Grant Solo Compact, Solo CompactMAX, Solo Hideaway Installation And User Instructions Manual

Page 1
UK | DOC 0139 | Rev 1.0 | October 2018
Grant Solo
Fan Convectors
Installation and User Instructions
Page 2
Page 2
GRANT ENGINEERING (UK) LIMITED
Tel: +44 (0)1380 736920 Fax: +44 (0)1380 736991
Email: [email protected] www.grantuk.com
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. However, no responsibility of any kind for any injury, death, loss, damage or delay however caused resulting from the use of this manual can be accepted by Grant Engineering (UK) Limited, the author or others involved in its publication.
All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
© Grant Engineering (UK) Limited. No part of this manual may be reproduced by any means without prior written consent.
IMPORTANT NOTE FOR INSTALLERS
These instructions are intended to guide installers on the installation, commissioning and servicing of the Grant Solo fan convectors. After installion, leave these instructions with the user.
User instructions to guide users in the operation of the fan convectors are given in Section X of these instructions.
SPECIAL TEXT FORMATS
The following special text formats are used in these instructions for the purposes listed below:
! WARNING !
Warning of possible human injury as a consequence of not following the instructions in the warning.
! CAUTION !
Caution concerning likely damage to equipment or tools as a consequence of not following the instructions in the caution.
! NOTE !
Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader.
PRODUCT CODES AND SERIAL NUMBERS COVERED
The serial numbers used on Grant Solo fan convectors consist
of a twelve or thirteen digit code with the rst two or three digits being the product identier.
For example: G3H2818000027 These instructions cover the following product codes and serial
numbers:
Product code Serial number identier
SC03 - Solo Compact G3
SC06MAX - Solo CompactMAX G6
SCHW - Solo Hideaway G3H
Page 3
1 INTRODUCTION 4
1.1 General 4
1.2 Operating principles 4
1.3 Control panel overview 5
2 TECHNICAL DATA 6
2.1 Fan convector technical data 6
2.2 Performance data 6
3 INSTALLATION 7
3.1 Introduction 7
3.2 Regulations 7
3.3 Location 7
3.4 System requirements 7
3.5 Pipework materials 8
3.6 Pipe connections 8
3.7 Installation procedure: 8 Solo Compact and Solo CompactMAX models
3.8 Installation procedure: 9 Solo Hideaway model
4 ELECTRICAL 11
4.1 General 11
4.2 Electrical connections 11
Contents Page 3
5 COMMISSIONING 11
6 FAULT FINDING 12
6.1 Initial checks 12
6.2 Fault diagnosis ow chart 13
7 SPARES PARTS 14
7.1 Fan convector parts list 14
8 OPERATING INSTRUCTIONS 14
8.1 Mains ON/OFF switch 14
8.2 Control panel 15
9 CLEANING 15
10 DECLARATION OF CONFORMITY 16
11 HEALTH AND SAFETY INFORMATION 16
12 END OF LIFE INFORMATION 17
13 GUARANTEE 18
CONTENTS
Page 4
Section 1: IntroductionPage 4
1.1 GENERAL
The Grant Solo range consists of two wall-mounted fan convectors, the Grant Solo Compact and Grant Solo
CompactMAX, and the Grant Solo Hideaway model designed to t
under kitchen units or in other similar locations. For heating capacity details on all three models refer to Section 2
of these Instructions. Grant Solo fan convectors are supplied with a simple electronic
control panel. Refer to Section 10 for further details and operating instructions. Each fan convector is individually controlled to
provide a exible and responsive means of heating each space.
They are designed to be integrated into low temperature heating systems using air source heat pumps, condensing oil, gas and biomass boilers, etc.
Each Solo fan convector requires a 3A fused 230V 1ph 50Hz electrical supply. Refer to Section 5 for further details.
A double pole mains ON/OFF switch is factory tted to all Grant
Solo units. On the Solo Compact and CompactMAX models this is located
under the right-hand end of the front casing. On the Solo Hideaway model this switch is located on the right-hand side of the unit.
The steel chassis of the Solo Compact and Solo CompactMAX is
xed directly to the wall. No wall mounting brackets are required,
keeping the unit as close to the wall as possible.
With the Solo Hideaway unit, the steel chassis is xed directly to the plinth or similar when tting under kitchen units or other xed
units.
Figure 1-1: Solo Compact and CompactMAX wall hung fan convector
Figure 1-2: Solo Hideaway fan convector
1.2 OPERATING PRINCIPLES
The Grant Solo range of fan convectors use backward curved impellers and they are designed to ensure zero convection and therefore minimal heat emission when the fan is not running. This eliminates the need for any radiator control valves.
The heat exchanger does not touch the outer case but is insulated from it, providing a low casing surface temperature regardless of
the water ow temperature. The top grille prevents contact with
the heat exchanger. With the electrical supply to the Solo fan convector switched
on; when the water temperature sensor (located in the heat exchanger) detects that the water temperature entering the unit exceeds 29°C the unit will start.
The air temperature is then sampled over a 60 second period by the air temperature sensor located at the rear of the unit.
The user can then set the required room air temperature between 18 to 24°C via the control panel on the front of the unit. Refer to Section 10 - Operating Instructions for further details on setting the required air temperature.
The Grant Solo microprocessor control system predicts the air temperature at occupant level as low-level temperatures are always colder than at occupant level and would provide incorrect data on which to determine the level of heat output required.
If the difference between the sampled air temperature and the air temperature setting on the unit is greater than 1°C the heat output of the unit is increased with the fan running on the ‘High’ setting.
When the air temperature rises and the difference between the sampled air temperature and the air temperature setting on the unit is less than 1°C the heat output is decreased with the fan running on the ‘Low’ setting.
When the air temperature reaches the setpoint, the unit is switched off and enters a ‘sleep’ period for 8 minutes. After this the air temperature is then sampled over a 60 second period.
If there is no change and no heat output is required, the unit enters an 8 minute ‘sleep’ period again before sampling the air temperature for 60 seconds again, until a difference exists between the sampled air temperature and the air temperature setting on the unit.
The Grant Solo unit will then repeat the start-up sequence again.
1 INTRODUCTION
Control panel
Mains ON/OFF switch
located on underside of unit
Control panel
Mains ON/OFF switch located on
underside of unit (not shown)
Page 5
Section 1: Introduction Page 5
BOOST FUNCTION
The boost function is activated by pressing the Boost button on the control panel fascia. Refer to Section 10 - Operating Instructions.
The boost function overrides the normal temperature control and runs the fan at higher ‘Boost’ level for a period of 20 minutes to provide a greater heat output than the normal operation.
After this period has elapsed the Solo unit automatically returns to the normal temperature control with the fan operating at either ‘Low’ or ‘High’ setting as dictated by the difference between the air temperature and the air temperature setting on the unit.
1.3 CONTROL PANEL OVERVIEW
Grant Solo fan convectors are supplied with a simple control panel. Refer to Figure 1-3 and Section 8.2 (control panel).
Temperature indicator lights
ON/OFF
button
Alarm light
Special function
light
Boost / cool button
Figure 1-3: Solo fan convector control panel overview
Page 6
2.1 FAN CONVECTOR TECHNICAL DATA
Table 2-1: Fan convector technical data
Units Solo Compact Solo CompactMAX Solo Hideaway
Height mm 410 410 120
Width mm 610 985 700
Depth mm 110 110 418
Water content litres 0.15 0.30 0.15
Weight (empty) kg 8.2 13.8 6.6
Weight (full) kg 8.35 14.1 6.75
Flow and return pipe size mm 15 15 15
Maximum water temperature °C 85
Maximum water pressure bar 10
Electrical supply ~230 1ph 50Hz 3A fused
Power input
Low speed W 8 13 8
High speed W 10 19 10
Boost W 20 36 20
Standby power W 4 4 4
Sound pressure level at 1 metre (ISO 3744)
Low speed dB(A) 18 18 18
High speed dB(A) 22 23 22
Boost dB(A) 38 39 38
2.2 PERFORMANCE DATA
Table 2-2: Heating capacity (BS EN ISO 16430) on high/low fan speed
Mean water temperature*
Units
Solo Compact Solo CompactMAX Solo Hideaway
High Low High Low High Low
35°C W 314 247 604 470 314 247
40°C W 426 335 831 646 426 335
45°C W 542 426 1,071 832 542 426
50°C W 660 519 1,318 1,024 660 519
55°C W 780 613 1,570 1,220 780 613
60°C W 901 708 1,828 1,420 901 708
65°C W 1,023 803 2,090 1,623 1,023 803
70°C W 1,146 900 2,356 1,830 1,146 900
* Mean water temperature = (ow temperature + return temperature) ÷ 2
Section 2: Technical DataPage 6
2 TECHNICAL DATA
Page 7
Section 3: Installation Page 7
3.1 INTRODUCTION
Each Solo fan convector requires a 3A fused 230V 1ph 50Hz
electrical supply and is tted with a terminal block for easy and
quick electrical connection. Refer to Section 5 for further details. Please ensure that Solo fan convectors are protected from dirt,
rubble, etc. and it is suggested to wait for all other building and
decorating works to be completed before nally xing in the
required location.
3.2 REGULATIONS
The Installation of a Grant Solo fan convector must be in accordance with the following recommendations:
• Building Regulations for England and Wales or the Building Standards for Scotland, as appropriate.
• Any local Byelaws which you must check with the local authority for the area concerned.
• The Water Supply (Water Fittings) regulations 1999 or the water Supply (Fittings) (Scotland) Bylaws 2014, as appropriate.
• Applicable Control of Pollution Regulations.
The installation should also be in accordance with the latest edition of the following British Standard Code of Practice (and any relevant amendments):
• BS EN 12828 (Heating systems for buildings. Design for water-based heating systems).
• BS EN 14336 (Heating systems in buildings. Installation and commissioning of water-based heating systems).
• BS 7593 (Code of Practice for treatment of water in domestic hot water central heating systems).
• BS 7671 (Requirements for Electrical installations, IET Wiring Regulations).
• BS 7291 (Thermoplastic pipe and ttings systems for hot and
cold water for domestic purposes and heating installations in buildings. General requirements.
• BS 7074-1 (Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. Code of practice for domestic heating and hot water supply.
3.3 LOCATION
Solo Compact and CompactMAX fan convectors should be positioned with the lower edge approximately 75-100mm above the skirting level.
The Solo Hideaway fan convectors are tted into the plinth or baseboard of xed units, e.g. kitchen units. Refer to Section 3.7
for dimension of the opening required. The lower edge of this
opening must be at least 12mm above the nished oor level.
The outlet from all Solo fan convectors must be unrestricted, e.g. no shelves above the wall hung Solo Compact and CompactMAX units.
Ensure that heating system ow/return pipework is not run along
the wall or skirting directly below either the Solo Compact or Solo CompactMAX fan convectors. The warm air rising from the pipework will affect the operation of the air temperature sensor
tted at the rear of the fan convector and may result in reduced
heat output from it.
3.4 SYSTEM REQUIREMENTS
Grant Solo fan convectors can be used on either open vented or sealed central heating systems.
The pressure characteristics of the Grant Solo fan convectors
were designed to facilitate even ow sharing by ensuring that the pressure drop at various ow rates considerably exceeds the
pipework friction loss. Care must therefore be taken to ensure that adequate pumping
capacity exists to guarantee adequate ow through each fan
convector unit. A 6metre head pump is suggested. A maximum of approximately six to eight Solo units on a circuit,
with 22mm ow and return pipework with 15mm radiator tails, is
recommended. It is suggested that reverse return pipework be used where
possible. Refer to Figure 2-4.
Figure 3-1: Conventional ow/return piping
Figure 3-2: Reverse return piping
3 INSTALLATION
3 way valve
Hot water cylinder
EV
Flow
Return
3 way valve
Hot water cylinder
EV
Flow
Return
Page 8
Section 3: InstallationPage 8
OPERATION WITH RADIATORS
Grant Solo fan convectors are ultra-low water content heat emitters and should ideally not share heating circuits with
conventional radiators, as this may result in a reduced ow
through the fan convectors. If this cannot be avoided and the fan convectors must be added
to an existing radiator circuit the following requirements must be met:
a) The ow and return pipework must be 22mm minimum.
Smaller pipework will result in poor or no heat output from the fan convector(s).
b) When installed, rst shut off the conventional radiator(s) to
check that the fan convector(s) operate correctly.
Then, turn on the radiator(s) and adjust the lockshield valve
on each radiator and reduce the ow until the fan convector(s)
operate.
3.5 PIPEWORK MATERIALS
The Grant Solo fan convectors can be used with both copper and plastic pipe. Where plastic pipe is used it must be of the oxygen barrier type and be the correct class (to BS7291-1) for the application concerned.
On sealed systems, if plastic pipe is to be used, the installer must check with the plastic pipe manufacturer that the pipe to be used is suitable for the temperatures and pressures concerned. Plastic pipe must be Class S to BS7291-1.
Two exible hose connections will be required for installation of
the Grant Solo Hideaway fan convector. These are supplied with the unit.
3.6 PIPE CONNECTIONS
SOLO COMPACT AND COMPACTMAX MODELS:
Remove the front cover to access the ow and return pipe
connections. Refer to Section 3.6 or 3.7, as required, for details on removal of the front cover.
The ow and return connections are located at the left-hand side
of the unit.
The ow and return pipework can enter/exit the unit either
a) To the rear of the unit through the wall, or b) To the bottom of the unit, through the opening in the lower
casing.
It is recommended that 15mm isolation valves (not supplied)
are tted to the ow and return connections before connecting the ow and return pipework. These valves must be of the ‘full bore’ type to ensure no added restriction to the ow and return
pipework.
SOLO HIDEAWAY:
The ow and return connections are located on the right-hand
side of the unit. To allow the unit to be fully withdrawn from the plinth or base
board in which it is tted, without having to disconnect it from the system, two exible hose connections (supplied) will be required
for installation of the Grant Solo Hideaway fan convector. These are long enough to allow the fan convector to be completely removed from the plinth/baseboard when they are connected.
These will be connected between the system ow and return pipework, located at the rear of the xed kitchen unit, and the 15 mm full bore valves on the ow and return connections on the fan
convector.
3.7 INSTALLATION PROCEDURE: SOLO COMPACT AND SOLO COMPACTMAX MODELS
1. Carefully remove the Solo fan convector unit from the packaging.
2. Lay the unit on a at surface (oor, table, etc.) with the front cover facing upwards.
3. Unscrew and remove the three xing screws from along the lower edge of the front cover.
4. Lift the lower front edge of the front cover and then slide it forwards and off the unit.
5. Safely store the front cover for now where it will not be
damaged or scratched for re-tting after the Solo Compact or
CompactMAX fan convector has been installed.
6. Position the unit against the wall so that the lower edge is approximately 75-100mm above the skirting level.
7. Use a spirit level on the top of the unit to ensure it is level
and mark the position of the three xing holes in the back plate onto the wall. Refer to Figure 2-5 0r 2-6 for the xing
hole positions.
8. Remove the unit from the wall and drill the three holes to take
a suitable wall xings (not supplied).
9. Securely x the unit to the wall using three screws (not supplied).
10. Remove the rubber bungs from the ow and return connections on the fan convector and check that the bleed
screws on the ow connection are both closed.
It is recommended that 15mm isolation valves (not supplied) are
tted to the ow and return connections before connecting the ow and return pipework.
These valves must be of the ‘full bore’ type to ensure no added
restriction to the ow and return pipework.
Solo Compact 410
610
Outline of front cover
65
90
155
Figure 3-3: Solo Compact xing holes (viewed from the front)
Page 9
985
410
Outline of front cover
65
90
155
Figure 3-4: Solo CompactMAX xing holes (viewed from the
front)
11. Connect the heating system ow and return pipes to the
corresponding ow and return connections on the Solo fan
convector unit via the isolation valves.
12. Connect the electrical supply to the Solo fan convector unit. Refer to Section 4 (Electrical).
13. When all the Solo fan convectors have been connected to
the system pipework, the system can be lled.
14. Once the system is lled, open the HIGHEST of the two bleed screws on the ow pipe to vent the fan convector heat
exchanger. Repeat this with all other fan convectors on the system.
15. Ret the front cover and secure along the lower front edge using the three screws previously removed.
16. When all the installation of all the Solo fan convectors has been completed they can be commissioned. Refer to Section 5 (Commissioning).
3.8 INSTALLATION PROCEDURE: SOLO HIDEAWAY MODEL
Accurately mark and cut the opening required in the plinth or
panel into which the Grant Solo Hideaway unit is to be tted. The
bottom edge of the opening MUST be at least 12mm above the
nished oor level.
Refer to Figure 2-7 for the dimensions of the opening.
Figure 3-5: Solo Hideaway cut-out and xings holes
! NOTE !
If the height of the opening above oor level is greater than
12mm, it may be necessary to place packing under the two rubber feet at the rear of the fan convector to support the unit.
Carefully remove the Solo Hideaway fan convector unit from the
packaging and lay it on a at surface.
Unscrew and remove the four xing screws. Refer to Figure 2-8.
Keep these screws in a safe place as they will be required later to
re-t the grille.
Figure 3-6: Solo Hideaway grille xing screws
Carefully remove the grille and lay it at in front of the unit.
Disconnect the control panel ribbon connector from the plug. Refer to Figure 2-9.
Section 3: Installation Page 9
Page 10
Figure 3-7: Solo Hideaway control panel ribbon connector and plug
Disconnect the air temperature sensor lead at the small plug. Refer to Figure 2-10.
Figure 3-8: Solo Hideaway air temperature sensor and plug
Once disconnected, safely store the front grille for now where
it will not be damaged or scratched for re-tting after the Solo
Hideaway fan convector has been installed.
Position the Solo Hideaway unit into the opening in the plinth/
baseboard. Mark the centres of the four xing holes. Refer to
Figure 2-5.
Withdraw the Solo Hideaway unit from the plinth/baseboard and
drill the four xing holes to suit the xing screws to be used (not
supplied).
Remove the rubber bungs from the ow and return connections on the fan convector and check that the bleed screws on the ow
connection are both closed.
It is recommended that 15mm isolation valves (not supplied)
are tted to the ow and return connections before connecting the ow and return pipework. These valves must be of the ‘full bore’ type to ensure no added restriction to the ow and return
pipework.
Connect the heating system ow and return pipes to the corresponding ow and return connections on the Solo fan convector unit using the two exible hoses (supplied). These are
long enough to allow the fan convector to be completely removed from the plinth/baseboard when they are connected.
Connect the electrical supply to the Solo fan convector unit. Refer to Section 4 (Electrical).
! NOTE !
Do NOT t the Solo Hideaway unit into the opening until the system has been lled and the fan convector(s) vented.
When all the Solo fan convectors have been connected to the
system pipework, the system can be lled.
Once the system is lled, open the HIGHEST of the two bleed screws on the ow pipe to vent the fan convector heat exchanger.
Repeat this with all other fan convectors on the system.
Set the mains ON/OFF switch, on the right-hand side of the unit, to ON.
Position the Solo Hideaway unit into the opening and carefully push fully into place.
! NOTE !
Ensure that the space into which the Solo Hideaway is
being tted is clear of any debris, uff, dust, etc.
Whilst tting the fan convector into the opening ensure that the exible hoses are not kinked or twisted.
Secure the Solo Hideaway unit to the plinth/baseboard using four screws (not supplied) in the previously drilled holes.
Lay the grille face down in front of the Solo Hideaway unit. Reconnect the control panel ribbon connector and the air temperature sensor lead at the small plug.
Position the grille on the front of the Solo Hideaway unit and
secure using the four xing screws previously removed.
Carefully remove the protective covering from the grille.
When all the Solo fan convectors have been installed they can be commissioned. Refer to Section 5 - Commissioning.
Section 3: InstallationPage 10
Page 11
Section 4: Electrical and Section 5: Commissioning Page 11
4.1 GENERAL
Grant Solo fan convectors require a ~230V 1ph 50Hz electrical supply protected by a 3 Amp fuse.
A fused double pole switch, with contact separation of at least 3mm in both poles, should be used for connection to the mains electrical supply, serving the boiler and heating system controls only.
For the Solo Compact and Solo CompactMAX this switch can be located on the wall next to the fan convector.
For the Solo Hideaway, this switch can be located in a convenient position for the user to access when necessary, e.g. on the wall above kitchen unit/worktop level or inside the kitchen unit.
For the UK, the electrical installation must be carried out by a competent installer in accordance with the requirements of the Electricity at work Regulations 1989 and BS7671:2018 – IET Wiring Regulations 18th Edition.
If installed in the Republic of Ireland, the wiring installation must comply with all ETCI rules. All the wiring and supplementary earth bonding external to the boiler must be in accordance with the above-mentioned wiring regulations.
Do NOT interrupt the electrical supply to the Grant Solo with any external controls.
4.2 ELECTRICAL CONNECTIONS
Connect the electrical supply to the fan convector as follows:
SOLO COMPACT AND SOLO COMPACTMAX
Remove the front cover from the fan convector (if not already removed).
To do this, unscrew and remove the three xing screws from
along the lower edge of the front cover.
Pull outwards the lower front edge of the front cover and then lift it off the unit.
The electrical supply terminal block is located at the lower right­hand side of the fan convector. Refer to Figure 4-1.
Pass the cable through the hole with grommet and the cable restraint – both located at the right-hand end of the fan convector. See Figure 4-1.
Connect the mains supply cable (from the fused double pole switch) to the terminal block as follows:
• Terminal L: Live – Brown wire
• Terminal N: Neutral – Blue wire
• Terminal P
E: Earth – Green/yellow wire
Secure the cable in the cable restraint to prevent it being pulled out of the terminal block.
Replace the front cover on the fan convector and secure with the three screws along the lower edge.
Switch on the electrical supply to the fan convector at the fused double pole switch.
SOLO HIDEAWAY
The Solo Hideaway is supplied with a pre-wired 1mm2 3-core cable 1,300mm long for connection to the electrical supply.
This can be connected directly to a fused double pole switch located under the kitchen unit.
Alternatively, a 3-pin 13A plug (tted with a 3A fuse) can be tted
to the cable for connection to a 3-pin socket under the kitchen unit and this socket is fed from a fused double pole switch located either within a kitchen unit or above the worktop level, as required.
Switch on the electrical supply to the fan convector at the fused double pole switch.
4 ELECTRICAL
Ensure that the system is lled and vented and that each Solo fan
convector has also been vented. Refer to either Section 3.6 or 3.7 as required.
Switch on the mains electrical supply to the fan convector at the fused isolator.
Switch the mains ON/OFF switch to ON. On the Solo Compact and CompactMAX models, the mains
switch is located under the right-hand end of the front casing. Refer to Figure 8-1.
On the Solo Hideaway model, the mains switch is located on the right-hand side of the unit and should have been set to the ON
position before being nally tted in to the plinth/baseboard. Refer
to Figure 8-2. Switch the boiler or heat pump on and set the heating system
controls to call for heat.
Operate the heating system to raise the ow temperature
REFERRING TO SECTION 8 – OPERATING INSTRUCTIONS
Check the operation of the Solo fan convector(s) as follows: Press and hold the ON/OFF button on the Solo fan convector
control panel to switch the unit on.
The Alarm/Boost light will ash until the water ow temperature
reaches 29°C.
When the ow temperature reaches at 29°C the Alarm/Boost light will stop ashing and one of the temperature Indicator lights will be lit – either ashing or constant.
Using the ON/OFF button, set the air temperature to each one of
the four settings in turn to check their operation and then nally
set the air temperature to the required setting.
! NOTE !
It is NOT possible to adjust the temperature setting if the
water ow temperature is at less than 29°C.
Press the Boost/Cool button to check the boost function operation. Press the Boost/Cool button again to switch the boost function off. Set the heating system controls to the user’s requirements.
5 COMMISSIONING
Page 12
Section 6: Fault FindingPage 12
6.1 INITIAL CHECKS
If your Grant Solo fan convector appears not to be operating correctly, please rst carry out the following simple checks before seeking
further assistance.
Symptoms Check Actions
No heat output from fan convector
Are there any lights on the control panel? ►
If NO: Check mains ON/OFF switch is set to ON Check power supply to unit is switched ON at fused isolator switch Check fuse in power supply fused isolator
Is the Alarm/Boost light ashing?
(refer to Section 8.2)
►
If YES: Heating system water temperature is less than 29°C (refer to
Section 8.2).
Is the boiler or heat pump operating? ►
If NO: Check the boiler/heat pump controls are correctly set for it to
operate If the boiler/heat pump is faulty, contact your installer/service
engineer If YES: Wait for the system water temperature to reach at least 29°C.
Is the heating system circulating pump operating?
► Check and contact your installer to investigate if there is a problem
Low room temperature
Is the required air temperature correctly set on the control panel?
(refer to Section 8.2)
►
Set required air temperature using the ON/OFF button on the control panel.
Is the required temperature setting indicator
light ashing?
(refer to Section 8.2)
►
Set point temperature has not yet been reached. Wait until indicator
light stops ashing
Low heat output from fan convector
Is the water ow through the fan convector
too low?
►
Check for low water ow A simple test for low ow is if there is a noticeable temperature
difference to the touch between the ow and return pipes when the
unit is operating
Are the isolating valves on the ow and return
connections open?
► Check and open valves if necessary
Are the ow and return connections reversed? ►
Check - the ow and return connections are indicated on the fan
connector.
The ow pipe should be hotter to the touch than the return pipe
when the unit is operating
Has the fan convector been completely bled of air?
►
Check by bleeding any remaining air - as described in either Sec­tions 3.7 or 3.8, as appropriate for the model of fan convector.
Are the exible hoses twisted or kinked
(Solo Hideaway model only)?
►
Remove unit from plinth and check. Rectify as necessary. (Refer to Section 3.7)
6 FAULT FINDING
Page 13
Section 6: Fault Finding Page 13
6.2 FAULT DIAGNOSIS FLOW CHART
The following owchart can be used to determine and rectify a
fault in the operation of a Grant Solo fan convector.
Please rst carry out the simple checks, as detailed in Section
6.1, before using the ow chart below.
! WARNING !
Exposure to live electrical connections.
The following fault-nding procedures should only be conducted by a suitably qualied competent person using
the correct test equipment.
START
Check electricity supply
is turned on at the
fused isolator.
Turn unit off and on
using the mains ON/
OFF switch
Electrical problem
230V AC at 3 way
terminal block
Are there any lights
illuminated on the
control panel?
Other problem
Fix issue with mains
power supply
230V AC after mains
ON/OFF switch
Replace mains ON/
switch (SP0068)
Power at grey and
white wires at PCB
~10V AC
Replace transformer
(SP0012)
Any lights illuminated
on the control panel
Replace power and
control PCB (SP0129)
and user interface PCB
(SP0128)
Boost light ashing
20°C indicator light
(2 bars) ashing?
Check fans are running
heat is being emitted
Check power on fan
output (blue wire) on
PCB ~50V AC
Replace transformer
(SP0012)
Check hot water supply
to Solo is above 29°C
Is the heat source
functioning correctly
Fix issue with heating
source
Check that the system
is balanced
Inlet pipe to the radiator
is above 29°C
Balance radiators on the system to ensure
ow to the Solo
Air and water
temperature sensor
connected?
Re-connect sensor.
Replace temperature
sensor if necessary.
(SP0350)
Check fans are running
and heat is being
emitted
Contact your installer /
service engineer
PROBLEM
RESOLVED
Replace fan (SP28-
24) and capacitor
(2μF - SP0229 / 4μF -
SP0237)
NO YES
YES
NO
NO
YES
YES
YES
NO
NO
YES
NO YES
YES
NO
NONO
YESYES
YES
YES
YES
NO
NO
The air temperature sensor can be disconnected at this point to stimulate cold room temperatures and force the
20°C indicator light (2 bars) to
ash and fans to run
Page 14
Section 7: Spare Parts and Section 8: Operating InstructionsPage 14
7.1 FAN CONVECTOR PARTS LIST
Table 7-1: Fan convector parts list
Description Grant UK product code Solo Compact Solo CompactMAX Solo Hideaway
User interface PCB SP0128 • • •
Power and control PCB SP0129 • • •
Plug-in microprocessor
board
SP0133 • • •
Mains ON/OFF switch SP0068 • • •
Fan SP28-24 • • •
Transformer SP0012 • • •
Temperature sensor SP0350 • • •
Capacitor 2μF SP0229 • •
Capacitor 4μF SP0237 •
Flexible hose - 900 mm SP-MB90 •
7 SPARE PARTS
8.1 MAINS ON/OFF SWITCH
Grant Solo units have a factory-tted double pole mains ON/OFF
switch.
SOLO COMPACT AND COMPACTMAX MODELS:
This switch is located under the right-hand end of the front casing. Refer to Figure 10-1.
Figure 8-1: Solo Compact and CompactMAX mains ON/OFF switch (underside of unit)
SOLO HIDEAWAY MODEL:
This switch is located on the right-hand side of the unit. It should
have been set to the ON position before being nally tted in to
the plinth/baseboard.
8 OPERATING INSTRUCTIONS
Figure 8-2: Solo Hideaway mains ON/OFF switch (right-hand
side of unit)
For the unit to operate, ensure that this switch is set to ON and the power supply to the Solo fan convector is on, i.e. the switch on the fused spur serving the unit is set to ON.
Page 15
Section 8: Operating Instructions and Section 9: Cleaning Page 15
8.2 CONTROL PANEL
Grant Solo fan convectors are supplied with a simple control panel. Refer to Figure 1-3.
This allows each Solo unit to be individually set to suit the room or area in which it is installed.
The functions of the buttons and indicator lights are as follows:
ON/OFF BUTTON
When the ON/OFF button is pressed for at least 1 second it will start the operation of the Grant Solo unit – provided that the water
ow temperature is at least 29°C AND the room air temperature
is low enough (i.e. below the air temperature setting of the Solo unit). See section on ‘Temperature indicator lights’ below.
To stop the unit operating, press the ON/OFF button for at least 1 second.
TEMPERATURE INDICATOR LIGHTS
There are four temperature indicator lights that display the air temperature setting of the Solo unit, and whether that temperature setting has been achieved or not.
These indicate increasing temperature settings from the lowest on the left to the highest on the right, as follows:
• 18°C – indicator light with single bar
• 20°C – indicator light with two bars
• 22°C – indicator light with three bars
• 24°C – indicator light with four bars
TO SET THE REQUIRED AIR TEMPERATURE
Press the ON/OFF button momentarily – the lowest (single bar)
indicator light will ash slowly indicating that the air temperature
setting is 18°C.
TO INCREASE THE SETTING
Press the ON/OFF button again momentarily – the next (two
bars) indicator light will now ash slowly indicating that the air
temperature setting is now 20°C. Press the ON/OFF button again momentarily to increase the
setting further (if required) – the next (three bars) indicator light
will now ash slowly indicating that the air temperature setting is
now 22°C. Press the ON/OFF button again momentarily (if required) and the
right hand (four bars) indicator light will now ash slowly indicating
that the air temperature setting is now at the maximum (24°C). Pressing the ON/OFF button again momentarily will return the
air temperature setting to the minimum (18°C) and the left hand
(single bar) indicator light will now ash slowly. The selected indicator light will continue to ash slowly whilst the
temperature is being raised. When the air temperature reaches
the setpoint, the indicator light will stop ashing and become
continuous. The Grant Solo unit will then stop heating until needed again.
! NOTE !
It is NOT possible to adjust the temperature setting if the
water ow temperature is at less than 29°C.
ALARM LIGHT
The Alarm light will ash if the water ow temperature is less than
29°C.
BOOST/COOL BUTTON
Press this button momentarily whilst the Solo unit is operating and the normal Solo temperature control will be overridden for a period of 20 minutes to provide a higher output than available in normal operation.
The temperature indicator light will go off and the Alarm/Boost light will come on to indicate the Solo unit is operating in the Boost mode.
To stop the Boost function
Press the Boost button momentarily at any time during the 20 minute boost period.
After 20 minutes have elapsed, the Solo unit will automatically revert to the normal temperature control. The Alarm/Boost light will go off and the temperature indicator light will revert to the original setting.
Momentarily pressing the Boost button again will re-start the boost function for another 20 minutes.
SUMMER COOLING FUNCTION
In the summer Solo fan convectors can be used to provide air movement to give passive cooling.
To use this function, press BOTH the ON/OFF and Boost buttons at the same time for more than 1 second.
The water temperature control will be ignored and the fan will run
at the highest (boost) level for maximum air ow until the Solo unit
is switched off. The Alarm/Boost light will come on in this mode. To switch off the summer cooling function, press BOTH the ON/
OFF and Boost buttons at the same time for more than 1 second.
! NOTE !
The Summer cooling function will NOT automatically
switch off after a xed period (as with the Boost function)
but will remain on until BOTH the ON/OFF and Boost buttons are presses at the same time.
SPECIAL FUNCTION LIGHT
This light is not used and will not be lit during the operation of the fan convector. This does NOT indicate a fault with the fan convector.
Whilst it is not necessary for the Grant Solo fan convectors to be regularly serviced, a limited amount of cleaning is required from time to time.
Only use a moist cloth to clean the outer surfaces of the Solo fan convectors. Do NOT use any abrasive cleaners, cleaning liquids or aerosols.
9 CLEANING
The warm air outlet grille on the top of the Solo Compact and Solo CompactMAX and the front grille of the Solo Hideaway can be vacuumed clean.
The air inlet lters on the Solo Hideaway (located either side of
the warm air outlet grille) are not removeable or replaceable. They can be vacuum clean from the front.
Page 16
Section 10: Declaration of Conformity and Section 11: Health and Safety InformationPage 16
EC DECLARATION OF CONFORMITY
We: Grant Engineering (UK) Limited Hopton House Hopton Industrial Estate Devizes SN10 2EU
Declare that:
Equipment: Solo Fan Convector Radiators Model name/number: Solo Compact, Solo CompactMAX and Solo Hideaway
In accordance with the following Directives:
Low Voltage Directive: 2014/35/EU EMC Directive: 2014/30/EU Radiator and Convector Standards:
EN 442-2 1997 EN 16430-2 2014
EMC Standards:
EN 55014-1 2002 EN 55014-2 2003 EN 61000-3-2 2006
EN 61000-3-3 1995, +A1:2001, +A2:2001 EN 61000-4-2 2009 EN 61000-4-3 2006, +A1:2007, +A2:2010 EN 61000-4-4 2004, +A1:2010 EN 61000-4-5 2006 EN 61000-4-6 2009 EN 61000-4-11 2004 EN 62233 2008
I hereby declare that the equipment named above has been tested and found to comply with the relevant sections of the above
referenced specications. The unit complies with all essential requirements of the Directives.
Responsible Person: Neil Sawers Position: Technical Manager Signature:
Date: 5th October 2018
10 DECLARATION OF CONFORMITY
Under the Consumer Protection Act 1987 and Section 6 of the Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health (COSHH Regulations 1988).
Adhesives, sealants and paints used in the manufacture of the product are cured and present no known hazards when used in the manner for which they are intended.
11 HEALTH AND SAFETY INFORMATION
! WARNING !
Isolate the fan convector from the electrical supply before removing any covers.
Page 17
Section 12: End of Life Information Page 17
GENERAL
Grant Solo fan convectors incorporate components manufactured from a variety of different materials. The majority of these materials can be recycled whilst the smaller remainder cannot. Materials that cannot be recycled must be disposed of according to local regulations using appropriate waste collection and/or disposal
services.
DISASSEMBLY
There is little risk to those involved in the disassembly of this product. Please refer to and follow the Health and Safety Information given in these instructions.
For guidance on the disassembly of the fan convector refer to the information given in the Servicing section of these instructions.
RECYCLING
Many of the materials used in Grant fan convectors can be recycled, these are listed in the table below:
COMPONENT MATERIAL
Chassis and casing Mild steel (galvanised)
Heat exchanger Copper tubes, Aluminium ns
Front casing panel (wall hung units) Polycarbonate Connection pipework Copper Foam insulation Semi closed cell polyester Electrical wiring Copper/plastic Printed Circuit boards Copper/plastic Transformer Fans WEEE electrical recycling (Disassemble)
DISPOSAL
All materials other than those listed above must be disposed of responsibly as general waste.
Neil Sawers Technical Manager
12 END OF LIFE INFORMATION
Page 18
You are now the proud owner of a Grant Solo fan convector from Grant Engineering (UK) Limited which has been designed to give years of reliable, trouble free operation.
Grant Engineering (UK) Limited guarantees the manufacture of the fan convector including all electrical and mechanical components for a period of twelve months from the date of
installation
4
, provided that the fan convector has been installed and operated in full accordance with the installation and user instructions issued.
This will be extended to a total period of ve years if the fan convector is registered with Grant Engineering (UK) Limited within thirty days of installation. See main Terms and Conditions below.
Registering the product with Grant Engineering (UK) Limited
Please register your Grant Solo fan convector with Grant Engineering UK Limited within thirty days of installation. To do so visit www.grantuk.com and follow the links to the ‘Register a Product’, where you can register your fan convector for a further four years guarantee (giving ve years from the date of installation
4
). This does not affect your statutory rights1.
If a fault or defect occurs within the manufacturer’s guarantee period
If your fan convector should fail within the guarantee period, you must contact Grant Engineering (UK) Limited who will arrange for the repair under the terms of the guarantee, providing that the fan convector has been correctly installed and commissioned by a competent person and the fault is not due to tampering, debris, system water contamination, misuse, trapped air or the failure of any external components not supplied by Grant Engineering (UK) Limited, e.g. motorised valves, etc.
This ve-year guarantee only applies if the fan convector is
registered with Grant Engineering (UK) Limited within thirty days of installation
4
and is installed and operated in full
accordance with the installation and user instructions.
In the rst instance
Contact your installer to ensure that the fault does not lie with the system components or any incorrect setting of the fan convector or system controls that falls outside of the manufacturer’s guarantee otherwise a service charge could result. Grant Engineering (UK) Limited will not be liable for any charges arising from this process.
If a fault covered by the manufacturer’s guarantee is found
Ask your installer to contact Grant Engineering (UK) Limited Service Department on +44 (0)1380 736920 who will arrange for a competent service engineer to rectify the fault.
Remember - before you contact Grant Engineering (UK) Limited
• Ensure the fan convector has been installed and
commissioned by a competent person in accordance with the installation and user instructions.
• Ensure there is an electrical supply the fan convector.
• Ensure the problem is not being caused by the heating
system or its controls.
Section 13: GuaranteePage 18
13 GUARANTEE
Free of charge repairs
During the ve year guarantee period no charge for parts or labour will be made provided that the fan convector has been installed and commissioned correctly in accordance with the manufacturer’s installation and user instructions and it was registered with Grant Engineering (UK) Limited within thirty days of installation
3
.
Proof of purchase must be made available to Grant Engineering (UK) Limited on request.
Chargeable repairs
A charge may be made (if necessary following testing of parts) if the breakdown is due to any fault(s) caused by the plumbing or heating system, e.g. contamination of parts due to system contamination, sludge, scale, debris or trapped air. Refer to ‘Extent of manufacturer’s guarantee’.
Extent of manufacturer’s guarantee
The manufacturer’s guarantee does NOT cover the following:
• If the fan convector has been installed for over ve years.
• If the fan convector has not been installed and commissioned
by a competent person in accordance with the installation and user instructions.
• Instances where the serial number has been removed or made illegible.
• Fault(s) due to accidental damage, tampering, unauthorised adjustment, neglect, misuse or operating the fan convector contrary to the manufacturer’s installation and user instructions.
• Damage due to external causes such as bad weather conditions (ood, storms, lightning, frost, snow, or ice), re,
explosion, accident or theft.
• Fault(s) due to incorrectly sized expansion vessel(s), incorrect vessel charge pressure or inadequate expansion on the system.
• Fault(s) caused by external electrics and external components not supplied by Grant Engineering (UK) Limited.
• Heating system servicing, de-scaling or ushing.
• Checking and replenishing system pressure.
• Electrical cables and plugs, external controls not supplied by
Grant Engineering (UK) Limited.
• Heating system components, such as radiators, pipes, ttings, pumps and valves not supplied by Grant Engineering
(UK) Limited.
• Use of spare parts not authorised by Grant Engineering (UK) Limited.
Page 19
Section 13: Guarantee Page 19
Terms of manufacturer’s guarantee
• The Company shall mean Grant Engineering (UK) Limited.
• The fan convector must be installed by a competent person
and in full accordance with the relevant Codes of Practice, Regulations and Legislation in force at the time of installation.
• The fan convector is guaranteed for ve years from the date of installation
4
, providing that the fan convector was registered with the Company within thirty days of installation. Any work undertaken must be authorised by the Company and carried out by a competent service engineer.
• The fan convector is operated correctly, in accordance with the Installation and user instructions.
• Grant Engineering (UK) Limited strongly recommends that a Grant Mag-One in-line magnetic lter/s (or equivalent
5
)
is tted in the heating system pipework. This should be installed and regularly serviced in accordance with the lter
manufacturer’s instructions. We reserve the right to ask for proof of installation – failure to provide this may result in the guarantee becoming invalid.
• Proof is provided that the system has been ushed or
chemically cleaned where appropriate (refer to BS 7593) and that the required quantity of a suitable corrosion inhibitor added.
• Proof of annual heating system servicing (including the checking of any expansion vessels and pressure relief valves) must be provided if and when requested by the Company.
• This guarantee does not cover breakdowns caused by incorrect installation, neglect, misuse, accident or failure to operate the fan convector in accordance with the manufacturer’s installation and servicing instructions.
• The fan convector is registered with the Company within thirty days of installation. Failure to do so does not affect your statutory rights
1
.
• The balance of the guarantee is transferable. Grant Engineering (UK) Limited must be informed of the new owner’s details.
• The Company will endeavour to provide prompt service in the unlikely event of a problem occurring but cannot be held responsible for any consequential losses.
• This guarantee applies to Grant Engineering (UK) Limited fan convectors purchased and installed on the UK mainland, Isle of Wight, Channel Islands and Scottish Isles only
2
. Provision of in-guarantee cover elsewhere in the UK is subject to agreement with the Company.
• All claims under this guarantee must be made to the Company prior to any work being undertaken. Invoices for call out/repair work by any third party will not be accepted unless previously authorised by the Company.
• Proof of purchase and date of installation, commissioning and service documents must be provided on request.
• If a replacement fan convector is supplied under the guarantee (due to a manufacturing fault) the product guarantee continues from the installation date of the original fan convector and not from the installation date of the replacement.
• Breakdown/failure due to system water contamination will not be covered by this guarantee.
• The replacement of a fan convector under this guarantee does not include any consequential costs, such as the removal or replacement of kitchen units, etc.
• The fan convector must not be sited in a location where it may be subjected to frost.
Foot notes
1. Your statutory rights entitle you to a one-year guarantee period only.
2. The UK mainland consists of England, Scotland and Wales
only. Please note that for the purposes of this denition,
Northern Ireland is not considered part of the UK mainland.
3. We recommend that your heating system is serviced every twelve months (even when the guarantee has expired) to prolong the lifespan and ensure it is operating safely and
efciently.
4. The guarantee period will commence from the date of installation, unless the installation date is more than six months from the date of purchase, in which case the guarantee period will commence six months from the date of purchase.
5. As measured by gauss. The MagOne magnetic lter has a gauss measurement of 12,000.
Page 20
GRANT ENGINEERING (UK) LIMITED
Hopton House, Hopton Industrial Estate, Devizes, Wiltshire, SN10 2EU
Tel: +44 (0)1380 736920 Fax: +44 (0)1380 736991
Email: [email protected] www.grantuk.com
Loading...