Set and reset point pressure switch used to
detect pressure changes.
Not approved for use in European explosive
atmospheres.
Models: 24K414
Equivalent: IFM Electronic GMBH PK6220
Maximum Working Pressure: 5800 psi (400 bar, 40
MPa)
Important Safety Instructions
Read all warnings and instructions in this manual
and the instructions included with your operating
system or pump. Save these instructions.
ENG
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point
symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When these symbols
appear in the body of this manual, refer back to these Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout the body of this
manual where applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding,
setup, or usage of the system can cause electric shock.
•Turn off and disconnect power at main switch before
disconnecting any cables and before servicing
equipment.
•Connect only to grounded power source.
•All electrical wiring must be done by a qualified
electrician and comply with all local codes and
regulations.
SKIN INJECTION HAZARD
High-pressure fluid from dispense device, hose leaks, or
ruptured components will pierce skin. This may look like
just a cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment.
•Do not point dispense device at anyone or at any
part of the body.
•Do not put your hand over the fluid outlet.
•Do not stop or deflect leaks with your hand, body,
glove, or rag.
•Follow Pressure Relief Procedure in this manual,
when you stop dispensing and before cleaning,
checking, or servicing equipment.
•Tighten all fluid connections before operating the
equipment.
•Check hoses and couplings daily. Replace worn or
damaged parts immediately.
CUS
Pressure Relief Procedure
Relieve pressure in the system following the procedure
recommended for your operating system or pump.
Installation
NOTICE
•Electrical ratings must not be exceeded. Overload on a switch can cause switch to fail on the
first cycle.
•Never exceed pressure limits. Unit can be operated up to maximum pressure on a limited basis
(i.e., set-up, testing) but continuous operation
must be restricted to the designated adjustable
range. Excessive cycling at maximum pressure
limits could reduce sensor life.
FIG. 1
2. Adjust set point to the desired pressure setting.
2500 psi (172 bar, 17.2 MPa) is the factory default
setting.
3. Adjust the reset point to the desired pressure setting. 500 psi (35 bar, 3.5 MPa) is the factory default
setting.
4. Rotate the top portion of the switch to align the lock
symbol with the two white arrows (F
IG. 2).
1. Disconnect power to pump.
2. Disconnect cable from switch.
3. If replacing a pressure switch on an existing installation, relieve pressure.
4. Locate unit where shock, vibration and ambient temperature fluctuations are minimal. Do not mount in
ambient temperature areas exceeding 160°F
(71°C).
•Unit may be mounted in any position. However,
if installation location results in frequent exposure to liquid it is recommended that the unit be
mounted vertically with the pressure connection
down.
5. Screw switch into manifold. Always use a wrench on
pressure connection wrench flats.
6. Test unit before use.
Adjustments
1. Rotate the top portion of switch (with the lock and
unlock symbols) to align the unlock symbol with the
two white arrows (F
IG. 1).
F
IG. 2
5. Recheck set point and reset point and install switch
according to installation instructions.
Status LED’s
Steady Green
LED
Yellow LED turns
off and on
Power is supplied to pressure switch.
When you reach pressure, yellow LED
lights. When pressure drops below reset
value, yellow LED turns off.
23A1827B
Troubleshooting
ProblemCauseSolution
Troubleshooting
In an injector installation only, pressure switch activates before all injectors fire
Another pressure switch or pressure
gauge on the system reads different
than the pressure switch
After all injectors have reset, the
pressure switch does not deactivate
The pressure switch seems to be
operating backwards
Pressure switch is installed at the
wrong location
Pressure switch is not set to a high
enough reset point
Pressure switch is installed at the
wrong location
Pressure switch is not set to a high
enough reset point
The Reset point is set too low
Normally Open and Normally Closed
outputs not completing connection
Verify pressure switch is correctly
installed - downstream from a bank of
injectors
Verify pressure switch is set sufficiently high at a level above the firing
point of the injectors and within the
margin for error.
Verify pressure switch is correctly
installed - downstream from a bank of
injectors
Verify pressure switch is set sufficiently high at a level above the firing
point of the injectors and within the
margin for error.
Turn the reset point to a higher setting. Then verify the system is functioning correctly.
Check the Normally Open and Normally Closed outputs and make sure
the proper connection is made.
Adjust connection as needed.
1. Attempt to lower the pressure
switch set point to verify the
switch is not sensing any pressure.
Power is supplied to the pressure
switch but the switch is no longer
sensing pressure
3A1827B3
Grease soap has accumulated in the
sensing orifice.
2. After verifing the pressure switch
is not sensing pressure, remove
the switch from the port.
3. Using a non-metalic tool, clean
out the sensing orifice.
4. Reinstall the switch in the port.
5. Retest.
Technical Data
)
Electrical DesignDC PNP
OutputNormally open /
closed complimentary
Operating Voltage9.6 - 32 VDC
Ambient Temperature Range-13° to 176°F (-25° to 80°C)
Storage Temperature -40° to 212°F (-40° to 100°C)
Current Rating500 mA
Voltage Drop<2.0 V
Current Consumption<25 mA
Set Point Range290 - 5800 psi (20 - 400 bar;
2.07 - 40 MPa)
Reset Point Range175 - 5685 psi (12 - 392 bar;
1.2 - 39 MPa)
Switch point accuracy< +
Repeatability< + 0.5% Full range
Termination Type1/4 NPT
ConnectionM12
Display
Power IndicatorLED green
Switching Status IndicatorLED yellow
Wetted Partsstainless steel 316L/1.4404
Weight3.2 oz (0.092 kg)
Enclosure (Ingression Protection) IP67
2.5% Full range
Dimensions
1.18 in. (3 mm
1.06 in. (27 mm)
2.77 in.
(70.4 mm)
1.18 in. (3 mm)
Wiring Diagram
Graco Information
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor.
Phone: 612-623-6928 or Toll Free: 1-800-533-9655, Fax: 612-378-3590
All written and visual data contained in this document reflects the latest product information available at the time of publication.
Graco reserves the right to make changes at any time without notice.
Original Insructions. This manual contains English. MM 3A1827
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
GRACO INC. P.O. BOX 1441 MINNEAPOLIS, MN 55440-1441
Copyright 2011, Graco Inc. is registered to ISO 9001
www.graco.com
6/2011
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.