The Communications Gateway Module (CGM) provides
a control link between the Electric Fixed Ratio (EFR)
system and a selected fieldbus. This provides the
means for report monitoring and control by external
automation systems.
NOTE: The following system network configuration files
are available at help.graco.com.
•EDS file: DeviceNet or Ethernet/IP fieldbus
networks
•GSD file: PROFIBUS fieldbus networks
•GSDML: PROFINET fieldbus networks
•ACD file: DeviceNet or Ethernet/IP fieldbus
networks
The following components are included in the CGM
Installation Kit.
Ref.DescriptionQty.
ACGM Kit
AA Gateway Module
AB Mounting Bracket
BScrew, #10-32 x .50
CWasher, #10, Nylon
DCommunication Cable (not shown)
1
1
1
2
2
1
Related Manuals
ManualDescription
312864
3A6165
406987GCA CAN Cables, Reference
Models
PartDescription
25B127DeviceNet CGM Kit
26A700EtherNet/IP CGM Kit
26A701PROFIBUS CGM Kit
26A702PROFINET CGM Kit
23A6338B
Communications Gateway Module,
Instructions - Parts
Electric Fixed Ratio Proportioner, Setup Operation
FIG. 1
CGM Software
The following software is must be installed on the CGM
module to work properly with the EFR CGM map
19A796.
•17P796, version 3.01.004
Installation
WARNING
F
E
G
A
B
C
CANH
J
ELECTRIC SHOCK HAZARD
To avoid electric shock, make sure the
system power is OFF before connecting or
disconnecting CAN cables.
PRESSURIZED FLUID HAZARD
This equipment stays pressurized until
pressure is manually relieved. To help
prevent serious injury from pressurized
fluid, such as skin injection, splashing fluid
and moving parts, follow Pressure Relief
Procedure when you stop spraying and
before cleaning, checking or servicing the
equipment.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment
when in the work area to help prevent
serious injury, including eye injury, hearing
loss, inhalation of toxic fumes, and burns.
Installation
3. Mount the CGM Kit (A) inside the system frame with
two screws (B) and washers (C).
FIG. 3
4. Secure cables (CAN, J) to the frame using the cable
ties (H) provided, and route them through the
protected opening as shown in F
IG. 4.
1. Ensure the system power is OFF and pressure has
been relieved. Follow the Pressure Relief Procedure
in the Electric Fixed Ratio Proportioner, Setup Operation manual.
2. Remove the pump yoke shroud (F) and frame cover
(G) from the EFR system.
FIG. 4
FIG. 2
3A6338B3
Installation
CAN
Connector 1
ti11972a
CAN
Connector 2
ti11985a
5. Connect the CAN cable from either CAN connection
on the CGM to port 2 on the EFR.
NOTICE
Ensure the CAN cable is connected to the appropriate
CAN connection. Failure to connect the CAN cable to
the correct CAN connection can result in damage to
the CGM module.
FIG. 5: Cable Connections
6. If used, connect the Ethernet, DeviceNet, or
PROFIBUS cable (J) to the CGM as applicable.
Connect the other end of the cable to the FieldBus
device.
7. Reinstall the pump yoke shroud (F) and the frame
cover (G) onto the EFR system.
8. Perform the Install or Update Data Map procedure
in the Communications Gateway Module,
Instructions – Parts manual.
9. See Available Internal Data on page 8 for details
regarding the FieldBus pinout setup.
10. Perform the Setup procedure on page 5 to
configure the fieldbus.
NOTE: To produce an accurate dispense, the dispense
valve must be controlled directly by the EFR. See the
Electric Fixed Ratio Proportioner, Setup - Operation
manual for I/O integration of the dispense valve with the
EFR.
NOTE: See Automation Outputs (signals from PLC
to EFR System) on page 22 for information on
triggering a dispense through the EFR using the CGM.
FIG. 6: Cable Connections
43A6338B
Setup
Setup
EFR and PLC Connection
Verify the PLC connection parameters are setup
correctly.
NOTE: The connection between the EFR and PLC will
not be made if the PLC connection parameters are not
set up correctly.
Standard Gateway Map: 19A796
Comm. FormatData-SINT
Input Assembly Instance100
Input Byte Size42
Output Assembly Instance150
Output Byte Size22
Gateway Screens
The Gateway screens are used to configure the
fieldbus. These screens are shown only if a CGM is
correctly installed in your system. See Installation on
page 3.
PROFIBUS Fieldbus Screens
These screens are shown only if a PROFIBUS Fieldbus
CGM is installed.
Screen 1
This screen enables the user to set the device address,
install date, location tag, function tag, and description.
FIG. 8: PROFIBUS Fieldbus Screen 1
Screen 2
1. With the system on and enabled, press to
access the Setup screens.
2. Press the left arrow key once to navigate to the
main Gateway screen. See F
FIG. 7: Example Fieldbus Screen
IG. 7.
This screen displays the hardware revision, system
serial number, and data map identification information.
FIG. 9: PROFIBUS Fieldbus Screen 2
3A6338B5
Setup
PROFINET Fieldbus Screens
These screens are shown only if a PROFINET Fieldbus
CGM is installed.
Screen 1
This screen enables the user to set the IP Address,
DHCP settings, subnet mask, gateway, and DNS
information.
Screen 3
This screen displays the hardware revision, system
serial number, and data map identification information.
FIG. 12: PROFINET Fieldbus Screen 3
FIG. 10: PROFINET Fieldbus Screen 1
Screen 2
This screen enables the user to set the station name,
install date, location tag, function tag, and description.
FIG. 11: PROFINET Fieldbus Screen 2
63A6338B
Setup
EtherNet/IP Fieldbus Screens
These screens are shown only if an EtherNet/IP
Fieldbus CGM is installed.
Screen 1
This screen enables the user to set the IP address,
DHCP settings, subnet mask, gateway, and DNS
information.
FIG. 13: EitherNet/IP Fieldbus Screen 1
DeviceNet Fieldbus Screen
This screen is shown only if a DeviceNet Fieldbus CGM
is installed.
This screen enables the user to set the device address
and baud rate, as well as view the hardware revision,
system serial number, and data map identification
information.
FIG. 15: DeviceNet Fieldbus Screen
Screen 2
This screen displays the hardware revision, system
serial number, and data map identification information.
FIG. 14: EtherNet/IP Fieldbus Screen 2
3A6338B7
Available Internal Data
Available Internal Data
See Appendix A - I/O Signal Descriptions on page 19
for additional details regarding each input/output.
Unless stated otherwise:
•In each instance, bytes are stored in little endian
order (most significant to least significant).
•PROFIBUS and PROFINET data must be mirrored
by the PLC to get the correct data out on the PLC
side. When the data is mirrored, the least significant
byte is inserted into the most significant spot, and
the most significant byte is inserted into the least
significant spot.
-Example: If the data is a binary number with
0011100110110111, mirroring it to get the
correct data out of the PROFIBUS or
PROFINET will result in 0111101110010011.
•Values are subject to the same maximum and
minimum restrictions as the ADM.
NOTE: Automation Outputs can be monitored by the
corresponding Automation Inputs to verify the EFR
received the data correctly.
83A6338B
Automation Inputs (signals from EFR system to PLC)
Available Internal Data
Instance IDDescriptionData TypeBIT
1Heartbeat To PLCBoolean0
2System OnBoolean1
3System ReadyBoolean2
4Active AlarmsBoolean3
5Active DeviationsBoolean4
6Active AdvisoriesBoolean5
7Current Sequence is PlayingBoolean6
8Current Sequence is PausedBoolean7
9Current Sequence is StoppedBoolean8
10Dispense Valve OpenBoolean9
11System is PrimingBoolean10
12System is PurgingBoolean11
13System is ParkingBoolean12
14System is DepressurizingBoolean13
15Gel Shot is RunningBoolean14
16EFR is DispensingBoolean15
17{Reserved Bits}Boolean16-232
18{Reserved Bits}Boolean24-313
19Current Active Sequenceuint80-74
20Current Step of the Active Sequenceuint80-75
21Time Remaining to Complete Step (XX.X s)uint16
22Red Pump Outlet Pressure (XXXX.X bar)uint16
23Blue Pump Outlet Pressure (XXXX.X bar)uint16
24Red Pump Inlet Pressure (XXXX.X bar)uint16
25Blue Pump Inlet Pressure (XXXX.X bar)uint16
26Pump Flow Rate (XXXX cc/min)uint16
27Active Error Number Requiring Acknowledgmentuint80-718
28
29Data Exchanged Element Selecteduint80-721
30Data Exchanged Element Valueuint16
31Selected Step of the Active Sequenceuint80-724
32Selected Step Amount (XXXX.XX)uint32
Active Operator Mode Dispense Flow Rate
(XXXX cc/min)
Automation Outputs (signals from PLC to EFR system)
Available Internal Data
Instance IDDescriptionData TypeBIT
1System Enable RequestBoolean0
2System Shutdown RequestBoolean1
3Start Current Sequence/Step, Trigger Operator ModeBoolean2
4Pause Current SequenceBoolean3
5Stop Current SequenceBoolean4
6Priming RequestBoolean5
7Purge RequestBoolean6
8Parking RequestBoolean7
9Depressurizing RequestBoolean8
10{Reserved Bits}Boolean9-15
11{Reserved Bits}uint80-72
12Desired Active Sequenceuint80-73
13Acknowledging of the Active Error Numberuint80-74