers, each
with burner and combined fan box
& flue starter.
An accessories box is packed with
each boiler and this contains the
following:
a) fan box (which comes complete
with exhaust fan and draught
stabiliser),
b) condensate drain trap items
c) wash pipe manifold assembly
d) auger feed tube
Check the packing list (supplied in the
accessories carton) to ensure all items
have been delivered.
The Grant ’Black’ flue system comes
separately and its configuration will
depend on the installation requirements.
4.2 Boiler Location
The boiler must be installed in a damp
free environment.
Refer to Section 2.4 for boiler and
hopper clearances. These clearances
are to allow for access during servicing.
Also if fitting a bulk hopper system refer
to Section 3.2.2 as the location of the
bulk hopper can influence the boiler
location.
4.3 Preparation for Installation
With the units on the pallet, remove all
outer packaging from the units. Unpack
the accessories box supplied with the
boiler and check the packing list
against all items present.
4.4 Installing the Boiler
The boiler and hopper must be
positioned on a level, solid, noncombustible base of at least 125mm
thick. This must also extend past the
boiler and hopper by 225mm at the
front and 150mm on the remaining
sides. The boiler position must comply
with clearances shown in Section 2.4.
4.5 Regulations
Installation of a Grant SPIRA wood
pellet boiler and hopper must be in
accordance the following
recommendations:
• National Building Regulations and
any local Byelaws which you must
check with the local authority for
the area.
• Model and local Water Undertaking
Byelaws.
The installation should also be in
accordance with the latest edition of the
following standards and codes of
Practice;
• BS 715:2005 Metal flue pipes,
fittings, terminals and accessories.
• BS EN 12828:2003. Heating
systems in buildings. Design for
water-based heating systems
• BS EN 12831:2003. Heating
systems in buildings. Method for
calculation of the design heat load.
• BS EN 14336: 2004. Heating
systems in buildings. Installation
and commissioning of water based
heating systems.
• BS 7593:2006 Code of Practice for
treatment of water in heating
systems.
• BS 7671:2008 Requirements for
electrical installations, IEE wiring
regulations.
• ONORM M7137 standard should
be used as a guideline for DIY bulk
storage units.
4.6 Heating System Design
Considerations
To achieve the maximum efficiency
possible from the Grant SPIRA wood
pellet boiler, the heating system should
be designed to the following
parameters:
Radiators
• Flow temperature 70°C
• Return temperature 50°C
• Differential 20°C
Size the radiators using a mean water
temperature of 60°C.
Design system controls with
programmable room thermostats, or
use weather compensating controls, to
maintain return temperatures below
55°C.
The use of a pipe thermostat is
recommended to control the return
water temperature when using weather
compensating controls.
Underfloor Heating
• Flow temperature 50°C
• Return temperature 40°C
• Differential 10°C
In underfloor systems it is essential that
the return temperature must be
maintained at or above 40°C to prevent
internal corrosion of the boiler water
jacket.
4.7 Pipework Materials
Grant SPIRA boilers are compatible
with both copper and plastic pipe.
Where Plastic pipe is used it must be of
the oxygen barrier type and be the
correct class (to BS 7291: Part 1:2001)
for the application concerned.
!
NOTE
Failure to install and commission the
appliance correctly will invalidate the
boiler warranty.
!
NOTE
The boiler should not be allowed to
operate with a return temperature of
less than 40°C when the system is
up to operating temperature.
Before starting any work on the
boiler or fuel supply please read the
Health & Safety information given in
Section 13.
!
WARNING