GRAND SOLAR BLAZING TUBES Installation, Operation And Maintenance Manual

Page 1
GRAND SOLAR INC.
BLAZING TUBES
INTEGRAL COLLECTOR STORAGE WATER HEATER
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Page 2
BLAZING TUBES INTEGRAL COLLECTOR
INSTALLATION, OPERATION AND MAINTE-
NANCE MANUAL
The Blazing Tubes domestic solar water heating system has gone through an extensive design, technical and performance review by the Solar Rating & Certification Corpora­tion (SRCC). The installation of your Blazing Tubes system is intended to be executed by properly licensed and experienced professional contractors in accordance with SRCC Standard OG-300, "Operating Guidelines and Minimum Standards For Certify­ing", and must conform to applicable federal, state and local regulations, codes, ordi­nances and standards governing the installation of solar water heating systems.
The solar energy system described by this manual, when properly installed and main­tained, meets the minimum standards established by the SRCC. This certification does not imply endorsement or warranty of this product by the SRCC.
OG-300 system certification is granted to Grand Solar by the SRCC. It may not be used for any commercial purpose without the prior written consent of Grand Solar. Grand So­lar must approve any deviation from the materials and methods described in this man­ual in writing.
Blazing Tubes units may be safely installed in areas within the continental United States that experience mild winter climates.
Because Blazing Tubes unit has superior heat conservation characteristics it may be safely installed wherever mild winters are the norm. However geographic areas, which experience continuous hard freezes, are inappropriate for Blazing Tubes installations. Do not install if local temperatures ever fall to:
10ºF / -12˚C for 6 consecutive hours, or
20ºF / -7˚C for 18 consecutive hours
Grand Solar prohibits the installation of Blazing Tubes systems in any areas susceptible to temperatures lower than those stated above. Warranty coverage is voided in the event this prohibition is ignored.
Page 3
TABLE OF CONTENTS
PREFACE ........................................................................................................................................... 1
1) INTRODUCTION ............................................................................................................................. 1
2) SYSTEM DESCRIPTION AND OPERATIONAL PRINCIPLE.......................................................... 2
3) INSTALLATION REQUIREMENTS - GENERAL - .......................................................................... 2
A. Permits .................................................................................................................................... 2
B. Code ........................................................................................................................................ 2
C. Structural & Shading Considerations ....................................................................................... 2
D. Roof and Site Inspection.......................................................................................................... 2
E. Confirmation of Installation Site ............................................................................................... 2
4) INSTALLATION REQUIREMENTS - SPECIFIC - ........................................................................... 3
A. Location, Orientation and Tilt ................................................................................................... 3
B. Blazing tubes Roof Mounting Procedures, Materials and Methods........................................... 3
C. Ground Mounting..................................................................................................................... 5
D. System Plumbing..................................................................................................................... 5
E. Plumbing Two Blazing Tubes................................................................................................... 8
F. Insulation Procedures .............................................................................................................. 8
5) SYSTEM START UP PROCEDURES ............................................................................................. 9
6) OVERHEAT PROTECTION ...........................................................................................................10
7) ROUTINE MAINTENANCE PROCEDURES ..................................................................................10
8) SYSTEM COMPONENTS ..............................................................................................................11
9) ESTIMATED COMPONENT LIFE ..................................................................................................11
10) SYSTEM MODEL NUMBERS ......................................................................................................11
Page 4
1 Grand Solar Inc. Blazing Tubes Manual
PREFACE
Let us first offer two words of grateful appreciation. Thank You! We sincerely appreciate your business. Grand Solar also wishes to say thank you for “going solar.” Solar water heating sys­tems reduce our nation’s dependence on polluting fossil fuels, minimize the greenhouse gas emissions associated with conventional water heating and, very importantly, lower your monthly utility costs.
Your Blazing Tubes system has been designed to meet exacting SRCC certification require­ments. The specific components found in your system have been selected by your contractor for their proven reliability, longevity and performance.
1) INTRODUCTION
Solar water heating systems are climate and site specific appliances. Different types of solar systems are installed around the world based upon local and regional weather and water quality conditions. System performance varies as a function of household hot water load, including daily showers and baths, laundry and kitchen uses, local ground water and ambient air tempera­tures, your home’s roof pitch and orientation and, of course, the seasonal intensity of solar ra­diation. These variables, some of which change from home to home in the same neighborhood, will determine how much energy and money your Blazing Tubes system will save on an annual basis.
This manual is intended as a basic solar water heating primer. Our goal is to familiarize you with the proper installation, operation and maintenance of your Blazing Tubes system. This sys­tem is required to be installed by properly licensed solar or plumbing contractors in accordance with SRCC certification requirements and all applicable national, state and local codes, ordi­nances and regulations governing solar water heating systems as well as good trade practices. Failure to follow the procedures and practices described in this manual can void the manufac­turer’s warranty for specific component parts.
Page 5
2 Grand Solar Inc. Blazing Tubes Manual
2) SYSTEM DESCRIPTION AND
OPERATIONAL PRINCIPLE
The Blazing Tubes is an integral collector stor­age system. Systems combine the collector and storage tank in a single roof-mounted unit. sys­tems, in general, serve as pre-heaters for con­ventional electric or gas water heaters. In some parts of the world the Blazing Tubes may serve as the sole water heater or will be used in con­junction with a tankless, wall-mounted instanta­neous gas water heater.
The Blazing Tubes also is referred to as a “pas­sive” system because it does not require me­chanical pumps, thermostats, sensors, wiring or electricity to make hot water. Your Blazing Tubes will neither freeze nor overheat during prolonged periods of disuse if installed and main­tained in accordance with the instructions con­tained in this manual.
The inherent simplicity and durability of the Blaz­ing Tubes makes it a popular choice for the con­tinental U.S. Sunbelt or markets outside the U.S. where persistent hard freezes do not occur.
The Blazing Tubes System combines collection and storage of solar heated water within eight 5” glass vacuum tubes. Mechanically attached to these tubes are eight EPDM boots, which house eight copper heat exchangers, plumbed in se­ries. Insulation surrounds these boots and their
internal heat exchangers, helping conserve the heat collected by the glass tubes. These tubes get filled with non-pressurized water, which acts as a thermal battery for collected solar energy. Pressurized domestic water flows though the copper heat exchangers upon demand. Each Blazing Tubes unit supplies 40 gallons of solar hot water in a completely passive manner. The Blazing Tubes system is used in conjunction with any conventional gas, oil or electric water heater.
3) INSTALLATION REQUIREMENTS - GENERAL -
A. Permits
The contractor shall obtain all required permits and approvals.
B. Code
The installation shall conform to all federal, state and local regulations, codes, ordinances and standards governing solar water heating system installations, and the contractor shall adhere to sound building safety and trade practices. Spe­cial consideration must be given to building code requirements for roof loading and the penetration of structural members and fire rated assemblies.
C. Structural & Shading Considera­tions
The Blazing Tubes must be located in a structur­ally sound area of the roof that will be unshaded for the majority of the day all year round. Adja­cent buildings and trees should be checked for possible winter shading. An instrument such as the Solar Pathfinder can be used for solar site analysis. (Solar Pathfinder can be reached at 605-528-6473).
D. Roof and Site Inspection
Before the installation, the contractor shall in­spect the condition of the roof and notify the homeowner of any existing roof damage or nec­essary repairs.
E. Confirmation of Installation Site
The homeowner and contractor shall confirm the location of all roof and ground mounted compo­nents in advance of the installation.
Page 6
3 Grand Solar Inc. Blazing Tubes Manual
4) INSTALLATION
REQUIREMENTS - SPECIFIC -
A. Location, Orientation and Tilt
Depending upon the model purchased, single Blazing Tubes units will weigh between 321 and 597 pounds when filled. DO NOT proceed with the installation unless the roof can safely support the unit. Consult your local building code for structural requirements before beginning the in­stallation.
The thermal performance of the Blazing Tubes is optimized in the Northern Hemisphere when the unit is mounted facing True South. Actual per­formance, however, suffers very little when the unit is oriented no more than 45º East or West of True South. The unit should be unshaded for the middle six hours of each day throughout the year.
The slope of your roof will have an impact on thermal performance. We recommend that you tilt the unit to achieve an angle from horizontal that is equal to your latitude plus an additional 10 degrees. This tilt angle favors the lower winter sun when system performance may suffer and minimizes overheating during the hot summer months.
To ensure optimal performance the unit must maintain a minimum angle from horizontal of at least 10º.
Never mount the Blazing Tubes directly or paral­lel to a flat roof.
B. Blazing tubes Roof Mounting Pro­cedures, Materials and Methods
In continental North America it is best to mount the Blazing Tubes horizontally on a south facing roof (fig 1). If necessary, the unit may be mounted on an east or west-facing roof, with the long axis perpendicular to the ridge and eve, and tilted toward the south. In two unit installations on east or west facing roofs, the Blazing Tubes must be mounted in a staggered, or “saw tooth”, con­figuration (See figure 3). For flat roof installations the unit must maintain a minimum angle from horizontal of 10˚.
The Blazing Tubes must be mounted in accor­dance with the materials and methods detailed in figures 5 to 11. Use integrated Solar Strut ano­dized aluminum mounting hardware for mounting the unit.
Secure the Solar Strut mounting hardware di­rectly to the rafters or support cross bracing. At­tach the Blazing Tubes to the Solar Strut mount­ing hardware with anodized aluminum mounting clips and a stainless steel nut, bolt, lock washer and flat washer. When the unit is flush mounted (figure 5) it should be anchored to the roof by no less than four support footings, two on each side of the unit.
Page 7
4 Grand Solar Inc. Blazing Tubes Manual
Follow these general principles when mounting the Blazing Tubes:
B.1 The roof must be rated to safely support the weight of the unit when filled with water.
B.2 The Blazing Tubes should be mounted as close to the storage tank as practical in order to minimize heat loss in the piping runs.
B.3 Grand Solar recommends that the Blazing Tubes be raised from the roof surface at least 1-1/2” to allow for rainwater and debris to pass under the unit and for proper ventilation of the roofing material.
B.4 In selecting mounting hardware and fasten­ers it is extremely important to avoid galvanic corrosion resulting from the direct contact of in­compatible metals. Use of Grand Solar anodized aluminum “Solar Strut” mounting hardware and stainless steel lag or hanger bolts, lock washers and round washers is recommended. In climates subject to severe winters or high humidity use of galvanized fasteners is prohibited.
B.5 Preserving the integrity of the roof mem­brane is the most important roofing considera­tion. Ensure that all roof penetrations required to plumb and mount the solar collector are properly flashed and sealed in accordance with standard roofing practices. Tremco “POLYroof” is the rec­ommended elastomer for sealing roof penetra­tions. Henry Co. 204, 208 or 209 roof mastic or Dow Corning Glazing Sealant also are approved sealants.
B.6 If the Blazing Tubes is mounted on a flat roof or the ground, a Blazing Tubes Tilt Mount Kit is required (figures 7 and 11). Optimal system per­formance is achieved by establishing a rack an­gle from horizontal equal to latitude plus ten de­grees
B.7 If the region is subject to hurricane condi­tions, additional steps may be required to secure the collector and mounting hardware the the structural members. In certain areas of the country, local building codes may require collec­tor wind load testing or prescribe specific mount­ing procedures. Consult your local building de­partment.
fig. 6
fig. 5
fig. 7
Page 8
5 Grand Solar Inc. Blazing Tubes Manual
C. Ground Mounting
The Blazing Tubes can be ground mounted. The unit must have a stable, permanent foun­dation. This may be either a concrete slab or four standard concrete piers embedded in the ground. All bolts and fasteners should be ei­ther cast in place or anchored and then ep­oxyed into the slab or pier. All exposed bolt threads used to secure the Blazing Tubes
mounting rack must be thoroughly coated with sili­cone oil to prevent corrosion.
Buried copper tubing must be insulated in accor­dance with the instructions in section 4F below. All insulated lines must be buried above the water ta­ble and use a clean fill such as a sand layer of 3” to 5” to protect the insulation before backfilling. All buried material must be properly sealed at all the seams and butt joints with Rubatex Contact Adhe­sive or equal. For optimum performance, the insu­lated lines should be encased in a conduit to pro­tect the material from problems associated with groundwater or frost.
D. System Plumbing
The Blazing Tubes should be plumbed with all copper and brass fittings and valves. Use of galva­nized fittings is prohibited. Solar loop piping shall be a minimum 2/4” Type-M copper tubing. 2/4” Type-L continuous soft copper tubing is recom­mended for all attic pipe runs. No tubing connec­tions or solder joints should be made in the attic. Use only lead-free solder (Englehard Silvabrite 100 is recommended). DO NOT use CPVC, PVC or any type of plastic piping in the solar loop. The Blazing Tubes can produce temperatures that will melt plastic piping.
Figure 13 details the plumbing connection between the Blazing Tubes and the conventional electric or gas water heater.
The Blazing Tubes units have pressurized water flowing through their copper heat exchangers. In
fig. 8
fig. 9 fig. 10
fig. 11
Page 9
6 Grand Solar Inc. Blazing Tubes Manual
addition the 5” diameter, six foot long, vacuum tubes and the attached EPDM boots are per­manently filled with non-pressurized water (fig­ure 12).
Each unit is designed with designated water ports. The two marked “pressurized” are where the household water flows upon demand by residents. Two half-inch ball valves are at­tached to other ports labeled “non-pressurized”. These valves are to be operated only by authorized, licensed installers. In addition one of these non-pressurized valves is equipped with a solenoid valve, which disallows unau­thorized filing during daylight hours. A light sensitive electronic unit activated the solenoid to be open only at nighttime.
In plumbing the conventional water heater use only copper and brass fittings, nipples and unions. Gal­vanized fittings and dielectric unions may not be used. All connections should be hard copper. Wa­ter heater flex hose connectors use gaskets that become brittle and compressed over time and may cause leaks.
Tank plumbing must allow for the isolation of the water heater from the city cold water supply line by means of an isolating ball valve (figure 13, valve 7). A high quality thermostatic mixing valve is a re­quired component on all OG-300 certified systems and should be plumbed in line with brass union connections for ease of future repair or replace­ment (figure 13, component 10). The specified mixing valve shall be the Heatguard model HGBASE or equal and shall have an operating range between 95ºF and 140ºF. Set the mixing valve to operate at 120ºF.
The temperatures generated by the Blazing Tubes unit will vary throughout the year. In the Northern Hemisphere the water temperature will be hottest in the spring and summer months while cooler temperatures are to be expect from November through March. On sunny days system tempera­tures may range between 110ºF to 180ºF depend­ing upon the season and hot water demand. The mixing valve described above blends the hot and cold water supplies to deliver hot water to your fix­tures at a safe, controlled temperature
Fig. 12
Page 10
7 Grand Solar Inc. Blazing Tubes Manual
Fig. 13
Page 11
8 Grand Solar Inc. Blazing Tubes Manual
WARNING: SCALDING CAN OCCUR WITHIN FIVE SECONDS WHEN WATER TEMPERATURES APPROACH 140ºF. THE MIXING VALVE SHOULD BE ADJUSTED BY YOUR CONTRACTOR TO PROVIDE WATER TO YOUR FIXTURES AT NO MORE THAN 120ºF.
All vertical copper piping from the conventional water heater to the Blazing Tubes unit shall be supported at each story at maximum intervals of ten feet (10'). Copper plumbers tape or tube strap is required to secure the piping. Piping insulation covering the copper tubing may not be crimped or compressed by the strapping material.
E. Plumbing Two Blazing Tubes
When two Blazing Tubes are plumbed together in a single system they must be plumbed in parallel in accordance with figures 14 and 15.
F. Insulation Procedures
Proper insulation of the copper tubing to and from the roof prevents heat loss and provides freeze protection. The 3/4” feed and return lines must be covered with pipe insulation of a minimum 3/4” wall thickness (specified as 7/8” X 3/4” flexible elastomeric thermal insulation, Rubatex “Insultube” or equal). A 1” wall thick­ness is highly recommended. All exposed pipe insulation must be coated with two coats of an acrylic water based paint, such as Rubatex Protective Coating or equal. The paint protects
the insulation from UV degradation, including cracking and shrinkage, and also provides mois­ture vapor protection. Inspect the insulation for cracks and signs of shrinkage every three to five years. Repaint and repair as necessary.
The 3/4”cold water supply line to the conventional water heater must be insulated with a minimum 1/2” thick elastomeric thermal insulation (specified as 7/8” X 1/2” Rubatex “Insultube” or equal) to a minimum distance of five feet (5') back from the storage tank, or to the wall if closer than 5'. The overall performance of the water heating system is enhanced if the hot water supply lines to all the fix­tures are well insulated. The insulation wall thick­ness may vary between 1/2” to 3/4” depending upon the local climate. The thicker the insulation wall the better the heat retention in the piping. If the Blazing Tubes is installed in new construction, all exposed hot water service piping in the home should be well insulated.
The outside and top of the conventional electric or gas heater also must be insulated with a water heater insulation jacket. The combined R-Value, or insulation value, of the water heater and insulation jacket should be no less than R-17. A foil-faced bubble-pack insulation material as manufactured by Reflectix, or equal, is recommended.
fig. 14 fig. 15
Page 12
9 Grand Solar Inc. Blazing Tubes Manual
An air gap between the tank jacket and the in­sulation material should be created. First apply three strips of the material around the complete tank circumference near the top, middle and bottom of the heater. Then attach the insula­tion blanket to the strips.
Thoroughly insulate the top of the water heater. Fit the insulation snuggly around the brass nip­ples or unions and temperature and pressure relief valve on the top of the water heater. If you have an electric water heater, cut two win­dows in the insulation around the access plates
covering the upper and lower thermostats and heating elements.
Insulate the area over the assess plates, but make sure that these areas always remain accessible for service or repair as necessary.
If the Blazing Tubes is installed in a new home, Grand Solar specifies that the conventional water heater have a minimum insulation value of R-20. The total insulation value of the water heater and the insulation jacket shall be no less than R-25.
The conventional water heater should not sit di­rectly on the concrete slab or floor. The heater should be placed on a well-insulated pad with a minimum insulation value of R-10. A 2” polystyrene insulation pad such as manufactured by Frost King is recommended.
5) SYSTEM START UP PROCEDURES
A. Once the Blazing Tubes is mounted and plumbed in accordance with the drawings and specifications in this manual the professional in­staller should:
Open the main cold water supply to the hot water system. Simultaneously open any hot water fixture in the home. This will send the water pressure up to the roof, filling the heat exchanger first, and then filling the conventional heater. After completion of the this phase of the start up, close the hot water fixture, but leave the cold water supply open.
Now the installer can return to the roof and fill the “non-pressurized” vacuum tubes/boot volumes. This procedure must be done before or after sun­light electronically closes the solenoid valve (which prohibits cold fill during hot daylight hours)
With the solenoid open, water pressure is available to fill the tubes. Open the two half inch ball valves at each end of the unit, first the outlet than the inlet; water will fill the tubes in parallel. Once the tubes are full, excess water will flow out of the “outlet” ball valve. Immediately shut the “inlet” ball valve, which will cause water to stop flowing out of the “outlet” valve. Finally shut the “outlet” valve and the filling process is complete. An internal diaphragm (see fig 18) will allow the water thermal expansion, which will occur each heating cycle.
Page 13
10 Grand Solar Inc. Blazing Tubes Manual
If you have an electric water heater DO NOT turn on the electricity to the heater until the tank is completely filled.
Make sure the tank is completely filled by open­ing and running a hot water fixture in the home, or by opening the pressure and temperature relief valve if located on the top of the water heater (Note: on some water heaters the tem­perature and pressure relief valve is located on the side of the tank near the top). It only takes 8 seconds to destroy the heating elements in an electric water heater if they are not completely submerged when the tank is first energized. Be careful.
A properly licensed contractor must make the final electrical or gas connection to the conven­tional water heater.
The thermostat on the electric or gas water heater should be set no higher than 120 de­grees. Use the “low” or “warm” setting if the thermostat is not calibrated in degrees.
6) OVERHEAT PROTECTION
The Blazing Tubes unit is designed to efficiently capture sunlight and heat water within an ap­propriate temperature range for domestic uses. Overheating is normally never an issue due to the ratio of solar interception area to water vol­ume. Therefore, high pressure and high tem­peratures (above 200˚F) are avoided. However, for ultimate safety each unit has a temperature and preassure relive valve attached.
7) ROUTINE MAINTENANCE PROCEDURES
A. Make sure that the Blazing Tubes glass stays clean. Hose off any caked on dirt or dust and then clean the glass with Windex or a household glass cleaner and a soft cloth.
B. Check the exterior exposed pipe insulation an­nually. Repaint as necessary to prevent cracking and shrinkage. Repair any exposed areas immedi­ately.
C. In the unusual instance of glass tube breakage, the glass tube should be replaced immediately. Contact your installation contractor.
D. The Blazing Tubes is capable of generating very high temperatures in some climates for eight to ten months a year. If the water temperature in your back-up heater is consistently in the range of 140º­160ºF, you may want to change the magnesium anode rod in your back-up water heater every five years. This “sacrificial anode” is installed in the heater to prevent internal corrosion and premature tank failure. Internal corrosion accelerates at higher tank temperatures. By replacing the anode rod every five years the life of the back-up water heater typically can be extended.
fig. 18
Page 14
Page 15
BLAZING TUBES SRCC OG-300 LABEL SET
The following labels must be attached to the relevant valves in the system in order for it to be considered OG-300 compliant. This page should be laminated, each label cut from it, punched in the margin at the left hand side and affixed to the appropriate valve with a wire tie, plastic ties are inappropriate due to high operating temperatures. Failure to affix these labels w ill void the SRCC OG-300 system certification.
Blazing Tubes units may be safely installed in areas within the continental United States that experience mild winter climates. Because of the large volume of water in the unit the Blazing Tubes does not readily freeze. The Blazing Tubes, however, is susceptible to freeze damage if installed in any location where local temperatures have ever fallen to:
10ºF / -12˚C for 6 consecutive hours, or
20ºF / -7˚C for 18 consecutive hours
Where these environmental conditions are met or exceeded the unit must not be installed. Failure to do so will void the warranty coverage.
LABELS
VALVE 5B DRAIN VALVE
THESE BRASS BOILER DRAINS ARE NORMALLY CLOSED AND CAPPED. USE THESE VALVES TO DRAIN THE RETURN LINE FOR THE BLAZING TUBES. ATTACH A GARDEN HOSE TO BOTH DRAIN VALVES. TERMINATE THE HOSES IN EITHER A SERVICE BASIN OR AN APPROPRIATE SPOT OUTSIDE THE HOUSE. OPEN BOTH BOILDER DRAINS AT ONCE TO DRAIN THE UNIT. BE EXTREMELY CAREFUL WHEN DRAINING THE HOT WATER FROM THE BLAZING TUBES. THE WATER MAY BE DISCHARGED AT A VERY HIGH TEMPERATURE.
VALVE 7 COLD WATER SUPPLY ISOLATION VALVE
THIS VALVE IS NORMALLY OPEN AND ALLOWS POTABLE WATER TO FILL THE BLAZING TUBES AND SUPPLEMENTAL WATER HEATER. WHEN CLOSED THE BLAZING TUBES AND SUPPLEMENTAL WATER HEATER ARE ISOLATED FROM THE PRESSURIZED CITY COLD WATER SUPPLY LINE PIPING.
Loading...