Graco 3A1704G User Manual

Instructions - Parts
Communications Gateway Module
3A1704G
Installation Kit
For use with HFR™, VRM™, and VPM™ systems to provide fieldbus communications abilities. For professional use only.
Kit 24J415
EN
Important Safety Instructions
Read all warnings and instructions in your system manual. Save all instructions.
ti11985a
CGM with DeviceNet connector shown

Kits

Contents
Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Available Internal Data . . . . . . . . . . . . . . . . . . . . . . 9
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . 26
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . 26
Kits
The following kit is the Communications Gateway Module (CGM) hardware/software and is required for all installations. The kit is used in conjunc­tion with the correct fieldbus device.
CGM Part No. Description
24J415 CGM Installation Kit (Required)

Related Manuals

Manual Description
3A1974 CAN Adapter Kit, Instructions 312864 Communications Gateway Module,
Instructions - Parts 313997 HFR Operation 313998 HFR Repair - Parts 313873 VRM Operation 313874 VRM Repair - Parts 313875 VPM Operation 312764 VPM Repair - Parts 406987 GCA CAN Cables, Reference

Overview

The Communications Gateway Module (CGM) provides a control link between the HFR, VRM, or VPM system and a selected fieldbus. This provides the means for remote monitoring and control by external automation systems.
The following kits work with kit 24J415 and includes all remaining parts necessary to install a CGM. See man­ual 312864 for repair parts for each assembly.
CGM Part No. Fieldbus
CGMDN0 DeviceNet CGMEP0 EtherNet/IP CGMPB0 PROFIBUS CGMPN0 PROFINET
The data available by the CGM to the fieldbus depends on which GCA based system is connected. Unique data maps are defined for each GCA system and are avail­able on the token provided in the kit.
See Available Internal Data on page 9 for a list of inter­nal data from the HFR, VRM, or VPM system that can be viewed or modified by your fieldbus master.
NOTE: The following system network configuration files are available at www.graco.com
EDS file: DeviceNet or Ethernet/IP fieldbus net­works
GSD file: PROFIBUS fieldbus networks
GSDML: PROFINET fieldbus networks
2 3A1704G

Installation

Installation
1. Install the CGM in the desired location.
a. Remove access cover (D). Loosen two screws
(C) and remove CGM (A) from base (B).
C
2. Install access cover (D).
3. Connect CAN cable from either CAN connection on the CGM to any CAN connection found on any other GCA device located on the machine. Attach the fer­rite suppressor to CGM end of the CAN cable. For additional extension cables, see GCA CAN Cables Reference manual.
NOTICE
To avoid severe damage to GCA modules, ensure the CAN cable is connected to the appropriate CAN connection.
A
NOTICE
To avoid severe machine damage, do not connect any CAN device to connectors 2A, 2B, or 2C on the Motor Control Module. Connectors 2A, 2B, and 2C are not CAN connectors.
NOTE: CAN ports are located on the base of cube shaped GCA modules or port 6 on the High Power Tem-
D
perature Control Module.
B
FIG. 1
b. Mount base (B) in desired location with four
screws supplied in this kit. See the following mounting dimensions.
#10-32 UNF
(M5 x 0.8)
2.75 in.
(69.9 mm)
3.25 in.
(82.6 mm)
c. Mount CGM (A) on base (B) with two
screws (C).
NOTE: If there are no free CAN ports, plug splitter (121807) into the CAN distribution block located in the Power Distribution Box (PDB). Connect the CAN cable into the splitter. For more detail, refer to the CAN Adapter Kit manual.
CAN Connector 2
CAN
Connector 1
F
IG. 2: Cable Connections
ti11972a
3A1704G 3
Installation
4. If used, connect the ethernet, DeviceNet, or PROFI­BUS cable to the CGM as applicable. Connect the other end of the cable to the FieldBus device.
ti11985a
F
IG. 3: Cable Connections
5. Connect cable (LC0032) to the MCM, port 2B, and a customer provided signal device. The signal device must have isolated, dry contacts.
6. Perform the Install or Update Data Map procedure in CGM manual 312864.
7. See Available Internal Data on page 9 for details on FieldBus pinout setup.
8. Perform Setup on page 5 to configure the fieldbus.
4 3A1704G

Setup

Setup
Gateway Screens
Fieldbus Screens Page
PROFIBUS 5 PROFINET 6 DeviceNet 7 EtherNet/IP 7
The Gateway screens are used to configure the fieldbus. These screens are shown only if a CGM is correctly installed in your system. See Installation on page 3.
1. With the system on and enabled, press to access the Setup screens.
2. Press the left arrow key once to navigate to the main Gateway screen. See F
IG. 4.
PROFIBUS Fieldbus Screens
These screens are shown only if you have a PROFIBUS Fieldbus CGM installed. See Kits on page 2.
Screen 1
This screen enables the user to set the device address, install date, location tag, function tag, and description.
FIG. 5: PROFIBUS Fieldbus Screen 1
F
IG. 4: Example Fieldbus Screen
Screen 2
This screen displays the hardware revision, system serial number, and data map identification information.
IG. 6: PROFIBUS Fieldbus Screen 2
F
3A1704G 5
Setup
PROFINET Fieldbus Screens
These screens are shown only if you have a PROFINET Fieldbus CGM installed. See Kits on page 2.
Screen 1
This screen enables the user to set the IP address, DHCP settings, subnet mask, gateway, and DNS infor­mation.
F
IG. 7: PROFINET Fieldbus Screen 1
Screen 3
This screen displays the hardware revision, system serial number, and data map identification information.
FIG. 9: PROFINET Fieldbus Screen 3
Screen 2
This screen enables the user to set the station name, install date, location tag, function tag, and description.
IG. 8: PROFINET Fieldbus Screen 2
F
6 3A1704G
Setup
EtherNet/IP Fieldbus Screens
These screens are shown only if you have a EtherNet/IP Fieldbus CGM installed. See Kits on page 2.
Screen 1
This screen enables the user to set the IP address, DHCP settings, subnet mask, gateway, and DNS infor­mation.
DeviceNet Fieldbus Screen
This screen is shown only if you have a DeviceNet Field­bus CGM installed. See Kits on page 2.
This screen enables the user to set the device address and baud rate, and to view the hardware revision, sys­tem serial number, data map identification information.
FIG. 12: DeviceNet Fieldbus Screen
F
IG. 10: EtherNet/IP Fieldbus Screen 1
Screen 2
This screen displays the hardware revision, system serial number, and data map identification information.
IG. 11: EtherNet/IP Fieldbus Screen 2
F
3A1704G 7

Maintenance

Maintenance
Install Upgrade Tokens
NOTE: The Motor Control Module, Fluid Control Mod-
ule, and Temperature Control Module connection to the system is temporarily disabled during the installation of upgrade tokens.
To install software upgrades:
1. Use correct software token stated in the table. See Graco Control Architecture
manual for instructions.
NOTE: Upgrade all modules in the system to the software version on the token, even if you are replacing only one or two modules. Different soft­ware versions may not be compatible.
All data in the module (System Settings, USB Logs, Recipes, Maintenance Counters) may be reset to factory default settings. Download all settings and user preferences to a USB before the upgrade, for ease of restoring them following the upgrade.
See manuals for locations of specific GCA compo­nents.
The software version history for each system can be viewed in the technical support section at www.graco.com.
Token Application
16H821 HFR:
- Communication Gateway Module
16G365 VPM:
- Communication Gateway Module
VRM:
- Communication Gateway Module
Module Programming
r_257396_3b9905_04b
ti12358a1
FIG. 13: Remove Access Cover
ti12334a1
ti12354a1
8 3A1704G

Available Internal Data

The following internal data with this system can be viewed and modified by your fieldbus master.
NOTE: Refer to appropriate system manual for machine operation instructions.
CGM Input
System Status
In
Units
(Bit Number | Name)
0 | Heartbeat 1-2 Needs to fol-
1 | Status of Dispense 1= Dispense
2 | Dispense Valve (1 = Open)
Byte
from PLC
Output
low the CGM Output.
0 = Close Dis­p e n s e V a l v e
Out
Byte
CGM Output to PLC Input Descriptions
1-2 Square wave
toggles every 3 sec.
A c t i v e ,
0 = Dispense not active
0 = Dispense V a l v e C l o s e d ,
CGM initiates a square wave that toggles every 3 sec. The PLC must follow the heartbeat. If the heart beat is lost from the PLC or CGM then the system will shutdown. If the PLC does not detect the heartbeat then the PLC should cycle the PLC output bit HI/LO in attempt to estab­lish the heartbeat from the CGM. If no heartbeat is detected then a dis­connected cable or major error may exist in the CGM.
Monitor Only: On Circulation sys­tems, this indicates that a dispense is pending or in progress (or when pre dispense timer is active and dur­ing a dispense).On an L-head sys­tem Dispense Valve is considered open until the end of the clean out cycle. On other types of systems the bit will indicate a dispense is active.
Used in diagnostics only. Not to be used to control a dispensed shot.
Available Internal Data
1 = Open Dis-
pense Valve 3 | Ratio Check Valve (1 = Enabled)
4 | Pump Parked (1 = Parked)
3A1704G 9
0 = Enable Dis-
pense Valve
1 = Enable
Ratio Check
Valve
1= Begin Park 0 = Pump is
1 = Dispense Valve Open 0 = Dispense Valve is enabled
1 = Ratio Check Valve is enabled
not Parked, 1 = Pump is Parked
Valid for VRM/VPM, Infusion/Paste systems only. Initiating a Dispense cycle will dispense material out of the Ratio Check valves when in Ratio Check mode. When bit is OFF the material will dispense normally thru the Dispense valve.
Parking the pump involves moving the Red pump to the position which the pump shaft is least exposed to the atmosphere. System must be in Standby mode. Chemical will dis­pense out of the dispense valve.
Available Internal Data
System Status
5 | DV Lockout / Circu­lation Control (1 = Locked out)
6 | Mix head Cleanout (1 = Closed)
Units
CGM Input
In
Byte
from PLC
Output
1-2 0 = Unlock Dis-
pense Valve, Non-Circula­tion State
1 = Lockout Dispense Valve , Circulation State
0 = Open Clean Out
Out
Byte
CGM Output
to PLC Input Descriptions
1-2 0 = Dispense
Valve is unlocked or in Non-Circula­tion State
1 = Dispense Valve is locked out or in Circulation State 0 = Clean Out is open
Used to lock out the dispense valve or configure to circulation mode (cir­culation type system) when in standby/operator or operator/night modes only. Only for stall to pres­sure systems with an electric dis­pense valve or any stall to pressure dispense valve configuration (circu­lation type system).
Used for L-Head systems cleanout / diagnostics only.
1 = Clean Out is closed
0 = System Startup OFF
1 = System Startup ON
System Startup bit will initiate a con­trolled startup of the system. The temperature conditioning zones will be initiated when the bit is high. Low pressure recirculation is also enabled when the bit is set (Standby
7 | SYSTEM STARTUP BIT (1 = On)
Valid for Circulation systems ONLY
1 = Close Clean Out
0 = Stop Sys­tem Startup
1 = Start Sys­tem Startup
and night modes). Turning off this bit will turn OFF the temperature condi­tioning zones and circulation. For stall to pressure systems with a manual dispense valve, setting this bit will configure the pumps to stall to the pressure set point. For stall to pressure systems, set to operator mode and set the DV Lockout / Cir­culation Control bit to high. Setting this bit will start a recirculation dis­pense for recirculation type sys-
tems. 8 | Not Used Not Used Not Used Not Used 9 | Prime Side
(1 = Blue)
0 = RED
1 = BLUE
0 = RED
1 = BLUE
Selects which pump- Red or Blue-
to dispense from in prime mode.
Used for priming the chemical thru
the pumps and hoses. Valid for
VRM/VPM, Infusion/Paste systems
only. Initiating a Prime shot is via the
ADM or the Footswitch. Chemical
will dispense out of the Ratio check
valves if the system is not setup for
circulation.
10 3A1704G
System Status
Units
10 | Base Purge (1 = On)
11 | Recirc Status (1 = High Pressure Recirc)
12 | Purge Alarm (1 = Purge Active)
CGM Input
In
Byte
from PLC
Output
Out
Byte
0 = Park Pump ON
1 =Base Purge ON
1-2 0 = Low Pres-
1-2 0 = Low Pres­sure circula­tion ON
1 = High Pres­sure circula­tion ON
-- 0 = Purge
Available Internal Data
CGM Output to PLC Input Descriptions
0 = Park Pump ON
Park mode is valid for all machine configurations. Material will dis­pense out of the mixer for all non cir-
1 =Base Purge ON
culating systems. Circulating systems can be parked without dis­pensing material.
Base purge is valid for VRM/VPM systems only. Material will be dis­pensed out of the ratio check ports.
Valid for full circulation systems sure circula­tion ON
only. Indicates status of the pump-
ing system when in circulation. If
system is in low pressure recirc the 1 = High Pres-
sure circula­tion ON
pumps will shift to High pressure
circ and then start the pre-dispense
time. When the pre-dispense time
expires, user can request dis-
penses. After expiration of post-dis-
pense time, the system will return to
low pressure modes. Pre and post
dispense times are settable on the
ADM system-2 sub screens.
Monitoring Only. Indicates status of shot not
the purging routine. Active
13 | PLC Disables dis­pensing
14 | CGM Control Enabled
15 | USED INTER­NALY
0 = Enable Dis­pensing
1 = Disable dis­pensing
0 = ADM has control of the system
1 = CGM has control on the system
-- --
1 = Purge Shot Active 0 = Dispens­ing Enabled
1 = Dispens­ing Disabled
0 = CGM can only monitor
1 = CGM can control the system
PLC enables / disable dispensing
from the GCA controller / footswitch
or remote start via the MCM.
Select via the PLC the control of the
system from either the CGM or the
ADM. CGM can monitor status in
either mode.
3A1704G 11
Available Internal Data
Operating
System Mode Select 3 DISABLED
Mode
Selected Shot
Select Shot number, or Sequence Position Number
Selected
Select sequence 5 In Sequence
Sequence
Condition­ing / Heat zones
Units
CGM Input
In
Byte
from PLC
Output
Mode = 1 STANDBY
Mode = 2 SHOT Mode= 3 SEQUENCE Mode = 4 OPERATOR Mode = 5 PRIME Mode = 6 NIGHT Mode= 7
4 In Shot Mode,
Selects the Active Shot number. In Sequence Mode, selects the Active Sequence position num­ber.
mode, selects that active sequence. Is ignored in other modes
6 Bit 0 = 1, Red
Tank heat enable
Out
Byte
CGM Output to PLC Input Descriptions
3 DISABLED
Mode = 1 STANDBY
Mode = 2 SHOT Mode= 3 SEQUENCE Mode = 4 OPERATOR Mode = 5 PRIME Mode = 6 NIGHT Mode= 7
4 Shot or
Sequence number feed­back
5 Sequence
selected feed­back
6 Bit 0 = 1, Red
Tank heat ON
PLC selects the various modes of the dispensing system.
CGM feedbacks the status of the system to the PLC.
Prime mode is only available for variable ratio systems.
Night mode is only available on standard HFRs with full circulation systems.
If using a manually controlled dis­pense valve, shot and sequence modes are not available. Select, via the PLC, the active shot number when in Shot mode or the Current Sequence position number when in Sequence mode
Select via the PLC the active sequence when in Sequence mode
PLC enables / disable the various Conditioning Zones.
Setting the bit = 1 enables the Heat Zone.
Setting the bit = 0 disables the Heat Zone.
Feedback: 0 = zone OFF, 1 = Zone ON
Bit 1 = 1, Blue Tank heat
Bit 1 = 1, Blue
Tank heat ON enable Bit 2 = 1, Red Inline heat
Bit 2 = 1, Red
Inline heat ON enable
Bit 3 = 1, Blue Inline heat
Bit 3 = 1, Blue
Inline heat ON enable
12 3A1704G
Tank Blue Fill
Tank Red Fill
Errors Needing Acknowl­edgement
CGM Input
Units
In
Byte
from PLC
Output
Bit 4 = 1, Red Hose heat enable
Bit 5 = 1, Blue Hose heat enable Bit 6 = 1, Red Chiller heat enable
Bit 7 = 1, Blue Chiller heat enable
1 = Filling, 0 = Off 7 Tank Fill Not
Active = 0
Begin Tank Fill­ing = 1
1 = Filling, 0 = Off 8 Tank Fill Not
Active = 0
Begin Tank Fill­ing = 1
9-12 The PLC ASCII
Output must match the PLC Input ASCII value.
Out
Byte
CGM Output to PLC Input Descriptions
Bit 4 = 1, Red Hose heat ON
Bit 5 = 1, Blue Hose heat ON
Bit 6 = 1, Red Chiller ON
Bit 7 = 1, Blue Chiller ON
7 Tank not Fill-
ing = 0
Tank Filling = 1
8 Tank not Fill-
ing = 0
Tank Filling = 1
9-12 CGM ASCII
value of the error cur­rently requir­ing Acknowledge­ment.
Available Internal Data
Initiates a fill valve open. This bit can be used to initiate a manual fill cycle or a auto fill cycle if the auto fill mode is selected. The tank fill valve will close upon reaching the high level switch. See Byte 79 for tank level status. If the Tank fill bit is maintained the GCA will close the valve when the tank is full. Auto time out and alarm if the Hi level is not reached within a preset time. Initiates a fill valve open. This bit can be used to initiate a manual fill cycle or a auto fill cycle if the auto fill mode is selected. The tank fill valve will close upon reaching the high level switch. See Byte 79 for tank level status. If the Tank fill bit is maintained the GCA will close the valve when the tank is full. Auto time out and alarm if the Hi level is not reached within a preset time. Errors requiring acknowledgement are presented on first in first out basis. The latest error is currently in the error register in the CGM. The PLC must send back the exact ASCII value for the error to be acknowledged in the CGM. If an incorrect ASCII error code is sent back to the CGM then the error will not clear and the CGM register will be overwritten with the incorrect error. If multiple error codes exists then the PLC must acknowledge them in the order the errors are sent to the PLC from the CGM. See bytes 80-83 and 84 for errors and status.
3A1704G 13
Available Internal Data
Units and
Units and Operating Operating Info
Bit | Function
0-1 | Volume Units -- 0 0 | Gallons;
2 -3 | Weight Units -- 0 0 | grams; 0
Units
Info
CGM Input
In
Byte
from PLC
Output
Out
Byte
CGM Output to PLC Input Descriptions
-- -- 13-14 Bit xx | Meaning
0 1 | cc's; 1 0 | Liter
1 | kilo­gram s; 1 0 | pounds
Monitoring Only. The operating units of the machine can be read into the PLC and used as required.
Flow rate setpoint
Dispense amount setpoint
4-5 | Pressure Units -- -- 13-14 0 0 | bar; 0 1 |
psi; 1 0 | MPa
6 | Temperature -- 0 = Fahren-
heit; 1 = Cel­sius
7 | Flow Unit -- 0 = Volume; 1
= Weight
8 | Rate Unit -- 0 = Minute; 1
= Second
9 | Control Mode -- 0 = Pressure;
1 = Flow 10 11 | Dispense Mode
-- 0 0 | Time; 0 1 | Volume; 1 0 | Weight
12 | Reserved for
-- --
future use 13 | Reserved for
-- --
future use 14 | Reserved for
-- --
Future use 15 | Reserved for
-- --
future use Depending on system
setup the units can be by weight or volume
-- -- 15-18 Integer value of the Flow rate setpoint in the dis­pensing sys­tem.
Depending on system setup the units can be by weight, volume, or time
-- -- 19-22 Integer value of the Dis­pense amount setpoint in the dispensing system.
Monitoring Only. The operating units of the machine can be read into the PLC and used as required.
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.0001 for the requested flow rate to be in system units
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.001 for the requested amount to be in system units
14 3A1704G
Ratio of the Blue / Red mate­rial - set­point
Pump Red Pressure ­Actual
Pump Blue Pres­sure ­Actual
Pump Flow ­Actual
Ratio of the Blue / Red mate­rials
-Actual
Dispense Amount ­Actual
Dispense Duration
-Actual Blue Inline
Temp ­Actual
Blue Hose Temp ­Actual Red Inline Temp ­Actual
CGM Input
Units
Depending on system setup the units can be by weight or volume
In
Byte
-- -- 23-24 Integer value
from PLC
Output
Out
Byte
CGM Output to PLC Input Descriptions
of the Blue / Red Material Ratio setpoint in the dis­pensing sys­tem.
PSI, bar, or MPa -- -- 25-28 Integer value
of the actual Red pump pressure in the dispens­ing system.
PSI, bar, or MPa -- -- 29-32 Integer value
of the actual Blue pump pressure in the dispens­ing system.
Depending on system setup the units can be by weight or volume
-- -- 33-36 Integer value of the actual Flow rate in the dispens­ing system.
Depending on system setup the units can be by weight or volume
-- -- 37-38 Integer value of the actual Material Ratio in the dis­pensing sys­tem.
Depending on system setup the units can be by weight or volume
-- -- 39-42 Integer value of the actual Dispense amount in the dispensing system.
mS -- -- 43-46 Actual Dura-
tion of the dis­pense in mS
Depending on system setup the units can be
-- -- 47-48 Actual tem­perature
read in C or F
Depending on system setup the units can be
-- -- 49-50 Actual tem­perature
read in C or F Depending on system setup the units can be
-- -- 51-52 Actual tem­perature
read in C or F
Available Internal Data
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.01 for the requested material Ratio to be in system units Blue is the value and Red is always = 1. Blue: Red == xx.xx:1
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.0001 for the actual Red pump pressure to be in system units
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.0001 for the actual Blue pump pressure to be in system units
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.0001 for the actual flow rate to be in system units
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.01 for the Actual material Ratio to be in system units. Blue is the value and Red is always = 1. Blue: Red == xx.xx:1 Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.001 for the actual amount to be in system units
Monitoring Only. Time base is 0.001 seconds == xxx ms.
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.1 for the actual tempera­ture to be in system units.
3A1704G 15
Available Internal Data
Red Hose Temp ­Actual
Blue Tank Material ­Actual Red Tank Material ­Actual
Blue Chiller Temp -
Depending on system setup the units can be read in C or F
Depending on system setup the units can be read in C or F Depending on system setup the units can be read in C or F
Depending on system setup the units can be read in C or F
Actual Red
Chiller Temp -
Depending on system setup the units can be read in C or F
Actual Blue Inline Temp - Set point
Depending on system setup the units can be read in C or F
Units
CGM Input
In
Byte
from PLC
Output
Out
Byte
CGM Output to PLC Input Descriptions
-- -- 53-54 Actual tem­perature
-- -- 55-56 Actual tem­perature
-- -- 57-58 Actual tem­perature
-- -- 59-60 Actual tem­perature
-- -- 61-62 Actual tem­perature
-- -- 63-64 Set point tem­perature
Monitoring Only. The value from the CGM is an integer and must be mul­tiplied by 0.1 for the set point tem­perature to be in system units.
Blue Hose Temp - Set point
Red Inline Temp - Set point
Red Hose Temp - Set point
Blue Tank Material­Set point Red Tank Material ­Set point
Blue Chiller Temp - Set point
Red Chiller Temp - Set point
Depending on system setup the units can be read in C or F
Depending on system setup the units can be read in C or F
Depending on system setup the units can be read in C or F
Depending on system setup the units can be read in C or F Depending on system setup the units can be read in C or F
Depending on system setup the units can be read in C or F
Depending on system setup the units can be read in C or F
See CGM Input bytes 23-26 for changing the temperature setpoints.
-- -- 65-66 Set point tem­perature
-- -- 67-68 Set point tem­perature
-- -- 69-70 Set point tem­perature
-- -- 71-72 Set point tem­perature
-- -- 73-74 Set point tem­perature
-- -- 75-76 Set point tem­perature
-- -- 77-78 Set point tem­perature
16 3A1704G
Tank Material Level Sta­tus Feed­back
Scrolling Error
Units
Tank Level High = 3
Tank Level Mid = 2
Tank Level Low = 1
ASCII values of the current errors
CGM Input
In
Byte
from PLC
Output
Out
Byte
CGM Output to PLC Input Descriptions
-- -- 79 Bits 3-0 = Red Tank Level
Bits 7-4 = Blue Tank Level
-- -- 80-83 This will con­tain the ASCII characters of the Error Code match­ing the Error in the Scroll­ing Error Bar on the ADM.
Available Internal Data
Monitoring Only. The values from the CGM:
Tank Level High = 3
Tank Level Mid = 2
Tank Level Low = 1
Monitoring Only. The ASCII value from the CGM matches the current Error Codes on the ADM. The errors scroll if multiple error exists. The errors may require acknowledge­ment, see Bytes 9-12. See system manual for description of the errors.
3A1704G 17
Available Internal Data
ADM Feedback
Units
CGM Input
In
Byte
from PLC
Output
-- -- 84
Out
Byte
CGM Output to PLC Input Descriptions
Monitoring Only:
Error types that need acknowledged will be indicated first. After all errors have been acknowledged then cur­rent error types will be indicated.
Bits 3-0 = ADM Status bits.
Bits 4-7 are broken down as follows:
Bit 4 = System Power status
Bit 5 = Dis­pense Sys­tem ready to dispense
Bits 7-4 Status
Error needing Acknowledged ­Alarm = (0x03)
Error needing Acknowledged - Devi­ation = (0x02)
Error needing Acknowledged - Advi­sory = (0x01)
Error - Alarm = (0x0C)
Error - Deviation = (0x08)
Error - Advisory = (0x04)
System status bits available.
Bits 3 thru 0 as noted:
S y s t e m Po w e r s t a tu s 0 = O f f, 1 = O n (Bit 0)
Dispense System ready to dispense 0 = Not Ready, 1 = Ready (Bit 1)
Bit 6 = Dis­pense Sys­tem is ready for external
Dispense System is ready for exter­nal requests 0 = Not Ready, 1 = Ready (Bit 2)
requests
Bit 7= Future Use
Dispense Valve Open (=1) Indica­tion
18 3A1704G
Change Dispense Flow Rate or Pres­sure Set point
Change Dispense Amount Set point
Change material Ratio Set point
Change Tempera­ture Con­ditioning Set point
Units
Depending on system setup the units can be by weight, volume, flow, or pressure
Depending on system setup the units can be by weight, volume, or time
Depending on system setup the units can be by weight or volume
Select conditioning zone set point to change
MSW = Conditioning Zone Selected
Available Internal Data
CGM Input
In
Byte
13-16 Integer value of
from PLC
Output
the requested rate in the dis­pensing sys­tem.
Out
Byte
CGM Output to PLC Input Descriptions
-- -- Changes current shot selected to a new rate. The value outputted to the CGM must be an integer. The PLC value is xxx.xxx and must be multi­plied by 1000 prior to being sent to the CGM
17-20 Integer value of
the requested Dispense amount in the dispensing sys­tem.
21-22 Integer value of
the requested Material Ratio in the dispens­ing system. Blue: Red
-- -- Changes current shot selected to a new dispense amount. The value outputted to the CGM must be an integer. The PLC value is xxx.xxx and must be multiplied by 1000 prior to being sent to the CGM
-- -- Changes current shot selected in a variable ratio system to a new ratio. The value outputted to the CGM must be an integer and must be multiplied by 100 for the requested material Ratio. Blue is the value and Red is always = 1. PLC input is: Blue: Red == xx.xx:1
23-24 0 = Red Tank -- -- When changing a heat zone, select
the appropriate zone number which will enable the CGM to write a new temperature set point to the heat zone selected. Only 1 heat zone can be selected at a time.
LSW = Temperature setpoint in 0.1 degree increments (example: 501 = 50.1)
MSW + LSW combined to form a DINT from the PLC output to CGM input.
NOTE: If the system is a standard HFR, the LSW setpoint must be
0.1 °C, regardless if Fahrenheit mode is selected on the ADM.
1 = Blue Tank 2 = Red Inline 3 = Blue Inline 4 = Red Hose 5 = Blue Hose 6 = Red Chiller 7 = Blue Chiller
3A1704G 19
Available Internal Data
Change Tempera­ture Con-
Depending on system setup the units can be read in C or F
ditioning Set point
LSW = Desired set point in 0.1°C for stan­dard HFR units. Desired setpoint in
0.1 °C / 0.1°F for recir­culation units.
Units
CGM Input
In
Byte
from PLC
Output
25-26 The tempera-
ture set points are limited by the tempera­ture high and low alarm val­ues. There must be a dif­ference of at least 10 between the new set point and the alarm values or the new set point will be ignored.
Out
Byte
CGM Output to PLC Input Descriptions
-- -- The value outputted to the CGM must be an integer and must be multiplied by 10 for the requested zone temperature. Temperature input into the PLC == xxx.x F or C and must be changed to xxxx C prior to sending to the CGM (stan­dard HFR only). The temperature set points are limited by the temper­ature high and low alarm values. The alarm setpoints must be greater than 10 degrees (standard HFR) or 2 degrees (recirculation unit) from the requested setpoint. If the alarm is closer than 10 degrees (standard HFR) or 2 degrees (recirculation unit) then the requested setpoint will be ignored. Manually changing the alarm setpoints on the ADM will be required prior to a new setpoint change. See Output Bytes 63 thru 78 for temperature zone feedback from the CGM.
System Power
System Power 27 Toggles Sys-
tem Power on change.
LSW = Desired Set point in 0.1° units
LSW + MSW combined to form a DINT from the PLC output to CGM input.
-- -- System power is ON when the ADM is in any active mode. System power is OFF when the power LED is in the yellow state. To turn the System power ON or OFF, write a different value to the System Power byte. Changing the value will toggle the state from ON to OFF or OFF to ON. See Out Byte 84 for System Power Status
20 3A1704G
Available Internal Data
Controlling Device
CGM Control and Night Mode
When the controlling device sets the HFR into night mode using the CGM, the controlling device will be responsible for turning on and off the pumps accordingly (by setting or clearing the “SYSTEM STARTUP BIT”, or bit 7 bytes 1-2) when the “CGM Control Enabled” bit is set (Bit 14, bytes 1-2). Any active night mode periodic or time of day timer will be over-ridden by the controlling device when the corresponding timer expires within the Advanced Display Module (ADM). If the controlling device clears the “CGM Control Enabled” bit after set­ting the HFR into night mode, the night mode timers will operate properly and condition the dispense material accordingly.
CGM Control and Parking the Pumps
After the HFR is set to Standby mode, the controlling device (and user by pressing the footswitch) will have the option to park the pumps. When the pumps are parked, the red material pump shaft will be immersed into the red material, hence preventing exposure of the shaft and red material on the shaft to the atmosphere.
ADM Screen Information when CGM Control is Started or ended
When the user or controlling device sets or clears the “CGM Control Enabled” bit, information provided on the ADM display may or may not be current. If the user nav­igates away, then back to the main home run screen, the information provided will be current.
If the system is a full circulation based system, the con­troller device will need to have the pumps cycling in low pressure mode (by setting the “SYSTEM STARTUP BIT”, or bit 7 bytes 1-2) prior to setting the “Pump Parked” bit (bit 4, bytes 1-2). For a standard HFR, the user will have to remove the “SYSTEM STARTUP BIT” immediately after the pump reaches the parked position. For a recirculation type system, the pump will remain in the park position, and ignore an active “SYSTEM STARTUP BIT” request. For a recirculation type sys­tem, to exit a parked state, the controlling device will need to clear the “Pump Parked” bit, then set the “SYS­TEM STARTUP BIT” from a cleared state. When this occurs, the pumps will start cycling in the last low pres­sure flow rate executed.
If the system is a stall to pressure type system, the con­trolling device simply needs to set the “Pump Parked” bit from an idle state, then the pumps will move to the parked position. If the system has a manual dispense valve, the user will need to ensure the pump pressures are less than approximately 391 psi (2.7 MPa, 27 bar) prior to setting the “Pump Parked” bit, and ensure either the dispense valve is opened, or the material is diverted out of the pressure relief valves at the material manifold.
3A1704G 21
Available Internal Data
Timing Diagrams
The following diagrams show the signal sequence of the CGM communication.
Heart Beat Timing Diagram
Heart Beat CGM Input
Bytes /Bit
CGM HB - Normal PLC HB - Normal
CGM HB - No HB PLC HB - Cycle Hi / Lo
I/O
I/O
System Power Bit Diagram
System Power Bit CGM Input
Bytes /Bit
Set CGM Control Verify CGM Control System Power ON
Verify System Power ON
2/7
27
Shot Setup - Change Diagram
Shot Setup - Change CGM Input
Bytes /Bit
Select Shot Mode
Verify Shot Mode Select Shot Number
Verify Shot Number Set Flow Rate
Verify Flow Rate Set Shot Size Verify Shot Size
3
4
13-16
17-20
CGM Output
Bytes /Bit
I/O
I/O
CGM Output
Bytes /Bit
2/7
84/0
CGM Output
Bytes /Bit
3
4
13-16
19-22
22 3A1704G
System Startup and Dispensing Recirculation Diagram
Power
Dispense
Dispense
Available Internal Data
OFF
End
Start
Ready
System
ON
Power
3
2/731/7
Bytes /Bit
CGM Output
2/7
Bytes /Bit
CGM Input
N/A
84/1
6/0 thru 7
3
N/A
4
2/6
2/4
1/1
1/2
1/6
4
2/6
N/A
Verify Heat Zones ON
Verify System Startup Bit
Verify CGM Control
Set CGM Control
System Startup and Dispensing
Recirculation System
System Startup Bit - Circ Only
System Heat / Startup time
Verify Shot Mode
Select Shot Mode
System Ready to Dispense
Select Shot Number
PLC Enable Dispense - 0 = Enabled
Verify Shot Number
Verify PLC Enabled Dispense
Circulation Status - 1 = Hi Press
Dispense Start - Direct to MCM
L-Head Cleanout (L-Head Only)
Dispense Valve Open
Dispense Active
3A1704G 23

Parts

Parts
Model 24J415
17
16
6
3
7
15
3
Ref Part Description Qty
3† CGMxx0 MODULE, CGM 1 6 114984 SCREW, tapping, phillips pan head 4 7 16J526 TOKEN, map 1 12121000 CABLE, CAN, female / female 0.5 m 1 13121901 SUPPRESSOR, box snap, ferrite 3 15 16H821 TOKEN, GCA, upgrade, ADM32 1 16 121807 CONNECTOR, splitter 1 17 124005 BUSHING, strain relief 1
Not included in kit. See Kits on page 2 for available
CGM modules. See the Communications Gateway Module manual 312864 for CGM parts list.
Not shown.
24 3A1704G
Parts
3A1704G 25

Graco Standard Warranty

Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to
the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés, à la suite de ou en rapport, directement ou indirectement, avec les procédures concernées.

Graco Information

For the latest information about Graco products, visit www.graco.com.
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor. Toll Free: 1-800-746-1334 Fax: 330-966-3006
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2011, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco reserves the right to make changes at any time without notice.
For patent information, see www.graco.com/patents.
Original instructions. This manual contains English. MM 3A1704
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
www.graco.com
Revised March 2013
Loading...