To re-pressurise the system by adding water:
1 Only add water to the system when it is cold and the boiler
i
s off. Do not overfill.
2. Ensure the flexible filling loop is connected and that the shut
off valve connecting it to the boiler is open and the double
check valve at the front is closed.
A valve is open when the operating lever is in line with the
valve, and closed when it is at right angles to it.
3 Gradually open the double check valve on the front of the
filling loop until water is heard to flow.
4 Vent each radiator in turn, starting with the lowest one in
the system, to remove air.
5 Continue to fill the system until the pressure gauge indicates
the required pressure between 0.5 and 1.0 bar. Close the fill
point valve.
6 Close the valves either side of the filling loop and
disconnect the loop.
The temperature of the water leaving the boiler to the radiators
can be increased by turning the boiler (heating) thermostat (see
Fig. A or B) clockwise.
With the Heating switch set to TIMED, the boiler will provide
central heating whenever the timer is in an 'on' period and the
room thermostat (if fitted) is calling for heat.
For summer time operation, when central heating is not
required, set the Heating switch (see Fig. A) to HOT WATER
ONLY, or OFF for Condensing Combi (see Fig. B).
1 Boiler controls - Refer to Section 2.2 or 3.2.
2 Pressure switch - If the heating system water pressure falls
below 0.2 bar the boiler low pressure cut-out switch will
activate and an amber light will illuminate. The system must
be recharged to between 0.5 and 1 bar. If the heating system
loses pressure on a regular basis then contact your Installer
to investigate the cause.
3 Burner Lock-out reset button - If there is a burner
malfunction, a built-in safety circuit switches the burner off
and the Lock-out reset button will light. Usually such
malfunctions are short lived and pressing the reset button
will restore normal operation.
If the burner continually goes to 'Lock-out' a fault exists or
the fuel supply is low. If you have sufficient fuel, you will
need to call your Service engineer.
4 Overheat thermostat - Your boiler is fitted with a safety
overheat thermostat which will automatically switch off the
boiler in the case of a control malfunction causing
overheating. A red neon (see Fig. A or B) will light
indicating the thermostat has operated.
I
f your boiler goes off and you try to light it but nothing
happens and the 'Lock-out' reset button on the burner is not
l
it, the overheat thermostat has probably operated. The
boiler will not light until the thermostat is reset. To reset,
unscrew the small plastic cap (see Fig. A or B), press the
button then replace the cap.
N
ote: You may have to wait for the boiler to cool down
before the button will reset. If this condition continually
repeats, contact your Service engineer.
5 Ventilation - Always ensure that the boiler has adequate
ventilation. Any ventilation openings provided by the
Installer must not be obstructed. Periodically check that
they are clear.
Do not attempt to 'box in ' the boiler or build a compartment
around it before consulting your Installer.
Do not place any combustible material around or on the
boiler or flue pipe.
6 Flue terminal - The flue terminal on the outside wall must
not be obstructed or damaged.
In severe conditions check that the terminal does not
become blocked by snow.
7 Frost protection - Your Installer may have fitted a frost
thermostat. If not, and you are likely to be away for a short
time, leave the boiler on with the boiler thermostat set at a
low setting. For Ionger periods the boiler and system should
be drained. Contact your Service engineer for draining and
filling the system.
8 Cleaning and servicing - Lightly wipe over the case with
a damp cloth and a little detergent. Do not use abrasive pads
or cleaners.
You should have your boiler serviced at least once a year to
ensure safe and efficient operation.
Contact your Service engineer for further details.
9 Failure of electricity supply - If the electricity supply fails,
the boiler will not operate. It should relight automatically
when the supply is restored. Note: The time on the internal
7-day or 24-hour timer may need to be reset after a power
failure.
The boiler requires a 230/240 V - 50 Hz supply. It must be
protected by a 5 Amp fuse.
The section of any worktop (if fitted) above the boiler must
be removable to provide access for servicing the Condensing
Combi 36.
The Combi 90 V3, Combi Max and Condensing Combi 26
boilers can be serviced from the front, but it is preferable for
any worktop above the boiler to be removable to provide
the best access for servicing.
3 - COMBI V3, COMBI MAX & CONDENSING COMBI USER INSTRUCTIONS
7
Combi V3, Combi Max and Condensing Combi Models
3.6
\
General notes and care of your system
3.7
\
Electricity Supply
3.8
\
Important
The expansion vessel air charge must be checked
a
nnually. Failure to maintain an adequate air charge in
the vessel may invalidate the warranty.
Warning: This appliance must be earthed.