Grandaire 4860, 2436 Installer's Manual

1
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the in­stallation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Condensing Units
Installer’s Guide
Split System Heat Pump
Up to 18 SEER
2-3-4-5 Ton Capacity
R410A
Table of Contents
Section 1. Safety............................................................................2
Section 2. Unit Location Considerations.....................................3
Section 3. Unit Preparation...........................................................5
Section 4. Setting the Unit............................................................5
Section 5. Refrigerant Line Considerations................................6
Section 6. Refrigerant Line Routing.............................................7
Section 7. Refrigerant Line Brazing.............................................8
Section 8. Refrigerant Line Leak Check....................................10
Section 9. Evacuation..................................................................11
Section 10. Service Valves..........................................................11
Section 11. Electrical - Low Voltage...........................................12
Section 12. Electrical - High Voltage..........................................13
Section 13. Start Up.....................................................................14
Section 14. System Charge Adjustment....................................15
Section 15. System operation and Troubleshooting.................19
NOTE: Appearance of unit may vary.
2
Section 1. Safety
Important - This document contains a wiring diagram
and service information. This is customer property and is to remain with this unit. Please return to service informa­tion pack upon completion of work.
Failure to follow this warning could result in property damage, severe personal injury, or death. Disconnect all electric power, Including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.
HAZARDOUS VOLTAGE!
Any attempt to repair a central air conditioning product may result in property damage, severe personal injury, or death. These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems with variable speed compressors use a PVE oil that readily absorbs moisture from the atmosphere To limit this ‘hygroscopic“ action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement.
May cause minor to severe burning. Failure to follow this Caution could result in property damage or personal injury. Do not touch top of compressor.
REFRIGERANT OIL!
HOT SURFACE!
Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening system.
CONTAINS REFRIGERANT!
Failure to inspect or use proper service tools may result in equipment damage or personal injury. Reconnect all grounding devices. All parts of this product that are capable of conducting electrical current are grounded. if grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
GROUNDING REQUIRED!
Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and/or property damage. Extreme caution should be exercised when opening the Liquid Line Service valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. No torque is required.
SERVICE VALVES!
Failure to inspect lines or use proper service tools may result in equipment damage or personal injury. If using existing refrigerant lines make certain that all joints are brazed, not soldered.
BRAZING REQUIRED!
Failure to follow this warning could result in property damage, severe personal injury, or death. Earth connection essential before connecting electrical supply.
HIGH LEAKAGE CURRENT!
WARNING
CAUTION
CAUTION
WARNING
WARNING
WARNING
CAUTION
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
CAUTION
WARNING
3
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure.
Maximum line length = 100 feet.
Maximum vertical length = 50 feet.
Compressor crankcase heat is required for line
lengths over 50 feet.
Use only the line diameters indicated in Table
5.1.
Section 2. Unit Location Considerations
2.1 Unit Dimensions
2.2 Refrigerant Piping Limits
Unit Dimensions
Models H x W x L(Inches)
2436
4860
24-15/16 x 29-1/8 x 29-1/8
33-3/16 x 29-1/8 x 29-1/8
Standard Line Set 100 ’ Max Line Length
50’ Max Line Lift
50’
Max
Line
L
if t
L
H
W
See Product Specifications for unit's weight.
4
Min. 20” to Shrubber y
Av oid Install Near Bedroom s
Min. 60” Unrestricted
Access Panel
Min. 24” Unrestricted
2.4 Location Restrictions
Ensure the top discharge area is unrestricted for at least 60 inches above the unit.
Do not locate outdoor unit near bedrooms since normal operational sounds may be objectionable.
Min. 20” to Shrubber y
Position unit to allow adequate space for unobstructed airflow, wiring, refrigerant lines, and serviceability.
Allow a minimum of 12 in. clearance on one side of access panel to a wall and a minimum of 24 in. on the adjacent side of access panel.
Maintain a distance of 24 in. between units.
Position unit so water, snow, or ice from roof or overhang cannot fall directly on unit.
Note: It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below-freezing temperatures occur.
• Units should be elevated 3-12 inches above the pad or rooftop, depending on local weather. This addi­tional height will allow drainage of snow and ice melted durIng defrost cycle prior to its refreezlng. Ensure that drain holes in unit base pan are not obstructed, preventing drainage of defrost water.
• If possible, avoid locations that are likely to accu­mulate snow drifts. if not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.
Min 12"
Snow barrier
3- 12" Elevation
Snow legs
pad
Cold Climate Considerations (Heat Pump Only)
Min. 12” to wall.
Access Panel
5
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report promptly to
the carrier any damage found to the unit.
The charge port can be used to check to be sure the refrigerant charge has been retained during shipment.
Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following:
The pad should be at least 1-2” larger than the unit
on all sides.
The pad must be separate from any structure.
The pad must be level.
The pad should be high enough above grade to
allow for drainage.
The pad location must comply with National, State,
and Local codes.
IMPORTANT NOTE:
These instructions are intended to provide a method to tie-down system to cement slab as a securing procedure for high wind areas. It is recommended to check Local Codes for tie-down methods and protocols.
SEE DETAIL A
#7 X 3/8” Self Tapping Screws (Don’t Exceed 3/8” long)
1/4” Χ 1-1/2” Hex Washer Head Concrete Screws (3/16” Pilot Hole Needed. Pilot Hole Should Be1/4” Deeper Than The Fastener Embedment)
DETAIL A
Brackets: 2” width, 1/16” thickness, height as required. Available from distributor or in market place.
The dimension see Unit Dimensions.
6
Determine required line length.
Section 5. Refrigerant Line Considerations
5.1 Refrigerant Line and Service Valve Connection Sizes
5.2 Required Refrigerant Line Length
Line Sizes Service Valve Connection Sizes
Model
Suction
Line
Liquid
Line
Suction Line
Connection
Liquid Line
Connection
2436
4860
3/4 3/8 3/4 3/8
7/8 3/8 7/8 3/8
Table 5.1
Line Lengt h
5.3 Refrigerant Line Insulation
Important: The Suction Line must always be insulated. DO NOT allow the Liquid Line and Suction Line to come in direct (metal to metal) contact.
Suction Line
Liquid Line
Insulation
7
5.4 Reuse Existing Refrigerant Lines
For retrofit applications, where the existing refrigerant lines will be used, the following precautions should be taken:
Ensure that the refrigerant lines are the correct
size. Refer to Section 2.2 listed and Table 5.1.
Ensure that the refrigerant lines are free of leaks,
acid, and oil.
CAUTION
!
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
For Example:
When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
Isolate the lines from all ductwork.
Minimize the number of 90º turns.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.
Isolation From Joist/Rafter
Side View
8 Feet Maximum
Joist/Rafter
Isolator
Line Set
8 Feet Maximum
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacturer’s split systems are A.H.R.I. rated only with TXV indoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum per ­formance and the best overall system reliability.
Secure Suction line from joists using isolators every 8 ft. Secure Liquid Line directly to Suction line using tape, wire, or other appropriate method every 8 ft.
8
Isolation In Wall Spaces
Side View
Wall
Isolator
Line Set
8 Feet Maximum
Secure Suction Line using isolators every 8 ft. Secure Liquid Line directly to Suction Line using tape, wire, or other appropriate method every 8 ft.
8 Feet Maximum
Isolation Through Wall
DO NOT hang line sets from ductwork
Sealant
Insulation
Suction Line
Wall
Ductwork
Isolator
Line Set
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a deburing
tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.
9
STEP 2 - Remove the pressure port cap from both service valves.
STEP 3 - Purge the refrigerant lines and indoor coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
Check liquid line filter drier’s directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as il ­lustrated. Braze the filter drier to the Liquid Line.
Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
Note: Install drier in Liquid Line.
This pipe must have a thimble
10
STEP 5 - Replace the pressure tap caps after the service valves have cooled.
STEP 2 - Check for leaks by using a soapy solution or bubbles at each brazed location.
Section 8. Refrigerant Line Leak Check
8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and evapo -
rator coil to 150 PSIG using dry nitrogen.
150 PSI
G
11
Section 9. Evacuation
9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.
STEP 1 - Evacuate until the micron gauge reads no higher than 350 microns, then close the valve to the vacuum pump.
STEP 2 - Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
1 MIN.
Section 10. Service Valves
10.1 Open the Service Valves
Important: Leak check and evacuation must be com ­pleted before opening the service valves.
Important: The Suction Service Valve must be opened first BEFORE opening the Liquid Service Valve!
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert hex wrench into the stem
and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns.)
STEP 3 - Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 4 - Repeat STEPS 1 - 3 for Liquid Service Valve.
Cap
Rolled Edge to
Captivate Stem
Hex Headed
Valve System
Service Port
3/16” Hex Wrench
for Liquid Service Valve
5/16” Hex Wrench
for Suction Service Valve
Unit Side
of Service
Valve
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclock ­wise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
0350
Micr ons
ON OFF
WARNING
!
REQUIRED PARTS LIST
Loading...
+ 24 hidden pages