Grant Euroflame 70/90, Euroflame 90/120, Euroflame 50/70 User, Installation And Servicing Instructions

USER, INSTALLATION
and
SERVICING INSTRUCTIONS
Euroflame Outdoor Condensing Oil
Boilers
For use with Kerosene only
Part No. IRL 010 Rev. 02 April 2010
with outputs from 50,000 to 120,000 Btu/h
This appliance is deemed a controlled service and specific regional statutory
requirements may be applicable.
After installing the boiler leave these instructions with the User
IMPORTANT NOTICE
This appliance must be commissioned upon installation, the information recorded and returned to
Grant Engineering (Ireland) Ltd., using the form contained within the boiler passport provided.
Failure to do so may invalidate the warranty.
EFFIC IENT HEATIN G SO LUTION S
GRANT
2
Grant Euroflame Condensing External Modules
Subject PageSection
1 Introduction .............................................. 3
2 User instructions ...................................... 4
3 Boiler technical information .................... 7
4 General boiler information....................... 10
5 Condensate disposal ................................. 19
6 Boiler installation ..................................... 22
7 Commissioning and Boiler passport ........ 30
8 Information for the user ........................... 32
9 Boiler servicing ........................................ 33
10 Wiring diagram ........................................ 36
11 Fault finding ............................................. 37
12 Burner spares ........................................... 39
13 Health and safety information .................. 41
14 EC declaration of conformity .................. 42
LIST OF CONTENTS
3
Grant Euroflame Condensing External Modules
During the combustion process, hydrogen and oxygen combine to produce heat and water vapour. The water vapour produced is in the form of superheated steam in the heat exchanger. This superheated steam contains sensible heat (available heat) and latent heat (heat locked up in the flue gas). A conventional boiler cannot recover any of the latent heat and this energy is lost to the atmosphere through the flue.
The Grant Euroflame condensing boiler contains an extra heat exchanger which is designed to recover the latent heat normally lost by a conventional boiler. It does this by cooling the flue gases to below 90° C, thus extracting more sensible heat and some of the latent heat. This is achieved by cooling the flue gases to their dew point (approximately 55° C).
To ensure maximum efficiency, the boiler return temperature should be 55° C or less, this will enable the latent heat to be condensed out of the flue gases. The boiler will achieve nett thermal efficiencies of 100%.
To achieve maximum performance from the Grant Euroflame condensing boiler, it is recommended that the heating system is designed so that a temperature differential of 20° C between the flow and return is maintained. The use of modulating circulating pumps (now widely available) and effective control systems should be considered.
The Grant Euroflame condensing boiler will however still operate at extremely high efficiencies even when it is not in condensing mode and therefore is suitable for fitting to an existing heating system without alteration to the radiator sizes. The boiler is capable of a maximum flow temperature of 75° C.
1 - INTRODUCTION
How a condensing boiler works
1.1
Heating system design considerations
1.2
To achieve the maximum efficiencies possible from the Grant Euroflame condensing boiler, the heating system should be designed to the following parameters:
Radiators:-
Flow temperature 70° C
Return temperature 50° C
Differential 20° C
Underfloor:-
Flow temperature 50° C
Return temperature 40° C
Differential 10° C
1 Size radiators with a mean water temperature of
60° C.
2 Design system controls with programmable room
thermostats or use weather compensating controls to maintain return temperatures below 55° C.
The boiler should not be allowed to operate with return temperatures of less than 40° C when the system is up to operating temperature.
3 The use of a pipe stat is recommended to control
the return temperature when using weather compensating controls.
4
Grant Euroflame Condensing External Modules
2 - USER INSTRUCTIONS
The boiler is fully automatic once switched on, providing central heating (and also heating your domestic hot water if you have a hot water cylinder fitted).
If your system includes a remote programmer, the boiler will provide hot water and central heating during the periods set on the programmer.
To gain access to the controls, remove the front panel by turning the handle and withdrawing it forwards at the bottom.
Controls for Euroflame Condensing Modules - Fig. A
1 Ensure that - There is sufficient fuel, of the correct
type, in the supply tank and all fuel supply valves are open. The water supply is on. The electricity supply to the boiler is off. The room thermostat (if fitted) is at the desired setting. The boiler thermostat is set to the required setting (see Section 2.7).
2 Switch on the electricity supply to the boiler.
3 If you have a remote programmer fitted in your
system, refer to the instructions supplied with the programmer and set the programmer. Set the HW and CH functions to TIMED. The boiler will now operate during the 'on' periods set on the programmer.
About your boiler
2.1
Boiler controls (see Fig. A)
2.2
Lighting your boiler (see Fig. A)
2.3
o
C
Overheat thermostat reset button (under screw cover)
Boiler thermostat
‘Lock-out’ reset button
Boiler front
panel removed
5
Grant Euroflame Condensing External Modules
Switch off the electricity supply to the boiler. If required, the fuel supply valve may be closed and the water and electricity supplies turned off at the mains.
To restart, refer to the full lighting instructions given in Section 2.3.
1 Check that the boiler electrical supply is ON.
2 Check that any remote programmer (if fitted) is
working and is in an 'on' period.
3 Check that all thermostats are set to the desired
setting and are calling for heat.
4 Check if the burner 'Lock-out' reset button (on the
burner) is lit. If it is, press it to start the burner. If the burner fails to light and goes to 'Lock-out' again, check that you have sufficient fuel in the storage tank and that the fuel supply valve is open. Check that the fire valve in the oil supply line has not tripped
5 Ensure that a fuse has not blown or that the
electricity supply has not failed.
6 Check to see if the safety thermostat has operated
(see Section 2.7).
If the burner still fails to light after carrying out these checks then a fault exists. Switch off the electricity supply to the boiler and contact your Service engineer.
Grant Euroflame condensing modules operate on Class C2 Kerosene only. You should always quote the type of fuel you require when ordering from your supplier.
Do not wait until the fuel runs out before you order some more. Sludge in the bottom of the tank may be drawn into the fuel lines. If it is possible, switch off the boiler when the new supply is delivered and leave the fuel to settle for an hour before restarting the boiler.
1 Boiler thermostat - This control allows the
temperature of the water leaving the boiler to heat the radiators and domestic hot water to be adjusted.
Note: If you have a cylinder thermostat on your hot water cylinder, this will control the temperature of your domestic hot water. The boiler thermostat setting must be equal to or above the cylinder thermostat setting to enable the cylinder thermostat to control the domestic hot water system.
2 Burner Lock-out reset button - If there is a
burner malfunction, a built-in safety circuit switches the burner off and the 'Lock-out' reset button (on the burner) will light. Usually such malfunctions are short lived and pressing the reset button will restore normal operation.
If the burner continually goes to 'Lock-out' a fault exists or the fuel supply is low. If you have sufficient fuel, you will need to call your Service engineer.
3 Safety thermostat - Your boiler is fitted with a
safety overheat thermostat which will automatically switch off the boiler in the case of a control malfunction causing overheating.
If your boiler goes off and you try to light it but nothing happens and the 'Lock-out' reset button on the burner is not lit, the overheat thermostat has probably operated. The boiler will not light until the thermostat is reset. To reset, unscrew the small plastic cap (see Fig. A), press the button then replace the cap.
If this condition continually repeats, contact your Service engineer.
4 Ventilation - Always ensure that the boiler has
adequate ventilation. Any ventilation openings must not be obstructed. Periodically check that they are clear.
Do not attempt to 'box in' the boiler or build a compartment around.
Do not place any combustible material around or on the boiler or flue pipe.
Do not place anything against the door of the Euroflame condensing modules that might obstruct the ventilation openings.
2 - USER INSTRUCTIONS
Turning off your boiler (see Fig. A)
2.4
Points to check if burner fails to light
2.5
About your fuel
2.6
General notes and care of your system
2.7
6
Grant Euroflame Condensing External Modules
5 Flue terminal - The flue terminal must not be
obstructed or damaged.
In severe conditions check that the terminal does not become blocked by snow.
6 Frost protection - Your Installer may have fitted a
frost thermostat. If not, and you are likely to be away for a short time, leave the boiler on with the boiler thermostat set at a low setting. For longer periods the boiler and system should be drained. Contact your Service engineer for draining and filling the system.
Note: For Euroflame condensing modules we recommend that a combined antifreeze and corrosion inhibitor be used in the primary water system.
7 Cleaning and servicing - Lightly wipe over the
case with a damp cloth and a little detergent. Do not use abrasive pads or cleaners.
You must have your boiler serviced at least once a year to ensure safe and efficient operation. Contact your Service engineer for further details.
Note: External equipment operated at 230 volts should not be serviced or repaired under adverse weather conditions.
8 Failure of electricity supply - If the electricity
supply fails, the boiler will not operate. It should relight automatically when the supply is restored.
The boiler requires a 230/240 V ~ 50 Hz supply. It must be protected by a 5 Amp fuse.
Warning: This appliance must be earthed.
If your boiler is operating on a sealed heating system, the installer will have pressurised the system and should have told you (or set it on the pressure gauge) the system pressure when cold (this is normally between 0.5 and 1.0 bar, which will increase slightly when hot). If the pressure (when cold) is below the set pressure mentioned above, you can re-pressurise the system. If the system requires frequent re-pressurising, ask your Installer or Service engineer to check the heating system for leaks and to check the expansion vessel air charge.
The boiler or system will be fitted with an automatic air vent to remove air from the system. Any air trapped in the radiators should be removed by venting the radiators using the vent screw at the top of each radiator. Only vent a radiator if the top is cool and the bottom is hot. Excessive venting will reduce the system pressure, so only vent when necessary and check the system pressure as mentioned above. Re­pressurise the system if necessary.
The boiler or system may be fitted with a safety valve to release excess pressure from the system. If water or steam is emitted from the end of the safety valve discharge pipe, switch off the boiler and contact your Installer or Service engineer.
The expansion vessel air charge must be checked annually. Failure to maintain an adequate air charge in the vessel may invalidate the warranty.
To re-pressurise the system by adding water:
1 Only add water to the system when it is cold and
the boiler is off. Do not overfill.
2 Ensure the flexible filling loop (see Fig. B) is
connected and that the shut off valve connecting it to the boiler is open and the double check valve at the front is closed. A valve is open when the operating lever is in line with the valve, and closed when it is at right angles to it.
3 Gradually open the double check valve on the front
of the filling loop until water is heard to flow.
4 Vent each radiator in turn, starting with the lowest
one in the system, to remove air.
5 Continue to fill the system until the pressure gauge
indicates between 0.5 and 1.0 bar. Close the fill point valve.
6 Repeat steps 4 and 5 as required.
7 Close the valves either side of the filling loop and
disconnect the loop.
2 - USER INSTRUCTIONS
Electricity supply
2.8
Sealed central heating system
2.9
Sealed system filling loop arrangement - Fig. B
Central heating system
Mains
water
supply
Pressure gauge
Double check valve
Shut off valve
Flexible filling hose
7
Grant Euroflame Condensing External Modules
Boiler technical data
3.1
3 - BOILER TECHNICAL INFORMATION
22 mm
22 mm
22 mm (only connect plastic pipe)
100 mm
28.5 mbar
10 mbar
28 m
1m
53 to 78° C
111° C ± 3° C
Less than 50° C
230/240 V ~ 50 Hz Fused at 5 Amp
90
4.2
0.85
¼" BSP Male (on end of flexible fuel hose)
Minimum flue draught - 8.7 N/m² (0.035 in wg)
Maximum flue draught - 37 N/m² (0.15 in wg)
2.5 bar
2.5 bar
Model
Water content litre
gal
* Weight (dry) kg
lb
Max. heat output kW
(kerosene) Btu/h
Flow connection
Return connection
Min. flow rate (∆T=10°C) l/h
Min. flow rate (∆T=20°C) l/h
Condensate connection
Flue diameter (conventional)
Waterside resistance
Flow/Return temp. diff. of 10°C
Flow/Return temp. diff. of 20°C
Maximum static head
Minimum circulating head
Boiler thermostat range
Limit (safety) stat shut off temp
Max. hearth temperature
Electricity supply
Motor power Watts
Starting current Amps
Running current Amps
Oil connection
Conventional flue
Max operating press - sealed sys
Max operating press - open sys
* Weight includes burner but excludes flue.
Euroflame Condensing Modules
70/90
13
2.9
103
227
25.6
87,350
2 200
1 100
90/120
19
4.2
121
267
34.7
118,400
22 mm
22 mm
2 980
1 490
50/70
13
2.9
103
227
20.7
70,600
22 mm
22 mm
1 780
890
8
Grant Euroflame Condensing External Modules
3 - BOILER TECHNICAL INFORMATION
Note: Grant Euroflame condensing boilers are only for use with kerosene.
Grant Euroflame condensing oil boilers using Class C2 kerosene
3.3
(kW)
15.1
18.1
20.7
20.7
22.7
25.6
25.6
30.8
34.7
(Btu/h)
51,500
61,750
70,600
70,600
77,500
87,350
87,350
105,100
118,400
Nozzle
0.50/80°EH
0.55/80°EH
0.60/80°EH
0.60/80°EH
0.65/80°EH
0.75/80°EH
0.75/80°EH
0.85/80°EH
1.00/80°EH
Oil
press.
(bar)
7.0
7.5
8.5
8.5
8.5
8.0
8.0
9.1
8.0
Smoke
No.
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
Fuel flow
rate
(kg/h)
1.29
1.53
1.78
1.78
1.95
2.19
2.19
2.65
2.93
Flue
70 - 75
75 - 80
80 - 85
85 - 90
85 - 90
90 - 95
75 - 80
85 - 90
90 - 95
CO
2
(%)
11 - 12
11 - 12
11 - 12
11 - 12
11 - 12
11 - 12
11 - 12
11 - 12
11 - 12
Heat Output
50/70
Riello RDB2.2
70/90
Riello RDB2.2
90/120
Riello RDB2.2
Model and
burner type
Sealed system data - Euroflame condensing modules with sealed system kit
3.2
Heating system pressure (cold)
Operating pressure of pressure relief valve
Expansion vessel size
Max heating system volume (including boiler)*
Cold water mains connection (for filling loop)
Pressure relief valve discharge connection
Maximum 1.0 bar, Minimum 0.5 bar
2.5 bar
12 litres (pre-charged at 1 bar)
128 litres (approximately)
15 mm compression (provided)
15 mm compression (provided)
* Based on vessel charge and system cold fill pressure of 0.5 bar
HARP/SEDBUK
efficiency
Disc setting B
Disc setting C
Disc setting C
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Burner
head/disc
setting
*
*
*
Notes:
1 The data given above is approximate only and based on the boiler using a low level flue. 2 The above settings may have to be adjusted on site for the correct operation of the burner. 3 Gas Oil is not suitable for use with the Grant Euroflame condensing boiler range. 4 The net flue gas temperatures given above are ± 10%. 5 When commissioning the air damper must be adjusted to obtain the correct CO2 level. 6 * Factory settings: 50/70 - 18.1 kW, 70/90 - 22.7 kW, 90/120 - 30.8 kW. 7 The combustion door test point may be used for CO2 and smoke readings only. Do not use this test point for temperature or
efficiency readings.
8 When setting the 50/70 to 15.1 kW output the burner air adjuster disc requires repositioning. Refer to Section 7 Commissioning.
When setting the 70/90 to 20.7 kW output the combustion head must be changed. Refer to Section 9.2 Cleaning the burner. When setting the 90/120 to 25.6 kW output the combustion head must be changed. Refer to Section 9.4 Cleaning the burner.
9 The installer must amend the boiler data label if the output is changed.
Flue gas analysis 1 Insert a combustion probe into the end of the flue terminal to measure the CO2 level. Do not use the test point in the cleaning
door.
To obtain the correct CO2 level the final flue gas reading must be taken with all the casing panels fitted. 2 The boiler efficiency and temperature must be taken from the flue test point on high level and vertical flue adaptors. 3 Low level flues do not contain a test point. The temperature and efficiency readings must be taken from the flue terminal.
Burner
head
type
T1
T1
T1
T1
T2
T2
T2
T3
T3
Flue gas temp °C
Door
155 - 160
175 - 180
185 - 190
195 - 200
205 - 210
215 - 220
190 - 195
215 - 220
220 - 225
(%)
93.0
92.4
92.1
9
Grant Euroflame Condensing External Modules
3 - BOILER TECHNICAL INFORMATION
Boiler dimensions
3.4
Fig 1 - Dimensions for Euroflame Condensing External modules
Side view
1005
797
269
50
117
179
418
660
757
804
908
Top view
797
118
210
94
160
160
507
Rear view
908
509
10
Grant Euroflame Condensing External Modules
Grant Euroflame condensing modules have an insulated weatherproof enclosure made of galvanised steel , and are designed for external installation, either against a wall or free standing some distance away from the property, as required.
For flue terminal clearances refer to page 15.
The Euroflame condensing modules are part of the Grant range of automatic pressure jet oil boilers have been designed for use with a fully pumped central heating system with indirect domestic hot water cylinder. They are not suitable for use with either a direct cylinder or a 'primatic' cylinder or gravity hot water.
The boilers are suitable for use on open vented or sealed central heating systems.
All models are supplied with the burner factory fitted.
The factory fitted low level discharge flue system can be adjusted on site for either rear, left hand or right hand flue outlet position, as required.
An external Plume Diverter kit (Fig. 14) is also available from your local stockist. Refer to Section 6.4 for further details.
All burners are pre-set for use with kerosene and are supplied ready to connect to a single pipe fuel supply system with a loose flexible fuel line and
3
/8" to 1/4" BSP
male adaptor supplied with the boiler.
If required, an additional flexible fuel line (600 mm) and
3
/8" to 1/4" BSP male adaptor are available to purchase
from your local stockist for two-pipe oil supply systems.
The temperature of the water leaving the boiler to heat the radiators and hot water cylinder is User adjustable.
The boiler is fitted with an overheat thermostat (which allows it to be used on a sealed central heating system) which will automatically switch off the boiler if the heat exchanger exceeds a pre-set temperature of 111°C ± 3°C.
The dual thermostat has a boiler thermostat control knob and the manual reset button for the overheat thermostat.
Boiler description
4.1
Boiler components
4.2
4 - GENERAL BOILER INFORMATION
Installation of a Grant boiler must be in accordance with the following recommendations:-
a Building Regulations and Building Standards
issued by the Department of the Environment and any local Byelaws etc.
b Model and local Water Undertaking Byelaws.
c Applicable Control of Pollution Regulations.
d The following OFTEC requirements:-
OFS T100 Polythene oil storage tanks for
distillate fuels.
OFS T200 Fuel oil storage tanks and tank
bunds for use with distillate fuels, lubrication oils and waste oils.
Further information may be obtained from the OFTEC Technical Information Book 3 (Installation requirements for oil fired boilers and oil storage tanks).
The installation should also be in accordance with the latest edition of the following British Standard Codes of Practice:-
BS 715 Metal flue pipes, fittings, terminals
and accessories. BS 799:5 Oil storage tanks. BS 1181 Clay flue linings and flue terminals. BS 4543:3 Factory made insulated chimneys for
oil fired appliances. BS 4876 Performance requirements for oil
burning appliances. BS 5410:1 Code of Practice for oil firing appliances. BS 5449 Forced circulation hot water systems. BS 7593 Code of Practice for treatment of
water in heating systems. BS 7671 Requirements for electrical
installations, IEE Wiring Regulations.
Failure to install and commission appliances correctly may invalidate the boiler warranty.
IMPORTANT
Before starting any work on the boiler, or fuel supply please read the health and safety information given in Section 13 on page 41.
Regulations to comply with
4.3
11
Grant Euroflame Condensing External Modules
4 - GENERAL BOILER INFORMATION
4 A metal bowl type filter with a replaceable
micronic filter must be fitted in the fuel supply line adjacent to the boiler. A shut-off valve should be fitted before the filter, to allow the filter to be serviced.
5 A flexible fuel hose, adaptor and 1/4" BSP isolation
valve are supplied loose with the boiler for the final connection to the burner. If a two pipe system or 'Tiger Loop' type de-aerator is used, an additional flexible fuel hose (600 mm) and 3/8" to 1/4" BSP male adaptor are available to purchase from your local stockist.
A de-aeration device should not be fitted within the boiler casing.
6 Metal braided flexible hoses should be replaced
annually when the boiler is serviced. Long life flexible hoses should be inspected annually and replaced at least every 60 months.
4.4.3 Single pipe system - (See Fig. 2)
1 Where the storage tank outlet is above the burner
the single pipe system should be used. The height of the tank above the burner limits the length of pipe run from the tank to the burner.
2 As supplied the burner is suitable for a single pipe
system.
4.4.1 Fuel storage
The tank should be positioned in accordance with the recommendations given in BS 5410:1:1997, which gives details of filling, maintenance and protection from fire.
A steel tank may be used and must be constructed to BS 799:5:1987 and OFS T200.
A galvanised tank must not be used.
A plastic tank may be used and must comply with OFS T100.
Note: Plastic tanks should be adequately and uniformly supported on a smooth level surface, across their entire base area.
4.4.2 Fuel pipes
1 Fuel supply pipes should be of copper tubing with
an external diameter of at least 10 mm. Galvanised pipe must not be used. All pipe connections should preferably use flared fittings. Soldered connections must not be used on oil pipes.
2 Flexible hoses must not be used outside the boiler case.
3 A remote sensing fire valve must be installed in the
fuel supply line, with the sensing head located above the burner. Recommendations are given in BS 5410:1:1997.
Fuel supply
4.4
Regional statutory requirements may deem this appliance to be a 'controlled service'.
Where this is the case, it is a legal requirement that the appliance is installed and
commissioned either under the remit of building control or by a 'Competent person' such
as a suitably qualified Oftec registered technician.
Fig. 2 - Single pipe system
Filter
Fire valve
Shut-off valve
Shut-off valve
A
Sludge valve
Fill pipe
Vent pipe
Level gauge
Fuel storage tank
Head A
(m)
Maximum pipe run (m)
0.5
1.0
1.5
2.0
10 mm OD pipe
10 20 40 60
12 mm 0D pipe
20 40 80
100
Fire valve sensor
Pump
1m
12
Grant Euroflame Condensing External Modules
4.4.5 Tiger Loop system - (See Figs. 4 and 5)
1 When the storage tank is below the burner, an
alternative to a two pipe system can be achieved using the 'Tiger Loop' type oil deaerator. This effectively removes the air from the oil supply on a single pipe lift.
2 The de-aerator is connected close to the boiler as a
two pipe system (omitting the non-return valve) as shown in Fig. 4. Refer to the manufacturers instructions supplied with the de-aerator. The de-aerator must be mounted vertically and externally.
3 To be used with a de-aerator, the burner must be
fitted with an additional flexible fuel hose (a flexible fuel hose (600 mm) and 3/8" to 1/4" BSP male adaptor are available to purchase from your local stockist. See Section 4.4.6.
4.4.4 Two pipe system - (See Fig. 3)
1 When the storage tank outlet is below the burner,
the two pipe system should be used. The pipe runs should be as shown in Fig. 3. The return pipe should be at the same level in the tank as the supply pipe, both being 75 to 100 mm above the base of the tank. The pipe ends should be a sufficient distance apart so as to prevent any sediment disturbed by the return entering the supply pipe.
2 Avoid the bottom of the tank being more than 3 m
below the burner.
3 A non-return valve should be fitted in the supply
pipe together with the filter and fire valve. A non­return valve should be fitted in the return pipe if the top of the tank is above the burner.
4 To be used with a two-pipe system, the burner
must be fitted with an additional flexible fuel hose (a flexible fuel hose (600 mm) and 3/8" to 1/4" BSP male adaptor are available to purchase from your local stockist. See Section 4.4.6.
5 The pump vacuum should not exceed 0.4 bar.
Beyond this limit gas is released from the oil.
For guidance on installation of top outlet fuel tanks and suction oil supply sizing, see OFTEC Technical Book 3. Available at www.oftec.org.uk
4 - GENERAL BOILER INFORMATION
Fig. 3 - Two pipe system
Filter
Fire valve
Shut-off valve
Shut-off valve
See
section 4.4.6
A
Return
Supply
Head A
(m)
Maximum pipe run (m)
0
0.5
1.0
1.5
2.0
3.0
3.5
10 mm OD pipe
35 30 25 20 15
8 6
12 mm OD pipe
100 100 100
90 70 30 20
Non return valve
Fire valve sensor
Sludge valve
Fill pipe
Vent pipe
Level gauge
Fuel storage tank
1m
13
Grant Euroflame Condensing External Modules
4 - GENERAL BOILER INFORMATION
4.4.6 Two pipe oil supplies
Riello RDB burner - See Fig. 6
1 The fuel pump is supplied for use with a single
pipe fuel supply system. For use on a two pipe system, it is necessary to fit the By-pass screw (see Fig. 6) into the tapping in the return port.
2 The By-pass screw is supplied in the boiler
accessory pack.
3 Remove the plastic burner cover (two screws).
4 Remove and discard the blanking plug from the
return connection of the pump and fit the By-pass screw using an hexagonal key.
5 Connect the return oil flexible fuel hose to the pump.
6 Connect the 3/8" to 1/4" BSP adaptor to the flexible
fuel hose.
7 Flexible fuel hoses and adaptors are available from
your local stockist.
Fig. 4 - De-aeration device system
Fig. 5 - Tiger loop 'de-aeration' device
Fig. 6 - Riello RDB pump
1 Oil inlet connection 2 Return connection 3 By-pass screw 4 Pressure gauge connection 5 Pressure adjuster 6 Vacuum gauge connection 7 Solenoid 8 Supply to nozzle
1
2
3
4
5
6
7
8
1/4" BSP female
connections
Tiger Loop
SUPPLY
TO PUMP
RETURN
FROM PUMP
SUPPLY
FROM TANK
Fire valve
Tankmaster
See
section 4.4.6
Sludge valve
Fill pipe
Vent pipe
Fuel storage tank
De-aeration device
e.g. Tiger Loop
See Fig. 5
Fire valve sensor
Supply
1m
Return
14
Grant Euroflame Condensing External Modules
1 A 230/240 V ~ 50 Hz mains supply is required.
The boiler must be earthed.
2 The supply must be fused at 5 Amp and there must
only be one common isolator for the boiler and control system, providing complete electrical isolation.
3 A fused double pole switch or a fused three pin
plug and shuttered outlet socket should be used for the connection.
4 The power supply cable should be at least 0.75 mm²
PVC as specified in BS 6500, Table 16.
5 All the wiring and supplementary earth bonding
external to the boiler must be in accordance with the current Wiring Regulations.
6 Any room thermostat or frost thermostat used must
be suitable for use on mains voltage.
7 The boiler requires a permanent mains supply, do
not interrupt it with any external time control.
8 In the event of an electrical fault after installation
of the boiler, the following electrical system checks must be carried out:- Short circuit, Polarity, Earth continuity and Resistance to earth.
The boiler does not come fitted with a frost thermostat. If there is a need for a frost thermostat, the installer should fit one within the casing.
4 - GENERAL BOILER INFORMATION
1 The Euroflame condensing module must stand on a
solid, level surface capable of supporting the weight of the boiler when full of water, e.g. a prepared concrete standing, paving slabs bedded down on sand/cement, or similar.
2 The Module can be installed either against the building
or 'free standing' some distance away from the building.
3 The Module must be positioned such that the
required clearances from the low level flue outlet, as shown in Fig. 7, are achieved.
4 Adequate clearance must be left around the Module
for servicing. In particular, a minimum clearance of 600 mm above the Module for removal of the top panel and 600 mm at the opposite end to the flue outlet for access to the burner.
Sufficient clearance is required at the rear of the boiler to allow the rear panel to be removed for access to the condensate trap.
5 The flue terminal must be a minimum distance of
1.8 m from an oil storage tank.
The flue terminal should be positioned so as to avoid products of combustion accumulating in stagnant pockets around the building or entering into buildings.
Electricity supply
4.5
Frost protection
4.6
Boiler location
4.7