Graco G3-G-24MX-2L0L00-10CV00R0, 96G020, 96G019, G3-G-24MX-2LFL00-10CV00R0, G3-G-ACMX-2LFL00-1D0V0000 Instruction Manual

...
Instructions
TI14705
Conforms to ANSI/UL 73 Certified to CAN/CSA Std. 22.2 No 68-09
3132066
G3 Max Automatic
332305B
Lubrication Pump
For dispensing of NLGI Grades #000 to #2 greases and oil with at least 40cSt. For Professional Use Only.
Not approved for use in explosive atmospheres or hazardous locations.
5100 psi (35.1 MPa, 351.6 bar) Maximum Working Pressure
EN
Important Safety Instructions
Read all warnings and instructions in this manual. Save these instructions.
Contents
Part / Model Numbers . . . . . . . . . . . . . . . . . . . . . . . 3
2 Liter Models . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4 Liter Models . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
8 Liter Models . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
12 Liter Models . . . . . . . . . . . . . . . . . . . . . . . . . . 4
16 Liter Models . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Understanding the Model Number . . . . . . . . . . . 5
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . 9
Choosing an Installation Location . . . . . . . . . . . 10
System Configuration and Wiring . . . . . . . . . . . 11
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Connecting to Auxiliary Fittings . . . . . . . . . . . . . 23
Setting Pump Outlet Volume . . . . . . . . . . . . . . . 24
Loading Grease . . . . . . . . . . . . . . . . . . . . . . . . 24
Filling Oil Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Priming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Quick Setup Guide . . . . . . . . . . . . . . . . . . . . . . . . 27
Max Model Setup . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Control Panel Overview . . . . . . . . . . . . . . . . . . 28
Programming the Max Model . . . . . . . . . . . . . . 29
Pump OFF / REST Setup . . . . . . . . . . . . . . . . . 34
DMS
Operation / Data Log . . . . . . . . . . . . . . . . . . . . . . . 39
System Event Log . . . . . . . . . . . . . . . . . . . . . . . 39
Error Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Functional Summary . . . . . . . . . . . . . . . . . . . . . 42
Technical Summary . . . . . . . . . . . . . . . . . . . . . 44
Advanced Programming . . . . . . . . . . . . . . . . . . . . 45
Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Time Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Fault / Warning Scenarios . . . . . . . . . . . . . . . . . 57
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Parts - 2 Liter Models . . . . . . . . . . . . . . . . . . . . . . 65
Parts - 4 Liter and Larger Models . . . . . . . . . . . . . 66
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Mounting Pattern . . . . . . . . . . . . . . . . . . . . . . . . 74
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . 76
Graco Information . . . . . . . . . . . . . . . . . . . . . . . 76
Models Only . . . . . . . . . . . . . . . . . . . . . 37
2 332305B
Part / Model Numbers
Part / Model Numbers
The Part Number is a six-digit unique number that is only used to order the G3 Pump. Directly related to this six digit Part Number is the configured Graco Model Number. This configured number identifies the distinct features of a spe­cific G3 Pump. To help you understand each component that makes up the Model Number see Understanding Your Model Number, page 5. The tables below shows the relationship between each Part Number and its related Model Number.
2 Liter Models 4 Liter Models
Part
Numbers
96G017 G3-G-24MX-2L0L00-10CV00R0 96G018 G3-G-24MX-2LFL00-10CV00R0 96G019 G3-G-ACMX-2L0L00-1D0V0000 96G020 G3-G-ACMX-2LFL00-1D0V0000 96G021 G3-G-12MX-2L0L00-1DMVA2R3 96G023 G3-G-24MX-2L0L00-1DMVA2R3 96G024 G3-G-24MX-2LFL00-1DMVA2R3 96G025 G3-G-ACMX-2L0L00-1DMVA2R3 96G026 G3-G-ACMX-2LFL00-1DMVA2R3 96G030 G3-G-12MX-2L0L00-10C00000 96G031 G3-G-24MX-2L0L00-10C000R0 96G032 G3-G-ACMX-2L0L00-1D000000
96G035 G3-G-12MX-2L0L05-10CV0000
96G036 G3-G-24MX-2L0L05-10CV0000
96G037 G3-G-ACMX-2L0L00-1D00A000 96G098 G3-G-12MX-2L0L00-UDMVA1R2
96G107 G3-A-24MX-2L0L00-1DMVA2R3 96G110 G3-G-24MX-2L0L00-UDMVA1R2 96G115 G3-G-24MX-2LFL00-UDMVA1R2
96G122 96G125 G3-G-ACMX-2L0L00-UDMVA1R2
96G132 G3-G-ACMX-2LFL00-UDMVA1R2
96G174 G3-A-ACMX-2L0L00-UDMVA1R2 96G178 G3-G-24MX-2L0L00-0D00A100
G3-A-ACMX-2L0L00-1DMVA2R3
Model Numbers
Part
Numbers
96G088 G3-G-24MX-4L0L00-10CV00R0
96G090 G3-G-24MX-4LFL00-10CV00R0
96G092 G3-G-ACMX-4L0L00-1D0V0000
96G094 G3-G-ACMX-4LFL00-1D0V0000
96G096 G3-G-12MX-4L0L00-1DMVA2R3 96G099 G3-G-12MX-4L0L00-UDMVA1R2
96G103 G3-G-24MX-4L0L00-1DMVA2R3 96G108 G3-A-24MX-4L0L00-1DMVA2R3
96G111
96G113 G3-G-24MX-4LFL00-1DMVA2R3
96G116 G3-G-24MX-4LFL00-UDMVA1R2
96G118 G3-G-ACMX-4L0L00-1DMVA2R3
96G123 G3-A-ACMX-4L0L00-1DMVA2R3
96G126 G3-G-ACMX-4L0L00-UDMVA1R2
96G128 G3-G-ACMX-4LFL00-1DMVA2R3
96G133 G3-G-ACMX-4LFL00-UDMVA1R2
96G141 G3-G-12MX-4L0L00-10C00000
96G143 G3-G-24MX-4L0L00-10C00000
96G145 G3-G-ACMX-4L0L00-1D000000
96G151 G3-G-12MX-4L0L05-10CV0000
96G153 G3-G-12MX-4L0L05-U0CV0100
96G155 G3-G-24MX-4L0L05-10CV0000
96G157 G3-G-24MX-4L0L05-U0CV0100
96G159 G3-G-12MX-4L0L05-00C0010M
96G160 G3-G-24MX-4L0L05-00C0010M
96G161 G3-G-12MX-4L0L05-U0C0010M
96G162 G3-G-24MX-4L0L05-U0C0010M
96G175 G3-A-ACMX-4L0L00-UDMVA1R2
96G181 G3-G-24MX-4L0L03-00C00100
96G183 G3-G-ACMX-4L0L00-1D00A000
96G188 G3-A-24MX-4L0L05-U0C0010M
G3-G-24MX-4L0L00-UDMVA1R2
Model Numbers
332305B 3
Part / Model Numbers
8 Liter Models 12 Liter Models
Part
Numbers
96G089 G3-G-24MX-8L0L00-10CV00R0
96G093 G3-G-ACMX-8L0L00-1D0V0000
96G097 G3-G-12MX-8L0L00-1DMVA2R3
96G100 G3-G-12MX-8L0L00-UDMVA1R2
96G104 G3-G-24MX-8L0L00-1DMVA2R3
96G109 G3-A-24MX-8L0L00-1DMVA2R3 96G112
96G119
96G124 G3-A-ACMX-8L0L00-1DMVA2R3
96G127 G3-G-ACMX-8L0L00-UDMVA1R2
96G142 G3-G-12MX-8L0L00-10C00000
96G144 G3-G-24MX-8L0L00-10C00000
96G146 G3-G-ACMX-8L0L00-1D000000
96G152 G3-G-12MX-8L0L05-10CV0000
96G154 G3-G-12MX-8L0L05-U0CV0100
96G156 G3-G-24MX-8L0L05-10CV0000
96G158 G3-G-24MX-8L0L05-U0CV0100
96G176 G3-A-ACMX-8L0L00-UDMVA1R2
96G177 G3-G-24MX-8L0L05-00C0010M
96G186 G3-A-12MX-8L0L05-U0C0010M
G3-G-24MX-8L0L00-UDMVA1R2
G3-G-ACMX-8L0L00-1DMVA2R3
Model Numbers
Part
Numbers
96G105 G3-G-24MX-120L00-1DMVA2R3 96G120 G3-G-ACMX-120L00-1DMVA2R3 96G164 G3-G-24MX-120L05-10CV00000 96G165 G3-G-24MX-120L05-U0CV0100
Model Numbers
16 Liter Models
Part
Numbers
96G106
96G121 G3-G-ACMX-160L00-1DMVA2R3
96G166 G3-G-ACMX-160L00-1D0V0000
96G168 G3-G-24MX-160L05-10CV0000
96G169 G3-G-24MX-160L05-U0CV0100
96G185 G3-G-24MX-160L05-U0C0010M
G3-G-24MX-160L00-1DMVA2R3
Model Numbers
4 332305B
Part / Model Numbers
k
m
n
p
h
j
i
g
DMS
TM
Models
Understanding the Model Number
Use the Code Sample provided below to identify each component’s location in the Model Number. The options for each component that make up the code are provided on the lists below.
NOTE: Some pump configurations are not available. Contact Graco Customer Service or your local Graco distributor for assistance.
G3 - G - MX
Code Sample: a a b b - c c d e f f - g h i j k m n p
G3 - G = Identifies pump as being a G3; G = Grease G3 - A = Identifies pump as being a G3; A = Oil
Code aa: Power Source
12 = 12 Volts DC
24 = 24 Volts DC
AC = 100 - 240 Volts AC
Code bb: Operation Control
MX = Max (Cycle) Control
Code cc: Reservoir Capacity (Liters)
2L = 2 Liters
4L = 4 Liters
8L = 8 Liters
12 = 12 Liters
16 = 16 Liters
Code d: Follower Plate Installed
F = Follower Plate Installed
0 = No Follower Plate
Code e: Low Level Option
L = Low Level with Controller
0 = No Low Level monitoring
Code ff: Options
00 = No Options
03 = Powered Alarm Contact
05 = 5 Pin CPC power cable
Code g, h, i, j, k, m, n, p NOTE: Codes g - p relate to a specific location on the
G3 pump. See F
•C = CPC
•D = DIN
1, 2, 3 = Sensor Number
R = Remote Manual Run
M = Machine Count
A = Alarm Output
V = Vent Valve
0 = Not populated
U = USB Port
IG. 1 for these locations.
FIG. 1
332305B 5
Warnings
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. When these symbols appear in the body of this manual, refer back to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
• Turn off and disconnect power at main switch before disconnecting any cables and before servicing or installing equipment.
• Connect only to grounded power source.
• All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
• Do not operate the unit when fatigued or under the influence of drugs or alcohol.
• Do not exceed the maximum working pressure or temperature rating of the lowest rated system component. See Technical Data in all equipment manuals.
• Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information about your material, request MSDS from distributor or retailer.
• Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
• Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
• Do not alter or modify equipment. Alterations or modifications may void agency approvals and create safety hazards.
• Make sure all equipment is rated and approved for the environment in which you are using it.
• Use equipment only for its intended purpose. Call your distributor for information.
• Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
• Do not kink or over bend hoses or use hoses to pull equipment.
• Keep children and animals away from work area.
• Comply with all applicable safety regulations.
6 332305B
Warnings
WARNING
SKIN INJECTION HAZARD
High-pressure fluid from dispensing device, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical
treatment.
Do not point dispensing device at anyone or at any part of the body.
Do not put your hand over the fluid outlet.
Do not stop or deflect leaks with your hand, body, glove, or rag.
Follow the Pressure Relief Procedure when you stop dispensing and before cleaning, checking, or servicing equipment.
Tighten all fluid connections before operating the equipment.
Check hoses and couplings daily. Replace worn or damaged parts immediately.
PRESSURIZED EQUIPMENT HAZARD
Over-pressurization can result in equipment rupture and serious injury.
• A pressure relief valve is required at each pump outlet.
• Follow Pressure Relief Procedure in this manual before servicing.
PLASTIC PARTS CLEANING SOLVENT HAZARD
Many solvents can degrade plastic parts and cause them to fail, which could cause serious injury or property damage.
Use only compatible water-based solvents to clean plastic structural or pressure-containing parts.
•See Technical Data in this and all other equipment instruction manuals. Read fluid and solvent manufacturer’s MSDSs and recommendations.
MOVING PARTS HAZARD
Moving parts can pinch, cut or amputate fingers and other body parts.
Keep clear of moving parts.
Do not operate equipment with protective guards or covers removed.
Pressurized equipment can start without warning. Before checking, moving, or servicing equipment, follow the Pressure Relief Procedure and disconnect all power sources.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective equipment includes but is not limited to:
Protective eyewear, and hearing protection.
Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer
332305B 7
Installation
A
D
H
I
B
E
C
K
F
J
G3-G-24NC-2L0A00-L0C00000
Grease Models with Follower Plate
L
M
96GXXX
Oil Models
N
Grease Models
DMS
TM
Models
P
Installation
Grounding
The equipment must be grounded. Grounding reduces the risk of electric shock by providing an escape wire for the electrical current in the event of malfunction or breakdown. This product is equipped with a cord having an equipment grounding conductor. The wire with insulation having an outer surface that is green with or without yellow stripes is the grounding wire.
Component Identification
FIG. 2:
Key:
AReservoir B Adjustable Pump Element (1 included. Can accommodate 3
total)
C Pressure Relief Valve (Not included / required for each outlet
- Available from Graco. See Parts, page 71.) D Zerk Inlet Fill Fitting (1 included / grease models only) E Pump Outlet Plug (2 included) F Volume Control Spacers (2 included. More spacers = less
output volume per stroke) (also see F
G Fuse (DC models only - Not included, not shown. Available
from Graco. See Parts, page 71.)
H Control Panel
8 332305B
IG. 15, page 24)
I Power / Sensor Panel (both sides; only one side shown) J Part Number / Model Number example only shown, (see
pages 5, Understanding the Model Number, for details) K Power Cord (DIN shown) L Follower Plate (grease models only / not available on all
grease models) M Vent Hole for Follower Plate (grease models only / not
available on all grease models) N Fill cap (oil models only) P USB Port (DMS
Models only)
Typical Installation
A
B
C
D
E
F
A
B
D
E
C
F
H
G
Divider Installations
Installation
Injector Installations
A Connected to fuse / power B Pressure relief valve (Not included/required for each
outlet - user supplied. See Parts, page 71)
C - Cycle indicator sensor cable (Divider Installations)
- Pressure switch cable (Injector Installations)
D - Series progressive divider valves (Divider Installations)
- Injectors (Injector Installations) E To lube points F - Proximity Switch (Divider Installations)
- Pressure switch (Injector Installations)
G Vent valve (Not included / available from Graco. See
Parts, beginning on page 67.)
H Return to reservoir
332305B 9
Installation
Choosing an Installation Location
AUTOMATIC SYSTEM ACTIVATION HAZARD
Unexpected activation of the system could result in serious injury, including skin injection and amputation.
This device has an automatic timer that activates the pump lubrication system when power is connected or when exiting the programming function. Before you install or remove the lubrication pump from the system, disconnect and isolate all power supplies and relieve all pressure.
Select a location that will adequately support the weight of the G3 Pump and lubricant, as well as all plumbing and electrical connections.
Refer to the two mounting hole layouts provided in the Mounting Pattern section of this manual, page 74.
NOTE: The two mounting hole layouts provided in the Technical Data section show the only cor­rect installation patterns to use for mounting the G3. No other installation configurations should be used.
Use designated mounting holes and provided configurations only.
Always mount the G3 oil models upright.
If the G3 grease model is going to be operated in a tilted or inverted position for any period of time, you must use a model that includes a fol­lower plate, otherwise the G3 must be mounted upright. Refer to your model number to confirm if a follower plate was installed on your pump. See page 5, Understanding the Model Number to identify this character in your model number.
Use the three fasteners (included) to secure the G3 to the mounting surface.
Some installations may require an additional reservoir support bracket. Consult your Graco distributor for assistance with this installation.
10 332305B
System Configuration and Wiring
Installation
Fuses
.
Improper installation of the grounding conductor may result in a risk of electric shock. This product must be installed by a qualified electrician in compliance with all state and local codes and regulations.
If the product is permanently connected:
it must be installed by a qualified electrician or ser­viceman.
it must be connected to a grounded, permanent wir­ing system.
If an attachment plug is required in the end use application:
it must be rated for the product electrical specifica­tions.
it must be an approved, 3-wire grounding type attachment plug.
it must be plugged into an outlet that is properly installed and grounded in accordance with all local codes and ordinances.
when repair or replacement of the power cord or plug is required, do not connect the grounding wire to either flat blade terminal.
NOTICE
Fuses (user supplied) are required on all DC mod­els. To avoid equipment damage:
Never operate G3 Pump DC models without a fuse installed.
A fuse of the correct voltage must be installed in line with the power entry to the system.
Fuse Kits are available from Graco. The following Table identifies the correct fuse to use for your input voltage and the corresponding Graco Kit number.
Input Voltage Fuse Value Graco Kit No.
12 VDC
24 VDC 4 A 571040
7.5 A
571039
Recommendations for Using Pump in Harsh Environments
Use pump with CPC style power cable.
If using a DIN style power or alarm harness with a right angle mating connector, make sure the con­nector does not exit the unit in the UP direction.
Use a corrosion preventative electrical grease on all contacts.
332305B 11
Installation
N.O.
N.C.
N.O.
N.C.
1 second
Alarm Output and Remote Illumination Response
The following tables include graphical representations of the connector as it appears on the unit, a pin-out associated with the connector and a typical installation wiring diagram. An internal representative wiring diagram is included where it is deemed useful.
Wire colors provided on these pages only refer to the power cable provided by Graco with this product.
Standard Remote
Illumination
(via 5 wire CPC power
Alarm Output
Unit in OFF Mode Deactivated (off) Off Off Unit in ON Mode Deactivated (off) On Green
Warning Condition Activated (on)
Fault Condition
Fault Condition (Advanced Programming Setting A7 OFF)
Fault Condition (Advanced Programming Setting A7 ON)
Toggles On and Off once per second
Toggles On and Off once per second
Activated (on)
Toggles On and Off once per second
Toggles On and Off once per second
Toggles On and Off once per second
Toggles On and Off once per second
cable)
(via illuminated manual run
Yellow
Red
Red
Red
Alarm Relay Response
Output Tied to Common
No Faults or
Warnings
Tri-Color Remote
Illumination
input)
N.O.
Warning
N.C.
Fault
(Advanced
Programming A7
OFF)
Fault
(Advanced
Programming
Setting A7 ON)
N.O.
N.C.
12 332305B
Wiring and Installation Diagrams
The following Table identifies the wiring and installation diagrams provided in this manual.
Diagram Symbol Page #
Power DIN AC 14
Power DIN DC 15
Power CPC DC 16
Installation
Inputs (M12)
Vent Valve Outputs 19
Alarm Outputs 20
Illuminated Manual Run Input
Kits: 571030, 571031, 571032, 571033
18
332305B 13
Installation
(4)
(2)
(1)
1
2
3
4
Example Wiring Diagram
Connector on Housing
Connector on Cable
(4)
(1)
(3)
(2)
Power DIN AC - 15 foot: Part No. 16U790
Pin and Related Wire Color (FIG. 3)
Pin Pin Name Color
1 Line Black 2 NEUTRAL White 3 Not Used Not Used 4GROUND Green
FIG. 3
14 332305B
Power DIN DC - 15 foot: Part No. 16U790
Ignition Switch
Fuse
1
2
3
4
Example Wiring Diagram
Connector on Housing
12V-pump - 7.5A - Graco kit #571039 24V pump - 4A - Graco kit #571040
(4)
(2)
(1)
Connector on Cable
(4)
(1)
(3)
(2)
NOTICE
Be sure when power is applied that stirring paddle rotates clockwise (when viewed from the top). If it is wired incorrectly paddle could rotate counter-clockwise which will damage the pump’s internal components. If this happens, stop the pump immediately and wire unit correctly.
Pin and Related Wire Color (FIG. 4)
Pin Pin Name Color
1-VDC Black 2+VDC White 3 Not Used Not Used 4 Not Used Green
Installation
FIG. 4
332305B 15
Installation
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Example Wiring Diagram
Connector on Housing
Connector on Cable
Ignition Switch
Fuse
1
2
3
4
5
6
7
12V-pump - 7.5A - Graco kit #571039 24V pump - 4A - Graco kit #571040
(1)
(3)
(2)
(7)
(6)
(5)
(4)
Power CPC DC -15 foot: Part No. 126217
Pin and Related Wire Color (FIG. 6)
Pin Pin Name Color
1 Not Used Not Used 2-VDC Black 3+VDC White 4 Not Used Not Used 5 Not Used Not Used 6 Not Used Not Used 7 Not Used Green
FIG. 5
16 332305B
Power CPC DC - 5 Wire
(1)
(2)
(3)
(4)
(5)
(6)
(7)
1
2
3
4
5
6
7
L
Fuse
12V-pump - 7.5A - Graco kit #571039 24V pump - 4A - Graco kit #571040
Example Wiring Diagram
Connector on Housing
Connector on Cable
(1)
(3)
(2)
(7)
(6)
(5)
(4)
Installation
Part No.: 126218: 15 ft (4.5 m) Part No.: 126219: 20 ft (6.1 m) Part No.: 126220: 30 ft (9.1 m)
NOTE: An Illuminated Remote Run Button Kit: 571030,
571031 for starting a manual run cycle if used in con­junction with a 5-wire CPC cable, is available from Graco. Contact your local Graco distributor or Graco Customer Service for additional information about these kits.
Pin and Related Wire Color (F
IG. 6)
Pin Pin Name Color
1 Not Used Not Used 2-VDC Black 3+VDC Red 4LIGHT White 5 MANUAL ORANGE 6 Not Used Not Used 7 Not Used Green
FIG. 6
332305B 17
Installation
1 SW +
2 Not Used
3 SW -
4 Signal
(3)
(4)
(1)
(2)
Sink (NPN) 2 or 3 wire
1
2
3
4
Source (PNP) 2 or 3 wire
1
2
3
4
Dry Contacts
1
2
3
4
Example Wiring Diagram
Pin-outConnector on Housing
Inputs (M12)
See Technical Data, page 72 for rat­ings.
FIG. 7
18 332305B
Vent Valve Outputs
See Technical Data, page 72 for ratings.
(3)
Installation
Pin-outConnector on Housing
1 Not Used
2 Relief+
3 Relief -
FIG. 8
(2)
(1)
Example Wiring Diagram
1
2
3
332305B 19
Installation
1 N.O.
2 N.C.
3 COM
4 Not Used
(1)
(4)
(2)
(3)
1
2
3
4
G3
Switch closes on alarm
(shown in non-alarm position)
Alarm +9-30V 1 Amp Max
1 A Fuse
Example Wiring Diagram
Pin-outConnector on Housing
Alarm Outputs
DC example shown. See Technical Data, page 72 for ratings.
FIG. 9
20 332305B
Part No. 124333: Cable Pin Out (M12)















Wire Colors
Item No. Color
1Brown 2White 3Blue 4Black

Installation
Part No. 124300: Field Wireable Pin Out (M12)
Wire Colors
Item No. Color
1Brown 2White 3Blue 4Black

FIG. 11
FIG. 10
332305B 21
Installation






Part No. 124594: 4 Pin Eurofast Field Wireable Connector
FIG. 12
Part No. 124595: 5 Pin Eurofast Field Wireable Connector



FIG. 13
22 332305B
Setup
Setup
Pressure Relief
Follow the Pressure Relief Procedure whenever you see this symbol.
This equipment stays pressurized until pressure is manually relieved. To help prevent serious injury from pressurized fluid, such as skin injection, splashing fluid and moving parts, follow the Pressure Relief Procedure when you stop spraying and before cleaning, checking, or servicing the equipment.
Relieve pressure in system using two wrenches working in opposite directions on pump element and pump element fitting to slowly loosen fitting only until fitting is loose and no more lubricant or air is leaking from fitting.
NOTE: When loosening pump element fitting, do NOT loosen pump element. Loosening pump element will change the output volume.
Connecting to Auxiliary Fittings
NOTICE
Do not attach unsupported equipment to auxiliary fittings such as fill ports and pump element. Attach­ing unsupported equipment to these fitting can result in irreparable housing damage.
Always use two wrenches working in opposite directions when connecting anything to pump element or auxiliary fittings. See F example.
Torque pump element fittings to 50 in. lbs (5.6 N•m).
When connecting pump element into housing torque to 50 in. lbs (5.6 N•m).
Pressure Relief Valves
IG. 14 for an
F
IG. 14
To prevent over-pressurization, which can result in equipment rupture and serious injury, a pressure relief valve appropriate for the lubrication system must be installed close to every pump outlet to alleviate unin­tended pressure rises in the system and protect the G3 pump from damage.
Only use a pressure relief valve that is rated for no more than the working pressure of the G3 pump it is installed on. See Technical Data, page 66.
Install a pressure relief valve close to every pump outlet; before any auxiliary fitting.
NOTE: A pressure relief valve can be purchased from Graco. See Parts, page 71.
332305B 23
Setup
Setting Pump Outlet Volume
NOTE:
Before making any adjustments to pump volume, Relieve Pressure following procedure on page 23.
Only use Graco supplied spacers to control output volume.
It may be necessary to repeat this outlet volume setup procedure after the pump is operating to re-adjust the volume of dispensed fluids.
1. Use a wrench to turn pump element counter-clock­wise to loosen. Do not remove entire pump element. Only back pump element out enough to allow spacer to be slid on or off.
2. If needed, remove or insert spacers to achieve required pump output volume. A tool may be needed to facilitate removal.
Pump volume control is set using either no (0) spac­ers, 1 or 2 spacers (F
Do not use more than 2 spacers to adjust output vol­ume.
IG. 15).
3. Tighten pump element fitting. Torque fitting to 50 in. lbs (5.6 N•m).
FIG. 15
Loading Grease
To ensure optimal performance from the G3:
Only use NLGI #000 - #2 greases appropriate for your application, automatic dispensing, and the equipment’s operating temperature. Consult with machine and lube manufacturer for details.
The reservoir can be filled using a hand operated pump, pneumatic pump or electric transfer pump.
Do not overfill (F
Do not operate G3 without reservoir attached.
IG. 17).
Output Volume / Minute
No. Spacers
20.122
10.183
00.254
NOTE:
The amount of dispensed volume can vary depend­ing on external conditions such as lubricant tem­perature and back pressure from downstream connections.
Use of these volume adjustment in conjunction with setting the ON time of the pump will allow for control of the output volume.
Use these volume adjustments as a starting point and adjust as necessary to ensure desired lubrica­tion dispense.
24 332305B
cubic inches cubic cm
Always clean fitting (D) with a clean dry cloth prior to filling reservoir. Dirt and/or debris can damage pump and/or lubrication system.
• Care must be used when filling the reservoir using a pneumatic or electric transfer pump to not pressurize and break the reservoir.
NOTICE
Setup
D
E
max fill line
vent hole
Models without a follower plate:
1. Connect fill hose to inlet fitting (FIG. 16).
F
IG. 16
2. For higher viscosity fluids, start pump to rotate stir­ring paddle during fill to prevent air pockets from forming in grease.
To start the pump press the manual run button.
To start the pump press the manual run button.
3. Fill reservoir with grease until seal of follower plate breaches the vent hole (F
IG. 18) and
the majority of air is expelled from the reservoir.
FIG. 18
NOTE: Vent port, located in rear of reservoir, should not
be used as an overfill port/indicator.
3. Fill reservoir with NLGI grease to max fill line.
NOTE: Vent port, located in rear of reservoir, should not be used as an overfill port/indicator.
F
IG. 17
4. Remove fill hose.
Models with a follower plate:
1. Connect fill hose to inlet fitting (FIG. 16).
4. Remove fill hose.
Changing Greases
When changing greases, always use compatible fluids or greases.
2. For higher viscosity fluids, start pump to rotate stir­ring paddle during fill to prevent air pockets from
forming in grease.
332305B 25
Setup
a
b
Filling Oil Unit
Only use oil appropriate for your application, auto­matic dispensing, and the equipment’s operating temperature. Consult with machine and lube manu­facturer for details.
The reservoir can be filled using a hand operated pump, pneumatic pump or electric transfer pump.
Do not overfill (F
IG. 19).
Do not operate G3 without reservoir attached.
Only use oils with viscosity at least 40 cSt.
F
IG. 19
1. Remove fill cap (a).
2. Pour oil into reservoir to fill line (b).
FIG. 20
2. Only run pump until air is no longer dispensed with the lubricant coming out of element fitting (F
IG. 21).
3. Replace fill cap. Hand tighten cap, securely.
Priming
NOTE: It is not necessary to prime pump every time
pump is filled with lubricant.
Pump only requires priming the first time it is used or if it is allowed to run dry.
1. Loosen pump element fitting (F
NOTE: When loosening pump element fitting, do NOT loosen pump element. Loosening pump element will change the output volume
26 332305B
IG. 20).
IG. 21
F
3. Tighten pump element fitting using two wrenches working in opposite directions (F
IG. 20).
Quick Setup Guide































 
























Quick Setup Guide
332305B 27
Max Model Setup
DISPLAY
A blinking LED under HH, MM, SS
or ## identifies type of measurement unit you are setting; i.e., HH is hours.
A blinking number on the display
indicates the G3 is in SETUP MODE.
In RUN MODE displayed numbers
count up or down. See Time ON and Time OFF.
ON TIME/BACKUP TIME
LED lights when ON
Time/Backup Time is running.
Display shows time as MM:SS
(minutes and seconds). i.e., 08:30 is 8 minutes: 30 sec­onds.
Sets the limits for the amount
of time to complete a cycle or build up pressure before a warning is activated.
Counts down from a set time to
zero.
OFF TIME/BACKUP TIME
LED lights when OFF
Time/Backup Time is used to con­trol Pump OFF function.
Value is entered in HH:M.
Displays in HH:MM (hours and
minutes) when > 1 hour.
Times pump rest between cycles.
Counts down from set time to
zero.
Can be set up to use as a backup
for Machine Count control.
ALARM ICONS
LED next to icon lights when a fault / warning event occurs during a run cycle. See page 57 for a complete description of these alarm scenarios.
PIN ICON
LED next to icon lights indi-
cating PIN is required to enter setup.
In SETUP MODE LED
lights when setting up the PIN.
PRELUBE
LED next to icon lights indicat­ing LED lights when Prelube function is enabled.
LEFT DIRECTION ARROW / RESET
In ADVANCED and SETUP
MODES, moves cursor in dis­play one field to the left.
In RUN MODE: single press
clears warning.
In ALARM MODE: pressing and
holding for 3 seconds clears fault / warning and switches cycle to OFF MODE.
RIGHT DIRECTION ARROW / MANUAL RUN / ENTER
In SETUP MODE, saves
entry, moves cursor in display one field to the right or to the next setup step.
In RUN MODE starts a man-
ual run cycle.
UP and DOWN ARROW
Hold both the UP and DOWN ARROW but-
tons down together for 3 seconds to enter SETUP MODE.
In SETUP MODE, increases or decreases
number values shown in display.
CYCLE / PRESSURE SETUP
Sets either Cycle (C) or Pressure
(P) Monitoring limits for up to 3 sensors.
Each sensor is set up and con-
trolled independently.
MACHINE COUNT
LED lights when Machine Count
is used to control Pump OFF function.
Counts independent machine
operations with a sensor to con­trol Pump Off duration.
Time OFF function can be used
as a backup for Machine Count.
Max Model Setup
Control Panel Overview (FIG. 22)
NOTE: Programming instructions begin on page 29.
IG. 22
F
28 332305B
Max Model Setup
Programming the Max Model
Powering Units With Controllers
By default, units with controllers are set to operate in a timed mode with 1 minute of ON time and 8 hours of OFF time. The unit should be powered up in OFF mode, counting down from the 8 hours. If the unit powers up in ON mode and has not been primed, hold the reset but­ton located on the control panel (example shown on the right) for 1 second to move to the OFF mode.
NOTE:
A blinking number on the display indicates the G3 is in SETUP MODE.
In RUN MODE numbers on the display do not blink.
After 60 seconds of no activity, the device returns to RUN MODE in the OFF Time cycle and the OFF Time restarts counting down the total programmed amount of time. It does not resume the countdown from the point where the cycle was interrupted when you entered SETUP MODE.
Entering Setup Mode
1. Press both the UP and DOWN ARROW buttons for 3 seconds.
2. The LED next to the LOCK ICON on the display lights and the 4 zeros appear on the display indicating the system requires a PIN Code entry to run the G3 in SETUP MODE.
3. The cursor is automatically positioned to enter the first character of the PIN Code. Use the UP and DOWN ARROW buttons to move up and down through the numbers 0-9 until the first number in the PIN code is displayed in the field.
4. Press the ENTER button to set the num­ber. The cursor automatically moves to the next number field.
5. Repeat steps 3 and 4 for each PIN Code prompt field.
If the PIN Code you entered is correct, the first editable character on the display will flash.
Press both the UP and DOWN ARROW buttons together for 3 seconds to enter the SETUP MODE.
NOTE: If the lock LED is lit after entering Setup Mode and four 0000’s are displayed, the unit has a PIN Code lock out enabled. See the follow­ing section: Entering a PIN Code to Access Setup Mode.
Entering a PIN Code to Access Setup Mode
The G3 controller does not require a user to provide a PIN code to access the programming features of the unit. However, Graco understands that some users may want to protect the programming settings and therefore, an option for adding PIN Code authorization is available. The instructions for setting up PIN Code Authorization are provided in the Advanced Programming section of this manual. See page 46.
NOTE: A blinking field on the display indicates the G3 is in SETUP MODE. In RUN MODE numbers on the dis­play will not blink.
To enter the PIN Code:
332305B 29
Max Model Setup
or
Setting the Real Time Clock
DMS™ Equipped Models Only
NOTE: Set the real time clock prior to plugging the USB flash drive into the pump.
Enter the Year:
The year displays. The first programma­ble character, the decade, blinks indi­cating the device is ready to program the decade digit of the year.
The LED under the # sign lights while setting the year.
1. Use the UP and DOWN arrow but­tons to move up and down through the number 0-9 until the number for the current decade is displayed in the field.
2. Press the ENTER button to set the decade number. The cursor auto­matically moves to the next field, the year number.
3. Use the UP and DOWN arrow but­tons to move up and down through the number 0-9 until the number for the current year is displayed in the field.
the list of months until the current month is dis­played in the field.
2. Press the ENTER button to set the month.
The 2-digit date displays indicating the G3 is now ready to program the date.
Enter the 2-digit Date:
The first programmable character of the 2-digit date blinks indicating the device is ready to pro­gram the first digit of the date.
The LED under the # sign lights while setting the date.
1. Use the UP and DOWN ARROW buttons to move up and down through the numbers 0-3 until the first digit of the date is displayed in the field.
2. Press the ENTER button to accept the selection. The cursor automati­cally moves to the second digit of the date.
3. Use the UP and DOWN ARROW buttons to move up and down through the numbers 0-9 until the second digit of the date is dis­played in the field.
4. Press the ENTER button to set the year number.
The 3-character month displays indicating the G3 is now ready to program the month.
Enter the Month:
1. Set the 3 character month by using the UP and DOWN ARROW but­tons to move up and down through
30 332305B
4. Press the ENTER button to set the date.
The time displays indicating the G3 is now ready to program the time.
Enter the Time:
The time displays in 24-Hour format. i.e., 2:45 PM displays as 14:45.
The clock is set in Hours and Minutes (HH:MM).
The LED under the HH lights when set­ting hours and the LED under the MM lights when setting minutes.
Max Model Setup
The first programmable number of the HH (hour) filed blinks, indicating the device is ready to program the first digit of the hour.
When programming a time of less then 12 hours, you must program a leading zero in the first number field and press the ENTER button to save the zero.
1. Use the UP and DOWN ARROW buttons to move up and down through the numbers 0-2 until the desired number appears in the first hour (HH) field.
2. Press the ENTER button to set the number.
3. Use the UP and DOWN ARROW buttons to move up and down through the numbers 0-9 until the desired number for the second HH number field appears.
4. Press the ENTER button to set the number.
5. The next number field to the right blinks and the LED under the MM lights indicating the G3 is ready to program the minutes fields.
The LED next to C/P1 lights, indicat­ing which sensor of the pump control you are programming using either a specific number of cycles or by mon­itoring a pressure switch.
C / P2 and C / P3 controls functions to the second and third sensors (when sensors are used).
Only sensor inputs that are available on the unit can be programmed.
NOTE: Field cannot be left blank. If C / P2 and C / P3 are not used, OFF must be entered instead.
Cycle (C1, C2, C3) Setup
Cycle controls the number of lube cycles (as monitored by an external cycle monitor) completed before the pump rests.
NOTE:
You must program at least one cycle. Zero is not an available option.
1. Use UP or DOWN arrow but­ton to toggle display between OFF / C1 / P1 on the display.
6. Repeat steps 1-4 to set the minutes (MM) fields.
7. After pressing the ENTER button to set the time, the programmed Time information is saved.
Programming ON Duration
OFF, C1 (C2, C3) or P1 (P2, P3) displays, identifying the func­tion you are program­ming.
Selection of OFF, C1 (C2, C3) or P1 (P2, P3) desig­nates the way pump run time is controlled:
C1, C2, C3 - Completing a specific number of
cycles measured by an external prox/cycle switch
P1, P2, P3 - Reaching a specific pressure
threshold measured by an external pressure switch - OR,
OFF - A specific duration of time elapses.
2. When C1 is on display, press the ENTER button to save selec­tion and begin programming Cycle data.
The first number
displayed after the “C1” on the dis­play blinks, indi­cating the device is ready to pro­gram the number of C1 cycles.
The LED under the
# sign lights when setting the number of cycles.
3. Program the number of cycles by pressing the UP or DOWN ARROW button to move up or down through number 0-9.
332305B 31
Max Model Setup
4. The cycle field is a 2 digit number. When the correct first numeral of the number displays, press the ENTER but­ton to save the number. The cursor automatically moves to the second number field.
NOTE: A leading zero (0) must be entered in the first field if the number of cycles is fewer than 10.
5. Press the ENTER button, to save the C1 information.
If your G3 is equipped with more than one sensor input, you will automatically be prompted to begin selecting the pump control type for the next sensor. Repeat steps 1 - 5 to program cycles for C2 and C3.
NOTE: If C / P2 and C / P3 are not used, the default OFF setting must be entered instead.
6. After you set the last field and press the ENTER button, the G3 saves the Cycle information and moves to setting Backup Time, page 34.
Pressure Control (P1, P2, P3) Setup
3. If your G3 comes equipped with more than one sen­sor input, you will automatically be prompted to begin selecting pump control type for the next sen­sor. Repeat steps 1 - 2 to program P2 and P3.
If P1 / P2 / P3 is selected the vent valve time is automatically set to 5 minutes. If the unit is used in an injector based system and a sensor input is not used, the user must update the vent valve time in advanced programming. (See Advanced Program­ming, A-3 Vent Valve Time, page 47.)
Input Not Used
Select OFF if your system does not use the applicable input.
1. Use UP or DOWN arrow but­ton to toggle between OFF / C1 / P1 on the display.
2. When OFF is on the dis­play, press the ENTER button to save selection.
For injector systems, monitoring pressure can be used as a way to ensure sufficient pressure has been reached to activate injectors. The pump runs, building up enough pressure to cause injectors to dispense fluid. Pressure continues to build to a pre­set maximum, activating the (user supplier) pres­sure switch. Then an external (user supplied) vent valve opens and pressure reduces, priming the injector for the next cycle.
Pressure control is an ON / OFF selection only.
1. Use the UP or DOWN arrow button to toggle between OFF / C1/ P1.
2. When P1 displays, press ENTER button to save selection.
If the sensor inputs are available and none are used in the ON Mode, the definition of the entered time is ON TIME.
Examples:
Model G3-G-24MX-2LFL00-1DMVA2R3 has 4 sensors, so C/P1, C/P2, and C/P3 and Machine Count can all be programmed.
Model G3-G-24MX-2LFL00-10CV00R0 has 1 sensor, only C/P1 is available for programming.
Backup Time
In both Cycle and Pressure Modes, a maximum run Time (Backup Time) for the lubrication period must be set up. If this Time expires before the lubrication is com­pleted an alarm/warning is triggered and the pump stops.
32 332305B
Max Model Setup
OR
To determine the Backup Time, Graco recommends the user verify the length of time it takes to complete a typi­cal cycle and double that value (to a maximum of 30 minutes).
Backup Time is setup after Cycle or Pressure Sensor Setup is complete.
NOTE:
The LED next to the clock in the ON field lights, indi­cating the Backup Time is being programmed.
BACKUP (ON) Time is set as minutes and seconds (MM:SS) only.
The small flashing LED under the MM indicates you are setting minutes.
The first field (left side of display) blinks indicating the device is ready for you to begin programming.
Programming Backup Time
NOTE: When programming a time of less than 10 min-
utes you must program the leading zero in the first num­ber field and press the ENTER button to save the zero selection.
1. To set the ON Time use the UP or DOWN ARROW button to scroll through numerals 0 to 5 until the desired number appears in the first MM (min­utes) field.
2. Press the ENTER button to lock in the selection. The next MM number field to the right flashes indicating it is ready for programming.
6. After pressing the ENTER button to set the last SS field, all the programmed ON Time information is saved.
The G3 automatically switches to the OFF Time SETUP MODE.
ON Time
The LED next to the clock in the ON field lights, indicating you are setting the ON Time parameters.
ON Time is set in Minutes and Seconds (MM: SS).
An LED flashes under either MM when pro­gramming minutes OR SS when pro­gramming seconds.
In SETUP MODE, the number displayed in the first field, on the left side of display blinks, indicating the device is ready to pro­gram the ON Time minutes.
The total amount of ON Time cannot exceed 30 minutes. If a value greater than 30 minutes is entered, the RED alarm LED lights and the value must be updated.
If this time does not meet the application needs, contact Graco Customer Support.
3. Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second MM number field.
4. Press the ENTER button to lock in the selection.
The next number field to the right flashes and the LED lights under SS; indicating it is ready to program the seconds fields.
5. Repeat steps 1 - 4 to set the SS (seconds) fields.
332305B 33
Programming ON Time
NOTE: When programming a time of less than 10 min-
utes you must program a leading zero in the first num­ber field and press the ENTER button to save the zero selection.
1. To set the ON Time use the UP or DOWN ARROW button to scroll through numerals 0 to 5 until the desired number appears in the first MM (min­utes) field.
Max Model Setup
2. Press the ENTER button to lock in the selection. The next MM number field to the right flashes indicating it is ready for programming.
3. Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second MM number field.
4. Press the ENTER button to lock in the selection.
The next number field to the right flashes and the LED lights under SS; indicating it is ready to program the seconds fields.
5. Repeat steps 1 - 4 to set the SS (seconds) fields.
6. After pressing the ENTER button to set the last SS field, all the programmed ON Time information is saved.
indicating you are now in the Machine Count setup mode.
2. Press the UP or DOWN ARROW button to move up or down through number 0-9.
3. When the correct number displays, press the ENTER button to set the num­ber.
NOTE: If the machine count input is available on the unit and not used, the value MUST be set to zero (0).
4. Repeat 2 - 3 to set the remaining fields.
NOTE: After the Machine Count value is entered, the G3 can be programmed to backup the machine count input with time.
Backup Time Setup
1. The OFF Time LED lights.
The G3 automatically switches to the OFF Time SETUP MODE.
PUMP OFF / REST Setup
After setting the parameters for either Cycle (C1, C2 or C3) or Pressure (P1, P2, or P3) ON modes, the OFF or pump rest cycle must be set up. There are 3 ways to control this function:
Machine Count switch activation, or
Machine Count activations limited by a maxi­mum Time, or
A specific set amount of Time (similar to Time Mode).
If the machine count sensor input is available and not used in the OFF Mode, the definition of the entered time is OFF TIME.
Machine Count
1. After you set the last ON Time field and press the ENTER button, the G3 automatically switches to the Machine Count setup.
OFF displays.
2. Press the UP or DOWN ARROW button to change OFF to ON on the display.
3. Press the ENTER button to set the selection.
Backup Time
The LED next to the clock in the OFF field lights, indicating you are setting the Backup Time parameters.
OFF Time is set in Hours and Minutes (HH: MM).
Notice the LED next to 123 on the G3 display lights
34 332305B
Max Model Setup
OR
OR
An LED flashes under either HH when pro­gramming hours OR MM when program­ming minutes.
In SETUP MODE the number displayed in the first field, on the left side of display blinks, indicating the device is ready to pro­gram the Backup Time hours.
The total amount of Backup Time must be at least twice as long as the pro­grammed ON Time. If a value less than twice the ON Time is entered, the RED alarm LED lights and the value must be updated.
If this time does not meet the application needs, contact Graco Customer Support.
Programming Backup Time
NOTE: When programming a Backup Time of less than 10 hours you must program a leading zero in the first
number field and press the ENTER button to save the zero selection.
1. To set the Backup Time use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the first HH (hour) field.
2. Press the ENTER button to lock in the selection. The next HH number field to the right flashes indicating it is ready for programming.
3. Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second HH number field.
4. Press the ENTER button to lock in the selection.
5. Repeat steps 1 - 4 to set the next MM (minutes) fields.
6. After pressing the ENTER button to set the last MM field, the OFF Time informa­tion is saved.
7. After selecting ON, refer to page 32.
NOTE: Backup time can be set in HH:MM for the machine count input.
OFF Time
The LED next to the clock in the OFF field lights, indicating you are setting the OFF Time parameters.
OFF Time is set in Hours and Minutes (HH: MM).
An LED flashes under either HH when pro­gramming hours OR MM when program­ming minutes.
In SETUP MODE the number displayed in the first field, on the left side of display blinks, indicating the device is ready to pro­gram the OFF Time hours.
The total amount of OFF Time must be at least twice as long as the pro­grammed ON Time. If a value less than twice the ON Time is entered, the RED alarm LED lights and the value must be updated.
If this time does not meet the application needs, contact Graco Customer Support.
Programming OFF Time
NOTE: When programming a time of less than 10 hours you must program a leading zero in the first
number field and press the ENTER button to save the zero selection.
The next number field to the right flashes and the LED lights under MM; indicating it is ready to program the minutes fields.
332305B 35
Max Model Setup
1. To set the OFF Time use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the first HH (hour) field.
2. Press the ENTER button to lock in the selection. The next HH number field to the right flashes indicating it is ready for programming.
3. Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second HH number field.
4. Press the ENTER button to lock in the selection.
The next number field to the right flashes and the LED lights under MM; indicating it is ready to program the minutes fields.
5. Repeat steps 1 - 4 to set the next MM (minutes) fields.
6. After pressing the ENTER button to set the last MM field, the OFF Time informa­tion is saved.
Prelube
The Prelube function determines operation of the pump when power is applied. It can be set to OFF or ON.
OFF (default) - The unit resumes its lubrication cycle at the point it was at when power was removed.
ON - The unit begins a pump cycle.
Setting Prelube
1. After you set the OFF Time information and press the ENTER button, the G3 automatically switches to the Prelube Delay setup.
Notice the LED next to the prelube icon on the G3 display lights indicat­ing you are now in the Prelube setup mode.
2. OFF displays. If you want the prelube cycle to begin imme­diately, leave this set to OFF.
3. Press the ENTER button to set the selection.
4. If you want to set a prelube delay time, press the DOWN ARROW button to change OFF to ON on the display.
Prelube Delay
Prelube Delay can be entered to delay the start of the pump’s cycle on power up. If prelube is set to ON, a pre­lube delay time in MM:SS must be entered. By default, the delay is set to 0 (begin an ON cycle immediately).
Delaying the prelube function may be desired if other critical functions or systems of your machine or vehicle are also coming on line during power up.
1. Prelube Delay is set in MM:SS (minutes and sec­onds). To set the time use the UP or DOWN ARROW button to scroll through numerals 0 to 5 until the desired number appears in the first MM (minutes) field.
The maximum length of time Prelube Delay can be set to is 59:59 (59 minutes:59 seconds).
2. Press the ENTER button to lock in the selection. The next MM number field to the right flashes indicating it is ready for programming.
3. Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second MM number field.
4. Press the ENTER button to lock in the selection.
36 332305B
The next number field to the right
Max Model Setup
flashes and the LED lights under SS; indicating it is ready to program the seconds fields.
5. Repeat steps 1 - 4 to set the SS (seconds) fields.
6. After pressing the ENTER button to set the last SS field the G3 automatically switches to the RUN MODE.
DMS™ Models Only
Downloading Data
1. Plug the USB flash drive into the USB port.
NOTE: The G3 pump stops pumping as soon as the USB flash drive is plugged into it.
2. The system automatically begins downloading data to the USB drive.
3. “data” is displayed while the system is downloading files.
4. When download is finished, “done” is displayed.
5. G3 pump restarts cycle in the OFF mode.
5. G3 pump restarts cycle in the OFF mode.
6. After the download is com­plete, press and hold the UP and DOWN ARROW button for 3 seconds to store the cur­rent setup to the USB flash drive.
7. “data” is displayed while the unit is downloading and storing the configu­ration on the USB drive.
8. When configuration is stored, “done” is displayed.
9. G3 pump restarts cycle in the OFF mode.
10. Remove the USB flash drive.
Uploading Pump Program Settings to the Pump
1. Plug the USB flash drive into the USB port.
NOTE:
The USB flash drive must contain file
GRACO/G3Config/g3config.bin.
6. Remove the USB flash drive.
Storing Pump Program Settings to the Flash Drive
The pump program settings file is named:
GRACO/G3Config/g3config.bin. This file cannot be modified. Modification of the file or file name may cause it to be unusable.
1. Plug the USB flash drive into the USB port.
NOTE: The G3 pump stops pumping as soon as the USB flash drive is plugged into it.
2. The system automatically begins downloading data to the USB drive.
3. “data” is displayed while the system is downloading files.
4. When download is finished, “done” is displayed.
The G3 pump stops pumping as soon as the USB flash drive is plugged into it.
2. The system automatically begins downloading data to the USB drive.
3. “data” is displayed while the system is downloading files.
4. When download is finished, “done” is displayed.
5. G3 pump restarts cycle in the OFF mode.
6. After the download is com­plete, press and hold the RESET button and UP ARROW button for 3 seconds to upload the setup stored in the USB flash drive.
7. “data” is displayed while the unit is uploading the configuration data.
8. When upload is finished, “done” is displayed.
332305B 37
Max Model Setup
9. G3 pump restarts cycle in the OFF mode.
10. Remove the USB flash drive.
11. After the USB flash drive is removed, press and hold the UP and DOWN ARROW but­tons for 3 seconds to enter the SETUP MODE (see Entering Setup Mode, page 29).
12. In SETUP MODE, set the YEAR, MONTH, DATE and TIME (see Setting the Real Time Clock, page
30).
13. After pressing the ENTER button to set the TIME, press the RESET button to exit the SETUP MODE.
Viewing the UNIT DMS ID Number
1. In RUN mode, press and hold the DOWN ARROW button.
2. The Unit DMS ID number displays. The unit continues to normal operation while the DMS ID is displayed.
3. Release the DOWN ARROW button after viewing the DMS ID number.
38 332305B
Operation / Data Log
Operation / Data Log
During operation the G3 Pump stores information as Log and Summary Files.
Logs contain the following information:
Log Name
DMS ID Number
Current Software Graco Part Number
Current Software Version
Date and Time of Upload
System Event Log
The System Event Log lists the date and time of the last 800 common system events such as pump cycles, man­ual run and setting changes. The most recent event is listed first.
The log file is stored in a folder structure created by the pump DMS ID and download date. If multiple downloads are done on the same date, the existing files will be writ­ten over.
Sample System Event Log
Example Event Log 1: Pump cycle of a divider valve
system with a proximity switch set to detect 5 divider valve cycles.
G3 System Event Log
DMS ID Number: 0025 (see page 38)
Software Part Number: 16F821 Software Version: 1019
09/29/2010 14:1400
Date Time Description 9/29/2010 14:13:02 Pump Run Off 9/29/2010 14:13:02 C1 Cycle Completed 9/29/2010 14:12:39 C1 Cycle Detected 9/29/2010 14:12:34 C1 Cycle Detected 9/29/2010 14:12:28 C1 Cycle Detected 9/29/2010 14:12:23 C1 Cycle Detected 9/29/2010 14:12:17 Pump Run On
The folder structure is as follows:
GRACO/G3_{DMS_id}/{download date - YYYYm­mDD}/EVENTLOG.CSV
Example: GRACO/G3_00025/20100911/EVENT­LOG.CSV.
332305B 39
Operation / Data Log
Example Event Log 2: Pump cycle of an injector valve system with a pressure switch feedback.
Date Time Description 9/29/2010 13:28:12 Venting Completed 9/29/2010 13:23:12 Venting Detected 9/29/2010 13:23:11 Pump Run Off 9/29/2010 13:23:11 P1 Pressure Completed 9/29/2010 13:22:20 Pump Run On
Common System Events are listed below.
Pump Run On The pump entered an on cycle and is
operating and dispensing material.
Pump Run Off The pump entered an off cycle and is
not dispensing.
Pump Run Can­celled
G3 Power On The pump powered on.
G3 Power Off The pump powered off.
Program Variable Change
C1 Cycle Detected The system is set up to monitor a prox-
C2 Cycle Detected
C3 Cycle Detected
C1 Cycle Com­pleted
C2 Cycle Com­pleted
C3 Cycle Com­pleted
P1 Pressure Com­pleted
P2 Pressure Com­pleted
P3 Pressure Com­pleted
Machine Count Completed
Local Manual Run Initiated
Remote Manual Run Initiated
A pump on cycle was cancelled by pressing the cancel button on the front panel and holding it for 3 seconds.
The setup mode was entered.
imity switch on a divider valve using the sensor input (C1, C2, and/or C3) and has detected one divider valve cycle.
The system is set up to monitor a prox­imity switch on a divider valve using the sensor input (C1, C2, and/or C3) and has achieved the number of counts required by the system for that input, completing a pump on cycle.
The system is set up to monitor a pres­sure switch for an injector system using sensor input (P1, P2, and/or P3), the system has achieved pressure and the switch has activated, completing a pump on cycle.
The system is set up to monitor a sen­sor on the equipment being lubricated using the machine count input and has achieved the number of counts required by the system for that input, completing a pump off cycle and initiating a pump on cycle.
The manual run button was pressed, initiating a pump on cycle.
The remote manual run button was pressed initiating a pump on cycle.
Venting Detected In an injector system, the pump on cycle
has completed and the system is cur­rently venting pressure through the vent valve.
Prelube Initiated The pump has entered a prelube delay
after powering up.
Prelube Completed The pump has completed prelube delay
and will begin a pump on cycle.
Successful Pin Code Entry
The pin code was successfully entered and the user has entered setup mode.
Error Log
The Error Log lists Set Time and Clear Time for the last 400 faults and warnings. The most recent event is listed first.
The log file is stored as:
GRACO/G3_{DMS_id}/{download date - YYYYm­mDD}/ERRORLOG.CSV
Example: GRACO/G3_00025/20100911/ERROR­LOG.CSV.
Sample Error Log
G3 Error Log DMS ID Number: 00025 (see page 38) Software Part Number:16F821 Software Version:0205 12/31/2015 23:04:00
Date Time
12/31/2015 23:03:54 12/31/2015 23:03:42 12/31/2015 23:03:32 12/31/2015 23:03:22 12/31/2015 23:03:22 12/31/2015 23:03:19 12/31/2015 23:03:19 12/31/2015 23:02:20 12/31/2015 23:02:11
Description Low Level Cleared Low Level Fault Low Level Warning P2 Not Detected Cleared C1 Not Detected Cleared P2 Not Detected C1 Not Detected
Machine Count Not Detected
Machine Count Not Detected
40 332305B
Operation / Data Log
Common Error Log entries are listed below.
Software Fault An internal software error
occurred. Contact Graco Cus­tomer Service.
Low Level Warning The unit entered a low level
warning mode and is running low on material. The pump continues to dispense material for the duration of the low level alarm time specified by the unit.
Low Level Fault The alarm time in low level
warning has elapsed. The unit will not pump until the reservoir is filled and the fault is cleared.
Cycle 1 Not Detected In a divider valve system, the
Cycle 2 Not Detected
Cycle 3 Not Detected
system has not received the programmed number of divider valve cycles for the specified input in the programmed backup time.
Pressure 1 Not Detected
Pressure 2 Not Detected
In an injector system the sys­tem has not received a signal from the pressure switch in the designated backup time.
Pressure 3 Not Detected
System Already Pres­surized 1
System Already Pres­surized 2
System Already Pres-
In an injector system the pres­sure switch is activated when the unit enters a pump on mode and may not have vented properly.
surized 3
Machine Count Sensor Failure
The specified number of machine count input activa­tions was not received within the designated backup time.
Motor Overcurrent The unit is out of expected
motor current range. Check the system to determine that it is functioning correctly (i.e., no blocked lines). Continued oper­ation at excessive motor cur­rents will cause degradation in pump life.
High Temperature Warning
Internal temperature of the unit is above the designated oper­ating. Check the unit and sys­tem to determine that it is functioning correctly. Operating outside of the specified tem­perature range may cause reduced performance and pos­sible unit failure.
Low Temperature Warning
Internal temperature of the unit is below the designated operat­ing. Check the unit and system to determine that it is function­ing correctly. Operating outside of the specified temperature may cause reduced perfor­mance and possible unit fail­ure.
USB Unable to Mount The USB flash drive that was
installed was unable to connect and communicate with the pump.
USB Unsupported Device
The USB flash drive is unsup­ported. Use a different flash drive.
USB File Not Found The pump program setting file
was not found or created cor­rectly. Restore the setting file to the flash drive.
USB Folder Navigation The pump program setting file
was not found or created cor­rectly. Restore the setting file to the flash drive.
USB Invalid File The pump program settings file
was not found or created cor­rectly. Restore the setting file to the flash drive.
Failed Pin Code Entry A failed attempt was made to
enter the pin code password.
332305B 41
Operation / Data Log
(see page 38)
Functional Summary
The Functional Summary contains two types of data.
The first report type, labeled User under the Type heading in the first column of the Sample Functional Summary, only provides data compiled since the last time the Functional Summary was reset through present day (see A6 - Clearing the Functional and Technical User Summary, page 49).
This is very similar to the resettable trip odometer in your car.
Sample Functional Summary
The second report type, labeled Factory under the Type heading in the first column of the Sample Functional Summary, covers the cumulative life of the pump from the first day it was put into service through present day.
This is very similar to an odometer in your car.
The log file is stored as:
GRACO/G3_{DMS_id}/{download date - YYYYm­mDD}/FUNCSUM.CSV
Example: GRACO/G3_00025/20100911/FUNC­SUM.CSV
42 332305B
Common Functional Summary Data entries are listed below.
Number of Cycles The number of lubrication cycles
the unit has started.
Total Run Hours Total amount of hours the pump
has been in the ON mode of the ON/OFF cycle.
Total Powered On Hours Total number of hours that the
unit has been powered on.
Local Manual Run The number of times the manual
run button was pressed.
Remote Manual Run The number of times the remote
manual run button was pressed.
Average Run Time The average amount of time per
lubrication cycle that the pump has been running (MM:SS).
Average Cycle 1 Time The average amount of time the
Average Cycle 2 Time
Average Cycle 3 Time
Average Duty Cycle The average percentage of time
Max Duty Cycle The highest percentage of time
Total Low Level Faults Total number of low level faults.
Total Cycle Pressure Faults
Total Other Faults Faults other than low level or
Total Fault Hours Number of hours the system has
Total Low Level Warnings Number of low level warning
Total Cycle Pressure Warnings
Total Other Warnings All other warnings including tem-
unit has been operating before the specified feedback for the sensor input was received (prox­imity switch counts in divider valve systems and pressure switch activation in injector sys­tems).
the unit has been pumping while it has been powered on.
for one lubrication cycle that the unit has been pumping while it has been powered on.
Total number of faults related to sensor feedback in an injector or divider valve system.
sensor feedback.
been powered on in fault mode.
conditions.
Total number of warning condi­tions related to sensor feedback. This is only applicable if fault retries are used.
perature and motor current.
Operation / Data Log
332305B 43
Operation / Data Log
Technical Summary
The Technical Summary contains two types of data.
The first report only provides data compiled since the Pump Summary was reset to present day (see A6 - Clearing the Functional and Technical User Summary).
This is very similar to the resettable trip odometer in your car.
The second is a report that covers the cumulative life of the pump from the first day it was put into ser­vice to present day.
This is very similar to an odometer in your car.
The log file is stored as:
GRACO/G3_{DMS_id}/{download date - YYYYm­mDD}/TECHSUM.CSV
Sample Technical Summary
Example: GRACO/G3_00025/20100911/TECH­SUM.CSV
Common Technical Summary Data entries are listed below.
Average Input Board Voltage (DC)
Peak Input Board Volt­age (DC)
Average Motor Current The average motor current mea-
Peak Motor Current The peak motor current mea-
Average Internal Tem­perature
Peak Internal Tempera­ture
Low Internal Tempera­ture
The average input voltage mea­sured by the internal circuit board.
The peak input voltage measured by the internal circuit board.
sured by the unit.
sured by the unit.
The average internal tempera­ture seen by the unit.
The peak internal temperature seen by the unit.
The lowest internal temperature seen by the unit.
G3 Technical Summary DMS ID Number: 00025 (see page 38) Software Part Number:16F821 Software Version: 0205 12/27/2010 9:50:51
Latest Values Temp Voltage 31C 23.877
Type Start Date Average
Board Voltage
Peak Board Voltage
Average Motor Current
Peak Motor Current
Average Internal Temp
Peak Internal Temp
Low Internal Temp
User 12/21/2010 23.877 23.877 0.062 0.06230C 35C 28C Factory 9/30/2010 22.804 23.877 1.091 0.36233C 42C -10C
44 332305B
Advanced Programming
Advanced Programming
There are 7 Advanced Programming options. The following Table Identifies each option and when it is used.
Advanced
Option
A1 Max Lockout
A2 Max Low Level
A3 Max Vent Valve
A4 Max Alarm Retry Sets number of automatic
A5 Max Active
Model Setting Format/ Description Why Use This?
Secures setup modes with Code (Optional)
Alarm Time
Time
Alarm
PIN
MM:SS (minutes:seconds)
sets amount of time
between Low Level Warning
to Low Level Fault.
Default = 3 minutes
MM:SS (minutes:seconds)
sets amount of time vent
valve stays open after Pump
ON Mode.
Default = 5 minutes
retries after a Cycle or Pres-
sure Alarm.
Default = 0
Changes alarm output
behavior.
Prevents unauthorized users to adjusting settings.
To accommodate most lubrication situa­tions, a conservative amount of time is pro­grammed between the low level warning and fault to help protect unit from running dry. If necessary the amount of time the unit runs before stopping due to a low level fault can be adjusted.
• In an injector based system that does not use a sensor for feedback, determines the amount of time the system vents.
• Vent time can be modified.
Establishes the number of times the unit automatically retries lubricating after a cycle or pressure alarm to determine if a temporary or false signal can be cleared.
Uses alarm output to determine if a unit has an alarm AND/OR loses power.
Default = OFF
A6
A7 Max Constant
332305B 45
DMS
Equipped
Models
Functional and Techni­cal User Summary Reset
Alarm Out­put on Fault
Clears the Functional and Technical User Summaries
Changes alarm output behavior.
Default = OFF
The output turns ON when power is applied. It turns OFF when power is lost or an alarm occurs.
Normal operation (OFF) will only activate alarm output in an alarm condition when power is on.
Can change (set to ON) to activate alarm with power ON and deactivate with power OFF OR warning.
Used to manage power outage. Allows user to track lube events from a spe-
cific point (reset), i.e. a month to month evaluation.
This function changes the behavior of the alarm output in a fault from either toggling once every second or steady on.
Advanced Programming
Entering a PIN Code for the First Time
A1 - Setting Up PIN Code
A PIN Code can be programmed into the G3 to protect the settings from inadvertently being changed by unau­thorized users.
1. Press the UP ARROW button for 10 seconds.
The LED next to the LOCK ICON on the display lights, indicating you have entered the PIN Mode.
2. The word OFF appears in the display. Press the UP or DOWN ARROW button to change this to ON.
3. Press the ENTER button to enter the PIN Code.
4. The cursor automatically is positioned to entered the first character of the PIN Code. Use the UP and DOWN ARROW buttons to move up and down through the numbers 0-9 until the first number in the PIN code is displayed in the field.
1. The cursor is automatically positioned to enter the first character of the PIN Code. Use the UP and DOWN ARROW buttons to move up and down through the numbers 0-9 until the first number in the PIN code is displayed in the field.
2. Press the ENTER button to set the num­ber. The cursor automatically moves to the next number field.
3. Repeat steps 1 and 2 for each PIN Code prompt field.
If the PIN Code you entered is correct, the first editable character on the display will flash.
Selecting Advanced Setup Options
1. Press the UP or DOWN ARROW button to move up or down through Advanced Options A1 - A7.
2. Press the ENTER button to set the selection.
5. Press the ENTER button to set the number. The cursor automatically moves to the next number field.
6. Repeat steps 4 and 5 for each PIN Code prompt field.
7. Press the ENTER button to save the PIN Code and exit Advanced Setup.
Entering Advanced Setup
Press the UP ARROW button for 10 sec­onds.
If the G3 was previously set up to require a PIN Code, the LED next to the LOCK ICON lights, indi­cating a PIN Code is required.
46 332305B
Advanced Programming
A2 - Low Level Alarm Time
Pump ON mode only.
Programs the amount of time in MM: SS (minutes and seconds) the pump can run between a Low Level Warn­ing and a Low Level Fault to help protect unit from run­ning dry.
The maximum recommended length of time is 3:00 min­utes.
Fault, and Low Level LED illuminate. (Max Model Dis- play shown in illustration below).
3. Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second MM number field.
4. Press the ENTER button to lock in the selection.
The next number field to the right flashes and the LED lights under SS; indicating it is ready to program the seconds fields.
5. Repeat steps 1 - 4 to set the SS (seconds) fields.
6. After pressing the ENTER button to set the last SS field, all the programmed ON Time information is saved.
Unit exits Advanced Programming.
A3 - Vent Valve Time
The Vent Valve Time is the amount of time the vent valve stays open after a cycle is completed.
F
IG. 23
NOTE: When programming a time of less than 10 min-
utes you must program a leading zero in the first num­ber field and press the ENTER button to save the zero selection.
1. To set the time use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the first MM (min­utes) field.
2. Press the ENTER button to lock in the selection. The next MM number field to the right flashes indicating it is ready for programming.
The recommended Vent Valve Time is 5 minutes.
To bypass the Vent Valve Time enter a value of 00:00.
Vent Valve time must be less than the programmed OFF time (page 35). If it is not set to a value less than the programmed OFF time, the G3 will automatically adjust the time to a value 2 seconds less than the set OFF time.
332305B 47
Advanced Programming
To set Vent Valve Time:
NOTE:
The LED next to the clock in the OFF field lights and P1, P2, and P3, indi­cating the Vent Valve Time is being programmed.
Time is set as minutes and seconds (MM:SS) only.
The small flashing LED under the MM indicates you are setting Minutes.
The first field (left side of display) blinks indicating the device is ready for you to begin programming.
7. After pressing the ENTER button to set the last seconds field, all the pro­grammed Time information is saved.
Unit exits Advanced Programming.
A-4 Alarm Retry
Programs the number of times G3 will automatically retry running a lubrication cycle after a cycle or pressure alarm activates. The default setting is 0. For assistance determining a reasonable number of Alarm Retries to program for your application, contact Graco Customer Service or your local Graco distributor.
1, 2, and 3 and Fault LED’s illuminate.
When programming a time of less then 10 minutes you must program a leading zero in the first number field and press the ENTER button to save the zero selection.
1. To set the Time use the UP or DOWN ARROW but­ton to scroll through numerals 0 to 5 until the desired number appears in the first minute field.
2. Press the ENTER button to lock in the selection. The next minute field to the right flashes indicating it is ready for programming.
3. Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second minute field.
4. Press the ENTER button to lock in the selection.
5. The next number field to the right flashes and the LED lights under SS; indicating it is ready to program the Seconds fields.
FIG. 24
To set the Alarm Retry:
1. The default value 0000 appears in the display.
2. Press the UP or DOWN ARROW button to move up or down through number 0-9.
6. Repeat steps 1 - 4 to set the MM (seconds) fields.
48 332305B
Advanced Programming
3. When the correct number displays, press the ENTER button to set the num­ber.
4. Repeat 2 - 3 to set the remaining fields.
5. Press the ENTER button to exit Advanced Programming.
A-5 Active Alarm
Changes the alarm output behavior. Uses output to determine if a fault has occurred.
Fault and ON LED’s illuminate.
3. Press the ENTER button to exit Advanced Programming.
A6 - Clearing the Functional and Technical User Summary (DMS
The Pump Summary shows run details since the last time the summary was cleared.
Models only)
F
IG. 25
1. The default OFF dis­plays.
2. Press the UP or DOWN ARROW button to change OFF to ON on the display to activate alarm condition.
FIG. 26
1. Press the UP or DOWN ARROW button to move through Advanced Options until Advanced Option A6 is displayed.
2. Press the ENTER button.
3. “Data” displays.
4. Press the RESET but­ton. “Reset” displays. The summary data is cleared.
5. Press the RESET or ENTER button to exit.
332305B 49
Advanced Programming
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
A-7- Constant Alarm Output on Fault
This function changes the behavior of the alarm output in a fault from either toggling once every second (default) or steady on.
Fault and Warning LEDs Illuminate
F
IG. 27
1. The default OFF is displayed. The alarm output will toggle once a second.
2. Press the UP or DOWN ARROW to change OFF to ON on the display to change the alarm output to be on steady
3. Press the ENTER button to exit Advanced Programming.
50 332305B
Run Mode
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
Run Mode
Time Control
After setup is complete, the G3 automatically begins to run the OFF Time sequence (F
The G3 runs the programmed OFF sequence.
(Notice the OFF Time LED on the display lights and the OFF Time counts down on the display.)
The example shown in F of 1 hour and 32 minutes before the lubrication cycle begins.
IG. 28).
IG. 28 shows an OFF Time
When the OFF Time count reaches zero, the G3 Automatic Lubrication Pump turns the pump on and it runs for the programmed ON Time cycle (F
IG. 29).
(Notice the ON Time LED is now illuminated on the display.)
The example shown in F
IG. 29 shows an ON Time
of 8 minutes and 42 seconds before the lubrication cycle ends.
FIG. 29
When the ON Time count reaches zero, the pump shuts off again and the system again runs OFF Time cycle and the OFF Time LED is now again illu-
F
IG. 28
minated (F
This sequence repeats itself until the device is reprogrammed or an alarm occurs.
IG. 28).
If power to the pump is lost during a lubrication cycle, when power is restored the pump will resume
332305B 51
the cycle with the same amount of time remaining in the cycle as when the power was lost.
Run Mode
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
Lubrication Mode (Pump ON) Controls
In Max models the Lubrication Mode (Pump ON) can be controlled by either cycle and/or pressure sensors.
If cycle and/or pressure controls have been set to some­thing other than OFF the display will alternate between cycles (C1, C2, C3) and/or active sensors (P1, P2, P3) and Backup Time.
If cycle or pressure controls have been set to OFF then the Lubrication Mode (Pump ON) will be controlled by On Time (see Time Control, page 51).
With cycle and/or pressure controls set, the lubrication cycle (Pump ON) is ended by meeting all required cycle and/or pressure settings.
Cycle Control
A set number of triggered counts in a cycle based system (C1). Typically a proximity switch connected to a divider valve.
The LED next to the appropriate sensor (C/P1, C/P2, C/P3) illuminates.
Pressure Control
A single triggered count in a pressure based system (P1). Typically a pressure switch on the
end of a line of injectors.
The LED next to the appropriate sensor (C/P1, C/P2, C/P3) illuminates (F
IG. 31 and FIG. 32).
The display indicates the sensor (P1, P2, P3) and whether the pressure switch for that sensor has been triggered or not.
- 01 = pressure switch has not been triggered
- 00 = pressure switch is triggered.
The example shown in F
IG. 31 shows sensor P1
with a pressure switch that has been triggered.
F
IG. 32 (page 53) shows sensor P2 with a pres-
sure switch that has NOT been triggered.
HH MM
SS ##
!
The display indicates the sensor (C1, C2, C3) and the remaining cycles for that sensor (F
30).
The example shown in F
IG. 30 shows sensor C1
with 5 cycles remaining.
IG.
FIG. 31
ON
OFF
MM : SS HH : MM
C
1
P
C
C
2
P
C
P
3
P
1 23
F
IG. 30
52 332305B
Backup Time
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
In both Cycle and Pressure modes a Backup Time (maximum run time) has been set.
The LED(s) next to all programmed sensors (C/P1, C/P2, C/P3) illuminate.
The display shows time remaining until a fault.
Run Mode
F
IG. 32
The example shown in F
IG. 33 shows 14 min-
utes and 33 seconds left until the fault occurs.
If all cycle and/or pressure requirements are met the unit exits the lubrication cycle (Pump ON) and enter the rest cycle (Pump OFF).
332305B 53
FIG. 33
Rest Mode (Pump OFF) Controls
In Max models the Rest Mode (Pump OFF) is controlled by machine counts.
If the Machine Count is set to a value greater than 0000 and the Backup Time option is activated, the display will alternate between Machine Counts and Backup Time.
If Machine Count has been set to a value greater than 0000 and the Backup Time option is NOT activated, the display will only show the number of Machines Counts remaining.
Run Mode
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
With machine count set, the Rest Cycle (Pump OFF) is ended when the machine count reaches zero (0000).
Machine Count
A set number of triggered counts.
The LED next to 1-2-3 illuminates (F
IG. 34).
The display indicates the number of machine counts remaining.
The example shown in F
IG. 34 shows the
remaining number of machine counts is 0045.
Backup Time
In Machine Count mode, if a Backup Time (maximum rest time) has been set:
The LED next to 1-2-3 illuminates (F
IG. 35).
The display shows the amount of time remain­ing till a fault.
The example shown in F
IG. 35 shows 4 hours
and 17 minutes remaining until a fault occurs.
If the Machine Count requirements are met the unit will exit the Rest Mode (Pump OFF) and enter the Lubrication Mode (Pump ON).
HH MM
SS ##
!
ON
MM : SS HH : MM
OFF
F
IG. 34
C
1
P
C
C
2
P
C
P
3
P
1 23
FIG. 35
OFF Time
In Max models if the Machine Count is set to 0000 then Reset Mode (Pump OFF) is controlled with OFF Time (see Time Control, page 51).
54 332305B
Run Mode
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C
P
C
P
C
P
Additional Controls
Venting
In Max models a Vent Time can be set using the Advanced Programming mode (page 47). This is typi­cally done in a Pressure Based System (P1) to allow injectors to reset.
Unit vents for a set amount of time (not dis­played).
The LED’s next to C/P1, C/P2, C/P3 flash while unit is venting.
If Machine Count is set, the display will alternate between machine counts remaining and backup time (Max Model Rest Mode, page 53).
If Machine Count has been set the LED next to 1-2-3 illuminates (F
If Machine Count has not been set the display shows OFF Time (See Time Control, page 51).
If Machine Count has not been set the LED next to the clock in the OFF field illuminates (See Time Control, page 51).
Prelube / Prelube Delay
In all models a power OFF/ON cycle can be controlled with the Prelube and Prelube Delay functions.
IG. 34, page 54).
Prelube
The Prelube function has been selected. Prelube delay is set to 00:00:
Power to the unit cycles OFF then ON.
Unit immediately begins a lubrication cycle.
Max Model - display shows Cycle/Pres­sure/Backup Time (See Max Model Lubrication Mode Controls, page 52).
Prelube Delay
The Prelube function has been selected. Prelube delay is set to something other than 00:00:
Power to the unit cycles OFF then ON.
Unit immediately begins the Prelube Delay count down until the lubrication cycle begins.
The LED next to the clock in the OFF field is illu­minated (F
The Prelube LED lights (F
IG. 36).
IG. 36).
The display shows time remaining until lubrica­tion cycle begins. The example shown in F
IG. 36
shows 8 minutes and 14 seconds left until a lubrication cycle begins.
332305B 55
IG. 36
F
Run Mode
Manual Run Cycle
To run an extra (non-programmed) lubrica­tion cycle, push the Manual Start button.
NOTE: Manual Run option is not available while unit is in Vent Mode.
56 332305B
Alarms
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C
P
C
P
C
P
Alarms
Any time a Fault / Warning occurs, a combination of LED’s will illuminate to notify you there is a problem and help identify the kind of Fault / Warning has occurred.
Faults and Warnings will not automatically clear.
To clear an fault, press and hold the RESET button on the display button pad for 3 seconds.
To clear a warning press and immediately release the RESET button.
Fault / Warning Scenarios
The following pages describe the most likely fault / warnings you could receive.
Alarm Type What it Looks Like What it Indicates Solution
Low Level Warning
Level of lubricant in reservoir is low and addi­tional lubricant needs to be added.
Unit continues to operate as normal for a limited period of time until a low level alarm is triggered.
Add lubricant to reservoir.
After lubricant is added, press the RESET but­ton to clear the warning.
332305B 57
Alarms
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
Low Level Fault
Cycle / Pressure Warning
Level of lubricant in reservoir is low and addi­tional lubricant needs to be added.
Unit stops pumping and displays amount of accu­mulated time since the alarm was triggered.
System fails to relieve pressure or a lubrication cycle was not completed in the user-defined amount of time.
Add lubricant to reservoir.
After lubri­cant is added press and hold the RESET button to clear fault.
If repriming pump is required, the low level alarm time should be decreased. See A-2: Advanced Programming, Low Level Alarm Time page 47.
Examine system to deter­mine if you have a plugged or broken line or other component failure, i.e., divider valve, injector.
Unit will continue to oper­ate for the number of lubri­cation cycles set by the warning retry parameter
Press the RESET but­ton to clear
warning. (see Advanced Program­ming, page 45).
If the warning condition clears itself on the next automatic lubrication cycle, the warning is cleared and the unit continues normal operation.
58 332305B
Alarms
Cycle / Pressure Fault
Machine Count Fault
HH MM
ON
MM : SS HH : MM
C
1
P
C
2
P
C
3
P
HH MM
ON
MM : SS HH : MM
C
1
P
C
2
P
C
3
P
SS ##
OFF
C
P
C
P
1 23
SS ##
OFF
1 23
In pressure mode indi­cates that unit is over pres-
!
surized or a lubrication cycle was not completed in the user-defined amount of
Examine system to deter­mine if you have a plugged or broken line or other component failure, i.e., divider valve, injector.
time.
Press and In cycle mode indicates that a cycle was not com­pleted in the user-defined amount of time.
hold the
RESET but-
ton to clear
fault.
LED corresponding to the affected sensor input blinks.
Could be more than one sensor alarm at the same time.
Unit has not received the correct number of machine
!
counts in the user defined Backup Time.
Examine system to deter-
mine if the machine sen-
sor is operating properly.
Press and
hold the
RESET but-
ton to clear
fault.
332305B 59
Alarms
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
ON
OFF
!
1 23
HH MM
SS ##
MM : SS HH : MM
2
3
1
P
C
C P
C P
C P
System Fault
Motor Cur­rent Warn­ing
An internal fault has occurred.
The measured motor cur­rent is above the recom­mended operating maximum value. Continued use at excessive motor currents could reduce life or cause permanent dam­age.
Contact Graco Customer Service.
Examine system to make sure it is operating cor­rectly. A blocked line could create excessive motor current
Examine pump to ensure that it is rotating properly.
If necessary, contact Graco Customer Service.
60 332305B
Alarms
Tempera­ture Warning
HH MM
SS ##
!
The internal temperature of the unit is out of its recom­mended operating range.
Use of the unit outside of
ON
MM : SS HH : MM
OFF
the recommended tem­perature range could cause degraded system perfor­mance and possible dam-
C
1
P
C
C
2
P
C
P
3
P
1 23
age.
USB Error An error occurred during a
DMS operation.
HH MM
SS ##
!
ON
MM : SS HH : MM
OFF
Ensure the unit is used in
the correct operating envi-
ronment for the specific
temperature: -13° F to
158° F (-25° C to 70°C).
If necessary contact
Graco Customer Service.
Read the Troubleshoot-
ing section of this manual
(page 62) for error num-
bers and fault descrip-
tions.
C
1
P
C
C
2
P
C
P
3
P
1 23
332305B 61
Troubleshooting
Troubleshooting
Problem Cause Solution
Unit does not power on
Unit does not power on (DC models only)
Unit does not power on (AC models only)
Can’t set desired ON/OFF times
Unit is not operating based on the time that was programmed
Lubricant leaks past seal located on the bottom of the reservoir
Unit not pumping during ON cycle, but controller lights and functions
Follower plate is not going down
Pump takes several minutes before it begins pumping at the highest pump volume setting (no stroke adjust spacers installed)
Dim display, unit is not operating
Unit indicates a cycle or pressure alarm before the lubrication cycle could complete
Incorrect/loose wiring Refer to Installation instructions,
page 8.
Tripped external fuse due to internal component failure
Tripped external fuse due to pumping non-cold weather lubricant in cold weather -13°F (-25°C)
Tripped internal power supply fuse due to power supply failure
Maximum duty cycle is 33% (2 min­utes OFF for each minute ON)
Time entered was misinterpreted as MM:SS instead of HH:MM (or visa versa)
Reservoir retaining tabs are cracked or broken
Reservoir is being pressurized during filling
Failed motor Replace unit.
Air is trapped in the reservoir between the follower plate and lubri­cant
Pumping non-cold weather lubricant in cold weather -13°F (-25°C)
Tripped internal, resettable fuse due to internal component failure or sen­sor short circuit condition
The ON Time was not entered cor­rectly
Contact Graco Customer Service.
Replace lubricant with pumpable lubricant, rated for environmental conditions and application.
Replace fuse.
Contact Graco Customer Service.
Adhere to allowable duty cycle. Con­tact Graco Customer Support if other duty cycles are required for applica­tion.
Verify the unit was programmed as intended, referencing programming instructions. Note the dot designation for hours, minutes, seconds on the top row of the display.
Replace reservoir.
Ensure vent hole is not plugged.
If problem persists, contact Graco Customer Service or your local Graco distributor for assistance.
Add grease following Loading Grease instructions, page 24. Ensure air is purged.
Add 1 stroke adjust spacer and adjust lube cycle time to accommo­date the difference in pump volume per stroke.
Verify sensor and manual run inputs have not created a short circuit condi­tion. Cycle power.
Refer to programming ON Time, pages 31 and 52.
62 332305B
Problem Cause Solution
In an Injector System without sensor feedback, unit does not vent properly
Display acts erratically
USB Error 00
USB Error 07
USB Error 11
USB Error 12
USB Error 13
Troubleshooting
Vent valve time needs to be config­ured
Faulty cycle/pressure wiring connec­tion to unit
Refer to Advanced Programming to set ON Time, page 45.
Unplug cycle/pressure cables from G3. Plug cables in one at a time to identify the faulty connection.
Flash drive was removed during operation
Flash drive unable to mount (initial­ize)
Keep the flash drive plugged in until the unit has completed the operation.
Unplug the flash drive and re-install.
Cycle power and re-install the flash drive.
Retry using a different flash drive.
If any of the above do not rectify the error, contact Graco Customer Ser­vice.
Pump program setting file not found Verify that the pump program setting
folder structure and file are stored correctly on the flash drive. See Stor­ing Pump Program Settings to the Flash Drive, page 37 for instructions.
Pump program settings directory not found.
Verify that the pump program setting folder structure and file are stored correctly on the flash drive. See Stor­ing Pump Program Settings to the Flash Drive, page 37 for instructions.
Bad pump program settings file The pump programs settings file is
corrupt. Restore file to the flash drive. See Storing Pump Program Settings to the Flash Drive, page 37 for instructions.
The following operations can be attempted if another error occurs using the USB.
All other USB errors
332305B 63
Unplug the flash drive and rein­stall.
Cycle power and re-install the flash drive.
Retry using a different flash drive.
If any of the above do not rectify the error, contact Graco Customer Ser­vice.
Maintenance
Maintenance
Frequency Component Required Maintenance
Daily and at refill Zerk Fittings Keep all fittings clean using a clean
dry cloth. Dirt and/or debris can dam­age pump and/or lubrication system.
Daily G3 Pump Unit and Reservoir Keep pump unit and reservoir clean
using a clean dry cloth.
Daily Display Keep display clean using a clean dry
cloth.
Monthly External Wiring Harness Verify external harnesses are secure.
64 332305B
Parts - 2 Liter Models
40a
44
14
1
42
13
18
17
34
36
33
37
41
21
30
15
4
3
31
Follower Plate Models Only
43
Torque to 4 in. lbs (0.45 N.m)
1
Torque to 30 in. lbs (3.4 N.m)
2
Torque to 50 in. lbs (5.6 N.m)
3
2
3
40b
3
45
35
27
23
16
60
57
Low Level Grease Models Only
Low Level Oil Models Only
66
67
1
12
Parts - 2 Liter Models
332305B 65
Parts - 4 Liter and Larger Models
40a
44
35
14
1
41
13
18
17
34
16
36
33
37
42
21
30
15
4
3
31
Follower Plate Models Only
43
Torque to 4 in. lbs (0.45 N.m)
1
Torque to 30 in. lbs (3.4 N.m)
2
Torque to 50 in. lbs (5.6 N.m)
3
2
3
61
62
40b
3
27
1
45
60
23
57
Low Level Grease Models Only
67
66
Low Level Oil Models Only
12
Parts - 4 Liter and Larger Models
66 332305B
Parts
Parts
Ref Part Description Qty
1 BASE, three pump housing 1
3 278142 COVER, bottom, with seal 1
4 115477 SCREW, mach, torx pan hd 9
12 127079
13 124396
14 PLATE, ricer 1
15 BEARING, ball 1
16
RECT-RING, included in Kit 571042, 571069, 571179
O-RING, 258, included in Kit 571042, 571044, 571045, 571069, 571179
PADDLE, stirring, 2 Liter models without follower plate - models 96G017, 96G019, 96G021, 96G023, 96G025, 96G030-96G032, 96G035-96G037, 96G098, 96G110, 96G125, 96G178, included in Kit 571044
PADDLE, stirring, 4 Liter models without follower plate - models 96G088, 96G092, 96G096, 96G099, 96G103, 96G111, 96G118, 96G126, 96G141, 96G143, 96G145, 96G151, 96G153, 96G155, 96G157, 96G159, 96G160, 96G161, 96G162, 96G181, 96G183, 96G188
PADDLE, stirring, 8 Liter models without follower plate - models 96G089, 96G093, 96G097, 96G100, 96G104, 96G112, 96G119, 96G127, 96G142, 96G144, 96G146, 96G152, 96G154, 96G156, 96G158, 96G177
PADDLE, stirring, 12 Liter models without follower plate - models 96G105, 96G120, 96G164, 96G165
Ref Part Description Qty
PADDLE, stirring, 16 Liter models without follower plate - models 96G106, 96G121, 96G166, 96G168, 96G169, 96G185
16
1
2
1
1
1
1
cont
17
18 16F368
21 278145 PLUG, pump, 3/4-16 2
23278136
27 123025
PADDLE, stirring, 2 Liter models with follower plate - models 96G018, 96G020, 96G024, 96G026, 96G115, 96G132 included in Kit 571045
PADDLE, stirring, 4Liter models with follower plate - models 96G090, 96G094, 96G113, 96G116, 96G128, 96G133
PUMP, element, included in Kit 571041
SPACER, stroke adjust, included in Kit 571041
PADDLE, low level, models 96G017-96G026, 96G030-96G032, 96G035-96G037, 96G088-96G090, 96G092-96G094, 96G096-96G100, 96G103-96G106, 96G110-96G113, 96G115, 96G116, 96G118-96G121, 96G125-96G128, 96G132, 96G133, 96G141-96G146, 96G151-96G162, 96G164-96G166, 96G168, 96G169, 96G177, 96G178, 96G181, 96G183, 96G185, 96G188
SCREW, M6, models 96G017-96G021, 96G023-96G026, 96G030-96G032, 96G035-96G037, 96G088-96G090, 96G092-96G094, 96G096-96G100, 96G103-96G106, 96G110-96G113, 96G115, 96G116, 96G118-96G121, 96G125-96G128, 96G132, 96G133, 96G141-96G146, 96G151-96G162, 96G164-96G166, 96G168, 96G169, 96G177, 96G178, 96G181, 96G183, 96G185, 96G188
1
1
1
1
2
1
1
332305B 67
Parts
Ref Part Description Qty
BOARD, circuit, Max, models 96G017-96G021, 96G023-96G026, 96G030-96G032, 96G035-96G037, 96G088-96G090, 96G092-96G094, 96G096, 96G097,
30 ‡
258697
96G103-96G109, 96G113, 96G118-96G124, 96G128, 96G141-96G146, 96G151, 96G152, 96G155, 96G156, 96G159, 196G160, 96G164, 96G166, 96G168, 96G177, 96G178, 96G181, 96G183
BOARD, circuit, Max, DMS
models 96G098-96G100, 96G110-96G112, 96G115, 96G116, 96G125-96G127,
262463
96G132, 96G133, 96G153, 96G154,96G157, 96G158, 96G161, 96G162, 96G165, 96G169, 96G174-96G176, 96G185, 96G186, 96G188
SCREW, machine, flat head, models 96G017-96G021, 96G023-96G026, 96G030-96G032, 96G035-96G037, 96G088-96G090, 96G092-96G094, 96G096-96G100,
31 119228
96G103-96G113, 96G115, 96G116, 96G118-96G128, 96G132, 96G133, 96G141-96G146, 96G151-96G162, 96G164-96G166, 96G168, 96G169, 96G174-96G178, 96G181, 96G183-96G186, 96G188
3316A579 LABEL, safety 1
LABEL, overlay, models 96G017-96G021, 96G023-96G026, 96G030-96G032, 96G035-96G037, 96G088-96G090, 96G092-96G094, 96G096-96G100, 96G103-96G113,
34 16A073
96G115, 96G116, 96G118-96G128, 96G132, 96G133, 96G141-96G146, 96G151-96G162, 96G164-96G166, 96G168, 96G169, 96G174-96G178, 96G181, 96G183-96G186, 96G188
Ref Part Description Qty
WIPER, stirring, models without fol­lower plate - models 96G017, 96G019, 96G021, 96G023, 96G025, 96G030-96G032, 96G035-96G037, 96G088, 96G089, 96G092, 96G093, 96G096-96G100, 96G103-96G106, 96G110-96G112, 96G118-96G121,
1
96G125-96G127, 96G141-96G146, 96G151-96G159, 96G160-96G162,
35
96G164, 96G165, 96G168, 96G169, 96G177, 96G178, 96G181, 96G183, 96G185, 96G188, included in Kit 571044
WIPER, stirring, models with fol­lower plate - models 96G018, 96G020, 96G024, 96G026, 96G090, 96G094, 96G113,
1 96G115, 96G116, 96G128, 96G132, 96G133 included in Kit 571045
36 LABEL, brand 1
FITTING, Zerk, grease, not
37 123741
included on models 96G107-96G109, 96G122-96G124,
1
96G174-96G176, 96G186, 96G188 RESERVOIR, 2 liter, grease,
2
40a 24E984
96G017-96G021, 96G023-96G026, 96G030-96G032, 96G035-96G037, 96G098, 96G110, 96G115,
1
96G125, 96G132, 96G178, included in Kit 571042, 571069
40b 16G021
RESERVOIR, 2 liter, oil, 96G107, 96G122, included in Kit 571179
1
RESERVOIR, 4 liter, grease, 96G088, 96G090, 96G092, 96G094, 96G096, 96G099, 96G103, 96G111, 96G113, 96G116, 96G118, 96G126,
40a 24B702
96G128, 96G133, 96G141,
1 96G143, 96G145, 96G151, 96G153, 96G155, 96G157, 96G159, 96G160, 96G161, 96G162, 96G181, 96G183, included in Kit 571183
40b 16G020
RESERVOIR, 4 liter, oil, 96G108, 96G123, 96G175, 96G188
1
68 332305B
Parts
Ref Part Description Qty
RESERVOIR, 8 liter, grease, 96G089, 96G093, 96G097, 96G100, 96G104, 96G112,
40a
96G119, 96G127, 96G142, 96G144, 96G146, 96G152, 96G154, 96G156, 96G158, 96G177
RESERVOIR, 8 liter, oil, 96G109,
40b
96G124, 96G176, 96G186, included in Kit 571182
40a
RESERVOIR, 12 liter, 96G105, 96G120, 96G164, 96G165
RESERVOIR, 16 liter, 96G106,
40a
96G121, 96G166, 96G168, 96G169, 96G185
SEAL, follower plate, 2 liter models
278139
41
16F472
96G018, 96G020, 96G024, 96G026, 96G115, 96G132
SEAL, follower plate, 4 liter models 96G090, 96G094, 96G113, 96G116, 96G128, 96G133
PLATE, follower, 2 liter models 96G018, 96G020, 96G024,
42
96G026, 96G115, 96G132 PLATE, follower, 4 liter models
96G090, 96G094, 96G113, 96G116, 96G128, 96G133
ROD, follower plate, 2 liter models 96G018, 96G020, 96G024,
43
96G026, 96G115, 96G132 ROD, follower, 4 liter models
96G090, 96G094, 96G113, 96G116, 96G128, 96G133
SPRING, compression, 2 liter mod­els 96G018, 96G020, 96G024,
44
96G026, 96G115, 96G132 SPRING, compression, 4 liter mod-
els 96G090, 96G094, 96G113, 96G116, 96G128, 96G133
BAFFLE, low level, 2 liter models 96G017, 96G019, 96G021,
45† 24D838
96G023, 96G025, 96G030 ­96G032, 96G035-96G037, 96G098, 96G110, 96G125, 96G178
Ref Part Description Qty
BAFFLE, low level, 4 liter models 96G088, 96G092, 96G096, 96G099, 96G103, 96G111,
1
24E246
96G118, 96G126, 96G141, 96G143, 96G145, 96G151,
1
96G153, 96G155, 96G157, 96G159, 96G160, 96G161, 96G162, 96G181, 96G183
1
BAFFLE, low level, 8 liter models 96G089, 96G093, 96G097, 96G100, 96G104, 96G112,
1
†24F836
96G119, 96G127, 96G142,
1
96G144, 96G146, 96G152,
1
96G154, 96G156, 96G158, 96G177
BAFFLE, low level, 12 liter models
1
†24F923
96G105, 96G120, 96G164,
1
96G165 BAFFLE, low level, 16 liter models
2
†24F924
96G106, 96G121, 96G166, 96G168, 96G169, 96G185
1
BEARING, sleeve, models
1
96G017-96G021, 96G023-96G026, 96G035-96G037, 96G088-96G090, 96G092-96G094, 96G096-96G100,
1
57 117156
96G103-96G106, 96G110-96G113, 96G115, 96G116, 96G118-96G121, 96G125-96G128,
1
96G132, 96G133,
1
96G141-96G146, 96G151-96G157, 96G160-96G162, 96G164, 96G165, 96G177, 96G178, 96G181, 96G183, 96G185
LABEL, models 96G019, 96G020. 96G025. 96G026, 96G032,
1
58196548
96G037, 96G092-96G094, 96G118-96G128, 96G132,
1
96G133, 96G145, 96G146,
1
96G166, 96G174-96G176, 96G183
1
332305B 69
Parts
Ref Part Description Qty
WASHER, low level, models 96G017-96G021, 96G023-96G026, 96G030-96G032, 96G035-96G037, 96G088-96G090, 96G092-96G094, 96G096-96G100, 96G103-96G106, 96G110-96G113, 96G115,
60 16D984
96G116, 96G118-96G121, 96G125-96G128, 96G132, 96G133, 96G141-96G146, 96G151-96G162, 96G164, 96G165-96G168, 96G177, 96G178, 96G181, 96G183, 96G185
RESERVOIR, mid-section, 8 liter models 96G089, 96G093, 96G097, 96G100, 96G104, 96G109, 96G112, 96G119, 96G124, 96G127, 96G142, 96G144, 96G146, 96G152, 96G154, 96G156, 96G158, 96G176,
61
96G166. 96G177, 96G186 RESERVOIR, mid-section, 12 liter
models 96G105, 96G120, 96G164, 96G165
RESERVOIR, mid-section, 16 liter models 96G106, 96G121, 96G166, 96G168, 96G169, 96G185
ADAPTER, reservoir, models 96G088-96G090, 96G092-96G094, 96G096, 96G097, 96G099-96G100, 96G103-96G106, 96G108, 96G109, 96G111-96G113, 96G116,
62
96G118-96G121, 96G123, 96G124, 96G126-96G128, 96G133, 96G141-96G146, 96G151-96G162, 96G164-96G166, 96G168, 96G169, 96G175-96G177, 96G181, 96G183, 96G185, 96G186
NUT, oil, models 96G107, 96G108,
66 126417
96G109, 96G122, 96G123, 96G124, 96G175, 96G176, 96G186
67 24N806
FLOAT, oil, models
96G108, 96G109, 96G122, 96G123, 96G124, 96G175, 96G176, 96G186,
96G107,
96G188
Ref Part Description Qty
126217
126218
200
126219
2
126220
CABLE,15 ft (4.5 m), SOOW w/7pos, 3 pin, 90 deg
CABLE, 15 ft (4.5 m), SOOW w/7 pos, 5 pin, 90 deg
CABLE, 20 ft (6.1 m), SOOW, w/7 pos, 5 pin, 90 deg
CABLE, 30 ft (9.1m) SOOW, w/7 pos, 5 pin, 90 deg
16U790 CABLE, DIN, bare) 1
124300
201
124333
124301
1
202
124594
124595
CABLE, M12, 15 ft., 4 wire, straight
male to flying leads
CABLE, M12, 15 ft., 4 wire, straight male to female
CONNECTOR, Eurofast, fem, straight, 4Pin
CONNECTOR, Eurofast, 4 Pin
CONNECTOR, Eurofast, 5 Pin
Replacement Danger and Warning labels, tags and cards are available at no cost.
2
Also order Ref 27, Part No. 123025 and Ref 60, Part No. 16D984
3
Also order Ref 31, Part No. 119228 and Ref 34, Part No. 16A073
† Also order Ref. 57, Part No. 117156 when ordering this part.
1
1
1
1
1
1
1
1
1
70 332305B
Parts
a
ti15644
b
a = adjustment screw b = locking nut
Pressure Relief Valves
Important Information regarding Pressure Relief Valve 16C807.
Pressure Relief Valve 16C807 can only be used on the G3 Pump. It is not intended for use with any other
products.
The pressure relief valve uses a pressure adjustment screw (a) to set the pressure release point. It
is not intended as a way to relieve pressure during normal operation, but as a protective
measure in the event there is an unintended pressure increase in the system. Do not use this pres­sure relief valve a means of relieving pressure in day-to-day, normal cycle operation.
The pressure adjustment screw will require periodic adjustments. Whenever the valve is set/adjusted (after the set point is found) it is important to ensure that the valve is not bot­tomed out and there is at least 1/2 turn of adjustment remaining. This is determined by turning the screw (a) 1/2 turn and then back turning it out again.
NOTE: Turning adjustment screw (a) clockwise increases pressure.
Part Description Qty
VALVE, pressure relief, 500-3500 psi (3.44
16C807
563156
563157
563158
563159
563160
563161
563190
MPa, 34.4 bar - 24.1 MPa, 241 bar), Set pressure 3000 psi + bar +
10%) Included in Kit 571028
VALVE, pressure relief, 750 psi (5.17 MPa,
51.71 bar)
VALVE, pressure relief, 1000 psi (6.89 MPa,
68.95 bar)
VALVE, pressure relief, 1500 psi (10.34 MPa,
103.42 bar)
VALVE, pressure relief, 2000 psi (13.78 MPa,
137.89 bar)
VALVE, pressure relief, 2500 psi (17.23 MPa,
172.36 bar)
VALVE, pressure relief, 3000 psi (20.68 MPa,
206.84 bar)
VALVE, pressure relief, 5500 psi (37.92 MPa,
379.21 bar)
10% (20.68 MPa, 206.8
1
1
1
1
1
1
1
1
Fuses
Part Description Qty
571039 FUSE, 12 volt DC
571040 FUSE, 24 volt DC
1
1
Installation and Repair Kits
Manual
Kit No. Description
571026 KIT, output union, 3 pump
571063 KIT, output union, 2 pump
571028
571071
571030 KIT, remote manual run, 12 volt DC
571031 KIT, remote manual run, 24 volt DC
571032
571033
571036 KIT, cover with “G” label NA
571041 KIT, pump element, includes Ref 17, 18, 33 3A0533
571042
571069
571044
571045
571046
571047
571058 KIT, output adapter, NPT
571070 KIT, output, adapter, BSPP
571060 KIT, fill, zerk, leakproof NA
571179
571183
KIT, return to reservoir NPT, includes pres­sure relief valve 16C807
KIT, return to reservoir BSPP, includes pres­sure relief valve 16C807
KIT, remote manual run, 12 volt DC, with cable
KIT, remote manual run, 24 volt DC with cable
KIT, repair, 2 liter reservoir, includes Ref 13, 36, 40
KIT, repair, 2 liter reservoir, for models with follower plate, includes Ref 13, 36, 40
KIT, replacement, paddle, 2 liter, for models without follower plate, includes Ref 13, 16, 35, 57
KIT, replacement, paddle, 2 liter, for models with follower plate, includes Ref 13, 16, 35,40a, 42, 57
KIT, replacement, paddle, 4-16 liter, for models without follower plate, includes Ref 13, 16, 35, 57
KIT, replacement, paddle, 4 liter, for models with follower plate, includes Ref 13, 16, 35, 57
KIT, repair, reservoir oil, 2 liter models, includes Ref 13, 36, 40b
KIT, repair, reservoir, oil 4 liter models, includes Ref 13, 36, 40b
KIT, repair, reservoir, grease, 4 liter models, includes Ref 13, 36, 40b
Number
3A0523
3A0525
3A0528
3A0534
3A0535
3A0522
3A0534571182
332305B 71
Technical Data
Technical Data
A
Maximum Working Pressure 5100 psi (35.1 MPa, 351.6 bar) Power
100-240 VAC 88 - 264 VAC; 0.8 A current, 90 VA Power, 47/63 Hz,
Single phase, inrush/locked rotor, max 40A (1ms) 12 VDC 9 - 16 VDC; 5 A current, 60 W, inrush/locked rotor 12 A 24 VDC 18 - 32 VDC; 2.5 A current, 60 W, inrush/locked rotor 6 A
Outputs - Alarm Relay
Rated Load Resistive: 0.4 A at 125 VAC, 2 A at 30 VDC
Inductive: 0.2 A at 125 VAC, 1 A at 30 VDC Max Operation Voltage Resistive: 250 VAC, 220 VAC
Inductive: 250 VAC, 220 VDC Max Operating Current Resistive: 3 A (AC), 3A (DC)
Inductive: 1.5 A (AC), 1.5 A (DC) Max Switching Capacity Resistive: 50 VA, 60 W
Inductive: 25 VA, 30 W Min Permissible Load
Outputs - Vent Valve
Required Vent Valve Type Normally closed Output Voltage
100/240 VAC 24 VDC 12 VDC Input Voltage
24 VDC Input Voltage Max Operating Current 2 A Max Operating Power 48 W
Inputs - Cycle Pressure, 1, 2, 3, Machine Count
Required Switch Type Normally open (sink, source, or dry contact) Sensor Voltage
100/240 VAC 24 VDC
12 VDC Input Voltage
24 VDC Input Voltage Load Current
100/240 VAC 22mA @ 24 VDC
12 VDC 11mA @ 12 VDC
24 VDC 22mA @ 24 VDC Maximum Residual Voltage
100/240 VAC 4 V
12 VDC 2 V
24 VDC 4 V Maximum Off Current
100/240 VAC 1.5 mA
12 VDC 1 mA
24 VDC 1.5 mA Input Impedance 1.1 K Response Time 60 ms Cycle Rate 8.0 Hz (50% duty cycle)
Resistive: 10 Inductive: 10
µA, 10m VDC µA, 10m VDC
72 332305B
Technical Data
Fluid
Grease Models Grease NLGI 000 - #2
Oil Models At least 40 cSt oil. Pumps Up to 3 Pump Output
0.12 in.
0.18 in.
0.25 in.
3
(2 cm3) / minute per outlet - 2 spacers
3
(3 cm3) / minute per outlet - 1 spacer
3
(4 cm3) / minute per outlet - 0 spacers Pump Outlet 1/4-18 NPSF. Mates with 1/4-18 NPT male fittings Reservoir Size 2, 4, 8, 12, 16 Liters IP Rating IP69K Sensor Inputs 3 (any of pressure or cycle)
1 (machine count) Ambient Temps -40°F - 158°F (-40°C to 70°C) Weight (Dry - includes power cord and plug)
Without follower plate 13.3 lbs (6.03 kg) With follower plate 14.2 lbs (6.44 kg)
Wetted Parts nylon 6/6 (PA), trogamid T5004-060, zinc plated steel,
carbon steel, alloy steel, stainless steel, nitrile rubber
(buna-N), bronze, nickel plated alnico, chemically lubri-
cated acetal, aluminum, PTFE, Grillamid Sound Data <60 dB
Dimensions
Model
2L 13.25 33.65 8.00 20.32 9.00 22.86 4L 14.50 36.83 9.25 23.50 10.00 25.40
8L 18.50 47.00 9.25 23.50 10.00 25.40 12L 23.00 58.42 9.25 23.50 10.00 25.40 16L 27.50 69.85 9.25 23.50 10.00 25.40
Height Width Depth
Inches cm Inches cm Inches cm
332305B 73
Technical Data
0.367inch
9.3 mm
2x Ø 0.366 inch
9.3 mm
3.544 inch
90.0 mm
7.087 inch
180.0 mm
0.722 inch
18.3 mm
2x Ø 0.366 inch
9.3 mm
3.189 inch
81.0 mm
6.378 inch
162.0 mm
3.740 inch
95.0 mm
0.708 inch
18.0 mm
Option 1
Option 2
Mounting Pattern
(For correct mounting configuration, choose either Option 1 or Option 2). See P/N 126916 template.
1.180 inch
30.0 mm
3.268 inch
83.0 mm
FIG. 37
74 332305B
Notes
Notes
332305B 75
Graco Standard Warranty
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to
the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés, à la suite de ou en rapport, directement ou indirectement, avec les procédures concernées.
Graco Information
For the latest information about Graco products, visit www.graco.com.
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor. Phone: 612-623-6928 or Toll Free: 1-800-533-9655, Fax: 612-378-3590
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2013, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco reserves the right to make changes at any time without notice.
For patent information, see www.graco.com/patents.
Original instructions. This manual contains English. MM 332305
International Offices: Belgium, China, Japan, Korea
Graco Headquarters: Minneapolis
www.graco.com
revised April 2014
Loading...