Grandaire R4H3 Series, WCH3**4Series Installation Instructions Manual

INSTALLATION INSTRUCTIONS
R410A Split System Heat Pump
Product Family: R4H3, WCH3**4
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Inspect New Unit 2.............................
Safety Considerations 2.........................
Location 2.....................................
Clearances 2..................................
Unit Support 2.................................
Refrigeration System 3.........................
Electrical Wiring 8..............................
Defrost System 10.............................
Startup Procedure 12..........................
Refrigerant Charge 12..........................
Sequence of Operation 16.......................
Maintenance 16................................
R410A Quick Reference Guide 17...............
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per­sons could result in equipment malfunction, prop­erty damage, personal injury and/or death.
The information contained in this manual is in­tended for use by a qualified service technician fa­miliar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.
WARNING
428 01 5301 05 2/6/14
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
INSPECT NEW UNIT
After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim.
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the dealer/distributor for information and assistance. The qualified installer must use factory authorized kits and accessories when modifying this product. Refer to the individual instructions packaged with the kit or accessory when installing.
The weight of the product requires careful and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use a heat sinking material such as a wet rag − during brazing operations. Keep a fire extinguisher available. Consult local codes and the National Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or maintenance can void the warranty.
!
CUT HAZARD
Failure to follow this caution may result in proper­ty damage.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
CAUTION
LOCATION
Check local codes for regulations concerning zoning, noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or bedroom windows. Noise may carry into the openings and disturb people inside.
Locate unit in a well drained area, or support unit high enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will be discharged onto unit (as from dryer vents).
Locate unit away from recessed or confined areas where recirculation of discharge air may occur (refer to CLEARANCES section of this document).
Rooftop installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require wind baffles. Consult the manufacturer for additional information.
CLEARANCES
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (610 mm) clearance to service end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6 in. (152.4 mm) clearance on one side of unit and 12 in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66m). Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. (152.4mm) above roof surface.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage
R410A systems operate at higher pressures than R22 systems. When working with R410A sys­tems, use only service equipment and replace­ment components specifically rated or approved for R−410A service.
2 428 01 5301 05
WARNING
CAUTION
UNIT SUPPORT
NOTE: Unit must be level | 2 degrees {a inch rise or3/8 fall
per foot of run (10mm rise or fall per 305 mm of run) } or compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel, or pressure− treated timbers approved for ground contact. Soil conditions must be considered so that the platform or pad does not shift or settle and leave the unit partially supported. Minimum pad dimensions are shown in Figure 2.
If beams or an open platform are used for support, it is recommended that the soil be treated or area be graveled to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is recommended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
C. FASTENING UNIT DOWN
!
CAUTION
If conditions or local codes require the unit be attached in place, remove the knockouts in the base pan and install
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Top surface of platform must be above estimated snow­fall level to prevent snow blocking coil and to allow water melt to drain from unit.
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof, locate unit minimum 6 inches
tie down bolts through the holes (refer to Figure 2). Contact local distributor for hurricane holddown details and
the P.E. (Professional Engineer) certification, when required.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Inadequate unit support may cause excessive vibration, noise, and/or stress on the refrigerant lines, leading to re­frigerant line failure.
(152mm) above roof level. Place the unit over one or more load bearing walls. If there
are several units, mount them on platforms that are selfsupporting and span several load bearing walls. These suggestions are to minimize noise and vibration transmission through the structure. If the structure is a home or apartment, avoid locating the unit over bedrooms or study.
NOTE: When unit is to be installed on a bonded guaranteed roof, a release must be obtained from the building owner to free the installer from all liabilities.
REFRIGERATION SYSTEM
A. COMPONENT MATCHES
Check to see that the proper system components are in place, especially the indoor coil.
R410A outdoor units can only be used with R410A specific indoor coils. If there is a refrigerant mis−match, consult the indoor coil manufacturer to determine if a refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed to achieve maximum efficiency when used with indoor coils that utilize a TXV refrigerant metering device or Piston with Teflon ring
Figure 2 Tie Down Knockouts
metering device. If any other type of metering device is installed on the indoor coil, consult the indoor coil
3/8” (10mm) dia. Tie Down Knockouts In Base Pan (2 places)
View From Top
manufacturer to determine if a conversion kit is available.
Installing with TXV.
When installing a TXV on an indoor coil, follow the instructions provided with the new TXV.
A typical TXV installation is shown in Figure 1.
Figure 1 Typical TXV Installation
INDOOR
COIL
C
Base
Pan
Depth
EQUALIZER TUBE
A
Base Pan Width x
Depth
23x23
(584x584)
2511/16x25−11/16
(652x652)
311/8x311/8
(791x791)
428 01 5301 05 3
Base Pan Width
Inches (mm)
Tie Down
Knockouts
A B C
73/4 (197)
91/16
(230)
91/16
(230)
47/16
(113)18(457)
47/16
(113)
61/2
(165)
211/4
245/8
B
Minimum
Mounting Pad
Dimensions
23x23
(584x584)
(540)
(625)
26x26
(660x660)
311/2x311/2
(800x800)
Specifications subject to change without notice.
SENSING BULB
TXV
10 O’Clock
7/8
2 O’Clock
SUCTION TUBE
IN. OD & SMALLER
SUCTION TUBE
LIQUID TUBE
SENSING BUL
STRAP
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Installing with Indoor Piston cooling operation. (Heat pumps also use an outdoor piston for heating
operation, refer to section F.)
Check piston size shipped with indoor unit to see if it matches required indoor piston size shown on outdoor unit rating plate.
If it does not match, replace indoor piston with cooling
piston, according to size marked on outdoor unit rating plate. (Some outdoor models include a cooling piston in the accessory bag.)
Heating piston is shipped in the service valve refer to section F.
Example fan coils with piston: FEM4P, FSM4P, FSU4P, FMA4P, FMC4P, FMU4P, WAPM, WAPT, WAPL, WAMA, WAMC.
See Figure 2. When changing indoor piston, use a back−up wrench.
Finger tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ftlbs (40.7 Nm).The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of distributor body, and must be installed properly to ensure proper seating in the direction for cooling operation.
Figure 2 Indoor (cooling) Piston
BRASS
HEX NUT
TEFLON SEAL
TEFLON RING
PISTON
FLOW IN COOLING
PISTON RETAINER
DISTRIBUTOR
BRASS HEX BODY
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation.
Refer to Product Specifications and Long Line Applications Guideline for line set sizing.
NOTE: Total line set length must not exceed 200 feet
(61m). NOTE: A crankcase heater must be used when the
refrigerant line length exceeds 80 feet (24.4m). If outdoor unit is more than 10 feet (3m) higher than the
indoor coil, refer to the Long Line Applications Guideline for instructions.
NOTE: When the outdoor unit is higher than the indoor coil, the vertical separation must not exceed 100 feet (30m).
NOTE: When the outdoor unit is lower than the indoor coil, the vertical separation must not exceed 50 feet (15.2m).
If it is necessary to add refrigerant line in the field, use dehydrated or dry, sealed, deoxidized, copper refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing until connections are ready to be made.
Be extra careful when bending refrigeration tubing. Tubing can “kink” easily, and if this occurs, the entire length of tubing must be replaced.
!
PERSONAL INJURY HAZARD
Failure to relieve system pressure could result in personal injury and/or death.
Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal. Use all service ports and open all flow control devices, including solenoid valves.
WARNING
STRAINER
!
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation. If using a TXV in conjunction with a singlephase reciprocat­ing compressor, a compressor start capacitor and relay are required. Consult outdoor unit presale literature for start as­sist kit part number.
4 428 01 5301 05
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improp­er product operation.
L10S017
Specifications subject to change without notice.
Do not leave system open to atmosphere any lon­ger than absolutely required for installation. Inter­nal system components especially refrigerant oils are extremely susceptible to moisture con­tamination. Keep ends of tubing sealed during installation until the last possible moment.
C. ROUTING AND SUSPENDING REFRIGERANT
LINES
Run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line. Both lines should be insulated when routed through an attic or when routed through an underground raceway.
CAUTION
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
When routing refrigerant lines through a foundation or wall, do not allow refrigerant lines to come in direct contact with the building structure. Make openings large enough so that lines can be wrapped with extra insulation. Fill all gaps with RTV caulk. This will prevent noise transmission between the tubing and the foundation or
Along floor or ceiling joists, suspend refrigerant lines so that they do not contact the building structure, water pipes, or ductwork. Use insulated or suspension type hangers. Metal straps must be at least 1” (25mm)wide to avoid cutting into the tube insulation. Keep the liquid and suction lines separate. Refer to Figure 3.
wall.
Figure 3 Routing and Suspending Refrigerant Lines
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL SUSPENSION
!
CAUTION
LIQUID TUBE
SUCTION TUBE
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
1” (25mm) MIN
Figure 4
JOIST
INSULATION
SUCTION TUBE
LIQUID TUBE
Liquid Line Filter−Drier
Installed at Indoor Coil
UNIT OPERATION HAZARD
Failure to follow this caution may result in improp­er product operation.
Do not bury more than 36” (1m) of line set under­ground. Refrigerant may migrate to cooler buried section during extended periods of unit shut down, causing refrigerant slugging and possible compressor damage at start−up. If ANY section of the line set is buried under­ground, provide a minimum 6” (152mm) vertical rise at the service valve.
D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT
Proper oil return to the compressor should be maintained with suction gas velocity. If velocities drop below 1500 fpm (feet per minute), oil return will be decreased. To maintain suction gas velocity, do not upsize vertical suction risers.
E. LIQUID LINE FILTER−DRIER
Outdoor units are shipped with an appropriate filterdrier for installation in the liquid line. Leave the plugs in the tube ends until the filterdrier is installed. The optimal location for the filterdrier is close to the indoor coil. Heat pump filterdriers are “biflow” type. Either end can be pointed towards indoor coil. Refer to Figure 4.
428 01 5301 05 5
FilterDrier
F. SERVICE VALVES
Service valves are closed and plugged from the factory. Outdoor units are shipped with a refrigerant charge sealed in the unit. Leave the service valves closed until all other refrigerant system work is complete or the charge
Specifications subject to change without notice.
381184
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
will be lost. Leave the plugs in place until line set tubing is ready to be inserted.
Heat pumps require a piston metering device in the liquid service valve for proper heating operation. Piston is shipped in the piston body of the liquid service valve, temporarily held in place with a plastic cap. Do not remove the plastic cap until line set tubing is ready to be installed.
Refer to Figure 5 and follow these steps for piston installation:
1. Remove plastic cap holding piston in piston body of liquid service valve.
2. Check that piston size (stamped on side of piston) matches with number listed on unit rating plate. Return piston to piston body of liquid service valve (either direction).
3. Find plastic bag taped to unit containing copper adapter tube, brass nut, and plastic washer.
4. Install plastic washer in the seat inside piston body.
5. Fit brass nut onto adapter tube and install tube onto liquid service valve. Tighten nut finger tight, then wrench additional ½ turn only 15ft lbs. Over tightening may damage the plastic washer.
Service valve bodies are brass and suction tube stub is copper.
helps prevent overheating and damage to valve seals (refer to Figure 5). Replace valve core when brazing is completed.
!
FIRE HAZARD
Failure to remove refrigerant and oil charge before brazing could result in personal injury, death, and/ or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes and contacts brazing torch. Make sure the refrigerant charge is properly removed from both the high and low sides of the system be­fore brazing any component or lines.
Clean line set tube ends with emery cloth or steel brush. Remove any grit or debris.
Insert line set tube ends into service valve tube stubs. Apply heat absorbing paste or heat sink product between
service valve and joint. Wrap service valves with a heat sinking material such as a wet cloth.
Braze joints using a SilFos or Phoscopper alloy.
WARNING
Figure 5
LIQUID SERVICE VALVE
VALVE CORE
G. BRAZING CONNECTIONS NOTE:
For Liquid Service Valve − Braze lineset to adapter tube BEFORE bolting adapter to valve. This helps prevent overheating and damage to plastic washer or o−ring.
For Vapor Service Valve remove valve core from schrader port on Service Valve BEFORE brazing. This
6 428 01 5301 05
Liquid Service Valve with Heating
Piston and Adapter Tube
BRASS NUT
ADAPTER TUBE
PLASTIC WASHER
PISTON
PISTON BODY
Vapor Service Valve
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Braze with SilFos or Phoscopper alloy on cop­pertocopper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV.
H. EVACUATING LINE SET AND INDOOR COIL
The unit is shipped with a factory refrigerant charge. The liquid line and suction line service valves have been closed after final testing at the factory. Do not disturb these valves until the line set and indoor coil have been evacuated and leak checked, or the charge in the unit may be lost.
NOTE: Do not use any portion of the factory charge for purging or leak testing. The factory charge is for filling the system only after a complete evacuation and leak check
SERVICE VALVE
has been performed.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Never use the outdoor unit compressor as a vacu­um pump. Doing so may damage the compressor.
Line set and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. If deep vacuum equipment is not available, the alternate triple evacuation method may be used by following the specified procedure.
Specifications subject to change without notice.
CAUTION
CAUTION