Granby Furnaces KLC-100 C User Manual

23
7.0 SERVICE AND MAINTENANCE
REGULAR MAINTENANCE
Check complete operation at least once a year. In Canada see CANB139, (Maintenance), in Unites States see NFPA 31, for recommended servicing procedure. Clean flue pipes on a regular basis. Check flue and combustion air pipes for any leak.
CHANGING NOZZLE
It is recommended that the nozzle be replaced once a year. If a new nozzle of a different size is installed, change the blower speed according to section BURNER INSTALLATION
AND
SPECIFICATIONS or operating decal as required.
7.1 CLEANING HEAT EXCHANGER
Heat exchanger must be inspected every heating season. Refer to instructions and pictures below.
After cleaning, do not forget to put back the baffles!!
IMPORTANT SEE WARNING PAGE 7
CONDENSATE NEUTRALIZER
The media bag contained within the condensate treatment tank should be replaced once per year or for every 600 USG (2300L) of oil used in the furnace or if the PH level at the outlet of the treatment tank falls below 5.0 (whichever comes first). A replacement media bag can be acquired from your local dealer.
The condensate from the furnace is slightly acidic with a pH of about 4; a neutral fluid would have a pH of 7. If the condensate is not conditioned, damage could result in waste water handling system which would result in expensive repairs.
Step 1: Remove top rear panel and condensing pan
!
Step 2: Remove & inspect baffles
Step 3: Clean the round tubes, if needed (use a 1-1/4’’ diameter brush)
Step 4: Remove burner
Step 5:
Clean combustion chamber, if needed
24
During the first hours of operation. The appliance self-cleans its interior. The result being that for the first 20 hours of activity, the condensate liquid will be brownish and thereafter stabilize and become of normal ‘’water’’ color.
AIR FILTERS
To maintain furnace performance and safety, replace dirty filters at least once every heating season or as required. Use new approved disposable filters of the same size and type. Dirty, clogged or wrong sized filters will impair the furnace performance and may cause the furnace to shut down or overheat.
7.2 BLOWER REMOVAL
This furnace has a blower sealing system, which is designed to be tight and rattle free. Refer to the instructions and pictures below.
1) Shut off oil and power to furnace.
2) Open blower compartment.
3) Disconnect the wiring to the blower motor.
4) Remove the air filter.
5) Remove the four (4) wing nuts securing the blower side to the base panel bracket.
6) Slide the blower toward you and then lift the blower straight up. Shift the blower out of the furnace.
Put back the blower assembly using the reverse procedure. Ensure wiring and ground wire are correctly reconnected.
Wing!Nuts!
25
8.0 ELECTRICAL / WIRING DIAGRAM
$
!
!
!
Loading...