Grant HPiD6, Aerona3 Series, HPiD16, HPiD10 Installation And Servicing Instructions

UK | DOC 0109 | Rev 2.0 | June 2017
Grant Aerona³
Air to Water High Efficiency Heat Pump Range
Installation and Servicing Instructions
GRANT ENGINEERING (UK) LIMITED
Hopton House, Hopton Industrial Estate, Devizes, Wiltshire, SN10 2EU Tel: +44 (0)1380 736920 Fax: +44 (0)1380 736991 Email: info@grantuk.com www.grantuk.com
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. However, no responsibility of any kind for any injury, death, loss, damage or delay however caused resulting from the use of this manual can be accepted by Grant Engineering (UK) Limited, the author or others involved in its publication. All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. © Grant Engineering (UK) Limited 2017. No part of this manual may be reproduced by any means without prior written consent.
Important Note for Installers
This manual is intended to guide Installers on the installation, commissioning and servicing of the Grant Aerona³ air source heat pump.
A separate manual is available to guide users in the operation of the heat pump.
Special Text Formats
The following special text formats are used in this manual for the purposes listed below:
Warning of possible human injury as a consequence of not following the instructions in the warning.
!
WARNING
Caution concerning likely damage to equipment or tools as a consequence of not following the instructions in the caution.
!
CAUTION
Used for emphasis or information not directly concerned with the surrounding tex t but of impor tance to the reader.
NOTE
!
Contents
1 Introduction 4
1.1 General 4
1.2 Outputs 4
1.3 Main Components 4
1.4 Planning Permission 4
1.5 DNO Application 4
1.6 Servicing 4
1.7 Important Advice 4
1.8 Product Contents 4
1.9 Installation Accessories 4
1.10 Control Parameters 4
1.11 Heat Pump Components 5
2 Technical Data 6
1.1 Heat Pump Technical Data 6
2.2 Main Supply Cable 6
2.3 Heat Pump Dimensions 7
2.4 Remote Controller Dimensions 8
3 Installation Information 9
3.1 Introduction 9
3.2 Heating System Design Criteria 9
3.3 Regulations 10
3.4 Heat Pump Location 10
3.5 Preparation for Installation 10
3.6 Installing the Heat Pump 12
3.7 Metering for Domestic RHI Installations 12
3.8 Buffer Tanks 12
3.9 Hydraulic Diagrams 13
3.10 Before you Commission 14
3.11 Completion 15
3.12 Installation Checklist 15
4 Sealed Systems 16
4.1 Sealed System Requirements 16
4.2 Filling the Sealed System 17
4.3 Pressure Relief (Safety) Valve Operation 17
5 Domestic Hot Water 18
5.1 Temperature Control 18
5.2 Heat Pump Cylinders 18
5.3 Legionella 19
5.4 Automatic DHW Boost Kit 19
6 Electrical 22
6.1 Wiring Centre 22
6.2 Terminal PCB Input/Output 23
6.3 Power Supply 23
6.4 Tightening Torques 25
6.5 Solar Thermal 25
6.6 Connection of Heating System Controls 25
6.7 Connection of Remote Controller 25
6.8 Wiring Diagrams 25
6.9 System Control Wiring Diagrams 26
7 Remote Controller 28
7.1 Remote Controller 28
7.2 Installation Requirements 28
7.3 Installing the Remote Controller 28
7.4 Connecting the Remote Controller 29 to the Heat Pump
7.5 Buttons 30
7.6 Display Panel 31
8 Operation 32
8.1 Heat Pump Operation 32
8.2 Weather Compensation 34
8.3 Water Pump Management 35
8.4 Frost Protection 38
8.5 ON/OFF DHW Production Remote 40 Contact
8.6 ON/OFF Heating Remote Contact 41
8.7 Night Mode 42
8.8 Low Tariff 43
9 Commissioning 44
9.1 System Setup 44
9.2 Setting the Day and Time 44
9.3 Access for Parameter Settings 45
9.4 Accessing the Parameter Setting Menu 45 (User level)
9.5 Accessing the Parameter Setting Menu
45
(Installer level)
9.6 Temperature Control - DHW function 45
9.7 Parameters Input/Output 46
9.8 Remote Controller Back Light Display 46 Parameters
9.9 Weather Compensation 47
9.10 Frost Protection Function Setting 47
9.11 Pump Operation and Air Bleeding 47 from Heating System
9.12 Pump Output Setting 47
9.13 Coastal Installations 47
10 Servicing 48
10.1 General 48
10.2 Air Inlet and Outlet 48
10.3 Condensate Disposal 48
10.4 Heating System Connections 48
10.5 Heat Pump Controls 48
10.6 Refrigerant 48
10.7 Monitor Display Function 49
11 Fault Finding 50
11.1 Error Code Display 50
11.2 Error History Display 50
11.3 Reset Error Code Display 50
11.4 Error Codes 51
11.5 Table of Controller PCB and Terminal 54 PCB Alarms
11.6 Error Codes and PCB Alarm Figures 55 and Tables
12 Spare Parts 58
12.1 Exploded Diagram - HPID6 58
12.2 Spare Parts List - HPID6 59
12.3 Exploded Diagram - HPID10 60
12.4 Spare Parts List - HPID10 61
12.5 Exploded Diagram - HPID16 62
12.6 Spare Parts List - HPID16 63
13 Declaration of Conformity 64
14 Health and Safety Information 65
14.1 General 65
14.2 Refrigerant (410A) 65
15 Disposal and Recycling 65
16 Product Fiches 66
17 Guarantee 72
Appendix A - Parameters List 74
Appendix B - Wiring Diagrams 76
Appendix C - Parameters 78 Record
Contents Page 3
Section 1: IntroductionPage 4
1.1 General
The Grant Aerona³ range consists of three compact, light weight, MCS approved, monobloc, air-to-water, inverter driven, single-phase air source heat pumps working with R410A refrigerant.
It is important that these installation and ser vicing instructions are followed to ensure correct installation and operation. Failure to do so may result in poor performance.
It is not within the scope of this manual to design the heating system or provide any advice regarding the layout of the system or any of the controls required for any individual heating system.
These instructions do not replace the installation or users manuals for any additional components used in the design of your system e.g. cylinders, motorised valves, programmers, solar thermal devices, buffers, etc.
These instructions must be left with the product for future reference.
1.2 Outputs
There are three models in the Aerona³ range as follows:
• HPID6 - 6kW*
• HPID10 - 10kW*
• HPID16 - 16kW*
* at 7°C air and 35°C flow temperature
1.3 Main Components
Each model incorporates the following main components:
• DC inverter - this responds rapidly to changing conditions
to provide the necessary output to meet heating demands by varying the speed and output of the compressor, fan and circulating pump. This reduces the on/off times of the compressor, keeping the water temperature constant during operation reducing the electricity consumption.
• Compressor - a high-ef ficiency DC twin-rotary compressor to
provide smooth performance and quiet operation.
• Plate heat exchanger (condenser) - the high-efficiency plate
heat exchanger is used to transfer heat to the heating system primary circuit.
• Fan - a high-ef ficiency DC fan motor is used for smooth and
quiet operation. A single fan is fitted to the 6kW (5 blade) and 10kW (3 blade) units. Two fans (3 blade) are fitted to the 16kW unit.
• Circulating pump - high-ef ficiency DC pump speed controlled
from the ASHP control PCB.
• Base tray heater - factory fitted electric heater prevents
condensate in the base of the heat pump from freezing. When the ambient temperature reaches 2.5°C, the base tray heater turns on and at 5.5°C turns off (ΔT of 3k). This cannot be adjusted or turned off.
• Pressure relief valve - a 3 bar pressure relief valve is factor y
fitted.
• Air purge valve (automatic air vent) - factor y fitted to assist
in the removal of air from the heating primary circuit of the heat pump.
1.4 Planning Permission
The installation of a Grant Aerona³ heat pump on domestic premises may be considered to be permitted development, not needing an application for planning permission, provided ALL the limits and conditions listed on the Planning Portal website are met.
For further information, visit w w w.planningportal.gov.uk.
1 Introduction
1.5 DNO Application
An application must be made to the Distribution Network Operator (DNO) before connecting the heat pump(s) to the mains electrical supply. There are six DNOs operating the electrical distribution network throughout England, Scotland and Wales and the application must be made to the DNO covering the area concerned.
The necessary information required to make this application (J-forms) can be downloaded from the Grant UK website (ww w.grantuk.com), completed and then submitted to the correct DNO for the area in question.
1.6 Servicing
It is recommended (and a requirement of the product guarantee) that the heat pump should be regularly serviced, at least once a year and the details entered in the Service Log by the service engineer.
1.7 Important Advice
1. It is essential that the full layout of the system is understood before the installation of any component is undertaken. If you are in any doubt, please stop and seek advice from a qualified heating engineer or from Grant UK. Please note that Grant UK will not be able to offer specific advice about your system unless we designed it. In this case, we will always refer you to seek the advice of a qualified system designer.
2. The heat pump must be installed and commissioned in accordance with these installation and servicing instructions. Deviations of any kind will invalidate the guarantee and may cause an unsafe situation to occur. Please seek advice from Grant UK if any of these user, installation and servicing instructions cannot be followed for whatever reason.
3. The heat pump contains high pressures and high temperatures during normal working conditions. Care must be taken when accessing the internal workings of the heat pump.
4. The heat pump contains an electrically driven fan which rotates at high speed. Disconnect the heat pump from the electrical supply before removing the top cover.
1.8 Product Contents
The Aerona³ comes supplied on a single pallet. The following items are included:
• 1 x Heat pump
• 1 x Condensate drain elbow
• 4 x Anti-vibration shoes (6kw only)
• 2 x Flexible hoses (6kW: 22mm, 10kW: 28mm, 16kW: 35mm)
• 2 x Isolating valves (6kW: 22mm, 10kW: 28mm, 16kW: 35mm)
• 1 x Remote controller
• 1 x Remote controller cable (length: 8 metres)
• 1 x Installation and servicing instructions
• 1 x User instructions
3
The following are available from Grant UK:
Product code Description
HPIDFOOT/KIT Anti-vibration mounts (2 x 600mm and fixing kit)
HPIDINSU/KIT Through wall insulation kit (22 - 28mm flexible hoses)
1.10 Control Parameters
All parameters are listed sequentially in Appendix A.
Section 1: Introduction Page 5
1.11 Heat Pump Components
Air inlet is located in the left and rear of the unit
Air outlet
Wiring cover
Screw
Air inlet is located in the left and rear of the unit
Air outlet
Wiring cover
Screw
Air inlet is located in the left and rear of the unit
Air outlet
Wiring cover
Screw
Terminal PCB
Auto-air vent
Terminal block
Pump
Compressor
Pressure relief valve
Main PCB
Main PCB
Terminal PCB
Terminal block
Pump
Pressure relief valve
Auto-air vent
Compressor
Terminal PCB
Pressure relief valve
Auto-air vent
Terminal block
Pump
Compressor
Main PCB
Figure 1-1: Main components (external) - 6kW
Figure 1-2: Main components (external) - 10kW
Figure 1-3: Main components (external) - 16kW Figure 1-6: Main components (internal) - 16kW
Figure 1-5: Main components (internal) - 10kW
Figure 1-4: Main components (internal) - 6kW
Section 2: Technical DataPage 6
2.1 Heat Pump Technical Data
Table 2-1: Technical data
Model Unit HPID6 HPID10 HPID16
Heating capacity (BS EN 14511 - air: 7°C / water: 35°C) kW 6.0 10.0 16.0
COP (BS EN 14511 - air: 7°C / water: 35°C) 4.11 4.35 4.10
SCOP (average climate conditions) - 35°C 4.34 4.35 4.19
Heating capacity (BS EN 14511 - air: 7°C / water: 55°C) kW 5.38 9.0 13.3
COP (BS EN 14511 - air: 7°C / water: 55°C) 2.59 2.71 2.67
SCOP - average climate conditions (BS EN 14825 - water: 55°C) 3.15 3.15 3.15
Power supply ~230V 1ph 50Hz
Power input (BS EN 14511 - air: 7°C / water: 35°C) kW 1.46 2.30 3.90
Mechanical protection IPX4
Compressor DC twin rotar y - inverter driven
Pressure (maximum) MPa 4.1
Refrigerant R410A
Mass of R410A kg 1.05 1.72 2.99
Circulating pump m head 10 6 12
Flow rate (minimum) litres/min 5 10 15
Outdoor temperature °C -20 to 43
Inlet water temperature °C 5 to 55
Water pressure (system) MPa (bar) 0.1 to 0.3 (1 to 3 bar)
Sound power level at 1 metre (external) dB(A) 63 67 63
Sound pressure level at 1 metre (external) dB(A) 40 44 40
Water connections BSPF ¾˝ 1¼˝
Weight (empty) kg 53 75 121
Weight (full) kg 54 76.8 123
Water content litres 1.0 1.8 2.0
Heat pump casing volume 0.19 0.27 0.48
ErP rating (low temperature: 35°C flow) - heating
A++
ErP rating (low temperature: 55°C flow) - heating
2.2 Mains Supply Cable
Always assume maximum possible load when considering cable sizing.
The cable supplying power from the consumer unit to the heat pump must be connected via an external 2 pole isolator. This allows the service engineer to isolate the power supply before working on the heat pump safely.
Refer to Section 6 for connection details.
Table 2-2: Electrical installation requirements
Heat pump
model
Maximum
running current
(A)
MCB
Rating (A) Type
HPID6 11.2 16 C
HPID10 17.5 20 C
HPID16 25.3 32 C
2 Technical Data
Section 2: Technical Data Page 7
2.3 Heat Pump Dimensions
327
57
388 54
R3/4(20A)
30015.3 42
825 73
16 659
580
122.5 122.5
43
Return
Flow
86616
850 21
R1(25A)
R1(25A)
25 330 38
480173
155540155
7570
357
Return
Flow
680185
36
356
13 330 13
80 80
241000
1418
205590205
Flow
Return
R1 1/4(32A)
R1 1/4(32A)
Figure 2-5: HPID16 dimensions
Figure 2-4: HPID10 dimensions
Figure 2-3: HPID6 dimensions
Section 2: Technical DataPage 8
2.4 Remote Controller Dimensions
12
37
37
23 23
18.25
120
16.5
6-4.2×7
120
83.5 18.25
(116)
Knock out hole
Mounting plate Door closed Door open
Figure 2-6: Remote controller dimensions
Section 3: Installation Information Page 9
3.2 Heating System Design Criteria
Before continuing with the installation of the Aerona³ heat pump, please spend a few minutes confirming the suitability of the heat pump to your system. Failure to do so may result in poor performance and wasted time:
• Has a room-by-room heat loss calculation been carried out?
• Is this system designed for mono or bivalent?
• If monovalent, total heating capacity?
• If bivalent, what is the load capacity of the heat pump?
• If bivalent, what is/are additional heat source(s)?
• Type of system design? - S-plan, S-plan plus
• Will a buffer be used?
• If yes, what is the capacity of the buffer?
• Has cavity wall insulation been installed?
• Has loft insulation of 270mm been installed?
• Have all system pipes been lagged correctly?
• Are the existing controls being upgraded?
3.2.1 System Design Criteria
A typical condensing oil or gas fired boiler operates with a flow of 70°C and a return of 50°C, i.e. with a DT of 20°C. A heat pump operates with a flow of between 30°C and 55°C with a DT of 8°C.
The design of any system in the UK is typically based on the following parameters:
1. That the outside design air temperature can fall to -3°C or lower
2. The internal design temperature can be between 18-22°C depending on the room concerned.
3. The heat pump operates at lower water temperatures than an oil or gas fired appliance. Designing a new system for use with a heat pump is straight forward, assuming the insulation properties of the dwelling meets or exceeds current Building Regulations and the lower flow/return temperatures are taken into account in the selection of the type and size of the heat emitters used.
While underfloor heating is the preferred heat emitter, a combination of underfloor heating and radiators, or radiators only, works just as efficiently. It is necessar y, however, to calculate the size of radiator required accurately – if this is not done, the house will fail to reach the target temperature and will be costly to rectify after the installation is complete.
When tested to BS EN 14511, the heat output for an heat pump is declared at the test conditions of 7°C outside air temperature and 35°C or 55°C water flow temperature.
At all other values of outside air temperature and water flow temperature the actual heat pump output will vary, e.g. the heat output will:
• decrease with lower outside air temperatures and increase
with higher outside air temperatures at any given water flow temperature, and
• decrease with higher water flow temperatures and increase
with lower water flow temperatures at any given outside air temperature
A back-up boiler can be added to the rated output of the heat pump.
Provided that the heat pump is sized correctly for the system, this back-up heater will only compensate for any short fall in me eting the heat load for the propert y below the minimum design air temperatures.
3.2.2 Heat Emitter Sizing
For guidance on sizing heat emitters, e.g. radiators and/or underfloor heating, refer to MCS Heat Emitter Guide (MCS 021).
3 Installation Information
3.1 Introduction
Grant Aerona³ heat pumps should be stored and transported in an upright position. If not, then the heat pump MUST be positioned in an upright position for at least four hours before being operated.
NOTE
!
For the heat pump to operate satisfactorily, install it as outlined in this installation manual.
• The Grant Aerona³ heat pump should only be installed by a
competent person.
• Before installing the heat pump, please read the following
installation information carefully and install the heat pump as instructed.
• Be sure to follow the safety notices given.
• After completing the installation, check the product operates
correctly. Then, explain to the user about the operation and maintenance requirements as shown in this manual.
• Be sure to install the heat pump in a suitable location that can
support the heat pump when filled. Installation in an unsuitable location may cause injury to persons and damage to the heat pump.
• Do not install in a position where there is any possibility of
flammable gas leakage such as from LPG cylinder around the heat pump. Leaked flammable gas around the heat pump may cause a fire.
• If the leaked refrigerant is exposed to fire, poisonous gas may be
produced.
• Connect the heat pump with the flexible hoses and valves
supplied, as described in this installation manual.
• Do not use an extension cable.
• Do not turn on the power until all installation work is complete.
• Only use correct Grant UK parts and accessories to avoid
accidents such as electric shock, fire and leakage of water.
• Never touch electrical components immediately after the power
supply has been turned of f as electrical shock may occur. After turning off the power, always wait five or more minutes before touching electrical components.
• Be sure to connect the power supply cable correctly to the
terminal block as overheating can cause a fire.
• Ensure the wiring lid is fitted following installation to avoid electric
shock at the terminal block.
• Always connect the earth wire to the heat pump.
• Install a correctly rated circuit breaker.
• After installation, the heat pump and heating system must be
commissioned. Hand over all documentation to the end-user and explain the operating functions and maintenance according to these instructions.
Section 3: Installation InformationPage 10
3.3 Regulations
Installation of a Grant Aerona³ heat pump must be in accordance with the following recommendations:
• National Building Regulations, e.g. Approved Document G
• Local Bylaws (check with the Local Authority for the area)
• Water Supply (Water Fittings) Regulations 1999
• MCS Installer Standards (if applying for the Renewable Heat
Incentive)
• MIS 3005 (Requirements for contractors undertaking the supply, design, installation, set to work commissioning and handover of microgeneration heat pump systems)
• MCS 021 (MCS Heat Emitter Guide for Domestic Heat Pumps)
The installation should also be in accordance with the latest edition of the following standards and codes of Practice:
• BS 7671 and Amendments
• BS EN 12831
3.4 Heat Pump Location
3.4.1 Selection of position
• Consider a place where the noise and the air discharged will not
affect neighbours.
• Consider a position protected from the wind.
• Consider an area that reflects the minimum spaces
recommended.
• Consider a place that does not obstruct the access to doors or
paths.
• The surfaces of the floor must be solid enough to suppor t the
weight of the heat pump and minimise the transmission of noise and vibration.
• Take preventive measures so that children cannot reach the unit.
• Install the heat pump in a place where it will not be inclined more
than 5°.
• When installing the heat pump where it may exposed to strong
wind, brace it securely.
• If the Aerona³ heat pump is to be installed within 1 mile of the
coast, avoid siting facing the sea.
• If the Aerona³ heat pump is to be installed within 15 miles of the
coast, the evaporator must be sprayed with AFC50 and this must be repeated on each annual service.
Decide the mounting position as follows:
1. Install the heat pump in a location which can withstand the weight of the heat pump and vibration. Please make sure it is installed level.
2. Provide the indicated space to ensure good airflow.
3. Do not install the heat pump near a source of heat, steam, or flammable gas.
4. During heating operation, condensate water flows from the heat pump. Therefore, install the heat pump in a place where the condensate water flow will not be obstructed.
5. Do not install the heat pump where strong wind blows directly onto the heat pump or where it is very dusty.
6. Do not install the heat pump where people pass frequently.
7. Install the heat pump in a place where it will be free from adverse weather conditions as much as possible.
3.4.2 Noise Level
All heat pumps make a noise. Discuss the potential nuisance factor with the end-user when considering the final position of the heat pump. Take opening windows and doors into account. It is not essential for the heat pump to be positioned next to a wall of the house. Behind an out-building may be more suitable so discuss the options with the end-user.
3.4.3 Orientation
The North face of the building will usually have colder ambient air than any other side. To ensure ma ximum efficiency from the Grant Aerona³ heat pump, position the heat pump on a warmer side. In order of preference, site the heat pump on a South face followed by either South East or South West, then by East or West. Only install on a North face if there is no other alternative.
3.5 Preparation for Installation
3.5.1 Base
The heat pump should be installed on a flat trowelled finished concrete base 150mm thick. This base should extend at least 150mm beyond the heat pump on three sides.
To avoid bridging the DPC, leave a gap of at approximately 150mm between the concrete base and the wall of the house.
The heat pump must be raised up from the base by approximately 100mm on suitable anti vibration mounts or blocks.
3.5.2 Clearances
The following minimum clearances must be used to enable the product to be easily commissioned, serviced and maintained and allow adequate air flow in and out of the heat pump.
Refer to Table 3-1 and Figure 3-2.
Table 3-1: Clearances
Aspect Minimum clearance required (mm)
To p 300
Bottom Approximately 100*
Front 600
Rear 300
Left 100
Right 600
* Height of A/V mounts (product code: HPIDFOOT/KIT)
Section 3: Installation Information Page 11
3.5.3 Condense Disposal
The underside of the heat pump has a condensate outlet (refer to Figure 3-3) that allows any condensate to drain from the heat pump.
Provision must be made to safely collect and dispose of the condensate.
For example, use 40 mm waste pipe to form a condensate disposal system into which the condensate flows from the opening in the bottom of the heat pump casing running to a suitable gulley or soakaway.
It is essential that the condensate is able to drain away and not allowed to run onto any adjacent paths or driveways where, in winter, this will result in icing and a potential hazard for anyone walking near the heat pump. The top of the concrete base must be either level with, or above, the surrounding ground level.
!
WARNING
Condensate outlet
Figure 3-3: Condensate outlet
3.5.4 Vibration
If the vibration from the heat pump is likely to cause a nuisance, use the anti-vibration mounts (product code: HPIDFOOT/KIT) and fix the heat pump securely to the mounts.
003 revO mm
Over 600 mm
Over 100 mm
Over 300 mm
Over 600 mm
HPID10
003 revO mm
Over 600 mm
Over 100 mm
Over 300 mm
Over 600 mm
HPID16
003 revO mm
Over 600 mm
Over 100 mm
Over 300 mm
Over 600 mm
HPID6
Figure 3-2: Clearances
Section 3: Installation InformationPage 12
3.6 Installing the Heat Pump
3.6.1 Insulation
The complete water circuit, including all pipework, must be insulated to prevent heat loss reducing the efficiency of the heat pump and also to prevent damage due to frozen pipes.
3.6.2 Connecting the Heating System to the Heat Pump
• Water connections must be made in accordance with diagram in
this manual and the labels on the heat pump.
• Be careful not to deform the heat pump pipework by using
excessive force when connecting.
• Pipework should be flushed before connecting the heat pump.
• Hold the pipe end downwards when removing burrs.
• Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
• The heat pump is only to be used in a sealed heating
system. It must not be used as part of an open-vented system.
Before continuing the installation of the heat pump, check the following points:
• The maximum system water pressure is 3 bar.
• Make sure the hose is connected to the pressure relief valve to
avoid any water coming into contact with electrical parts.
• Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for servicing. An automatic air purge valve is provided inside the heat pump. Check that the air purge valve can operate.
• Take care that the components installed in the pipework can
withstand the water pressure.
3.6.3 System Connections
The system connections of the heat pump must be carried out using the flexible hoses, valves and fittings supplied with the heat pump.
The hydraulic circuit must be completed following the recommendations below:
1. It is important to install the isolation valves bet ween the heat pump and the building.
2. The system must have drain cocks in the lowest points.
3. Air vents must be included at the highest points of the system.
4. A system pressure gauge must be installed upstream of the heat pump.
5. All pipework must be adequately insulated and supported.
6. The presence of solid particles in the water can obstruct the heat exchanger. Therefore, protect the heat exchanger using a magnetic filter such as a Grant Mag-One.
7. After system assembly flush and clean the whole system, paying particular attention to the state of the filter.
8. A new installation must be thoroughly flushed and cleaned before filling and adding anti-freeze/biocide/inhibitor.
Do not use the heat pump to treat industrial process water, swimming pool water or domestic drinking water. Install an intermediate heat exchanger for all of the above cases.
!
WARNING
3.6.4 Remote Controller
For details on how to install the remote controller, refer to Section 7.
For setting, refer to Section 9.
3.7 Metering for Domestic RHI Installations
Some air source heat pump installations may require a heat meter to be fitted under certain circumstances, for example:
• Where the property is occupied for less than 183 days per year
• If there is a back-up heating system installed
A heat meter must be installed and regular meter readings will have to be submitted as the RHI payment will be determined from these readings.
‘Meter Ready’ Installations
Currently, air source heat pump installations that are receiving a domestic Renewable Heat Incentive (RHI) payment will not usually require a heat meter to be fitted. The payment is based on the annual heat demand, as stated on the EPC for the propert y.
However, even though a heat meter is not required for these domestic installations to receive an RHI, they must be ‘meter ready’ in accordance with MCS requirements. Refer to the MCS Domestic RHI Metering Guidance Document for full details.
3.8 Buffer Tanks
3.8.1 Buffer Tanks
A buffer tank is NOT required for the Grant Aerona³ HPID6 (6kW) and HPID10 (10kW) heat pumps.
A buffer tank will be required for the Grant Aerona³ HPID16 (16kW) heat pump where:
• The overall system volume is less than 100litres OR
• If the part of the system connected to the heat pump is less than 30 litres during the normal operation of the system
For example:
• When the heating zone valves(s) are closed leaving only the primary circuit to a cylinder connected to the heat pump
• When the hot water zone valve is closed leaving a heating zone (or zones) connected to the heat pump
The buffer tank must be large enough to ensure that the volume of that part of the system will be at least 30 litres.
This buffer tank is simply a vessel required to increase the volume of the system, to meet the requirements given above. It must be fitted in the return to the heat pump. Refer to Figure 3-4.
Buffer tanks suitable for this purpose are available. For further information, please contact Grant UK on +44 (0)1380 736920.
A buffer tank temperature probe is NOT required as this is not a thermal store.
NOTE
!
Section 3: Installation Information Page 13
3.9 Hydraulic Diagrams
3.9.1 S-plan type with Buffer (optional)
2
1
2 3
4
5 6
7
8
9
15
Static head of system
10
11
10
11
13
14
12
Figure 3-4: Monovalent system - with optional buffer and S-Plan type controls
The above system diagram is only a concept drawing, not a detailed engineering drawing, and is not intended to describe complete systems, nor any particular system.
It is the responsibilit y of the system designer, not Grant UK, to determine the necessary components for and configuration of the particular system being designed including any additional equipment and safety devices to ensure compliance with building and safety code requirements.
Table 3-5: Key
Key Description
1 Expansion vessel
2 Pressure gauge
3 Pressure relief valve
4 Tundish
5 Removable filling loop
6 Double check valve
7 Automatic air vent
8 Thermostatic radiator valve
9 Automatic bypass
10 Flexible hose
11 Isolation valve
12 Buffer (optional)
13 Motorised 2-port valves
14
Optional additional circulating pump
(refer to Section 8.3.7)
15 Drain point
Optional
Section 3: Installation InformationPage 14
3.10 Before you Commission
3.10.1 Flushing and Corrosion Protection
To avoid the danger of dir t and foreign matter entering the heat pump the complete heating system should be thoroughly flushed out – both before the heat pump is operated and then again after the system has been heated and is still hot.
This is especially important where the heat pump is installed as a replacement for a boiler on an existing system.
In this case the system should be first flushed hot, before the old boiler is removed and replaced by the heat pump.
For optimum performance after installation, this heat pump and the central heating system must be flushed in accordance with the guidelines given in BS 7593:2006 ‘Treatment of water in domestic hot water central heating systems’.
This must involve the use of a proprietary cleaner, such as Sentinel X300 or X400, or Fernox Restorer.
After flushing, a suitable thermal fluid should be used (such as Sentinel R600) specifically designed for use in air source heat pump installations. This provides long term protection against corrosion and scale as well as the risk of the freezing in the ex ternal section of the heating system (i.e. the flexible hoses, condenser and circulating pump within the heat pump casing) in the event of power failure during winter months.
In order to avoid bacterial growth, due to the lower system operating temperatures, a suitable Biocide (such as Sentinel R700) should also be used in conjunction with the thermal fluid.
Both the thermal fluid and biocide should be added to the system water when finally filling the heating system.
Alternatively, Fernox HP5C can be used (or HP15C for greater frost protection).
This is a suitable thermal fluid that already contains a suitable biocide.
Full instructions on the correct use of thermal fluids and biocides are supplied with the products, but further information can be obtained from either ww w.sentinel-solutions.net or ww w.fernox.com.
Failure to implement the above guidelines by fully flushing the system and using a suitable thermal fluid and biocide corrosion inhibitor will invalidate the heat pump product guarantee.
Grant Engineering (UK) Limited strongly recommends that a Grant MagOne in-line magnetic filter/s (or equivalent*) is fitted in the heating system pipework. This should be installed and regularly serviced in accordance with the filter manufacturer’s instructions.
* As measured by gauss. The MagOne magnetic filter has a gauss measurement of 12000.
3.10.2 Anti-freeze function setting
This function is factory set to ON, i.e. DIP SW1 is set to ON (up position).
With the frost protection function set to ON, it will operate as described in Sections 8.4.1, 8.4.2 and 8.4.3.
Table 3-6: Antifreeze concentration
% Monoethylene glycol inhibitor 10% 20% 30% 40%
Freezing temperature* -4°C -9°C -15°C -23°C
Correction
factor
Capacity 0,996 0,991 0,983 0,974
Power absorbed 0,990 0,978 0,964 1,008
Pressure drop 1,003 1,010 1,020 1,033 * The temperature values are indicative. Always refer to the temperatures given for the specified product used. For details of how to access the parameter settings, refer to Section 9.3.
This function is not required if ethylene glycol is used in the heating system water to prevent freezing.
If a suitable concentration of ethylene glycol (heating system antifreeze) is used in the system water. Refer to Table 3-6 for suitable antifreeze concentrations or follow the manufacturer’s instructions supplied with the antifreeze.
If not required, frost protection function can be disabled as follows:
• Remove the wiring cover at the right hand end of the heat pump. Refer to Figure 6-1.
• Set DIP SW1 to OFF (down position). Refer to Figure 3-7.
• Replace the wiring cover and secure in place with the screws
provided.
Terminal PCB
ON
1
OFF
DIP SW. position
2 345
6 7 8
Figure 3-7: Anti-freeze function setting
Dip switch positions: Up: ON Down: OFF Refer to Sections 8.4.1, 8.4.2 and 8.4.3.
NOTE
!
Even with DIP SW1 set to OFF, to prevent the circulating pump operating for frost protection it will also be necessary to r eset four of the factory set frost protection contr ol parameters to the ‘disabled’ setting. Refer to Table 3-8.
NOTE
!
To do this, use the remote controller as follows (refer to Section 9.1 page 46):
First access the Installer level:
1. Press and hold the ‘Menu’ (3) and the ‘-‘ and ‘+’ (6) buttons together for 3 seconds to enter the installer level.
2. “InSt” parameter number “00 00” and parameter value “----“ will be shown on the display. The first two digits of the parameter number will be blinking.
Then, access the Service level:
1. Use the ‘Up’ and ‘Down’ (8) buttons to change these first two digits to 99 and then press the ‘+’ button.
Section 3: Installation Information Page 15
3.12 Installation Checklist
Location and positioning
• The vibration damping feet/shoes are fitted (if supplied)
• The heat pump is fixed to the surface or mountings that it rests
on
• Maintenance clearances comply with those given in this manual
• The position of the remote controller complies with the guidance
given in this manual
• All safety requirements have been complied with
Water circuit pipework and appliances
• Water connections have been carried out as per the information
in this manual
• All water connections are tight with no leaks
• The magnetic in-line filter is installed on the primary circuit return
as close to the heat pump as possible but still within the building and in a position that is easy to access for maintenance
• The pressure gauge with a suitable scale is installed on the
sealed system pipework or expansion vessel manifold
• The connection pipes are suitably supported so that these do not
weigh on the appliance
• The expansion vessel installed on the heating circuit is suitably
sized
• The low-loss header or buffer tank is installed if the water content
is insufficient (16kW unit only - refer to Section 3.8)
• The water circuit has been thoroughly flushed
• The air vent valves are installed at the highest points on the
system
• There is no air in the system (vent if necessary)
• The shut off valves are installed on the inlet/outlet of system
circuit
• The drain valves are installed at the lowest points in the system
• The flexible hoses are installed on the inlet/outlet of system circuit
• The system water content complies with the specification in the
manual
• The DHW immersion heater has been installed in DHW tank for
Legionella prevention
• Suitable water flow rate for operation of the entire heat pump is
achieved as specified in this manual. Refer to Section 9.12
• All pipes are insulated with suitable vapour barrier material to
prevent formation of condensation and heat loss, with control and shut-off devices protruding from the insulation
Electrical connections
• All electrical connections are secure
• Electrical connections have been carried out correctly
• Voltage is within a tolerance of 10% of the rated voltage for the
heat pump (230V)
• Electrical power supply complies with the data on the rating plate
and as specified in the manual
• The earth wires are connected securely
2. The second two digits will then blink. Use the ‘Up’ and ‘Down’ buttons to change these two digits to 99 and then press the ‘+’ (6) button.
3. The parameter value on the display will now be ‘0’.
4. Use the ‘Up’ and ‘Down’ (8) buttons to change the parameter value to “738” and then press the ‘Set’ (7) button.
Now, reset the value for parameter 4300 to 0 (disabled):
1. The first two digits of the 4-digit parameter number (the parameter group number) will blink.
2. Set the parameter group number to 43 using the ‘Up’ or ‘Down’ (8) button.
3. Press the ‘+’ (6) button and the second two digits (the parameter code) will blink.
4. Set the parameter code number to 00 using the ‘Up’ or ‘Down’ (8) button.
5. Press ‘Set’ (7) button and the parameter value 4300 (1 = enabled) will be displayed and will blink.
6. Reset the parameter value 4300 to 0 (disabled) using the ‘Up’ or ‘Down’ (8) button.
Repeat this process to reset the values of parameters 4310, 4320 and 4330 to 0.
Return to normal operation:
Press and hold the ‘Menu’ (3) and the ‘-‘ and ‘+’ (6) buttons together for 3 seconds or simply leave the remote controller for 10 minutes.
Do NOT disable the heat pump antifre eze function unless a suitable concentration of glycol is present in the system water. Refer to Table 3-6. If there are any leaks of water from the heating system and the system requires topping up then the concentration of ethylene glycol must be checked and topped up as required.
Failure to follow this instruction will invalidate the product guarantee.
NOTE
!
3.11 Completion
Please ensure that the heat pump commissioning form (supplied with the heat pump) is completed in full and that it is signed by the householder/user.
Leave the copy with the user and retain one copy for your own records.
Ensure that these installation and servicing instructions and the user instructions are handed over to the householder.
Table 3-8: Frost protection parameters
Level
Parameter
Function description
Display and input value
Remarks
Group Code Default Min. Max. Unit
S 43 00
Frost protection on room temperature
0=disable
1=enable
1 0 1 -
S 43 10
Frost protection by outside temperature
0=disable
1=enable
1 0 1 -
S 43 20
Frost protection based on outgoing water temperature
0=disable
1=enable
1 0 1 -
S 43 30
DHW storage frost protection
0=disable
1=enable
1 0 1 -
Section 4: Sealed SystemPage 16
4.1 Sealed System Requirements
2
1
2 3
4
5 6
7
8
9
15
Static head of system
10
11
10
11
13
14
12
Figure 4-1: Sealed System heating components
4 Sealed Systems
Table 4-2: Sealed System heating components key
Key Description
1 Expansion vessel
2 Pressure gauge
3 Pressure relief valve
4 Tundish
5 Removable filling loop
6 Double check valve
7 Automatic air vent
8 Thermostatic radiator valve
9 Automatic bypass
10 Flexible hose
11 Isolation valve
12 Buffer (optional)
13 Motorised 2-port valves
14
Optional additional circulating pump
(refer to Section 8.3.7)
15 Drain point
All Grant Aerona³ heat pumps must be used with sealed systems complying with the requirements of BS EN 12828, BS EN 12831 and BS EN 14336.
The system must be provided with the following items:
• Diaphragm expansion vessel complying with BS EN 13831
• Pressure gauge
• Pressure relief (safety) valve
• Approved method for filling the system
Expansion vessel
The expansion vessel can be fitted in either the return or flow pipework in any of the recommended positions as shown in Figure 4-1. To reduce the operating temperature of the expansion vessel, position it below the pipe to which it is connected.
The expansion vessel may be positioned away from the system, providing the connecting pipe is not less than 13 mm diameter. If the expansion vessel is connected via a flexible hose, care must be taken to ensure that the hose is not twisted.
Ensure that the expansion vessel used is of suf ficient size for the system volume. Refer to BS 7074:1:1989 or The Domestic Heating Design Guide for sizing the required vessel.
NOTE
!
Optional
Section 4: Sealed System Page 17
Pressure Gauge
The pressure gauge must have an operating range of 0 to 4 bar. It must be located in an accessible place next to the filling loop for the system.
Safety Valve
The safety valve (provided with the heat pump) is set to operate at 3 bar. It should be fitted in the flow pipework near to the heat pump.
The pipework between the safety valve and heat pump must be unrestricted, i.e. no valves. The safety valve should be connected to a discharge pipe which will allow the discharge to be seen, but cannot cause injury to persons or damage to propert y.
Filling Loop
Provision should be made to replace water lost from the system. This can be done manually (where allowed by the local water undertaking) using an approved filling loop arrangement incorporating a double check valve assembly. The filling loop must be isolated and disconnected af ter filling the system.
Heating System
The maximum ‘setpoint’ temperature for the central heating water is 55°C.
An automatic air vent should be fitted to the highest point of the system.
If thermostatic radiator valves are fitted to all radiators, a system by-pass must be fitted. The by-pass must be an automatic type and correctly set when the system is commissioned.
All fittings used in the system must be able to withstand pressures up to 3 bar. Radiator valves must comply with the requirements of BS 2767:1991.
One or more drain taps (to BS 2879) must be used to allow the system to be completely drained.
4.2 Filling the Sealed System
Filling of the system must be carried out in a manner approved by the local Water Undertaking.
Only ever fill or add water to the system when it is cold and the heat pump is off. Do not overfill.
!
WARNING
The procedure for filling the sealed system is as follows:
1. Check the air charge pressure in the expansion vessel BEFORE filling the system.
The expansion vessel charge pressure should always be approximately 0.2 bar lower than the maximum static head of the system, at the level of the vessel (1 bar = 10.2 metres of water).
Refer to Figure 4-1.
The charge pressure must not be less than the actual static head at the point of connection.
2. Check that the small cap (or screw) on all automatic air vents is open at least one turn. The cap (or screw) remains in this position until filling is completed and then it is closed.
3. Remove the top (6kW) and front right (10kW and 16kW) casing and loosen the plug on the automatic air vent located inside the heat pump. Refer to Figure 4-3.
loosen
tighten
Auto air vent
Plug
Figure 4-3: Auto Air Vent
4. Ensure that the flexible filling loop is connected and that the double check shut off valve connecting it to the water supply is closed. A valve is open when the operating lever is in line with the valve, and closed when it is at right angles to it.
5. Open the fill point valve.
6. Gradually open the double check valve from the water supply until water is heard to flow.
7. When the needle of the pressure gauge is between 0.5 and 1.0 bar, close the valve.
8. Vent each radiator in turn, starting with the lowest one in the system, to remove air.
9. Continue to fill the system until the pressure gauge indicates between 0.5 and 1.0 bar. Close the fill point valve. The system fill pressure (cold) should be 0.2 - 0.3 bar greater than the vessel charge pressure – giving typical system fill pressures of approx
0.5 bar for a bungalow and 1.0 bar for a two storey house. Refer to the Domestic Heating Design Guide for further
information if required.
10. Repeat steps 8 and 9 as required until system is full of water at the correct pressure and vented.
11. Water may be released from the system by manually operating the safety valve until the system design pressure is obtained.
12. Close the fill point and double check valves either side of the filling loop and disconnect the loop.
13. Check the system for water soundness, rectifying where necessary.
The air charge pressure may be checked using a t yre pressure gauge on the expansion vessel Schraeder valve. The vessel may be re-pressurised, when necessary, using a suitable pump. When checking the air pressure, the water in the heating system must be cold and the system pressure reduced to zero.
NOTE
!
4.3 Pressure Relief (Safety) Valve Operation
Check the operation of the pressure relief (safety) valve as follows:
1. Turning the head of the valve anticlockwise until it clicks. The click is the safety valve head lifting off its seat allowing water to escape from the system.
2. Check that the water is escaping from the system.
3. Top-up the system pressure, as necessary.
The expansion vessel air pressure, system pressure and operation of the pressure relief valve must be checked on each service. Refer to Section 10.
NOTE
!
Section 5: Domestic Hot WaterPage 18
5.1 Temperature Control
If a DHW demand is made, the heat pump will continue to provide space heating for a minimum period of 15 minutes (parameter 3122
- refer to Table 5-1). If space heating is already being demanded and has been on for this minimum period, then the heat pump will change over to prioritise DHW.
In either case, once DHW is being provided, the flow temperature will target 60°C, irrespective of the space heating target temperature. Also note that there is no weather compensation control when in DHW mode.
The time limit for DHW can be set using parameter 3121. The default setting is 60 minutes but you may want to increase or decrease this time period. After this time period has been reached, the heat pump will default back to the original demand that was in place prior to the DHW demand or to a stand by state if the change is demand state occurred during the DHW demand.
If the unit times out on parameter 3121, remember the motorised valve of the DHW circuit will remain open as it is controlled by the cylinder thermostat and not the heat pump and will not heat up to the correct temperature when using the space heating flow temperature. It is also possible that the cylinder could be robbed of heat to the space heating circuit if the stored water is hotter than the flow temperature to the space heating circuit.
If the motorised valve for space heating is open during DHW demand, the 60°C flow temperature will also enter the space heating circuit, increasing the recovery time of the cylinder.
To minimise this high temperature period and higher than normal running costs, ensure that space heating and DHW demand times to not occur simultaneously.
5 Domestic Hot Water
Table 5-1: DHW and space heating parameters
Level
Parameter
Function description
Display and input value
Remarks
Group Code Default Min. Max. Unit
I 31 11 DHW comfort set temperature 50.0 40.0 60.0 0.5°C
I 31 21 Ma ximum time for DHW request 60 0 900 1 min
I 31 22 Minimum time for space heating 15 0 900 1 min
For details of how to access the parameter settings, refer to Section 9.3.
5.2 Heat Pump Cylinders
As the water temperature from the heat pump is lower than from a traditional system using a boiler, a much larger coil is required inside the cylinder to transfer the heat efficiently.
Grant UK has developed a 200 litre high-efficiency cylinder (Band A) for use with a combination heat pump. Other Band B and C cylinders are available but consideration should be given to system efficiency.
In order to ensure that a minimum of at least 8K temperature difference is maintained between cylinder flow and return, the correct Grant UK heat pump cylinder must be selected to match the heat pump output.
Failure to use the correct cylinder can result in a reduced heat transfer in the cylinder and a lower temperature differential.
Section 5: Domestic Hot Water Page 19
5.3 Legionella
It is possible to use the heat pump to raise the HW cylinder to around 50 to 55°C.
For protection against Legionella the temperature can be periodically raised to 60°C using the Grant Automatic DHW Boost Kit 2, available from Grant UK (product code: HPDHWBK2).
This boost kit also allows the cylinder immersion element to be used to raise the temperature to 60°C for one hour either daily or weekly to sterilise the cylinder against Legionella.
For this system to operate, the existing immersion switch must be left set permanently to ON.
To totally prevent operation of the immersion element, the existing immersion switch must be set to OFF.
NOTE
!
5.3.1 Legionella Sanitisation Regime
Care must be given to vulnerable people who may be exposed to potentially life-threatening legionella. This group of people include the elderly, pregnant women, young children and those with breathing difficulties.
Care must also be given to households who do not use a lot of water on a daily basis. While this chart is not exhaustive, it is impor tant that you discuss any potential issues with the occupants before deciding on the appropriate regime. It is important that this decision is based on the welfare of the occupants and not on energy saving measures.
Table 5-2: Legionella group sanitisation regime
Uses less than 50 litres of hot water
per day
Uses more than 50
litres of hot water
per day
Vulnerable Group
Store at 50°C and raise
hot water cylinder to
60°C for 1 hour every
day
Store at 50°C and raise
hot water cylinder to
60°C for 1 hour every
3 days
Non-Vulnerable Group
Store at 50°C and raise
hot water cylinder to
60°C for 1 hour every
week
Store at 50°C and raise
hot water cylinder to
60°C for 1 hour every
2 weeks
If the hot water stored in the cylinder has not been used for a prolonged period of time (e.g. a few days) and has not been stored at 60°C, then it is impor tant that the temperature is raised to at least 60°C for a period of one hour before using the hot water.
!
WARNING
5.4 Automatic DHW Boost Kit
This system uses both the existing cylinder immersion heater and cylinder thermostat. This is switched via a contactor operated by a small timeswitch, both enclosed in a separate unit to be mounted next to the cylinder. Thus the immersion element can be programmed to operate for the required period on either a daily or weekly basis.
Once set, this system is fully automatic but can be overridden by the user if required. Also, the user can still switch the immersion element off, via the immersion heater switch, irrespective of the programmer or cylinder thermostat setting or whether the heat pump is operating.
5.4.1 Installation
The Automatic DHW Boost Kit 2 comes pre-wired within its enclosure, ready for installation. The connections to the Immersion heater switch, Immersion heater and cylinder thermostat must be made after it is installed on site.
When installed, this kit interrupts the electrical supply between the existing immersion heater switch and immersion heater. Refer to Figure 5-4 for electrical connection details.
In order to connect and use this kit the existing cylinder thermostat must have two output terminals; one ‘make on rise’ (normally open) contact and the other ‘break on rise’(normally closed) contact. If not, then the cylinder thermostat MUST be replaced with one that does have two output terminals.
The use of any other type of cylinder thermostat, or any modification to an existing thermostat, will invalidate the product guarantee and may result in a potentially dangerous installation.
IMPORTANT Do not alter the pre-wired connections within the enclosure and only make the external connections as shown in the wiring diagrams. See Figure 5-4.
Where a 3-phase supply is present, ensure that BOTH the immersion switch and heating system controls are taken from the same phase. If in doubt, contact a qualified electrician.
!
WARNING
Section 5: Domestic Hot WaterPage 20
5.4.2 Setting
To set the timeswitch use the following procedure:
To set the time and day:
1. Press and hold down the ‘clock’ button throughout the ‘time and day’ setting process.
2. Press ‘h+’ button repeatedly to set hour (24 hour clock).
3. Press ‘m+’ button repeatedly to set minutes.
4.
If you hold down either the ‘h+’ or ‘m+’ buttons for longer than a second the figures in the display will scroll continuously.
NOTE
!
Press the ‘day’ button repeatedly to scroll through to required day of week.
5. Release the ‘clock’ button. The clock is now running as indicated by the flashing colon.
To set switching times:
You can set up to six ON and OFF commands per day, if required, as follows:
1. Press the ‘timer’ button. The actual time will disappear from the display. The first ‘ON’ indication will be displayed.
2. Press ‘h+’ button repeatedly to set hour (24 hour clock).
3. Press ‘m+’ button repeatedly to set minutes.
4. Press the ‘day’ button repeatedly to scroll through day options – each single day, all weekdays, weekend and entire week.
5. Press the ‘timer’ button again. The first ‘OFF’ indication will be displayed.
6. Repeat steps 2 to 4 (above) to set first OFF time – hours minutes and day.
7.
Ensure that day (or days) for the OFF set ting match those for the ON setting.
NOTE
!
Press the ‘timer’ button again. The second ‘ON’ indication will be displayed.
8. Repeat the above procedure to set second ON and OFF times, if required.
9. After setting all required ON and OFF times – press the ‘clock’ button to return to current time display.
To check ON/OFF settings
Repeatedly press the ‘timer’ button to scroll through all ON and OFF settings.
To change an ON or OFF setting
When a setting is showing on the display – press the ‘h+’ ‘m+’ or ‘day’ buttons to alter the setting as required.
To delete an ON/OFF setting period
1. Press the ‘timer’ button until the ‘ON’ setting for the period to be deleted is displayed.
2. Press the ‘h+’ button repeatedly until ‘- -‘ appears (after 23 hours).
3. Press the ‘m+’ button repeatedly until ‘- -‘ appears (after 59 minutes).
4. Press the ‘timer’ button and the ‘OFF’ setting for the period to be deleted is displayed.
5. Repeat steps 2 and 3 (above) to delete the ‘OFF’ setting.
6. Press the ‘timer’ button to save the amended command.
7. The deleted ON/OFF period is now available for re-programming if required.
8. Press the ‘clock’ button to return to the current time display.
To override the timeswitch
If timeswitch is ON - press the ‘override’ button to set timeswitch to OFF.
If timeswitch is OFF – press the ‘override’ button to set timeswitch to ON.
The hot water controls must be ‘calling’ for this switch to bring the immersion on.
NOTE
!
Operation
With the Automatic DHW Boost Kit 2 fitted, the HW cylinder thermostat should be set to between 50 and 55°C for optimum operation. When the heat pump raises the cylinder to this temperature the cylinder thermostat will be ‘satisfied’ and switch to the ‘make on rise’ or ‘normally open’ connection.
The HW zone valve, being no longer fed from the cylinder thermostat, will close.
The resulting switched live from the normally open contact of the cylinder thermostat supplies power to terminal 3 on the Boost Kit timeswitch. See Figure 5-4.
When the timeswitch contact closes, at the pre-set time, the output from terminal 4 of the timeswitch energises the contactor coil, closing the contactor contacts and connecting the output from the Immersion heater switch to the immersion heater.
If, whilst the immersion heater is in operation, hot water is drawn off and the temperature in the cylinder falls to below the cylinder thermostat setting, the cylinder thermostat will operate and interrupt the power supply to the Boost kit and the immersion heater will stop operating.
In this case the heat pump will receive a HW demand to operate, to heat the HW cylinder.
If the amount of hot water drawn off is small, the temperature drop in the cylinder may be minimal and the cylinder thermostat may not detect it.
In this case the cylinder thermostat will continue to supply power to the Boost kit. The Immersion heater will continue to operate and no HW demand will be sent to the heat pump.
IMPORTANT There must be a demand from the HW channel of the heating/hot water programmer for the Automatic DHW Boost Kit 2 to operate when required. When setting the ON periods on the Auto Boost Kit timeswitch, ensure that they are within a HW ON period on the programmer.
Two separate power supplies are connected within the HW boost kit enclosure – one from the immersion heater switch and the other from the heating controls circuit. Ensure that BOTH supplies are isolated before commencing any work on the boost kit relay or switch.
A warning label informing the user of this has been fixed on the enclosure.
THIS LABEL MUST NOT BE REMOVED FROM THE ENCLOSURE.
!
WARNING
Section 5: Domestic Hot Water Page 21
Figure 5-4: Boost kit wiring diagram
1
A1
Cylinder
Stat
1 2
C
2234 3 4
1
A2
Immersion
Heater Switch
Immersion
Heater
HW Controls
To HW Valve
E N
L
E
N
L
Red
Earth connections have been excluded for
clarity. Ensure all earth connections ar e made
prior to energising.
The HW boost pack contains a power relay and
an additional 2-pole isolator and programmable
timer.
NOTE
!
Figure 5-3: Boost kit timeswitch
Day h+
Timer M+
R
MO
TU
WE
TH FR SA SU
TIMER
OFF ON
LCD display
Day button
Timer button
Clock button
Hours adjust button
Minutes adjust button
Override button
Section 6: ElectricalPage 22
6 Electrical
6.1 Wiring Centre
Electric shock may cause serious personal injury or death.
All electrical work must be undertaken by a competent person. Failure to observe this legislation could result in an unsafe installation and will invalidate all guarantees.
All electrical connections made on-site are solely the responsibilit y of the installer.
!
WARNING
All wiring connections are made to the Terminal PCB (refer to Figure 6-1) and terminal block (refer to Figure 6-3) inside the heat pump.
To access these connections, remove the wiring cover at the right hand end of the heat pump.
Terminal block
Cable clamp
ON
Reset
SW.
Pump
SW.
OFF
Terminal PCB
3
4
2
1
Remote
Controller
1
2
3
4
5
6
7
17
18
19
20
21
22
23
Humidity Sensor
COM DHW Remote
Contact ON/OFF
or EHS Alarm
GND
24VAC
COM
Control
DHW
T.probe
OUTDOOR T.probe
BUFFER
T.probe
Mix water
T.probe
3-way mixing valve
RS485
+
-
Dehumidifier
Alarm
Pump1
Pump2
Neutral
N.C.
Neutral
EHS
Heating Cooling
mode
output
Phase
Signal
3-way valve
8
9
10
11
12
13
14
Dual Set Point Control
Heating Cooling mode
Flow switch
Night mode
Low tariff
RS485 GND
45
46
47
48
49
50
31
32
24
25
26
27
28
29
30
15
16
N
41
42
43
44
51
52
Electric heater
Figure 6-1: Terminal PCB
Section 6: Electrical Page 23
6.2 Terminal PCB Input/Output
Serial connections
Terminal Function Analogue Input Digital Input
1 - 2 - 3 Remote controller 1=S1, 2=S2, 3=GND
Wire length is
maximum 100m with
1mm² shielded cables
Analogue/Digital INPUTS Table 6-2: Terminal PCB input/outputs
Terminal Function Analogue Input Digital Input
19 - 18 DHW remote contact
Voltage free contact
12V10mA
20 - 21 Configurable input -ON/OFF remote contact
28 - 29* Night mode - optional
30 - 31* Low tarif f - optional
* Requires external timer For details of how to access the parameter settings, refer to Section 9.3.
Terminal block
Cable clamp
Connection diagram
Unit side terminal
Power supply
Earth
N
)L( )N(
1 2 3
Earth wire
Power supply cord
)L( )N(
POWER
N
Do Not Use
Do Not Use
L
Figure 6-3: Power supply
6.3 Power Supply
Use a dedicated power supply with a correctly sized circuit breaker.
The final power supply connection must be made from a weatherproof lockable isolator located outside the building.
The cable should be either armoured or run in a flexible conduit between the isolator and heat pump.
Section 6: ElectricalPage 24
Cable and circuit breakers should be to EN Standards.
NOTE
!
Table 6-5: Power supply cable and breaker capacity
Model
Power supply cable (mm²)
Breaker
capacity
Maximum Minimum
HPID6 2.5 1.5 16A Class C
HPID10 4.0 2.5 20A Class C
HPID16 6.0 4.0 32A Class C
In the case of long cable runs, selection of correct cable must be done in accordance with BS 7671 (IET Wiring Regulations)
NOTE
!
Strip ends of connecting cables in accordance with Figure 6-6.
Crimp terminals with insulating sleeves can be used if required as illustrated in the diagram below for connecting the wires to the terminal block. Stranded conductors shall not be soldered.
• Use a circuit breaker with a 3 mm clearance of air gap between the contacts.
• Be sure to FULLY inser t the cable cores into the proper position
of the terminal block.
• Faulty wiring may cause not only abnormal operation but also
damage to PCB board.
• Fasten each terminal screw securely.
• To check the connections are secure, pull the cable slightly.
10 mm 30 mm
Terminal block
Crimp terminal
Stripped wire :10mm
Sleeve
Crimp terminal
Sleeve
PCB(Terminal)
Figure 6-6: Stripping the cables
It is important that the cable is stripped back 10mm. If shorter, it is possible to clamp down onto the insulation. If longer, a short circuit may occur.
!
CAUTION
Lockable isolator
Consumer
unit
Figure 6-4: Heat pump, isolator and consumer unit
Loading...
+ 56 hidden pages