Graco 3A1827B User Manual

Instructions
Set / Reset Point
3A1827B
Pressure Switch
Set and reset point pressure switch used to detect pressure changes.
Not approved for use in European explosive atmospheres.
Models: 24K414
Maximum Working Pressure: 5800 psi (400 bar, 40 MPa)
Important Safety Instructions
Read all warnings and instructions in this manual and the instructions included with your operating system or pump. Save these instructions.
ENG

Warnings

The following warnings are for the setup, use, grounding, main­tenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard sym­bols refer to procedure-specific risks. When these symbols appear in the body of this manual, refer back to these Warn­ings. Product-specific hazard symbols and warnings not cov­ered in this section may appear throughout the body of this manual where applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before
disconnecting any cables and before servicing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified
electrician and comply with all local codes and regulations.
SKIN INJECTION HAZARD
High-pressure fluid from dispense device, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in ampu­tation. Get immediate surgical treatment.
Do not point dispense device at anyone or at any
part of the body.
Do not put your hand over the fluid outlet.
Do not stop or deflect leaks with your hand, body,
glove, or rag.
Follow Pressure Relief Procedure in this manual,
when you stop dispensing and before cleaning, checking, or servicing equipment.
Tighten all fluid connections before operating the
equipment.
Check hoses and couplings daily. Replace worn or
damaged parts immediately.
CUS

Pressure Relief Procedure

Relieve pressure in the system following the procedure
recommended for your operating system or pump.

Installation

NOTICE
Electrical ratings must not be exceeded. Over­load on a switch can cause switch to fail on the first cycle.
Never exceed pressure limits. Unit can be oper­ated up to maximum pressure on a limited basis (i.e., set-up, testing) but continuous operation must be restricted to the designated adjustable range. Excessive cycling at maximum pressure limits could reduce sensor life.
FIG. 1
2. Adjust set point to the desired pressure setting. 2500 psi (172 bar, 17.2 MPa) is the factory default setting.
3. Adjust the reset point to the desired pressure set­ting. 500 psi (35 bar, 3.5 MPa) is the factory default setting.
4. Rotate the top portion of the switch to align the lock symbol with the two white arrows (F
IG. 2).
1. Disconnect power to pump.
2. Disconnect cable from switch.
3. If replacing a pressure switch on an existing installa­tion, relieve pressure.
4. Locate unit where shock, vibration and ambient tem­perature fluctuations are minimal. Do not mount in ambient temperature areas exceeding 160°F (71°C).
Unit may be mounted in any position. However,
if installation location results in frequent expo­sure to liquid it is recommended that the unit be mounted vertically with the pressure connection down.
5. Screw switch into manifold. Always use a wrench on pressure connection wrench flats.
6. Test unit before use.

Adjustments

1. Rotate the top portion of switch (with the lock and unlock symbols) to align the unlock symbol with the two white arrows (F
IG. 1).
F
IG. 2
5. Recheck set point and reset point and install switch according to installation instructions.
Status LED’s
Steady Green LED
Yellow LED turns off and on
Power is supplied to pressure switch.
When you reach pressure, yellow LED lights. When pressure drops below reset value, yellow LED turns off.
2 3A1827B
Loading...
+ 2 hidden pages