Graco 334129B User Manual

Page 1
Instructions-Parts
334129B
Therm-O-Flow® 20
For applying hot melt sealant and adhesive materials from 20 Liter (5 Gallon) pails. For professional use only. Not approved for use in European explosive atmosphere locations.
Important Safety Instructions
Maximum Operating Temperature 400°F (204 °C) See page 6 for model information.
EN
See Techni cal Specica tio ns , page 106 , for maximum working pressures.
PROVEN QUALITY. LEADING TECHNOLOGY.
Page 2

Contents

Warnings ............................................................. 3
Models................................................................. 6
Related Manuals .................................................. 7
Component Identication....................................... 8
Advanced Display Module (ADM).................. 12
Overview............................................................15
Air and Fluid Hoses...................................... 15
Heat Control Zone........................................ 15
Setup ................................................................. 16
Unpack........................................................16
Location Requirements.................................16
Install System.............................................. 16
Mechanical Setup ........................................ 17
Install Heated Hose...................................... 18
Connect Multiple Devices ............................. 20
Connect Power............................................ 21
Grounding ................................................... 22
Connect Secondary System..........................22
Check Sensor Resistance ............................ 23
Check Heater Resistance............................. 24
Select ADM Settings .................................... 25
Connect PLC...............................................27
Operation........................................................... 30
Purge System.............................................. 30
Load Material...............................................31
Heat Up System........................................... 32
Prime Pump ................................................ 33
Prime System..............................................35
Setback Mode..............................................35
Pressure Relief Procedure............................ 36
Shutdown .................................................... 37
Schedule..................................................... 37
Change Pail................................................. 38
Troubleshooting..................................................39
Repair................................................................ 47
Replace Wipers ........................................... 47
Replace Platen RTD ....................................48
Separate the Air Motor and Pump ................. 49
Remove Platen............................................ 50
Replace Heater Bands and Pump
RTD...............................................51
Replace MZLP Fuse .................................... 52
Replace MZLP............................................. 52
Replace MZLP Daughter Card......................54
Replace AWB .............................................. 55
Replace Power Supply................................. 55
Replace Fan................................................ 56
Replace Transformer....................................57
Update Software.......................................... 59
Electrical Schematics .......................................... 60
Parts.................................................................. 66
Accessories and Kits...........................................87
Wiper Kits....................................................87
Applicators and Dispense Valves.................. 87
Air-OperatedHeated DispenseValves........... 87
Flow Control and Manifolds .......................... 87
Accessory Extension Cables......................... 87
Light Tower Kit, 24W589 .............................. 87
Tie Rod Kits.................................................87
8 Zone Upgrade Kit Installation..................... 91
12 Zone Upgrade Kit Installation...................93
Appendix A ADM............................................. 94
Operation Screens....................................... 96
Setup Screens............................................. 97
Appendix B USB Data .................................. 102
Download.................................................. 102
Access Files .............................................. 102
Upload ...................................................... 102
USB Logs.................................................. 103
System Settings File .................................. 103
System Language File................................ 104
Create Custom Language Strings ............... 104
Dimensions...................................................... 105
Notes ............................................................. 107
Technical Specications.................................... 108
Graco Standard Warranty.................................. 110
2
334129B
Page 3

Warnings

Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When these symbols appear in the body of this manual or on warning labels, refer back to these Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.
WARNING
BURN HAZARD
Equipment surfaces and uid that is heated can become very hot during operation. To avoid severe burns:
Do not touch hot fluid or equipment.
SPLATTER HAZARD
Hot or toxic fluid can cause serious injury if splashed in the eyes or on skin. During bl ow off of platen, splatter may occur.
Use minimum air pressure when removing platen from drum.
MOVING PARTS HAZARD
Moving parts c an pinch, cut or amputate ngers and other body parts.
Keep clear of moving parts.
Do not operate equipment with protective guards or co ve rs removed.
Pressurized equipment can start without warning. Before checking, moving, or servicing equipment, follow the
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before disconnecting any cables and before servicing or installing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
TOXIC FLUID OR FUMES HAZARD
Toxic uids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed.
Read MSDSs to know the specic hazards of the uids you are using.
Store hazardous uid in approved containers, and dispo s e of it according to applicable guidelines.
Pressure Relief Procedure
and disconnect all power sources.
334129B 3
Page 4
Warnings
WARNING
THERMAL EXPANSION HAZARD
Fluids subje cted to heat in confi ned spaces, including hoses, can create a rapid rise in pressure due to the thermal expansion. Over-pressurization can result in equipment rupture and serious injury.
Open a valve to relieve the fluid expansion during heating.
Replace hoses proactively at regular intervals based on your operating conditions.
SKIN INJECTION HAZARD
High-pressure uid from dispensing device, hose leaks, or ruptured components will pierce skin. This ma y look like just a cut, but it is a seriou s injury that can result in amputation.
immediate surgical treatment.
Engage trigger lock when not dispensing.
Do not point dispensing device at anyone or at any part of the body.
Do not p ut your hand over the uid outlet.
Do not stop or deflect leaks with your hand, body, glove, or rag.
•Followthe checking, or servicing equipment.
Tighten all uid connections before operating the equipment.
Check hoses and couplings daily. Replace worn or damaged parts immediately.
Pressure Relief Procedure
when you stop dispensing and before cleaning,
Get
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in prevent re and explosion:
Use equipment only in well ventilated area.
Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop cloths (potential static arc).
Keep work area free of debris, including solvent, rags and gasoline.
Do not plug or unplug power cords, or turn power or light switches on or off when ammable fumes are present.
Ground all equipment in the work area. See
Use only grounded hoses.
Hold gun rmly to side of grounded pail when triggering into pail. Do not use pail liners unless they are antistatic or conductive.
Stop operation immediately
equipment until you identify and correct the problem.
Keep a working fire extinguisher in the work area.
if static sparking occurs or you feel a shock.Donotuse
Grounding
work area
instructions.
canigniteorexplode.Tohelp
4
334129B
Page 5
Warnings
WARNING
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate th e unit when fatigu ed or unde r the in flu ence of drugs or alcohol.
Do not ex ceed the max im um working press ure or temperature rating of the lowest rated system component. See
Use uids and solvents that are compatible with equipment wetted parts. See Technical Data in a ll equipment manuals. Read uid and solvent manufacturer’s warnings. For complete information about your material, request MSDS from distributor or retailer.
Do not leave the work area while equipment is energized or under pressure.
Turn off all equipment and follow the
Check equipment d aily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
Do not alter or mo dif y equipmen t. Alterati ons or modifications may void agency approva ls and create safety hazards.
Make sure all equipment is rated and approved for the environment in which y ou are using it.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over be nd hoses or use h os es to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
Technical Data
Pressure Relief Procedure
in all equipm ent manu als.
when equipment is not in use.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective equipment includes but is not limited to:
Protective eyewear, and hearing protection.
Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer.
334129B 5
Page 6

Models

Models
The model number stamped on your systems defines the equipment in the following categories.
See Technical Specifications, page 108, for maximum working pressure.
SER
Series Frame Size
Code A Frame Size
P20
Code B
Code C
11P 4 Zones , 230 V, Primary 11S 4 Zones , 230 V, Secondary 12P 4 Zones, 400 V/N, Primary 12S 4 Zones, 400 V/N, Secondary 13P 4 Zones , 400 V, Primary 13S 4 Zones , 400 V, Secondary 14P 4 Zones , 480 V, Primary 14S 4 Zones , 480 V, Secondary 15P 4 Zones , 575 V, Primary 15S 4 Zones , 575 V, Secondary 21P 8 Zones , 230 V, Primary 21S 8 Zones , 230 V, Secondary 22P 8 Zones, 400 V/N, Primary 22S 8 Zones, 400 V/N, Secondary 23P 8 Zones , 400 V, Primary 23S 8 Zones , 400 V, Secondary 24P 8 Zones , 480 V, Primary 24S 8 Zones , 480 V, Secondary 25P 8 Zones , 575 V, Primary
Gallon (20 Liter)
Air/Electric
A Air control only E Air and Electric
Zones, Volts, Type
AB
Air
Air/Electric
C
Zone Config
25S 8 Zones, 575 V, Secondary 31P 12 Zones , 230 V, Primary 31S 12 Zones , 230 V, Secondary 32P 12 Zones, 400 V/N, Primary 32S 12 Zones, 400 V/N, Secondary 33P 12 Zones , 400 V, Primary 33S 12 Zones , 400 V, Secondary 34P 12 Zones , 480 V, Primary 34S 12 Zones , 480 V, Secondary 35P 12 Zones , 575 V, Primary 35S 12 Zones , 575 V, Secondary
NNN None
Code D
Pump Ratio
1
23:1 CF (Carbon-Fill ed)
2
36:1 CF
3
70:1 CF
4
23:1 GF (Gl ass-Filled)
5
36:1 GF
6
70:1 GF
7 15:1 PTFE
Code E Platen Style
S Smooth Bottom (No Fin) F
DE
Pump Ratio
Standard Finned Bottom
Platen Style
6 334129B
Page 7

Related Manuals

Related Manuals
Manual Description Air Motor Manuals
306982
311238 3A1211 Saniforce® Air Motor,
Displacement Pump Manual
334127
334128
Presiden Air Motor, Instructions-Parts
NXT® Air Motor, Instructions-Parts
Instructions-Parts
Check-Mate® 800 P ump, Repair-Parts
Check-Mate 800 Throat Seal Repair Kit, Repair-Parts
Manual Description
307431
Ram Manual
334198 Therm-O-Flow Ram, Instructions-
Accessory and Kit Manuals
309160 Heated Hose, Instructions-Parts 309196 Wiper Kits, Repair-Parts 310538
311209 Top Feed and Bottom Feed Hot Melt
334201
Displacement Pump, Carbon Steel, Instructions-Parts
Parts
Air-Operated Dispense Valves, Instructions-Parts
Dispense Guns, Instructions-Parts Air Cont rols, Repair Kit
334129B
7
Page 8
Component Identication
Component Identification
Figure 1 TOF 20
Key:
A B Multi-Zone Low Power Temperature
C D ERam F Heated Pump G H J
8 334129B
Lift Strap Positions
Control Module (MZLP) Light Tower
Cable Track
Heated Platen Integrated Air Controls (3/4 in npt inlet) Electrical Control Panel
Key:
K LADM M N Electrical Power Input PAirMotor R S Drum Blow Off Valve (behind ram plate
T
Main Power Switch
Air M otor Solenoid
Ram Plate Bleed Stick
bleed stick) Drum Low and Empty Sensors
Page 9

Integrated Air Controls

Component Identication
Figure 2 Integrated Air Controls
Key: CA Main Air Slider Valve
Turns air on and off to the entire system. When closed, the valve relieves pressure downstream.
CB
CC Ram Director Valve
CD
CE
CF
CG Blowoff Button
Ram Down Air Regulator
Controls the ram down pressure.
Controls the ram direc tion.
Ram Up Air Regulator
Controls the ram up pressure.
Ram Down Air Gauge
Displays the ram down pressure.
Ram Up Air Gauge
Displays the ram up pressure.
Turns air on and off to push the platen out of an empty drum.
Key: CH Blowoff Pressure Gauge
Displays the blowoff pressure.
CJ
CK
CL
CM Air Motor Slider Valve
CN Air Motor Solenoid Valve
Blowoff Air Regulator
Controls platen blowoff pressure.
Air Motor Air Regulator
Controls the air pressure to the motor.
Air M otor Pressure Gauge
Displays the air pressure to the motor.
Turns air on and off to the air motor. When closed, the valve relieves air trapped between it and the motor. Push the valve in to shutoff air.
Turns air on and off to the air motor when system stopped on the ADM. When closed, the valve relieves air trapped between it and the motor.
334129B 9
Page 10
Component Identication

Electrical Control Enclosure

Figure 3 Electrical Enclosure
10 334129B
Page 11
Component Identication
Key:
DA Multi-Zone Low Power Temperature
Control Module (MZLP)
DB DC Electrical C ontrol Panel DD DE DF
Ventilation Grill
Automatic Wiring Board (AWB) Power Supply (24V) Residual Current Devic e (GFI), 63A
Key:
DGPlatenSSR(65A) DH DJPlatenFuse DK DL DM
Platen Contactor
Transformer Circuit Breaker Transformer Fuse Transformer
334129B
11
Page 12
Component Identication

Advanced Display Module (ADM)

The ADM display shows graphical and text information related to setup and spray operations.
For detail on the display and individual screens, see
Appendix A ADM, page 94.
Use the USB port on the ADM to download or upload data. For more information about the USB data, see
Appendix B USB Data, page 102.
NOTICE
To prevent damage to the softkey buttons, do not press buttons with sharp objects such as pens, plastic cards, or ngernails.
Figure 4 Front View
Key BA BB BC BD BE
BF
BG BH
Function
Heating sy stem and pump enable/disable
m status i ndicator (LED)
Syste
ll system processes
Stop a
dbyiconnexttosoftkey
Define
current operation
Abort Accept change, acknowledge error, select item,
toggle selected item Toggle between Operation and Setup screens
Navigatewithinascreenortoanewscreen
12
334129B
Page 13
Figure 5 Back View
BK BL BM

Table 1 ADM LED Status Descriptions

Part Number and Identication Label USB Interface CAN Cable Connection (Power Supply and
Communication)
BN BP
BR
Component Identication
Module Status LEDs Light T ower (Optional)
Software Token Access Panel
LED System Status
USB Status (BL)
ADM Status (BN)
Conditions
Green Solid Run Mo de, System On Green Flashing Setup Mode, System On Yellow Solid Run Mode, System Off
Green Flashing Yellow Solid Downloading information to USB Green an d Yellow Flashin g ADM is busy, USB cannot transfer
Green Solid Yellow Solid Active Communication Red Steady Flashing Software upload from token in
Red Random Flashing or Solid
Description
Data recording in progress
informationwheninthismode Power applied to module
progress Module error exists
334129B 13
Page 14
Component Identication
Screen Components
1. Screen Order
2. Current date and time
3. Operating Mode
4. Faults, Status
5. MZLP Plug Identifier
6. Zone Setpoint Temperature
7. Zone Actual Temperature
Operating Mode Description Component Status
System Off The system do
es not have power.
No system sta ADM
tus indicator LED on the
Inactive The heating system and pumps are
disabled.
Warm Up The system is heating the material to the
setpoint temperature.
Heat Soak
Ready All enabled zones are at setpoint
Heat zones are all at temperature. Material is soaking for a user specied amount of time.
temperature. The air motor does not have power.
•Noheat
•Pumpisoff
Yellow system indicator LED on the ADM
•Noheat
•Pumpisoff
Flashing green system status indicator LED on the ADM
Heat is increasing to setpoint temperature
•Pumpisoff
Flashing green system status indicator LED on the ADM
Heatisatsetpoint
Material is abs orbing more heat
•Pumpisoff
Heat so ak counter counts down on the Home screen.
Flashing green system status indicator LED on the ADM
Heatisatsetpoint
Act
14
ive
system is ready to dispense.
The
•Pumpisoff
Solid green system status indicator LED on the ADM
Heatisatsetpointtemperature
•Pumpison
334129B
Page 15

Overview

A heated platen melts the sealant or adhesive and directs the molten material to the pump inlet. The material then travels through a heated pump and heated u id moves to the application tool.

Air and Fluid Hoses

The Therm-O-Flow requires Graco single-circuit material hoses rated at a maximum of 1250 watts. Make s u re all air and uid hoses are properly sized for the system.

Heat Control Zone

The Therm-O-Flow has 4, 8, or 12 heat zones. Zones for the heated drum platen and the heated pump are not included in the zone count. Zones 1 and 2, 3 and 4, 5 and 6, 7 and 8, 9 and 10, and 11 and 12 are each available through 12-pin connectors. The heated hoses have a 16-pin connector at the inlet, and an 8-pin connector at the outlet. All heated valves, manifolds, and heaters are equipped with an 8-pin mating connector.
Overview
Figure 6 Heat Control Zone Selection
334129B 15
Page 16

Setup

Setup
1. Unpack the ram
2. Locate and Install the ram
3. Mechanical Setup
4. Connect hoses to electrical control panel
5. Connect el e ctrical control panel to power source
6. Ground system
7. Select ADM settings

Unpack

1. Inspect the shipping box carefully for damage. Contact the carrier promptly if there is damage.
2. Open the box and inspect the contents carefully. There should not be any l oose or damaged parts in the box.
3. Compare the packing slip against all items in the box. Report any shortages or other inspection problems immediately.
4. Remove the unit from the skid and place it in the desired location. See
Location Requirements
.
2. If you are installing a vent hood, make sure there is sufficient horizontal clearance for it. Locate the ram near a connection to the factory ventilation system.
3. Make sure the integrated air controls for the pump and ram are fully accessible, with room to stand directly in front of the controls and the ADM.
4. Make sure there is easy access to an appropriate electrical power source. The National Electrical Code requires 3 ft (0.9 m) of open space in front of the electrical panel. Comply with all local codes and regulations.

Install System

Refer to Dimensions, page 105, for mounting and clearance dimensions.
Follow all Location Requirements, page 16,when selecting a location for the ram.
1. Apply 50 psi download pressure to ram.
2. Wrap the bar with the lifting sling.
3. Lift the system off the pallet using a crane or a forklift and place in desired location.
4. Level the base of the ram, using metal shims.

Location Requirements

1. Make sure there is sufficient overhead clearance for the pump and ram when the ram is in the fully raised pos ition (approximately 75 in. (190.5 cm).
5. Bolt the ram to the oor, usin g ancho rs that are long enough to prevent the unit from tipping.
16 334129B
Page 17
Setup

Mechanical Setup

1. Fill displacement pump wet cup 2/3 full with Graco Throat Sea l Liquid (TSL) for Butyl and PSA materials.
Note
Use IsoGuard Selec (IGS) (part no. 24F516) for PUR or reactive Polyurethane material. IGS is designed to dissolve and suspend the Polyurethane materials. IGS will so lidify after a period of time and should be replaced once the solidied lube does not return to liquid form after heating.
Figure 7 Wetcup
4. Ensure drum low and empty sensors (C) are mounted as shown.
Note
TheDrumLowandEmptySensorsare used to indicate that a drum is empty. The kit contains a sensor mounting bracket (A), activator (B), sensors (C1, C2), and a cable for connecting the panel inside the electrical enclosure.
2. Turn all air regulators to their ful l counterclockwise position. See Integrated Air Controls, page 9.
3. Connect a 1/2 in. (13 mm) air line from an air source to the system air inlet (H), capable of delivering a minimum of 25–50 cfm at 100 psi (0.7 MPa, 7.0 bar).
Figure 8 Air Connect ion
Do not use quick disconnects
.
5. Increase the distance betwee n the low (C1) and empty (C2) sensors to increase the heat up time for the tandem secondary system. Lower the empty sensor (C2) to force the heated platen lower into the drum . If empty sensor is set too low,thepumpcouldcavitateandcauseanalarm.
334129B
17
Page 18
Setup

Install Heated Hose

To connec t a hose to a uid control device or heated manifold.
1. Install tting and heated hose onto pump outlet with the large electrical connector side toward thesystem.Use2wrenchestotightenhose. Torque to 45 ft-lbs (61 N•m).
Note
See Accessories and Kits, page 87 ,for available ttings and heated hoses.
Figure 9
2. Wrap exposed ttings on the pump outlet with Nomex insulation and secure insulation using fiberglass tape.
18 334129B
Page 19
Setup
3. Connect large heated hose connector to adapter cable from MZLP.
Note
All MZLP adapter cables are shipped loose.
4. Repeat fo r any remaining channels.
5. Install cap on any unused MZLP electrical connectors.
6. Connect the small 8 pin connector from the heated hos e to the uid control device or heated manifold.
Figure 11 Heated Manifold 243697
Note
Figure 10
The heated manifold (part no. 243697) shown. See
Accessories and Kits, page 87 ,
for available manifolds and uid control devices.
7. Use 2 wrenches to tighten hose. Torque to 45 ft-lbs (61 N•m).
8. To connect multipl e devices, see
Connect Multiple D ev ic es , page 20.
334129B 19
Page 20
Setup

Connect Multiple Devices

If your application requires multiple uid control devices:
Connect heated hose electrical connections to the electrical enclosure. Use accessory cables if necessary. Additional cables (part no. 17C694) areprovidedwith8and12zonesystems.Remove from shipping box to connect heated hoses to the electrical enclosure. For additional cables, heated hose, and uid control devices, see
Accessories and Kits, page 87.
Connect uid control devices to a heated hose or the electrical enclosure. Use accessories if necessary.
Setup all heat zones on Heat-A and Heat-B screens.
Example: Heated zones used to connect a primary andsecondarysystemtoamanifoldandtwoguns. A-# zon es are on the Heat-A screen and B-# zo nes are on the Heat-B screen.
Figure 12
20 334129B
Page 21
Setup

Connect Power

The elec trical control panel comes already attached and wired to the ram, however before the supply unit becomes functional you must connect the electrical control panel to a power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
Note
Required voltage and amperage is noted on the control panel label. Before running power to the unit, make sure the plant electrical service meets the machines electrical requirements.

Table 2 Electrical Requirements

Elec-
trical
Panel
Voltage
220 / 240
380 / 400
470 / 490
Hz Phase Platen
50/60 3
50/60 3
50/60 3
EF, ES
EF, ES
EF, ES
Full
Load
Amps
39
20
19
power source wires to the appropriate terminals on the DISCONNECT switch.
Figure 13
To reduce the risk of re, explosion, or electric shock, the resis tance between the supply unit components and true earth ground must be less than 0.25 ohms.
3. Connect t Haveaqu between the true less tha than 0.2 require proble
he ground wire to the ground lug.
alified electrician check the resistance
each Therm-O-Flow system ground and
earthground. Theresistancemustbe
n 0.25 ohms. If the resistance is greater
5 ohms a different groun d site may be
d. Do not opera te the sy s tem until th e
m is corrected.
Note
Use a meter that is capable of measuring resistance at this level.
570 / 590
EF Standard Finned Bottom ES Smooth Bottom
1. Locate the opening in the control panel’s top housing for the conduit that will enclose the wire from the facility’s power source. The hole will accept a a cord diameter range of 0.7–1.2 in (17–30 mm).
2. Route the wire from the power source into the control panel housing, and then connect the
334129B
50/60 3
EF, ES
22
21
Page 22
Setup

Grounding

Ground the unit as instructed here and in the component manuals.
The e quipment must be grounded to reduce the risk of static sparking and electric shock. Electric or static sparking can cause fumes to ignite or explode. Improper grounding can ca use electric shock. Grounding provides an escape path for the electric current.
System:
enclosure. See Connect Power.
Air and fluid hoses:
hoses.
Air compressor:
recommendations.
Spray gun/Dispense valve:
connection to a properly grounded uid hose and pump.
ground through ground lug in electrical
use only electrically conductive
follow manufacturers
ground through
Material drums:
drums placed on a grounded surface. Do not place the drum on a nonconductive surface, such as paper or cardboard, which interrupts the grounding continuity.
To maintain grounding continuity when ushing or relieving pressure:
separate gun manual for instructions on how to safely ground your gun while flushing.
follow local code. Use only metal
follow instructions in your

Connect Secondary System

A secondary system is a Therm-O-Flow supply system that connects to the primary Therm-O-Flow system, with the AD M. See Model s, page 6 for secondary system model numbers.
1. Connect a dapter cable (AC) and communication cable (SC) to the secondary electrical enclosure androutetosplitter(SS)installedontheprimary system.
2. To enable a sec ondary system, select “Enable Tandem System on the System 1 screen. See
Select ADM Settings, page 25.
Figure 14
22
334129B
Page 23
Setup

Check Sensor Resistance

To reduce risk of injury or damage to equipment, conduct these electrical checks with the main power switch OFF.
The packag e includes up to twelve heat sen sors and controllers for each of the heated zones. To check sensor resistance:
1. Turn mai n pow er switch off.
2. Wait for components to cool down to ambient room temperature 63°-77°F (17°-25°C). C heck electrical resistance for the components.
MZLP Zones Pins
First Heat Zone A,J Second Heat Zone C,D First RTD Second RTD Earth Ground
G, K M, K B
3. Replace any parts whose resistance readings do not comply with the ranges listed in the RTD Sensors chart below.
Cable 17C694
A
J
M
H
G
F
E
L
K
C
D

Table 3 RTD Sensors

MZLP MZLP Plug
1
2
B
ti24580a
3
1,2
3,4
5,6
7,8
9,10
11,12
Component
RTD Range (Ohms)
Ram Plate 100 +/- 2 Fluid Pump 100 +/- 2 Heated
100 +/- 2 Accessory 1 Heated
100 +/- 2 Accessory 2 Heated
100 +/- 2 Accessory 3 Heated
100 +/- 2 Accessory 4 Heated
100 +/- 2 Accessory 5 Heated
100 +/- 2 Accessory 6 Heated
100 +/- 2 Accessory 7 Heated
100 +/- 2 Accessory 8 Heated
100 +/- 2 Accessory 9 Heated
100 +/- 2 Accessory 10 Heated
100 +/- 2 Accessory 11 Heated
100 +/- 2 Accessory 12
334129B 23
Page 24
Setup

Check Heater Resistance

To reduce risk of injury or damage to equipment, conduct these electrical checks with the main power switch OFF.
1. Turn main power switch off.

Table 4 Heaters

Component
Platen
Between Terminals
FHA1/FHB1 to FHA2/FHB2 (without jumper) FHA1 to FHA2 or FHB1 (withjumper) FHA1 to FHB2 (withjumper) Any to GND 100,00 Min
For Unit Voltage
220/240 VAC EF, ES 14.4Ω +1.5/ -2
380/590 VAC EF, ES 28.8Ω +3 / -4
380/590 VAC EF, ES 57.6Ω +6 / -8
2. Make electrical resistance checks for the components.
3. Replace a ny parts whose resistance readings do not comply with the ranges listed in tables.
Note
Check resistance at ambient room temperature 63° 77°F (17°– 25°C).
Platen Model Code Resistance Values (ohms)
Component
Pump
24
Between Terminals For Unit Voltage
T1/B1 or T2/B2 to T3/B3 T1/B1toT2/B2 Any Any
Any Any
Platen Model Code Resistance Values (ohms)
192.0 +/- 19.2Ω
384.0 +/- 38.4Ω
334129B
Page 25

Select ADM Settings

Note
See Appendix A ADM, page 94 for detailed ADM information, i n cluding general operation.
1. Turn mai n power switch on.
Setup
2. When the ADM is nished s tarting u p, press to switch from the Operation screens to
the Setup sc reens. Use the arrows to navigate between screens.
3. Check system settings on the System 1 screen.
4. Set alarm levels on the System 2 screen.
Note
Setback temperatures must be at least 20°F (10°C) lower than the setpoint temperatures
Note
To ensure accurate hose temperatures, be sure all heated hoses have their zone type” set to Hose.” Hoses are only present on odd zone numbers: 1, 3, 5, 7, 9, or 11.
a. Select the appropriate “Zone Type for all
installed zones.
b. Check the A and B boxes according to
which systems needs to use the heated accessory.
6. If a secondary system is used, set temperatures on the Heat-B screens.
7. Set the system date and time on the Advanced 1 screen.
5. Set primary system setpoint and setback temperatures for the pump, platen, and heat zones on th e Heat-A scree ns.
334129B 25
Page 26
Setup
8. Set the temperature and mass units on the Advanced 2 screen. Set the specic gravity of the material for Material Tracking functionality.
Note
If the Specic Gravi ty is set to zero, the Home screen will display a cycle counter instead of gram s or pounds.
9. To setup the optional Schedule function, see
Schedule, page 37.
The schedule function allows the system to automatically enable and disable heating and setback at specified times.
10. Optional: Set any remaining settings in the Setup screens before using the system. These are not required for system operation, but include useful functions. See Appendix A— ADM, page 94 for detailed information about each setup item.
26 334129B
Page 27
Setup

Connect PLC

A PLC can control and monitor all items shown in the Customer Digital Inputs and Outputs shown on the Diagn ostics screen. See
Appendix A ADM, page 94.
When the PLC has control of the system:
Functionality is restricted from the ADM
Automatic crossover is disabled. Rely on the PLC and machine state indicators to know when to cross over using the I/O.

Table 5 Customer Input

Signal No.
1 2
3 4

Table 6 Customer Output

Signal No.
1 2 3
4
Unit A Description
Heat On Request Setback Request
Pump On Request PLC Control Request
(input applies to primary to unit A only)
Unit A or B Description
Run State Bit Low See Run State Chart Run State Bit High See Run State Chart Error State Bit Low See Error State
Error State Bit High See Error State
Turn on the Heat Put the Unit in
Setback Turn on the Pump
Control the primary and s econdary TOF systems from the PLC instead of the ADM
Chart
Chart

Table 7 Output Error States

Error State Bit High
0 0 Machine is
01ActiveUnit
10ActiveUnit
1 1 Alarm Present

Table 8 Output Run States

Run State Bit High
00
01
10
11
Note
All out puts are normally open when power is OFF. For error (alarm) output, the contacts close when an alarm occurs. For all others, contacts close.
Note
The TOF system ships with two screw terminal connectors that plug into MZLP connectors H1 and H2. Connectors are locatedinabagontheinsideoftheelectrical enclosure. To replace the connectors, order kit 24P176.
1. Turn mai n power switch off.
2. Open the elec trical enclosure door.
3. Route I/O cables through strain relief.
Error State Bit Low
good, no errors are present
Drum Low
Drum Empty
in Sy stem
Run State Bit Low
Pump Off/ Heat Off Pump Off/ Heat On Pump Off/ Heat At Temp Pump On/ Heat At Temp
334129B
4. Remove power from the PLC.
5. Connect the PLC to connectors H1 and H2.
Note
Each connector has four signals. The MZLP board specifies the input range for each signal. See the following table for pin assignments.
27
Page 28
Setup
H2 Customer Output
Signal
11,2 23,4 35,6 47,8
Pin
Figure 15
Inputs:
function without concern for polarity. Applying high voltage w ill turn the heaters on and enable setback. Removing voltage will turn the heaters off and disable setback.
Outputs:
H1 Customer Input
Signal
11,2 23,4 35,6 47,8
Pin
High: 10–30 VDC, Low: 0– 5 VDC. Inputs
0250VAC,030VDC,2AMaximum.
28 334129B
Page 29

PLC Connections Block Diagrams

The following block diagrams show how to connect customer i nputs and outputs to the MZLP. For convenience, each system ships with connector kit 24P176. If a connector is lost or damaged, order kit 24P176 for replaceme nts.
Setup
Figure 1
Figure 17 Customer Out put
6 Customer Inp ut
334129B 29
Page 30

Operation

Operation
1. Turn the main power switch ON. The Graco logo will display u ntil comm unication and initialization is complete.
2. Press the button. Verify the machine is in Warm Up state, and that the temperatures are increasing. Allow the system to reach the “Ready state before pumping. The pump will automatically turn on, if autostart is enabled in setup screens, when all the heat zones reach their setpoint temperature.

Purge System

NOTICE
Use uids that are chemically compatible with the equipment wetted parts. See Technical Specifications in all of the equipment manuals.
1. Select the material for the initial material load.
2. Verify whether the factory-test oil and the initial material load are compatible:
a. If the two substances are compatible omit the
remaining steps in this procedure and refer to the Load Material, page 31.
b. If the two substances are incompatible
perform the remaining steps in this procedure to ush the system.
3. Select a pail of material that can eliminate the factory-test oil from the system. If necessary, check with Graco or the material supplier for a recommended solvent.
4. Beforepurgingbesuretheentiresystem and waste pail are properly grounded. See
Grounding, page 22.
5. Turn all heat zones setpoint temperature to the material manufacturers recommended dispense temperature, or a minimum of 100°F (37°C) minimum.
Note
NOTIC
Purge the system before initial use and when chemicals are changed to prevent material contamination, which may cause the material to fail or perform poorly. The system was factory- tested using a light soluble oil, a soybean oil, or some other oil as tagged. Flush the system to avoid contaminating the material that has been designated for initial material loading.
E
Remove any dispense valve orifices before purging. Reinstall after purging has been completed.
6. Purge the material through the system for approximately 1 to 2 minutes.
7. Remove the pail if purge material was used. See
Change Pail, page 38.
30 334129B
Page 31
Operation

Load Material

NOTICE
To prevent damage to platen wipers, do not use a pail of material that has been dented or damaged.
An empty pail clamp can interfere with up and down operation of the ram.
make sure the pail clamp stays clear of the platen.
Note
Before loading material, make sure there is a minimum overhead clearance of 75 in. (191 cm) and all air regulators are backed off to their full counterclockwise position.
1. Open the main air slider valve (CA).
2. Set ram director valve (CC) to UP and slowly turn the ram up regulator (CD) clockwis e until the platen (G) begins to rise.
When raising the ram,
4. Fill displacement pump wet cup 2/3 full with Graco Throat Seal Liquid (TSL™) for Butyl and PSA materials.
Note
Use IsoGuard Selec (IGS) (part no. 24D086) for PUR or reactive Polyurethane material. IGS is designed to dissolve and suspend the Polyurethane materials. IGS will solidify after a period of time and should be replaced once the solidified lube does not return to liquid form after heating.
Figure 19 Wetcup
5. Open pail, remove any packing material, and inspect material for any contamination.
6. Slide the pail against the stops at the back of the ram baseplate.
Figure 18 Raise the Platen
3. Apply a thin coating of high temperature grease lubricant (part no. 115982) to the platen pail seals.
334129B 31
Figure 20 Drum Placement
Page 32
Operation
7. Remove the platen bleed stick (R).
Figure 21 Platen Bleed Handle
8. Set ram director valve (CC) to down and lower the platen.

Heat Up System

To reduce the risk of bursting a hose, never pressurize a hot melt system before turning on the heat. The air will be lock ed from the air motor until all tem perature zones are within a preset window of the tempe rature se tpoints.
Keep the dispense valve open over a waste container while the system is heating up and also when cooling down. This will prevent a pressure build-up c aused by fluids or gases expanding from the heat.
Note
Operate at the lowest temperature and pressure necessary for your application.
1. Turn the main power switch on the electrical control panel do or to the ON position.
Figure 22 Lower the Platen
9. Slowly turn the ram down air regulator (CB) clockwise to approximately 510 psi (34–69 kpa,
0.3–0.7 bar). The platen will begin to lower into the pail.
10. After the platen seals enter the material pail, adjust the ram down air regulator (CB) to 30–50 psi (207–345 kPa, 2.1–3.4 bar).
11. When the ram stops, reinsert the platen bleed stick (R) and hand tighten.
2. Press the button. The zones begin to heat (provided they are enabled). Press
if the zones do not begin to heat. Display status bar reads temperature reaches setpoint, the display status bar reads the status will display in the status bar. See
Advanced Display Module (ADM), page 12,for
operation mode descriptions.
Note
The air will be locked from the air motor until all temperature zones are within a preset window of the temperature set points, allowing the system to heat fully and complete the material heat soak period.
Heat Soak
Warm Up
.Whenheatison,
.When
32 334129B
Page 33

Prime Pump

1. Ensure that the system has completed the heat soak cycle. The display status bar should read
Active
.
2. Adjust the air motor air regulator (CK) to 0 psi.
Operation
5. Adjust the air motor air regulator (CK) to approximately 20 psi (138 kPa, 1.38 bar).
3. Ensure air motor solenoid valve (CN) is on. The indicator light on the solenoid connector will only be on if Enable Pump Autostart” is selected on the System 1 Setup screen.
4. Adjust the air motor slider valve (CM) to the open position.
6. Place a waste container under the bleed stem (Z). Using an adjustable wrench, open the bleed stem counterclockwise 1/3 -1/2 turn.
334129B 33
Page 34
Operation
7. If a new pail was installed and the unit is equipped with proximity sensors, press the Pump Ready button . Press pause button on material tracking.
8. Adjust the air motor air regulator (CK) up by 5 psi (34 kPa, 0.3 bar). Never adjust the regulator by more than 5 psi (34 kPa, 0.3 bar) increments. Make sure the pump begins to cycle and heated material flows from the bleed stem (Z) after several cycles of the pump.
9. Prime the pump until it moves smoothly in both directions with no air popping or erratic movement and close the main air slider valve (CA).
10. Close the bleed stem (Z).
11. Press Play button on home screen to enable material tracking.
34 334129B
Page 35
Operation

Prime System

1. Close the main air slider valve (CA).
2. If us ing a manual gun, lock the dispense valve trigger o pen by pulling and securing the trigger using the trigger retainer (Z).
7. Close the main air slider valve (CA) and release trigger lock.
8. Engage trigger lock.
Figure 23 Trigger Lock Engaged
9. Press
10. Turn the air motor regul ator to operating pressure.
Note
The system is now ready to operate.
to engage material tracking.

Setback Mode

3. Place the dispense valve over a waste container.
4. Press the pause material tracking button on home screen.
5. Slowly open the main air slider valve (CA).
6. Prime the system until a smooth ow of material dispenses from each dispense valve.
Note
On i nitial system startup, the pump will cycle until the hos es are lled. If a new drum was placed on the frame, the pump will cycle until all air has been removed.
Set the ADM to setback mode if the system will only be inacti ve for a few hours. This will reduce the time system n eeds to return to setpoint temperatures.
1. Press
Note
The amount of time before the pump is automatically placed in setback is determined by the Pump Inactivity Timeout, locatedonSystemSetupScreen1. See
Setup Screens, page 97.
to enter Setback Mode.
334129B 35
Page 36
Operation

Pressure Relief Procedure

Follow the Pressure Relief Procedure whenever you see this symbol.
This equipment stays pressurized until pressure is manually relieved. To help prevent serious injury from pressurized uid, such as skin injection, splashing uid and moving parts, follow the Pressure Relief Procedure when you stop spraying and before cleaning, checking, or servicing equipment.
Note
If using a different dispense applicator, see the applicator manual for pressure relief instructions.
1. Engage the trigger lock.
3. Set the ram director valve (CC) to the neutral position.
4. Disengage the trigger lock.
Figure 24 Engaged
2. Close the system master air slider valve (CA).
Figure 25 Disengaged
5. Holdametalpartofthegunrmlytoagrounded metal pail. Trigger the gun to relieve pressure.
6. Engage the trigger lock.
7. Open all uid drain valves in the system, having a waste container ready to catch drainage. Leave drain valve(s) open until you are ready to dispense again.
8. If you suspect the tip or hose is clogged or that pressure has not been fully relieved after following the steps above, VERY SLOWLY loosen hose end coupling to relieve pressure gradually, then loosen completely. Clear hose or tip obstruction.
36 334129B
Page 37
Operation

Shutdown

1. Press to disable the heaters and pump. The screen will say Inactive. If using the Schedule function, the heaters and pump will be disabled automatically at the set time. Only press
to disable the heating system before the set time. If the heaters were manually disabled, the Schedule function will automatically enable them at the nex t set time.
Table 9 Schedule Screen Color Identification
Color Description
Green System on Yellow Setback Red System off Gray Disabled
Set Schedule Times
Times are set using a 24hour clock. Several on and off times can be set each day.
Note
Do not perform step 2 if using the Schedule function. Leave the power on.
2. Turn mai n pow er switch off.

Schedule

The Schedule function allows the user to specify times when the system will automatically turn ON and OFF th e hea ters and pump.
1. On the Schedul e screen (in the Setup screens), set the ON times for each day of the week.
2. Set the OFF times for each day of the week.
3. Set the setback times for each day of the week.
Enable Schedule Function
The Schedule function is automatically enabled when values are entered in the Schedule screen. To disable a schedule d event, navigate to the event and
press The event will appear gray on the screen when it
is d isabled. To re-enable an event, navigate to the
event and press The event will appear red (system off), yellow (system
setback), or green (system on). If no events are needed, turn the main power switch OFF to prevent system from automatically enabling and disabling the heaters.
.
.
Use the Schedule Function
At the end of the work day leave the main power switch ON. The Schedule function will automatically enable and disable the heaters and pump at the specified times.
334129B 37
Page 38
Operation

Change Pail

To prev ent serious burns from dripping material, never reach under the heated platen after the platen is out of the pail.
Follow the procedure to change the pail on a fully heated system.
NOTICE
Be sure to reload the empty supply unit with a full pail of material immediately.
and remove the platen from the empty pail until you are ready to immediately install a new pail.
Do not raise the ram and remove the platen from the empty pail unless the supply unit is at full operating temperature.
performed when the system is heated.
Donotraisetheram
Drum changes can only be
3. Set ram director valve (CC) to UP and raise the platen (G) and immediately press and hold the blowoff buttons (CG) until the platen is completely out of the pail. Use minimum amount of air pressure necessary to push the platen out of the pail.
An empty pail clamp can interfere with the up and down operation of the ram.
loweringtheram,makesurethepailclampstays clear of the platen assembly.
Do not use a pail of material that has been dented or otherwise damaged;
wipers can result.
All systems include Low/Empty Sensors:
The air will shutoff to prevent the pump from cavitation. If the light tower kit is installed, a solid red light indicates that the pail is empty and ready to change.
In a tandem system, a ashing red light means that both drums are empty and the system has shutdown.
1. Press
2. Push in the air motor slider valve (CM) to stop
the pump.
to stop material tracking.
damage to the platen
When raising or
Excessive air pressure in the material pail could cause the pail to rupture, causing serious injury. The platen must be free to move out of the pail. Never use pail blowoff air with a damaged pail.
4. Release the blowoff air button and allow the ram to rise to its full height.
5. Remove the empty pail.
6. Inspect platen and if necessary, remove any remaining material or material build-up.
7. Follow steps in Load Material, page 31, and
Prime Pump, page 33.
38 334129B
Page 39

Troubleshooting

Light Tower (Optional)

Troubleshooting
Signal
Red Light Off If green light is also off, system power may be off or system operating mode is Inactive. If
Red Light On User interaction required alarm, system is shut down Red Light
Flashing Green Light Off System is inactive
Green Light On System is ready to dispense. The heat and pump are on. Green Light
Flashing
Description
green is o n or ashing, there are no active errors.
User in teraction required advi sory, deviation, or system is in a state that could prohibit dispensing.
System will be ready to dispense in time without user interaction (heat on, pump off, and temperature control zones have not reached set point)
334129B 39
Page 40
Troubleshooting

Error Codes

There are three types of errors that can occur. Errors are indicated on the display as well as by the optional light tower.
Alarms are indicated by a parameter critical to the process has reached a level requiring the system to stop. The alarm needs to be addressed immediately.
Deviations are indic at ed by indicates a parameter critical to th e process has reached a level requiring attention, but not sufficient enough to stop the system at this time.
Advisories are indicated by indicates a parameter that is not immediately critical to the process. The advisory needs attention to prevent more serious issues in the future.
To acknowledge the error, press
The thi code, i multi
rd digit, or sometimes the last digit of the error
ndicates which unit the error is active on. The
tar) character indicates the code applies to
”(s
ple system components.
Third or Last Digit
AUnitA BUnitB
. This condition indicates
. This condition
. This condition
.
Codes Relates To:
The last digit of the error code indicates which system component the error applies. The # (pound) character indicates the code applies to multiple system components.
Last Digit #” Codes Relates To
System Component:
1MZLP1 2MZLP2 3MZLP3 5 6MZLP6 7 VAWBUnitA WAWBUnitB X Daughter Boa rd Unit A Y Daughter Boa rd Unit B
The last digit of the error code indicates which heat zone the error applies. The _” (underscore) character indicates the code applies to multiple system components.
Last Digit _ Codes Relates To Heat
1Zone1 2Zone2 3Zone3 4Zone4 5 6Zone6 7 8Zone8 9Zone9 AZone10 BZone11 CZone12 D Pump EPlaten
MZLP 5
MZLP 7
Zone:
Zone 5
Zone 7
40 334129B
Page 41
Troubleshooting
Code
A3MF
A4C# High Current
A8_
A8C
AM3 # High Current
AM4 # High Current
AM8# No Current
CAC# Comm Error
CACX
CACY
Description Type
AWB Clean Fan Filter
Unit _ Zone _
Fan AWB, Unit _
Unit _ Zone _
No Current Unit _Zone_
AWB No Fan
Current
SSR MZLP _
Contactor MZLP _
Contactor MZLP _
MZLP _
DB Not Present Unit A
DB Not Present Unit B
Cause Solution
Alarm
Alarm Defective or
Deviation Fan is drawing
Alarm Unexpected
Alarm
Alarm
Alarm Excessive
Alarm
Alarm
Alarm
Alarm Daughter
Alarm Daughter
Cooling inlet screen is dirty
shorted to ground on zone
too much current
current flow to zone
No Current Flow to the Zone
Cooling fan not working
current flow in the SSR Defective or shorted to ground on MZLP No Current Flow to the Contactor System not responding to ADM.
Board not responding
Board not responding
Clean inlet screen.
Verify accessory is rated for 240 VAC.A4_ High Current Verify heater resistance and check for shorts to
ground. Replace as necessary.
Verify there is not an air obstruction at the inlet/outlet of enclosure. verify nothing is preventing fan rotation. Replace fan if necessary. Replace MZLP.A7_ Unexp. Curr.
Faulty accessory heater. Measure resistance to ground between heater leads. Check fo r loose or disconnected wires or plugs.
Check for blown fuses on MZLP. Check heater resi stance for open circuit. Check for shorts between heater and ground. Verify cable is plugged into zones 3–4. Replace
heater if necessary. Verify fan is plugged in. Replace if necessary.
Check for shorts in harness to SSR. Check polarity of wiring to SSR. Replace if necessary.
Check for shorts in the harness to contactor. Check the polarity to contactor. Replace contactor if necessary.
Ensure harness to MZLP is connected. Ensure wiring to contactor is secure. Replace c ontactor if necessary.
System is not properly loaded with correct Software. Dial not set correct on MZLP. Duplicate MZLP dial
positions (i.e. 1 to 1, 2 to 2, ect) Check all CAN connections between the ADM and missing MZLP. Check if hardware exists on the network.
Replace MZLP if necessary. Dial not set correct on MZLP 5. Set to 5 on boa rd with
daughter board. Ensure c onn ectio ns between the AD M and hardware are secure. Replace Daughter Board.
Dial not set correct on MZLP . Set to 4 on board with daughter board. Ensure c onn ectio ns between the AD M and hardware are secure. Replace Daughter Board.
334129B
41
Page 42
Troubleshooting
Code
CACV
CACW
DAX Pump Runaway
DEX
DCX
L1X Material Level
L2X Material Level
L3X Material Level
MMUX
MNXPump_
Description Type
AWB not present Unit A
AWB not present Unit B
Detected
Reed Switch Failure Detected
Pump Diving Alarm
Sensor Error
Empty
Low USB Log Full
Requires Maintenance
Cause Solution
Alarm AWB not
responding
Alarm AWB not
responding
Alarm
Alarm Reed switch
Alarm Machine is
Alarm Material drum
Deviation Material level
Advisory
Advisory User dened
Pump is trying to feed adhesive, no adhesive to feed.
Worn or damaged pump s eals
failed
Pump is trying to feed adhesive, no adhesive to feed.
Worn or damaged pump s eals
detecting an empty state without a low state
is empty
is low USB logs fulls. Data loss will occur if not downloaded.
pump maintenance counter has run out
Ensure c onnections between the ADM and hardware are secure. If a tandem system, ensure AWB 2 jumper is installed at startup. Replace AWB.
AWB 2 jumper was not in place at start up Ensure c onnections between the ADM and hardware
are secure. Replace AWB.
Adjust the drum empty level sensor to detect an empty state. Ensure the ram director valve is in the down position and s ufficient air is forcing the ram down. Melter at incorrect temperature, too low. Check setpoint and set to manufactures recommendation. Inspect pump seals and replace if necessary
Check that senso r cable is plugged into the daughter board at J16. Check for loose connection at reed switch. Ensure reed switch is securely attached to the air motor. Replace if necessary. Adjust the drum empty level sensor to detect an empty state. Ensure the ram director valve is in the down position and s ufficient air is forcing the ram down. Melter at incorrect temperature, too low. Check setpoint and set to manufactures recommendation. Inspect pump seals and replace if necessary
Make sure the empty level sensor is not covered in material Verify the low level sensor is plugged into J15 of the daughter board. Verify the low level sensor is close enough to the metal bar; adjust if necessary. Replace sensors.
Replace material container. If more material is leftover, lower the empty level sens o r. Replace at appropriate time.
Download USB data or disabl e the US B log errors on theAdvancedscreen3.
Perform pump maintenance, then reset the counter on the maintenance setup screen.
42
334129B
Page 43
Troubleshooting
Code
T1_ Low Temp. Unit
T2_ Low Temp. Unit
T3_HighTemp.
T4C#
T4M#
T4_HighTemp.
T6_
T6C#
T8V _ No Temp. Rise
V1I# Low CAN
Description Type
_Zone_
_Zone_
Unit _ Zone _
AWB Temperature Runaway Transformer AWB High Transformer Temp
Unit _ Zone _
Sensor Err. Unit _Zone_
AWB Invalid Thermistor Reading
Unit _ Zone _
Voltage, MZLP _
Cause Solution
Alarm Zone
temperature too low
Deviation Zone
temperature too low
Deviation Temperature
reading has risen too high
Alarm
Alarm
Alarm Temperature
Alarm Bad RTD
Alarm
Alarm Temperature
Alarm Bad or
Cooling fan not working or inlet is blocked/dirty Transformer Temperature is too High
reading has risen too high
Reading Transformer
thermistor temperature is incorrect
reading does not change.
overloaded power supply
Reduce ow rate. Increase temperature of accessory upstream. Faulty accessory heater measure resistance between
heater leads. Change Low Temp Alarm.
Replace accessory. Reduce ow rate. Change Low Temp Alarm. Add z one (temperature) upstream. ChangeHighTempAlarm. Verify setpoint upst ream is not hotter than this zones
setpoint. Ensure inlet and outlets are not obstructed.
Verify fan is plugged in.
Ensure inlet and outlets are not obstructed. Verify fan is plugged in.
ChangeHighTempAlarm. Verify setpoint upst ream is not hotter than this zones
setpoint. Check RTD wiring and harness/connector integrity.
Replace RTD. Verify thermister is securely connected to J7 of the
AWB. Replace transformer i f necessary.
Check fuses on MZLP connected to that Zone. Check wiring to device. Check heater res istance on device. Verify power supply voltage is 24 VDC. If voltage is
low, disconnect the power lines and re-check voltage reading. If voltage is still low, replace power supply. If voltage is correct after disconnecting the power lines.
Connect items one at a time until the voltage drops to i solate the bad module.
V1M# Low Voltage
Line AWB, Unit _
V4I# High CAN
Voltage, MZLP _
334129B 43
Deviation The voltage
to the AWB is below threshold
Alarm Bad or
overloaded power supply
Verify transformer voltage top matches incoming voltage. Verify incoming voltage is correct.
Verify power supply voltage is 24 VDC. If voltage is high, replace power supply unit.
Page 44
Troubleshooting
Code
V6M#
V8M#
WJ1
WJ2
WSUX Configuration
Description Type
Wiring Error Line MZLP _
No Line Voltage MZLP _
AWB High Line Voltage
Pump _ Solenoid is disconnected
Pump _ Solenoid High Current
Error USB
Cause Solution
Alarm Incoming
power is wired incorrectly
Alarm Incoming line
voltage is less than 100VAC.
Alarm Incoming
voltage is too high
Alarm Pump is not
turning on when it should
Alarm
Advisory
Solenoid is drawing too much current USB configuration is not loaded
Correct the Wiring.
Verify transformer has the correct tap selected. Verify CB-1 or FU-4, FU-5, and FU-6 are not
tripped/blown. Verify RCD-1 is not tripped.
Measure incoming power with system unplugged. If line voltage is less than 100 VAC, contact qualied electrician to correct the low voltage. Verify the MZLP is plugged in at J2 and the AWB is plugged in at J5 and J6. Check i ncoming voltage is correct for conguration.V4M#
Verify the transformer has the correct tap (400, 480,
600) selected. Verify harness is plugged into J13 of the daughter board. Verify it is secured to the solenoid. Replace Solenoid.
Inspect for short in harness. Inspect for a shorted solenoid cable/short to the ground. Replace solenoid.
Install software.
44
334129B
Page 45

Ram Troubleshooting

Troubleshooting
Problem
Ram will not raise or lower.
Ram raises or lowers too fast.
Air leaks around cylinder rod. Worn rod seal.
Pump will not prime properly, or pumps air.
Air pressure will not push platen out of drum.
Closed main air valve or clogged air line,
Not enough ram air pressure. Increase ram air pressure. Worn or damaged ram piston.
Platen not fully up to temperature. Wait for full temperature. Ram ai r pressure too high. Decrease ram air pressure. Dented drum has stopped platen. Fix or replace drum. Ram "up / down" air pressure too
high.
Ram ai r pressure too high. Decrease ram air pressure.Fluid squeezes past platen wipers. Worn or damaged wipers. Replace wipers. Closed main air valve or clogged air
line. Not enough air pressure. Increase air pressure.
Worn or damaged ram piston.
Ram directional valve closed or clogged.
Ram directional valve dirty, worn, or damaged.
Directional valve not in the down position.
Dented drum has stopped platen. Fix or replace drum. Closed main air valve or clogged air
line. Platen not fully up to temperature. Wait for full temperature.
Not enough blow-off air pressure. Increase blow-off air pressure. Blow-off valve passage clogged. Clean valve passage. Dented drum has stopped platen. Fix or replace drum. Wipers bonded to drum or drum liner. Lubricate wipers with high
Cause Solution
Open air valve; clear air line.
Replace piston. See instruction manual 310523.
Decrease ram air pressure.
Replace o-rings in guide sleeve. See instruction manual 310523.
Open air valve; clear air line.
Replace piston. See instruction manual 310523.
Open val ve; clear valve or exhaust.
Clean; repair valve.
Position handle in the down position.
Open air valve; clear air line.
temperature grease at every drum change.
334129B 45
Page 46
Troubleshooting

Heated Pump Troubleshooting

See pump manual for additional pump troubleshooting information. See Related Manuals, p age 7.
Problem
Rapid downstroke or upstroke (pump cavitation).
Material leaks around pump outlet. Material leaks around bleed port. Pump will not move up and down.
Leak a round pump wet-cup. Worn throat seals.
Material not heated to proper temperature.
Air is trapped in pump. Bleed air from pump. See
Downstroke: Dirty or worn pump intake valve.
Upstroke: Dirty or worn pump piston valve.
Machine is out of material Loose outlet tting. Tighten outlet tting. Loose bleed port tting. Tighten bleed p ort tting. Problem with air motor. Foreign object lodged in pump. Platen not fully up to temperature. Wait for full temperature. Valve to air motor is off. Check gauges and valves to the air
Cause Solution
Check and adjust temperature to proper set point. Wait for pump/platen to heat up.
Prime Pump, page 33.
Clean or repair. See Pump Manual.
Clean or repair.
Adjust empty level sensor.
See Air Motor Manual. Relieve press ure. See Pump Manual .
motor. Replace throat seals. See Servicing
the Throat packings in manual 334127 or 334128.

Air Motor Troubleshooting

See air motor manual for additional air motor troubleshooting information. See Related Manuals, page 7
Problem
Air m otor will not run.
Air m otor stalled. Damaged mai n air valve spool or
Air con tinuously exhausting around air m otor shaft.
Air con tinuously exhausting around air valve/slide valve.
Air continuously exhausting from muffler when motor is idle.
Icing on muffler.
Air motor soleno id is off. Wait for heat zones in use to reach
poppets.
Damaged ai r motor shaft seal. Replace air motor shaft seal. See
Air valve/slide valve gasket is damaged.
Internal seal damage.
Air motor operating at high pressure or hig h cycle rate.
Cause Solution
temperature setpoint values. Inspect and clean poppets. See Air
Motor Manual. Rebuild main air val ve. See Air
Motor Manual.
Air M otor Manual. Replace the valve gasket. See Air
Motor Manual. Rebuildairmotor. SeeAirMotor
Manual. Reduce pressure, cycle rate, or duty
cycle of motor.
46 334129B
Page 47

Repair

Replace Wipers

1. To replace a worn or damaged wiper raise the ram plate up out of the drum. Perform steps 1 through7ofChange Pail, page 3 8 .
2. Separate the wiper joint, and bend back the strapping that covers the clamp (207).
3. Unscrew the worm gear and remove the wiper (202).
4. Thread the strapping through the new wiper (202).
5. Insert the strap end through the clamp (207) and tighten.
6. Use a rubber mallet to pound the wiper around the pl aten (201) until the wiper ends are butted tightly together.
Repair
7. Apply a lubricant to the wiper (202). Use a lubricant that is compatible with the material to be pumped. Check with the material supplier.
Figure 26
334129B
47
Page 48
Repair

Replace Platen RTD

Reference Electrical Schematics, page 60 for wiring connections.
1. If the m aterial pail has already been remo ved from the supply unit, go to step 2. If you need to remove the material pail, see
Change Pail, page 38.
2. Make sure the ram plate is down and the ram hand valve is in the OFF position.
4. Remove th e front and right side pump cover.
Figure
27
5. Remove the platen RTD (616) from the platen.
6. Disconnect the platen RTD quick connect terminal (62 5 ) from J5 connector on the AWB.
7. Attach the leads from the new sensor (616) to the leads of the old sensor and pull the new sensor leads through the cable pump shield, cable track, and i nto the electric al enclosure.
To reduce the risk of injury or damage to equipment, make sure the main power switch is off before continuing with this procedure.
3. Turn main power switch off.
8. Install the new sensor (616) into the follower/tire plate after coating with non-silicone heat sink compound. Tighten compression nut. Ensure RTD is fully inserted.
9. Reconnect the quick connect terminal (625).
10. Replace the pump covers.
48 334129B
Page 49
Repair

Separate the Air Motor and Pump

Thisproceduremustbedonewiththeunitstill warm. The material and equipment will be hot!
1. If the material drum has already been removed from the supply unit, go to step 2. If you need to remove the material pail, perform steps 1 throu gh 6ofChange Pail, page 38.Pumpmustbeinthe full down position (air motor shaft fully extended).
2. Make sure the ram plate is down and the ram director va lve (CC) is in the neutral position.
6. Turn the main power switch off.
7. Disconnect all material hoses.
8. If system includes pump shield, rem ove the pump shee t metal enclosure (A). See Fig 28.
a. Remove the cover screws (B). b. Remove heater bands (HB) and disconnect
thegroundwire(R).
9. Pump must be in the full down position (air motor shaft fully extended).
10. If vent hood is installed, remove it.
11. Disconnect electrical cable from air motor (X).
12. Remove air line from air motor a n d air lines to the follower blow-off valve.
13. Remove nuts (F) from pump/air motor tie rods at the pump end.
14. Remove nuts and bolts (T) holding cable tract to air motor support plate. Slide end of cable track outboard of the mounting plate .
3. Follow Pressure Relief Procedure, page 36.
4. Bleed off excess material and pressure in the system by opening the dispense gun and catching the material in a waste container.
5. On ADM, turn off the system heat (D).
15. Remove screws and washers from pump inlet.
16. Fully loosen pump rod coupler (G) to the air motor rod.
17. Slowly raise elevator to achieve enough separation of the pump (air motor) tie rods to remove the pump.
18. Remove the pum p (P).
19. Reverse th is procedure to reinstall the new or rebuilt air motor.
334129B 49
Page 50
Repair
Figure 28

Remove Platen

50 334129B
1. Turn the m ain power switch off.
2. Disconnect the platen power wires and the ground wire from within the main control panel and pull out of conduit.
3. Removetheplatenassemblyfromtheram.
4. Reverse this procedure to reinstall the new or rebuilt platen assembly.
Page 51
Repair

Replace Heater Bands and Pump RTD

Replace Heater Band
1. If the material drum has already been removed from the supply unit, go to step 2. If you need to remove the material drum, perform steps 1 through 6 of the Change Pail, page 38.Pump must be in the full down p osition (air motor shaft fully extended).
2. Make sure the ram plate is down and the ram hand valve is in the neutral position.
3. Follow Pressure Relief Procedure, page 36.
4. Bleed off excess material in the system by opening t he applicator and catching the material in a waste container.
5. On ADM, turn off the system heat (D).
6. Turn the main power switch off.
b. Tighten the heater band. c. Re-connect heater wires and re-attach
ceramic caps that insulate terminal.
Figure 29
Replace Pump RTD
1. Turn the main power switch off.
7. Remove the pump covers.
8. Remove white cerami c caps and disconnect the electrical wires from heater band (309a, 309b).
9. Remove the screw that holds the heater band in place.
10. Remove the heater band (309a, 309b) from pump.
11. Coat the inside of the heater with non silicone heat sink compound before mounting. Maximum thickness is 0.005 in. Coat only to within 3/4 in. of vertical ends.
12. Install a new heater band (309a, 309b) in the same l ocation as the old heater band:
a. Locate heater termin als so they line up with
back of pump.
2. Remove the screws that hold the front shroud in place and remove front shroud.
3. If sensor wire is connected to electrical enclosure, disconnect it.
4. Loosen the clamp (321) holding sens or on pump.
5. Tie the leads of the new sensor (320) to the old sensor and remove the old sensor. The leads of the new sensor will be easily drawn through the conduit for reconnecting.
6. Replace the sensor (320) in clamp (321):
a. Place sensor approximately 3 counter
clock-wise from pump outlet.
b. Tighten clamp (321).
7. Re-connect s ensor wire to electrical enclosure.
334129B 51
Page 52
Repair

Replace MZLP Fuse

Each MZLP module comes with the following fuses:
J1
F1
J3
J7
J6
F10
J5
F9
F8
F7
F6
F5
J2
F4
F3
F2
3. Use a proper non-conductive f use puller tool to remove the blown fuse.
NOTICE
Using an improper tool, such as screw drivers or pliers, may break glass on fuse.
Note
F1andF2arewhiteceramicandindicate 25A on the barrel.
Note
F3-F10 are clear glass and indicate 8A on the barrel.
4. Use a proper non-conductive f use puller tool to install the new fuse
NOTICE
Using an improper tool, such as screw drivers or pliers, may break glass on fuse.
5. Close electrical enclosure.
Figure 30 Fuse Loc ations
Fuse Kit Fuse Part
24V289
To prevent system damage, alway s use fast acting fuses. Fast acting fuses are required for short-circuit protection.
1. Turn the main power switch off.
2. Open electrical enclosure door.
F1, F2
F3-F10 250VAC, 8A, fast acting, clear
Spare fuse kit included with system.
250VAC, 25A, long, white ceramic
glass
NOTICE

Replace MZLP

1. Turn the m ain power switch off.
2. Disconnect heated hose electrical connectors from MZLP (111 or 112).
3. Note location of each cable, then unplug all cables from the M ZLP (111 or 112) that will be replaced.
4. Remove four screws (115) securing MZLP (111 or 112) to electrical enclosure then carefully remove MZLP from electrical enclosure.
52 334129B
Page 53
Figure 31 MZLP Identification
5. Replace MZLP.
a. To replace MZLP #1, remove the daughter
card and standoffs, and re-install them on the new MZLP #1.
Repair
8. Reconnect cables to MZLP.
Note
Do not force the electrical connection. Minimal force is requ ired to seat the connector. If resistance is felt, stop and verify the connector orientation.
Note
If unable to determine connect or location, see Electrical Schematics, page 60.
9. Connect heated hose electrical connectors to
new MZLP.
Note
MZLP may need updated software. See
Update Software, page 59.

Table10MZLPRotarySwitch

b. To replace MZLP #2 or #33, remove the
jumper(162)fromMZLP#2or#3J5 connector and reinstall it on the new MZLP J5 connector.
6. To reas semble MZLP, Set MZLP rotary switch based on location. See
Table
.
7. Use four screws (115) to install MZLP (111 or
112) to elec trical enclosure.
MZLP Rotary Switch
MZLP
#1 with Daughter Card
#2
#3
System Rotary Switch
Primary 1 Secondary Primary 3 Secondary Primary 4 Secondary
5
6
7
334129B 53
Page 54
Repair

Replace MZLP Daughter Card

1. Turn the main power switch off.
2. Note location of each cable then unplug all cables from MZLP daughter card on MZLP#1 (112).
3. Remove four mounting screws (112b) from daughter card (112a) and set aside.
4. Unplug daughter card (112a) from the MZLP #1 (112).
5. Plug new daughter card (112a) into the MZLP (112).
6. Use screws (112b) to secure daughter card to MZLP (112).
7. Connect cables to new daughter card (112a).
Note
Do not force the electrical connection. Minimal force is required to seat the connector. If resistance is felt, stop and verify the connector orientation.
Note
If unable to determine connector location, see Electrical Schematics, page 60.
Figure 3 2 MZLP Daughter Card
54 334129B
Page 55
Repair

Replace AWB

1. Turn the main power switch off.
2. Note location of each c a ble, then unplug all cables from the AWB (205).
Note
For an AWB on a secondary system, remove connector (182) and connect to new AWB.

Replace Power Supply

1. Turn the main power switch off.
Figure 33 AWB Connections
3. Remove two screws (223) securing AWB (205) to electric al panel then carefully remove AWB.
4. Install new AWB (205) and reconnect cables.
Note
Do n ot force the electrical connecti on. Minimal force is required t o set the connector. If resistance is felt, stop and verify the connec tor orientation.
Note
See Electrical Schematics, page 60, if unable to determine the connector location.
2. Open electrical enclosure.
3. Remove power supply (208) from din rail (206). Disconnect screw terminal connections between the power supply and power supply harness.
Power Supply
Connection
V+ V+
V- V-
GND GND
LL
NN
4. Connect power supply harness to new power supply.
5. Reattach power suppl y to din rail (206).
6. Torque terminals to 4.53–6.2 in-lbs (0.50.7 N•m).
7. Close electrical enclosure door.
Harness Label
334129B 55
Page 56
Repair

Replace Fan

1. Turn the main power switch off.
2. Disconnect plug from power outlet or turn off circuit breaker for incoming power.
3. Open electrical enclosure door.
4. Remove connector from J7 connector on AWB board. Remove red (+) and black (-) fan wires from connector.
6. Remove screws (141), grill (137), four nuts (139), rear fan grill (138), and fan (136).
7. Mount new fan (136), rear fan grill (138), and nuts (139) on grill (137) with the arrow pointing toward the grill (137).
8. Tie down fan wires onto tie down locations on grill (137) using cable zip ties.
5. Cut any cable ties between the end of the fan wirestothefan(136).
9. Route fan wires into the electrical enclosure. Connect red and black fan wires to J7 connector. Reconnect J7 connector to AWB. Use cable ties to secure fan wires to other cables in electrical enclosure.
Note
To prevent fan errors on ADM, remove excess slack and ensure cabling and zip ties do not contact fan blades.
10. Reinstall fan grill (137) and close the electrical enclosure.
56 334129B
Page 57
Repair

Replace Transformer

See Fig 35, page 57.
1. Turn the main power switch off.
2. Open electrical enclosure door.
3. Disconnect incoming power harness (234) from top of trans former (235).
4. Disconnect transformer (235) output pow er harness wires (RCD-W1, -W2, -W3, -W4) from RCD-1.
5. Disconnect transformer (235) ground wire from the b ack panel ground lug.
6. Disconnect the red (+) and black (-) wire of fan from pins 4 and 3 of J7 connector on AWB (205). Disconnect J7 connector from AWB.
13. Connect transformer output power harness (234) to power terminal connections. Torque to 25–27 in-lbs (2.8–3.1 Nm).

Table 11 Transformer Output Power Harness Connections

Power Harness Wires
RCD-W1 RCD-W2 RCD-W3 Terminal 3 RCD-W4
14. Install incoming power harness (234) to top of transformer in voltage port specified on machine serial number label.
RCD-1 Connections
Terminal N Terminal 5
Terminal 1
7. Cut wire zip ties securing fan wires.
8. Remove flanged n uts (N) and transformer (235) from the back panel (201).
9. Install transformer (235) onto mounting studs on back panel (201) and secure with anged nuts (N).
10. Insert thermal sensor connector from transformer (235) onto J7 connector on AWB (205).
11.Reconnectred(+)wirefromfanintopin4and theblack(-)wireintopin3ofJ7connector.
12. Install transformer (235) ground wire onto ground lug of b ack panel (201).
15. Verify all electrical connections, including earth grounds, a re compete and tight. All connections and plugs must be connected prior to applying power.
16. Close the electrical control panel door.
17. Apply power to the machine. Turn on the main power switch.
18. Restart the s ystem.
334129B 57
Page 58
Repair
Figure 34 Inside of Electrical Control Enclosure
58 334129B
Page 59
Repair

Update Software

When s oftwa re is u pda ted on the ADM the software is then automatically updated on all connected GCA components. A status screen is shown while software is updati ng to indicate progress.
1. Turn sys tem main power switch OFF.
2. RemoveADMfrombracket.
3. Remove token access panel.
4. Insert and press software upgrade token (T) firmly into slot.
First:
Software is checking which GCA modules will ta ke the available updates.
Second:
Status of the update with approximate time until completion.
Third:
Updates are complete. Icon indicates update success/failure. See the following Icon table.
Icon Description
Update successful.
Note
There is no preferred orientation of token
T
5. Install ADM into bracket.
6. Turn system main power switch ON.
NOTICE
A status is shown while software is updating to indicate progress. To prevent corrupting the software load, do not remove token until the status screen disappears.
Note
When th e screen turns on, you will see the fol lowing screens:
Update uns uccessful.
Update complete, no changes necessary.
Update was successful/complete but one or more HCA modules did n ot have a CAN boot-loader so software was not updated on that module.
7. Remove token (T).
8. Replace token access panel.
9. Press
to continue to the operation screens.
334129B 59
Page 60

Electrical Schematics

Electrical Schematics

230V, 3 Phase/60 Hz

60 334129B
Page 61

400V, 3 Phase/50 Hz

Electrical Schematics
334129B 61
Page 62
Electrical Schematics

400–600VV, 3 Phase/60 Hz

62 334129B
Page 63

AWB and MZLP#1

Electrical Schematics
334129B 63
Page 64
Electrical Schematics

MZLP #2, MZLP#3, Overtemp, and Pump Heaters

64 334129B
Page 65

MZLP Zones

Electrical Schematics
334129B 65
Page 66

Parts

Parts

Therm-O-Flow 20 Supply Unit

66 334129B
Page 67
Therm-O-Flow 20 Supply Unit
Parts
Part Description
Ref
1 2 24W870 KIT; air control; see
3
4
5
6 7 24W812 ADM 1 8 24W589
9 10
11 101864 12 100020 13 111820
---
---
---
---
C31065 SEAL
---
---
Frame 1
Air Control Assembly
CONTROL, electrical (not used with air control only systems) MODULE, pump; see
Pump Modules
PLATEN; see
Heated Platens
KIT, light tower (optional); see Accessories and Kits,
page 87
CABLE, track BRACKET, cable track,
enclosure SCREW, cap, sch
WASHER, lock SCREW, cap, sch
Qty
1
1
1
1
1
1
1 1
4 6 6
Part Description
Ref
14 288543 15 16 112166 17 110755 18 100016 19
20 106285 21 100179 NUT, hex mscr 4 22 24V745 23
24
25
26
27
---
---
15J076 LABEL, warning,
15J074 LABEL, warning; moving
15H668 LABEL, warning; hot
15J075 LABEL, warning; hot
184090 LABEL, warning 1
BRACKET, hose, spring BRACKET, enclosure, ram SCREW, cap, sch WASHER, plain WASHER, lock BRACKET, cable track,
NXT BOLT, u
SENSOR, level, low/empty
instructions
objects, pinch
surface, splatter
surface, shock
Qty
1 1 4 8 8 1
2
1 2
4
2
2
334129B 67
Page 68
Parts

Air Control Assembly

Integrated Control For
TOF With Electrical Enclosure
Ref
51 24W870
52 121235 53 17A557
Part Description
KIT, CONTROL, air, 3 regulator; see manual 334201 SOLENOID, air motor, ram
HARNESS, solenoid, MZLP
Replacement Warning labels, signs, tags, and cards are available at no cost.
Qty
Integrated Control For
TOF Without Electrical Enclosure
Ref
54 113445
1
55 56 120375 ADAPTER, elbow, 3/4–14
1 1
Part Description
FITTING, elbow, street
121282
FITTING, swivel, straigh t
nptf x 1/2–14 npsm
Qty
1 1 1
68 334129B
Page 69

Electrical Module

Parts
334129B 69
Page 70
Parts
70 334129B
Page 71
Electrical Control Module Parts
Parts
Ref. Part Description Qty
101 103
104
105 125946 106 123967 107
108 100133 109 100307 NUT, hex 8 110 123396
111
112 24V510
112a 24R042 KIT, daugh 113
114 24P175 PLATE, blank
115 125856
116 16T440
117
118 119 100166 120 122 17A543
---
---
---
---
---
---
---
---
17C694 CAB LE, tof, lapp to souriau
---
---
ENCLOSURE, electrical 1 BUSHING, strain relief, m40
thread NUT, strain relief, m40
thread PLUG, hole, 1/2 in
KNOB, operat or disconnect PANEL, elec, transformer
(transformer assemblies only)
PANEL, elec, 400v/n
(400V modules only)
PANEL, elec, 230v
(230V modules only)
WASHER, lock, 3/8
NUT, ange, serrated, 3/8-16
MODULE, gca, mzlp w/ daughter board
MODULE, gca
(8 zone asse Qty 1) (12 zo only; Qty 2
GASKET, foam
(8 zone assemblies only; Qty 1) (12 zone assemblies only; Qty 2)
(4 Zone assemblies only; Qty2)(8zoneassemblies only; Qty 1)
SCREW, 8-32, serrated flange
CAP, souriau, uts14
(4 Zone only; Qty 2) (8 zone assemblies only; Qty 4) (12 zone assemblies only; Qty
6)
(4 Zone only; Qty 2) (8 zone assemblies only; Qty 4) (12 zone assemblies only; Qty
6)
WIRE, groun ding, door 1 NUT, full hex GASKET, hphm HARNESS, power, mzlp1,
awb
,mzlp
mblies only; ne assem blies
)
ter, board
12
Ref. Part Description Qty
123 17A544 HARNESS, power, mzlp2,
1
1
2 1 1
1
1
4
4
1
1
2 1 1
17A545
125
126
127 17A555
128 17A559
129 127511 CABLE, board, samtec
130 121226
131 121612
132 123969
134
136 24V911 FAN, 24
137 16X884 GRILL, fan
138 115836
139 127278 NUT, keps, hex
140 24V746
141 119865
142
143 24W812 ADM
144 15V551SHIELD, membran e, ADM
45121001
1
---
---
123968
---
17A547
--
awb
(8 zone assemblies only )
HARNESS, power, mzlp2/3, awb
(12 zone assemblies only)
HARNESS, pump, mzlp1, tb, tof
HARNESS, output, mzlp1, ssr, contact
HARNESS, pump, reed switch, tof
HARNESS, boar comm
(8 zone assemblies only; Qty 1) (12 zone assemblies only; Qty 2)
CABLE, can, male / female,
0.4m CONNECTOR, thru, m12,
mxf SWITCH, disconnect, 100a
SWITCH, disconnect, ph exp 100 A
(400V only)
HARNESS, disc, fuse, 230-600v
HARNESS tof
(400V on
(400V o
(400V only)
GUARD, nger
(400V only)
(400V only)
GRILL, vent
(230V and 400V assemblies only; Qty 2) (Transformer assemblies only; Qty 1)
SCREW, mach, hex serrated
-
CONTROL, air, assy; with solenoid
(Primary assemblies only)
Primary assemblies only)
(
CABLE, can, female / female 1.0m
(Primary assemblies only)
ly)
vdc,120mx120m
nly)
d, mxm,
, disc, cb, 400v/n,
1
1
1
1
1
1
1
1
1 1
1
1
1
1
1
4
4
1
1
0.1
1
334129B
71
Page 72
Parts
Part Description
Ref.
146
147 121250
148 102040 NUT, lock, hex
149 110755
150 121253 KNOB, display adj., ram
151
152 101550
153 100016
156 24V745 157 158 159 160 124654
161 121228
162 16W035 CONNE CTOR, jumper
163
---
---
---
---
---
---
BRACKET, mounting, assembly
(Primary assemblies only)
SCREW, sh cs, 1/4uncx4.25
(Primary assemblies only)
(Primary assemblies only)
WASHER, plain
(Primary assemblies only)
pkgs
(Primary assemblies only)
BRACKET, pe ndant pivot,
(Primary assemblies only)
SCREW, cap, sch
(Primary assemblies only)
WASHER, lock
(Primary assemblies only)
SENSOR, level, low/empty BUSHING, strain relief NUT, b ushing 1 GROMMET, wire CONNECTOR, splitter,
12(m) x m12(f)
(Secondary modules only)
CABLE, can, female/female,
15.0 m
(Secondary modules only)
(8 zone assemblies only; Qty 1) (12 zone assemblies only; Qty 2)
CONTACT, socket, 20-24 awg, crimp, tin
Qty
Part Description
Ref.
164
1
165
1
166 127771
1
1
167
1
168
1
169
4
170
5
172
1
181
1
1
182 17C669 CONNECTOR, jumper,
1
1
183 123856
184
3
---
---
---
---
---
196548 LABEL, warning, shock 1
---
---
17C712 TOKEN
TUBE, 1/16 shrink tube 0.13 HARNESS, input, mzlp1,
RTD BRIDGE, plug-in, 2pos,
ut16
(400V and Transformer modules only)
FERRULE, wire, 10awg
(230V modules only; Qty
2) (400V and transformer modules only; Qty 8)
FERRULE, wire, 16awg 6 FERRULE, wire, 18 awg,
long
ARTWORK, instructions, wiring, ul
FERRULE, wire, 10awg, twin
(Secondary assemblies only)
male
(Secondary assemblies only)
HARNESS, CAN, cable
(Secondary assemblies only)
(Secondary assemblies only)
Qty
1
1
6
1
3
1
1
1
Replacement Warning labels, signs, tags, and cards are available at no cost.
72
334129B
Page 73

Electrical Panel

230V 400V/N Transformer
Parts
Transformer Panel Shown
Torque terminals to 25–27 in-lbs (2.8–3.1 Nm).
1
Torque terminals to 13.3–16 in-lbs (1.5–1.8
2
N•m). Torque terminals to 4.53–6.2 in-lbs (0.5–0.7
3
N•m).
334129B 73
Page 74
Parts
230V Panel 400V/N Panel
Torque termina ls to 25–27 in-lbs (2.8–3.1 N•m).
1
Torque terminals to 13.31 6 in-lbs (1.5–1.8
2
N•m). Torque terminals to 4.53–6.2 in-lbs (0.5–0.7
3
N•m).
74
334129B
Page 75
Electrical Panel Parts
Parts
Ref.
201
202 117666 TERMINAL, ground 1 203 113783 204 100985 205 24V816 206 207 123363
208 126453 209
210 127712
211 212 126811 213 214 120399
215 123359 RELAY, contactor, 30a,
216 6690-24-
217 126818 218 126817 219 126819
220 127717
221 127718 222 223 103833 224 123452
225
Part Description
---
---
---
---
---
165
17C137 LABEL, multi safety
---
PANEL, elec, tof, 11ga, zinc
SCREW, machine, pn hd WASHER, lock ext MODULE, gca, awb RAIL,din,6.5in 1 BLOCK, terminal, ground,
10mm POWER SUPPLY, 24v
HARNESS, power supp ly, awb CIRCUIT, breaker, 63a, 4p, rcd HARNESS, rcd, awb
BLOCK, clamp end RAIL,din,19in 1 CONTROL, 65 amp,
120-600v
3p, 24vdc co FUSE, fuse block buss jt60060 BLOCK, t erminal 3-wire
COVER, end BRIDGE, plug-in,
2-position BLOCK, terminal, 2pos, ut16 COVER, end, ut16
SCREW, mach, crbh HOLDER, anc hor, wire tie,
nylon HARNESS, wire, ground, 8awg
Qty.
33 12
Ref.
226
1
227 228
1 1 1
3
230
1 1
1
1 2
231 81/0196-
1
232 17A546
1
233 17A558
3
234 17A541
7 1 1
235 24V718
3
237 128014 FILTER, voltage, transient,
1 1
238 112380 239 81/0163
240 81/0164
1
Part Description
---
---
---
81/0196- 40/11
81/0196- 60/11
6690-24- 164 127744
127745
20/11
–B/11
–B/11
HARNESS,fuse,contactor HARNESS, c ontactor, ssr HARNESS, rcd, ssr fan FUSE, class j, 40amp,
dual elmnt;
Transformer Panel only
FUSE, class j, 60amp, dual elmnt;
only
FUSE, fuse block buss jt60030 CIRCUIT, breaker, 3p, 32a, ul489;
only
CIRCUIT, breaker, 20a, 4p, ul489; FUSE, class j, 20amp, dual elmnt;
panel only
HARNESS, cb, rcd, 230-400V;
Panel only
HARNESS, cb, rcd, 400v/n; HARNESS, fuses, transformer;
panel only
TRANSFORMER, multi-tap/230v, 6kva;
Transformer panel only
600V, 3P SCREW, m ach, pn hd
WIREWAY, panduit 4
COVER, panduit
400V Panel only
400V Panel only
230V and 400V
Qty.
1 1 1 3229
400V and
3
230V Panel
3
1
230V Panel
1
3
Transformer
1
1
Transformer
1
1
2
4
Replacement Warning labels, signs, tags, and cards are available at no cost.
334129B 75
Page 76
Parts

Merkur 2200, 23:1 Pump Modules

Torque to 50–60 ft-lb (68–81 n•m).
1
Torque to 145–155 ft-lbs (196–210 n•m).
2
Coat mounting surface of sensor mounting
3
block with non-silicone heat sink compound. do not coat sensor.
Prior to tightening band clamp (321) RTD
4
sensor (320 ) must be fully contained within the
Coat inside of heater (309a, 309b) only to within
5
3/4 in of verti cal ends, with non-silicone heat sink compound before mounting.
Cap screw s (311) must be loose while tie rods
6
(307) are being torqued. Torque to 150 ft-lbs (203 nm).
7
Apply anaerobic sealant.
8
sensor mount (322).
76 334129B
Page 77
Merkur 2200, 23:1 Pump Modules
Parts
Ref. Part
301 24V530
302 155470 303
304 24X441 305 15H173 306 15H397 307 16A223 308 106166 309 120271 310 24W152
311 109211 312 17A637 315 102656 316 186925 317 184129 318 103345 319 100016 320 17F009
---
24W153 PUMP, tof200, gf; 24V575
Description
MOTOR, air, 6.0in, 4.75 strk, blue 1
FITTING, swivel, union, 90° 1 FASTENER, screw, slot hex, #8-32 tap
SWITCH, reed assy BRACKET, motor mount 1
ADAPTER, rod, pump ROD,tie,vertdriver 3 NUT, mac h ,hex 3 HEATER, pump, 600 watt
PUMP, tof200, cf; 24V572 only
only SCREW, cap, sch BLOCK, sta ndoff, mountin g MUFFLER 1 NUT, co upling COLLAR, coupling SCREW, cap, sch WASHER, lock 4 SENSOR, RTD 1
Qty
1 1
1
2
1
1 3 3
1 2 2
Ref. Part
321
C31012
322
C03507
323
C38162
324
C38163 325 326 329 103347 330 331
333 206994 334 127766
365 127671
335 17B715
336 127671
337 122338 338 214056 339 16C009
---
---
C33049
---
Description
CLAMP 1 SUPPORT, sensor 1 SCREW, machine 1 WASHER, lock, ext. tooth 1 CONDUCTOR, g round SHIELD, pu mp, tof20 VALVE, s afety, 100 psi TAPE, adhesive, fibergl ass
LUBRICANT, high temp, thermal 1
FLUID, tsl 8 oz bottle 1 FITTING, 45 elbow swivel, 1/2 npt(f) x 1/2 nps SWITCH, ov er temp, xed, 45F (232°C) SUPPORT, block, overtemperature SWITCH, ov er temp, xed, 45F (232°C)
SCREW, cap, socket bh HOSE, coupled HOOK 1
Qty
1.5
1 1 1
1
2
1
2 4 1
334129B
77
Page 78
Parts

Merkur 3400, 36:1 Pump Modules

Torque to 50–60 ft-lb (68–81 n•m).
1
Torque to 145–155 ft-lbs (196–210 nm).
2
Coat mounting surface of sensor mounting
3
block with non-silicone heat sink compound. do not coat sensor.
Prior to tighteni ng band clamp (321) RTD
4
sensor (320) must be fully contained within the
Coat inside of heater (309a, 309b) only to
5
within 3/4 in of vertical ends, with non-silicone heat sink compound before mounting.
Cap screws (311) must be loose while tie rods
6
(307) are being torqu ed. Torque to 150 ft-lbs (203 nm).
7
Apply anaerobic sealant.
8
sensor mount (322).
78 334129B
Page 79
Merkur 3400, 36:1 Pump Modules
Parts
Part Description
Ref.
301 24R015
302
C20485 FITTING, nipple, hex
303
304 24X441 305 15H173
306 15H397 ADAPTER, rod, pump 1 307 16A223 ROD, tie, vert driver 3 308 106166 NUT, mach ,hex 3 309 120271 HEATER, pump, 600 watt 2 310 24W152 PUMP, tof20, long shaft, cf;
311 109211 SCREW, cap, sch 3 312 17A637 BLOCK, standoff, mounting 3 315 102656 MUFFLER 1 316 186925 NUT, coupling 1 317 184129 COLLAR, coupling 2 318 103345 SCREW, cap, sch 6 319 100016 WASHER, lock 6
---
24W153
MOTOR,assy,air,7.5in ,blue
FASTENER, screw, slot hex, #8-32 tap SWITCH, reed assy
BRACKET, motor mount, tof 200
24V573 only PUMP, tof20, long shaft, gf; 24V576 only
Part Description
Qty
1
1 1
1 1
1
Ref.
320 17F009 321
C31012 CLAMP 322
C03507 SUPPORT, sensor 323
C38162 SCREW, machine 324
C38163 WA SHER, lock, ext. tooth 325 326 327 329 103347 330
331
333 206994 FLUID, tsl 8 oz bottle 1 334 127766
335 17B715
336 127671
337 122338 SCREW, cap, socket bh 4 338 214656 HOSE, coupled 1 339 16C009 HOOK 1
---
---
---
C33049 TAPE , adhesive, berglass;
---
SENSOR, RTD
CONDUCTOR, g round SHIELD, pump LABEL, identication VALVE, s afety, 100 psi
1.5 ft (x m) LUBRICANT, high temp, thermal
FITTING, 45 elbow, swivel, 1/2 npt(f) x 1/2 nps SUPPORT, block, overtemp SWITCH, ov er temp, xed, 45F (232°C)
Qty
1 1 1 1 1 1 1 1 1 1
1
1
1
2
334129B 79
Page 80
Parts

NXT 6500, 70:1 Pump Modules

Torque to 50–60 ft-lb (68–81 n•m).
1
Torque to 145–155 ft-lbs (196–210 nm).
2
Coat mounting surface of sensor mounting
3
block with non-silicone heat sink compound. do not coat sensor.
Prior to tightening band clamp (412) rtd sensor
4
(410) must be fully contained within the sensor
Coat inside of heater (407a, 407b) only to
5
within 3/4 in of vertical ends, with non-silicone heat sink compound before mounting.
Torque to 150 ft-lbs (203 nm).
6
Apply anaerobic sealant.
7
mount (411).
80 334129B
Page 81
NXT 6500, 70:1 Pump Modules
Parts
Ref. Part
401 N65LR0
402 120375 ADAPTER, elbow, 3/4 NPTI
403 15J288
404 17A406 405 16A223 406 106166 407 120271 408 24W152 PUMP, tof 20, cf; 24V57 4
24W153
409 C19837 410 17F009 411 C03507 412 C31012 413 186925 414 184129
Description
MOTOR, 6500, low-noise, remote 1
x1/2NPTE 1 BRACKET, mounting, motor, tof20 2
ADAPTER, rod, pump, tof ROD,tie,vertdriver 3 NUT, mac h, hex 3 HEATER, pump, 600 watt
only PUMP, tof 20, gf; 24V577 only
SCREW, cap, socket hd SENSOR, RTD 1 SUPPORT, sensor 1 CLAMP 1
NUT, co upling COLLAR, coupling
Qty
1
2
1
1 4
1 2
Ref. Part
415
C38163 416 15H297 417
C38162 418 103345 419 100016
---
420 422 24V620 423 120588 424 120012 425 120996
426
C33049 428 206994 429 17B715
430 127671
431 122338
Description
WASHER, lock, ext. tooth 1 CONDUCTOR, g round
SCREW, machine 1 SCREW, cap, sch WASHER, lock 6 LABEL, ID 1 SHIELD, pu mp, tof20 PLUG, pipe, rou nd VALVE, safety, 50 psi
LUBRICANT, high temp, thermal 1
TAPE, adhesive, fibergl ass FLUID, tsl 8 oz bottle 1
SUPPORT, block, overtemp SWITCH, ov er temp, xed, 450 2
SCREW, cap, socket bh
Qty
1
6
1 1 1
1.5
1
4
334129B 81
Page 82
Parts

Pump Shield

Ref
501 502 503 504
Part Description
---
---
---
C20474 SCREW, self-tapping
Replacement Warning labels, signs, tags, and cards are available at no cost.
COVER, p ump, bottom COVER, pump, back COVER, PUMP, front
Qty
1 1 1 6
Ref
505 506 104088 RIVET, blind 2 507
Part Description
184090 LABEL, warning 1
15J075
LABEL, safety, hot surface and shock
Qty
1
82 334129B
Page 83

President, 15:1 Pump Module

Parts
Torque to 2030 ft-lb (27–41 N•m).
1
Torque to 30–40 ft-lbs (41–54 Nm).
2
334129B 83
Page 84
Parts
Ref.
551 288505 PUMP, president 1 551a 24B229 551b 551c
551d 198369 551e 100340 NUT 3 551f 551g 298073 ADAPTER, pump 1 551h 156082 551j 112166 551k 100016 551m 207370 551n 198412 551p 551r 101946 PIN, cotter, sst 2 551s 206994 552 112756 553
554
Part Description
MOTOR, AIR, president
---
---
100133
C38225 PACKING, o-ring
---
196548 LABEL, warning, shock 1
PUMP, hot melt mini-5 1 PLATE, president
mounting ROD, standoff
WASHER, lock, 3/8
PACKING, o-ring, 112 SCREW, cap, sch WASHER, lock ROD, connecting ROD, connecting
FLUID,TSL,8oz SCREW, cap, socket hd BRACKET, mounting,
junction box,
Qty
Ref.
555 556 100179 NUT, hex mscr 2
1
557
1
558
3
559 516587
3
560 154628 561 101015
2
562
2
563
2
564 155470
1
565 100016
1
566 103345
1
567
1
568 127732
4 2
569 214656
Part Description
100020
---
---
C19187
---
---
WASHER, lock
JUNCTION BOX, front cover FASTENER, thread-cutting screw BOLT,3/4-10x1.5hex head WASHER
WASHER,lock NUT, hex 1 ADAPTER 1 FITTING, swivel, union,
90 degree WASHER, lock
SCREW, cap sch JUNCTION BOX, main
body FITTING, 3/ 4 " knockout, romex, pushin HOSE, coupled, 61209, 10 ft
Qty
2
1
2
1
2 1
1
6 6 1
1
1
Replacement Warning labels, signs, tags, and cards are available at no cost.
84 334129B
Page 85

Heated Platens

24V742, Heated Drum Platen, Smooth Bottom (Code E- option S) 24V743, Heated Drum Platen, Standard Finned Bottom(Code E- option F)
Parts
Coat RTD sensor (616) with non-silicone heat
1
sink com pound. Coat from tip to 1 in from tip. Label cables for identification. See Cable
3
Identification Do not tighten heater terminal nuts down onto
4
ceramic insulators to prevent damage.
Coat botto m of overtemperature switch (627)
8
with non-si licone heat sink compound. Label the wires on overtemperature switch
9
(627) 2732. 2740 at the opposite end of the sensor.
334129B 85
Page 86
Parts
Ref
601 PLATEN see table
602 603 207440 VALVE, dispenser 1 604 288855 HANDLE, bleed 1 605 606 514930 607 608 609 167730 610 100176 611 115948
612 115949
613
614
615
616 15K032
Part Description
below
C31052 HOSE, seal, Mini - 5
---
C31154 CLAMP, worm gear
---
---
---
---
ADAPTER, bushing 1 SCREW, cap, skt hd
PLATE, designation 1 GASKET, copper BUSHING, hex ELBOW, 1/4 npt(m), 5/16
OD tube ELBOW, 1/4npt(m), 5/32 OD tube TUBE, PTFE, 1/4 x 5/16; 14 ft (4.2 m) TUBE, PTFE, 3/32 x 5/32; 14 ft (4.2 m) CONDUIT, hi-temp, w/ ttings SENSOR, RTD, temp, w/connector
Qty
Ref
617
1
618
1
619 620 102931 NUT, mach. hex 4 621
3
623
2
624 625 17F011
1 1
626 100508
1
627 127671 628 122338
1
629 127689
1
630 127690
1
631 9704-03
1
632
1
Part Description
C38163 WAS HER, lock, ext. tooth
C19049 SCREW, mach, slotted,
rnd hd
15C171 GASKET
---
---
---
---
WASHER, lock, internal tooth CONDUCTOR, heater
CONDUCTOR, ground CONDUCTOR, RTD, temp
w/ connector SCREW, drive
SWITCH, overtemp, fixed SCREW, cap, socket, bh FITTING, adapter, 1/4 in x
5/32 in tube FITTING, adapter, 5/16 in tube x 1/4 in tube HOSE,tubing;1/4inOD; 17 ft (5 m) LUBRICANT, high temperature, thermal
Qty
1 1
1
4
4 1 1
2 1 2 1
1
1
1
Parts included in Seal Kit C31065 (purchase separately).
Platen Model Plate (601) Description Qty. Element Resistance
24V742 Standard Finned 1 28.8 ohms +3/-4 24V743 Smooth Bottom 1 28.8 ohms +3/-4
86 334129B
Page 87

Accessories and Kits

Accessories and Kits

Wiper Kits

Part No. Description
C31065 Seal Kit

Applicators and Dispense Valves

Part No. Description
249515 249514 249513
249512

Air-Operated Heated Dispense Valves

Part No. Description
243694 Automatic Dispense Valve, 240V,
244951 Automatic Endure Dis pense Valve,
244909 Automatic Endure Dis pense Valve,
243701
Manual Gun, Top Feed, 240V Manual Gun, Bo ttom Feed, 240V Manual Gun, Top Feed, Electric Switch,
240V Manual Gun, Bottom Feed, Electric Switch, 240V
Air-Operated Heated Dispense Valve
240V, Air-Operated High Flow Heated Dispense Valve
240V, Air-Operated Snuff-Back Heated Dispense Valve 45 in (114 cm) Distribution Header With Valve, 240V
Part No. Description
243657
243697
289208
51:1 Heated Pressure Compensator Valve, 240V Heated Distribution Manifold, 240V
Includes (2) 3/4 npt(f) inlet check valves, (1) npt 4–ported manifold, (2) 1 in npt(f) outlet gate valves, mounting bracket, 400w 230 VAC heaters, RTD sensor, and 8 pin connec tor box.
Compact Heated Regulator

Accessory Extension Cables

Use to connect uid control devices and heated hoses to the electrical control enclosure.
Part No. Description
Connect between controller and heated hose 196313 15ft,16pinto16pin 196314 25 ft, 16 to 16 pin Connect betwe en controller and heated accessory 196315 15 ft, 16 pin to 8 pin 196316 25 ft, 16 pin to 8 pin Connect between controller and heated devices 196317 15 ft, 16 pin to (2) 8 pin 196318 25 ft, 16 pin to (2) 8 pin

Light Tower Kit, 24W589

Tie Rod Kits

Flow Control and Manifolds

Part No. Description
243700
243656
334129B 87
Heated Air Operated Mastic Pressure Regulator, 240V 23:1 Heated Pressure Compensator Valve, 240V
UsetoretrotCheck-Mate800DisplacementPump to an existing Therm-O-Flow syst em.
Part No. Description
24V750
24V754
Bulldo and Senator® Tie Rod Kit; see manual 334131 NX Tie Rod Kit; see manual 334132
Page 88
Accessories and Kits

Heated Hoses and Fittings

Hose Diameter
Hose Length
3ft(1.5m) 6ft(1.8m) 10 ft (3 m) 15 ft (4.6 m) 20 ft (6 m) 25 ft (7.6 m) 30 ft (9 m)
Pump Fittings
TOF 20/2 00 PUMP 1-11 1/2 DUAL OUTLET ADD 120263 TOF MINI 5 PUMP 1/2 NPT DUAL OUTLET ADD 120241
Hose to Hose Fittings
-6 Hose (.308 ID)
-8 Hose
-10Hose(.495ID)
-12Hose(.617ID)
-16 H
-20Hose(1.125ID)
(.401 ID )
ose (.687 ID)
-6 (9/16in-18 JIC)
None None None None 115902 115875 None 115884 None 16J875 115873 115876 115880 115885 117821 None 115874 115877 115881 115886 117822 None None 115878 115882 115887 None None None 115879 115883 115888 None None None 121200 None None None
16V432
100380
16V432 C20678 C20679 C38006 6301-85
125778 123684 123683
123684 120241 120242 120244
123683 120242 120243 120246 123683
120265 123683 120265 120267
None
-8 (3/4 in -16 JIC)
253267 253268 120260 120261 120262
120244 120246 120247 120248
120244 120267
6308-82
126521
-10 (7/8 in -14 JIC)
120246 120267
120246 120267 120268
-12 (1-1/16 in
-12 JIC)
15C586
123683 120265
120248 120249
123135 126521
-16 (1-5/16 in
-12 JIC)
None None
123683 120265 120267 120244 120267 120246 120267
120249 120268
-20 (1-5/8 in -12 JIC)
6308-85
120268
None
6308-82
126521
6308-82
126521 123135 126521
120249 120268
120250
88 334129B
Page 89
Accessories and Kits
Hose Diameter
Fittings
Compensator 51:1, 243657 Compensator 23:1, 243656 Inlet & Outlet: 1-11 1/2 in NPTF Distribution manifold, 243697 Inlet: 3/4 in NPTF Distribution manifold, 243697 Outlet: 1-11 1/2 in NPTF Compact Heated Regulator, 289208 Inlet & Outlet: 3/8 in NPTF Mastic Regulator, 243700 Inlet & Outlet: 3/4 in NPTF Top and bottom feed guns with and without switch, 249512, 2 49513, 249514, 249515 Inlet: 7/8-14 (JIC -10) male Standard, High Flow & Snuff-back Dispense valves, 243694, 244951, 244909 Inlet: 1/2 NPTF Distribution header, 243701 Inlet: 1/2 NPTF Precision Gear Meter PGM Inlet: 1-5/16-12 o-ring face seal Precision Gear Meter PGM Outlet: 3/4 NPTF PCF Metering System Inlet & Outlet: 3/4 NTPF
-6 (9/16in-18 JIC)
16V432 100380
16V432 100896
16V432 100380
16V432 100896
16V432 100896
117677 120264 None 120265 None None
16V432 124287
16V432 124287
None None None 124238 124239 124240
16V432 100896
16V432 100896
-8 (3/4 in -16 JIC)
6308-82
124286 15Y934 C20708 125661
6308-82
121311 116765 116766
124286 15Y934 C20708 125661
124286 15Y934 C20708 125661
124286 15Y934
-10 (7/8 in -14 JIC)
123135 120266
123135 120266
C20768
C20768
-12 (1-1/16 in
-12 JIC)
123135 123854 15D936
123135 123854 15D936
94/1027/99 125662
94/1027/99 125662
C20708
-16 (1-5/16 in
-12 JIC)
116766 120267
125661
-20 (1-5/8 in -12 JIC)
125661 120268
116766 120267 120268
125661 120268
125662 120268
125662 120268
125661 120268
125661 120268
334129B 89
Page 90
Accessories and Kits

8 Channel Upgrade Kit, 24V755

Use this kit to upgrade a 4 Channel system to a 8 channel system.
Part Description
Ref
1 2 125856
3 16T440 4 127511 5 16W035
MODULE, GCA, MZLP SCREW, 8–32, serrated
ange CAP, s ouriau, UTS14
CABLE, board, samtec CONNECTOR, jumper
Qty
1 4
2 1 1
Part Description
Ref
6 17A544
7 112190 8
17C712 TOKEN, software upgrade
9
17C694 CABLE, TOF, LAPP to
HARNESS, power, MZLP2, AWB STRAP, wrist, grounding
souriau
Qty
1
1 1 2
90 334129B
Page 91
Accessories and Kits

8 Zone Upgrade Kit Installation

1. Disconnect plug from power outlet or turn off circuit breaker for incoming power.
2. Place grounding wrist strap (7) over your wrist and secu re other end to a grounded surface.
3. Set the ki t’s MZLP (1 ) rotary switch to “3” on a primary sy stem or 6” on a secondary system.
4. Remove screws (B), remove plate (A), and gasket (C) from system. Use screws (2) to i nstall MZLP (1) onto system as shown.
Note
The new MZLP (1) will be referred to as MZLP 2, and the original MZLP that came with the system will be referred to as MZLP 1.
5. Open the elec trical enclosure door.
Note
Do not force the electrical connection. Minimal force is requ ired to seat the connector. If resistance is felt, stop, and verify the connector orientation.
6. Connect cable (4) to J3 connector on MZLP 1 andJ6connectoronMZLP2.
7. Connect powe r harness (6) to MZLP 2 connector J2 and J5 connector on AWB. Install jumper (5) on the MZLP 2 J5 connector
8. Use ttings and hoses that meet yourhoserouting needs. See Accessories and Kits, page 87.
9. To ensure your system has the latest software, insert token (8) into the ADM. See
Update Software, page 59.
334129B 91
Page 92
Accessories and Kits

12 Channel Upgrade Kit, 24V756

Use this kit to upgrade a 8 channel system to a 12 channel system.
Part Description
Ref
1 2 125856
3 16T440 4 127511 5 16W035
MODULE, GCA, MZLP SCREW, 8–32, serrated
ange CAP, s ouriau, UTS14
CABLE, board, samtec CONNECTOR, jumper
Qty
1 4
2 1 1
Part Description
Ref
6 17A545
7 112190 8
17C712 TOKEN, software upgrade
9
17C694 CABLE, TOF, LAPP to
HARNESS, power, MZLP2/3, AWB STRAP, wrist, grounding
souriau
Qty
1
1 1 2
92 334129B
Page 93
Accessories and Kits

12 Zone Upgrade Kit Installation

1. Disconnect plug from power outlet or turn off circuit breaker for incoming power.
2. Place grounding wrist strap (7) over your wrist and secu re other end to a grounded surface.
3. Set the ki t’s MZLP (1 ) rotary switch to “4” on a primary sy stem or 7” on a secondary system.
4. Remove screws (B), remove plate (A), and gasket (C) from system. Use screws (2) to i nstall MZLP (1) onto system as shown.
Note
The new MZLP (1) will be referred to as MZLP 3, and the other two that came with the system will be referred to as MZLP 1 and MZLP 2.
5. Open the elec trical enclosure door.
Note
Do not force the electrical connection. Minimal force is requ ired to seat the connector. If resistance is felt, stop, and verify the connector orientation.
6. Connect cable (4) to J3 connector on MZLP 2 and J6 connector on MZLP (1). Remove existing power cable from MZLP 2 J2 and AWB J5 connector.
7. Connect power harness (6) to MZLP 2 and MZLP 3 J2 connector and J5 connector on AWB. Install
8. See Install Heated Hose , to connect a heated hose or uid c ontrol device.
9. To ensure your system has the latest software, insert token (8) into the ADM. See
Update Software, page 59.
334129B 93
Page 94

Appendix A— ADM

Appendix A— ADM

General Operation

ADM Power
The ADM automatically turns on when the main power switch is turned on.
Screen Navigation
To switch between the Setup and Operation screens, press
screens.
. Use the keypad to navigate between
Enable, Disable Heating System
To enable or disable the entire heating sy stem, press
the heating system is enabled, use the Heat-A and Heat-B Setup screens.
. To set which channels are active when
94 334129B
Page 95

Icons

Appendix A— ADM
Screen Icons
These are frequently used icons on the screens. The f ollowing descriptions ex plain what each icon represents.
Icon Description
Primary System= A Secondary System = B
Heating Disabled
Warm Up, Actual temperature is outside of Target Temperature
Reached Target Temperature
Hose Gun Manifold
PGM
Softkey Icons
The fo llowing icons appear in the ADM, directly to theleftorrightofthesoftkeywhichactivatesthat operation.
Icon Function
Pause Material Tracking
Continue Material Tracking
Pump Ready
Setback
Reset Cycl (press an
Add or edit event
Accept sc
Crossov
e Counter
dhold)
hedule
er for Tandem Systems
Flow Me Pressure Regulator
Other
Advisory. See Error Codes for more information.
Deviation. See Error Codes for more information
Alarm. See Error Codes for more information
ter
Erase or canc el schedule
Cancel
Clear
Schedule Event On/Off
Heat On/Off
334129B 95
Page 96
Appendix A— ADM

Operation Screens

Home
This screen shows the temperature state of the system and material usage.
Note
If present, secondary systems will be shown on the home page.
Color A and B Zone Status
Yellow
Green/Yellow Flashing
Outside of advisory range Warmup
Events
The Events screens store a maximum of 200 events. The events list can be downloaded in the USB logs. See Appendix B USB Data, page 102.
Heat-A
This screen shows the target and actual temperatures for all zones on the system.
Note
The Heat-B screen shows information for an optional secondary system.
Color A and B Zone Status
White Green On and at set point
Red Outside of alarm range
Off
temperature
Tracked Events
Custom Language Downloaded Custom Language Uploaded Fill Valve Closed Fill Valve Open Heat Off Heat On Logs Downloaded Pump Cycles Total Reset Pump Off Pump On RedStopButtonPressed Setup Value Changed System Power Off System Power On System Settings Downloaded System Settings Uploaded USB Disabled USB Drive Inserted USB Drive Removed User M aintenance Count Reset
96 334129B
Page 97
Errors
The Errors screens store a maximum of 200 errors. See Error Codes. Download the errors list in the USB logs. See Appendix B USB D ata, page 102.
Appendix A— ADM
CAN:
24 VDC power supply voltage reading (18–28
VDC)
DI:
System Digital Inputs 0: Drum Empty 1: Drum Low 2: Pump Cycle Switch Up 3:PumpCycleSwitchDown
DO:
System Digital Outputs 0: Pump Solenoid 1: Not Used 2: Not Used 3: Not Used
ISO DI:
See Connect PLC, page 27.
Customer Digital Inputs
Diagnostic-A
This screen shows details of various items to aid in troubleshooting the system. This screen can be hidden b y de-selecting Enable Diagnostics Screen on the System 3 screen. The ow rate up dates every 15–20 seconds with average ow rate over the last 15–20 seconds.
Note
Diagnostic-B shows information for an optional secondary system.
ISO DO:
See Connect PLC, page 27.
Fan:
Heat Soak:
has reached set temperature.
Life Cycles:
system
MZLP 1:
32–160°F(0–71°C)
Pump Sol:
(0 mA - off)
(150-250 mA - on)
Pump CPM: USB DL%:
downloading USB data. 5 downloads will occur.
Weight:
system
XFMRTemp:
temperature sensor
Customer Digi tal Outputs
current to fan
set time for platen to heat after the platen
total number of pump cycles over life of
temperature on MZLP 1
Current draw of pump solenoid
Pump cycles per minute.
Percentage complete, only applies whe n
Weight of material dispensed over life of
Temperature of transformer
The following information is displayed.
Diagnostic Data
ACurrent Draw B RTD Reading
uty Cycle
CD
334129B 97

Setup Screens

Note
It is important to se t all settings in the System screens correctly to ensure optimal system performance.
Page 98
Appendix A— ADM
Password
If the password is not “0000”, the pas sword must be entered to access the setup screens.
System 1
Pump Inactive Timeout:
detected or either pump for (x) am ount of time, all heated zones enter setback mode. After an additional amount of time (x), the heat will turn off.
(x) R ange: 0–120 minutes
0 disables heat soak
If no pump movement is
System 2
Enter low and high temperatures for an alarm or warningtooccur.
External Pump Control:
automatically turns on and off the pump when using a han dheld dispense gun with an integrated trigger switch.
Enable Diagnostic Screen:
the Diagnostic screen .
Enable Temp. Adjustments:
adjustments on the Heat-A and Heat-B Run screens.
Enable Pump Autostart:
pump on after reaching setpoint temperature and heat soak is complete.
Enable Tandem System:
system ADM screens.
Heat Soak:
reached their target temperatures. Pump cannot turn on un til timer is complete. The heat soak is a user-defined time.
Range: 0–120 minutes
Time for to preheat after all zones have
Enable feature that
Choose whether to show
Allows temperature
Automatically turns the
Enable all secondary
Advanced 1
Language: Date Format: Date: Time: Enter Password:
be password protected.
Screen Saver:
amount of time.
Language d isplayed on the screen.
Choose format of the date.
Set the date.
Set the time.
If not 0000”, the Setup screens will
The scree n will go black after the set
0 disables heat soak
98 334129B
Silent Mode:
Disable ADM sounds.
Page 99
Appendix A— ADM
Advanced 2
Temperature Units:
temperatures.
Mass Units:
Specic Gravity:
dispensed to mass dispensed for tracking the total weight and ow rate. When the specific gravity value is popul ated, the total mass dispensed since the last total weight reset is shown on the Home screen and the mass ow rate is shown on the Diagnostic screen.
Units of measure for mass.
Units of measure for display ed
Required to convert the volume
Disable USB Downloads/Uploads:
the USB for downloading and uploading.
Disable USB Log Errors:
will not warn the user when logs are full. If the logs are full, the oldest data will be overwritten.
Download Depth: Last ___ Days:
will provide data as old as the number of days entered. Old data may be in memory but will not be downloaded if older than the number of days entered.
When dis abled, the system
Disables use of
The USB download
Advanced 4 and 5
Note
If the Specic Gravity is set to zero, the Home screen will display a cycle counter instead of gram s or pounds.
Advanced 3
Advanced 4 screen shows the part number and version of each installed software module on a primary unit and Advanced 5 shows each module on a secondary unit.
334129B 99
Page 100
Appendix A— ADM
Heat-A
Use these screens to set target and setback temperatures for the pump, platen, and zones. Select which system needs to use the heated accessory.
Zone Types:
•Hose
•Gun
•PGM
•Flowmeter
Pressure Regulator
•Manifold
Other
Note
To ensure accurate hose and gun temperatures,sethoseaszone1,3,5,7,9, or 11 whe n cable 17C694 is connected to MZLP a nd a heated hose.
100 334129B
Loading...