Graco 334014A User Manual

Operation
Husky ™ 1050HP 2
Air-Operated
1–inch high-pressure pump with modular air valve for fluid transfer applications. For professional use only.
Important Safety Instructions Read all warnings and instructions in this manual and in your Repair/Parts manual. Save these instructions.
Maximum F 200 psi (1
Maximum A 100 psi (
luid Working Pressure:
.38MPa,13.8bar)
ir Input Pressure:
0.69 MPa, 6.9 bar)
Diaphragm Pump
:1
334014A
EN
PROVEN QUALITY. LEADING TECHNOLOGY.
Contents
Related Manuals ................................................ 2
Ordering Information........................................... 3
Configuratio
Warnings ........................................................... 5
Installation.......................................................... 8
Tighten Fasteners Before Setup.................... 8
Mounting ..................................................... 8
Grounding ................................................... 8
Air Line........................................................ 9
Air Exhaust Ventilation ................................. 10
Fluid Supply Line ......................................... 11
Fluid Outlet Line........................................... 11
Fluid Inlet and Outlet Ports ........................... 11
Typical Floor Mount Installation..................... 12
Operatio
Pressure
Relate
Manual No. Description
n Number Matrix ............................... 4
n........................................................... 13
Relief Procedure............................ 13
d Manuals
Tighten Fasteners Before Setup.................... 13
Flush the Pump Before First Use .................. 13
High/Low Lever............................................ 13
Start and Adjust the Pump ............................ 14
Pump Shutdown .......................................... 14
Maintenance ...................................................... 15
Maintenance Schedule................................. 15
Lubrication................................................... 15
Tighten Threaded Connections ..................... 15
Flushing and Storage ................................... 15
Torque Instructions ...................................... 16
Dimension
Performance Charts............................................ 18
Technical Data ...................................................20
Graco Sta
s and Mounting................................... 17
Fluid Temperature Range............................. 21
ndard Husky Pump Warranty................ 22
334390
NOTE: Repa
For Troubleshooting information, see the
ir/Parts Manual 334390.
Husky
1050HP Air-Operated Diaphragm Pump, Repair/Parts
2
334014A
Ordering Inform
ation
Ordering Info
To Find Your Ne
1. Visit www.graco.com.
2. Click on Where to Buy and use the Distributor Locator.
rmation
arest Distributor
To Specify the Configuration of a New Pump
Please call your distributor.
To Order Replacement Parts
Please call your distributor.
Distributor N
1. To find part numbers for replacement parts:
a. Use the 20–di
on the pump.
b. Use the Confi
next page to described b
c. Use the Rep
main Parts Quick Refe on these tw informati
2. Please ca
ote
git number from the ID plate
guration Number Matrix on the
understand which parts are
y each digit.
air/Parts Manual. Refer to the
illustration and to the Parts/Kits
rence. Follow the page references
o pages for further ordering
on, as needed.
ll Graco Customer Service to order.
334014A 3
Conguration Nu
mber Matrix
Configuration
Check the identification plate (ID) for the 20–digit Configuration Number of your pump. Use the following matrix to define the components of your pump.
Sample Configuration Number:
Number Matrix
1050HP A01A A1 SS SP SP
Pump Model
Pump
1050HP
Aluminum
Check Valve Seats Check Valve Balls
316 Stainless Steel
SS
Center Section and Air Valve
Center Section and Air Valve Material
Aluminum
Manifolds Seats
A01A
SP
Santoprene
Air Valve
Standard
Balls Diaphragms
Manifolds
A1
A2
S1
S2
Diaphragm Material
SP
PT
Manifold O-Rings
Aluminum, standard ports, npt
Aluminum, standard ports, bsp
Stainless steel, standard ports, npt
Stainless steel, standard ports, bsp
Manifold O-Rings
Santoprene
PT
PTFE
4
334014A
Warnings
Warnings
The following exclamation p risks. When th Warnings. Pr the body of th
warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The oint symbol alerts you to a general warning and the hazard symbols refer to procedure-specific
ese symbols appear in the body of this manual or on warning labels, refer backtothese
oduct-specific hazard symbols and warnings not covered in this section may appear throughout
is manual where applicable.
WARNING
FIRE AND EXPLOSION HAZARD
Flammable prevent fir
• Use equipment only in well ventilated area.
• Eliminat plastic d
• Keep work area free of debris, including solvent, rags and gasoline.
• Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes are present.
•Grounda
• Use only grounded hoses.
• Hold gun firmly to side of grounded pail when triggering into pail. Do not use pail liners unless they are antistatic or conductive.
• Stop op equipm
• Keep a working fire extinguisher in the work area.
• Route exhaust away from all ignition sources. If diaphragm ruptures, fluid may be exhausted with air.
fumes, such as solvent and paint fumes, in work area can ignite or explode. To help
e and explosion:
e all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and
rop cloths (potential static arc).
ll equipment in the work area. See Grounding instructions.
eration immediately if static sparking occurs or you feel a shock. Do not use
ent until you identify and correct the problem.
PRESS
Fluid from the equipment, leaks, or ruptured components can splash in the eyes or on skin and cause serious injury.
• Follow the Pressure Relief Procedure when you stop spraying/dispensing and before
• Tighten all fluid connections before operating the equipment.
•Che
334014A 5
URIZED EQUIPMENT HAZARD
cleaning, checking, or servicing equipment.
ck hoses, tubes, and couplings daily. Replace worn or damaged parts immediately.
Warnings
WARNING
EQUIPMENT MISUSE HAZARD
Misuse can ca
• Do not operate the unit when fatigued or under the influence of drugs or alcohol.
• Do not exceed system compo
• Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information about your material, request MSDS from distributor or retailer.
• Do not leave the work area while equipment is energized or under pressure.
•Turnoffal
• Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
• Do not alter or modify equipment. Alterations or modifications may void agency approvals and create safety hazards.
•Makesure
• Use equipment only for its intended purpose. Call your distributor for information.
• Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
• Do not ki
• Keep children and animals away from work area.
• Comply with all applicable safety regulations.
THERMA
Fluids subjected to heat in confined spaces, including hoses, can create a rapid rise in pressure due to the thermal expansion. Over-pressurization can result in equipment rupture and serious injury.
use death or serious injury.
the maximum working pressure or temperature rating of the lowest rated
nent. See Technical Data in all equipment manuals.
l equipment and follow the Pressure Relief Procedure when equipment is not in use.
all equipment is rated and approved for the environment in which you are using it.
nk or over bend hoses or use hoses to pull equipment.
L EXPANSION HAZARD
• Open a valve to relieve the fluid expansion during heating.
• Replace hoses proactively at regular intervals based on your operating conditions.
TIC PARTS CLEANING SOLVENT HAZARD
PLAS
Many solvents can degrade plastic parts and cause them to fail, which could cause serious injury or property damage.
• Use only compatible water-based solvents to clean plastic structural or pressure-containing parts.
•SeeTechnical Data in this and all other equipment instruction manuals. Read fluid and solvent manufacturer’s MSDSs and recommendations.
6 334014A
WARNING
TOXIC FLUID OR FUMES HAZARD
Warnings
Toxic fluids o inhaled, or s
• Read MSDSs to know the specific hazards of the fluids you are using.
• Route exhaus the air.
• Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
BURN HAZAR
Equipment surfaces and fluid that’s heated can become very hot during operation. To avoid severe burns:
• Do not touch hot fluid or equipment.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective equipment includes but is not limited to:
•Protect
• Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer.
r fumes can cause serious injury or death if splashed in the eyes or on skin,
wallowed.
t away from work area. If diaphragm ruptures, fluid may be exhausted into
D
ive eyewear, and hearing protection.
334014A
7
Installation
Installation
The Typical Fl only a guide fo components. C assistance i
oor Mount Installation, page 12,is
r selecting and installing system
ontact your Graco distributor for
nplanningasystemtosuit your needs.
Tighten Fasteners Before Setup
Before usin and retorqu
Torque Ins
operation
g the pump for the first time, check
e all external fasteners. Follow
tructions, page 16. After the first day of
, retorque the fasteners.
Mounting
• The pump exhaust air may contain contaminants. Ventilate to a remote area. See Air Exhaust Ventilation, page 10.
• Never move or lift a pump under pressure. If dropped, the fluid section may rupture. Always follow the Pressure Relief Procedure, page 13, before moving or lifting the pump.
Grounding
The equipment must be grounded to reduce the risk of static sparking. Static sparking can cause fumes to ignite or explode. Grounding provides an escape wire for the electric current.
Pump:
one end of a 12 ga. minimum ground wire (R) behind the grounding screw and tighten the screw securely. Connect the clamp end of the ground wire to a true earth ground. A ground wire and clamp, Part 238909, is available from Graco.
Loosen the grounding screw (GS). Insert
1. Be sure the mounting surface can support the weight of the pump, hoses, and accessories, as well as the stress caused during operation.
2. For all mountings, be sure the pump is bolted directly to the mounting surface. Mount the pump horizontally, with the feet at the bottom of the pump. Do not mount the pump on a vertical surface, such as a wall.
3. For ease of operation and service, mount the pump so air valve, air inlet, fluid inlet and fluid outlet ports are easily accessible.
Figure 1 Grounding Screws and Wires
8 334014A
Installation
Air and fluid hoses:
with a maximum of 500 ft (150 m) combined hose length to ensure grounding continuity.
Air compressor:
recommendations.
Fluid supply container:
Solvent pails used when flushing:
local code. Use only conductive metal pails placed on a grounded surface. Do not place the pail on a nonconductive surface, such as paper or cardboard, which interrupts the grounding continuity
Check your s initial in for checki is maintai
ystem electrical continuity after the
stallation, and then set up a regular schedule
ng continuity to be sure proper grounding ned.
Use only grounded hoses
Follow manufacturer’s
Follow your local code.
Follow your
Air Line
See Typic
1. Install an air filter/regulator (C). An air line filter
al Floor Mount Installation, page 12
removes harmful dirt and moisture from the compressed air supply. Use the regulator and
gauge to control the fluid pressure. The fluid stall pressure will be the same as the setting of the air regulator.
2. Locate a bleed-type master air valve (B) close to the pump and use it to relieve trapped air. Be sure the valve is easily accessible from the pump and located downstream from the regulator.
Trapped air c unexpectedl injury from
3. Locate another master air valve (E) upstream from all air line accessories and use it to isolate them during cleaning and repair.
4. An adjustable inlet air valve or needle valve (G) my be installed for pump speed control.
5. Install a grounded, flexible air hose (A) between the accessories and the 3/4 npt(f) pump air inlet (D). Use a minimum 5/8 in. (16 mm) ID air hose.
an cause the pump to cycle
y, which could result in serious
splashing.
334014A 9
Installation
Air Exhaust Ventilation
The air exhaust port is 3/4 npt(f). Do not restrict the air exhaust port. Excessive exhaust restriction can cause erratic pump operation.
To provide a remote exhaust:
1. Remove the muffler (T) from the pump air exhaust port.
2. Install a grounded air exhaust hose (U). Connect the muffler (T) to the other end of the hose. The minimum size for the air exhaust hose is 3/4 in. (19 mm) ID. If a hose longer than 15 ft (4.57 m) is required, use a larger diameter hose. Avoid sharp bends or kinks in the hose.
3. Place a container at the end of the air exhaust line to catch fluid in case a diaphragm ruptures. If the diaphragm ruptures, the fluid being pumped will exhaust with the air.
Figure 2 Vent exhaust air
KEY
A Air supply line
B Bleed-type master air valve T
C Air filter/regulator
D Air inlet V
E
Master air valve (for accessories)
G Optional needle valve for pump speed
adjustment.
Muffler
U
Grounded air exhaust hose
Container for remote air exhaust
10 334014A
Installation
Fluid Supply L
See Typical Floor Mount Installation, page 12
1. Use grounded fl See Groundin
2. If the inlet fl than 25% of th check valves in inefficie
3. Excessive i diaphragm l
0.03 MPa, 0 for most ma
4. For maximu
Technical
always ins the mater
ine
exible, fluid supply hoses (G).
g, page 8 .
uidpressuretothepumpismore
e outlet working pressure, the ball
will not close fast enough, resulting
nt pump operation.
nlet fluid pressure also will shorten
ife. Approximately 3 - 5 psi (0.02-
.21-0.34 bar) should be adequate
terials.
m suction lift (wet and dry), see
Data, page 20. For best results,
tall the pump as close as possible to
ial source.
Fluid Outlet L
See Typical Floor Mount Installation, page 12.
1. Use grounded,
Grounding, p
2. Install a flui
3. Install a shu
ine
flexible fluid hoses (L). See
age 8 .
d drain valve (J) near the fluid outlet.
toff valve (K) in the fluid outlet line.
Fluid Inlet and Outlet Ports
NOTE: Remo change the
Torque Ins
1050HP — Aluminum Manifolds
The fluid inlet and outlet manifolds each have two 1 in. npt(f) or bspt threaded ports (M, N). Close off the unused port using the supplied plugs.
1050HP —
The fluid inlet and outlet manifolds each have one 1 in. npt(f) or bspt port.
ve and reverse the manifold(s) to
orientation of inlet or outlet port(s). Follow
tructions, page 16.
Stainless Steel Manifolds
334014A
11
Installation
Typical Floor Mount Installation
Figure
3 Typical floor mount installation
KEY
A Air supply line J
B
Bleed-type master air valve (required for pump)
C Air fi
D Air inlet M
E
F
G Optional needle valve for pump speed
lter and regulator
Master air valve (for accessories)
exible fluid suction hose
Fl
adjustment.
Fluid drain valve (required)
K
Fluid shutoff valve
L
N
R
ible fluid outlet hose
Flex
Fluid inlet (2 ports on aluminum manifolds,1 port on SST manifolds)
Fluid outlet (2 ports on aluminum manifolds,1 port on SST manifolds)
ound wire (required; see
Gr
ounding, page 8 ).
Gr
2
1
334014A
Operation
Operation
Pressure Reli
Follow the Pr whenever you
This equipm is relieved injury from in the eyes Procedure clean, che
1. Shut off t
2. Open the d
3. Shift the two times as shown
ent stays pressurized until pressure
manually. To help prevent serious
pressurized fluid, such as splashing
or on skin, follow the Pressure Relief
when you stop pumping and before you
ck, or service the equipment.
he air supply to the pump.
ispensing valve, if used.
high/low pressure lever back and forth
. Leave the lever in the “Low” position
.
ef Procedure
essure Relief Procedure
see this symbol.
4. Open the fluid d system) to re container re
rain valve (installed on the
lieve all fluid pressure. Have a
ady to catch the drainage.
Tighten Fasteners Before Setup
Before usin and retorq
Torque Ins
operation
g the pump for the first time, check
ue all external fasteners. Follow
tructions, page 16. After the first day of
, retorque the fasteners.
Flush the Pump Before First Use
The pump w contami pump tho
Flushin
as tested in water. If water could
nate the fluid you are pumping, flush the
roughly with a compatible solvent. See
g and Storage, page 15.
High/Low Lever
ure 4 High/Low Pressure Lever
Fig
Use the mode. W press When t press air pr incre cons
NOTE: The lever must be fully seated into the High or Low position for proper operation.
High/Low lever to set the desired pressure
hen the lever is set to “Low,” the fluid outlet
ure is slightly less than the air inlet pressure.
he lever is set to “High,” the fluid outlet
ure is slightly less than two times the inlet
essure. Note that the High pressure setting ases both fluid outlet pressure and inlet air umption.
334014A 13
Operation
Start and Adju
1. Be sure the pump is properly grounded. Refer to Grounding, page 8 .
2. Ensure the High/Low pressure lever is in the “Low” position before starting the pump.
3. Check all fittings to be sure they are tight. Use a compatible liquid thread sealant on all male threads. Tighten fluid inlet and outlet fittings securely.
4. Placethesuctiontube(ifused)inthefluidtobe pumped.
NOTE: If fluid inlet pressure to the pump is more than 25% of outlet working pressure, the ball check valves will not close fast enough, resulting in inefficient pump operation.
st the Pump
NOTICE
Excessive fluid inlet pressure can reduce diaphragm life and may result in pump damage.
5. Place the end of the fluid hose into an appropriate container.
9. Slowly increase air pressure with the air regulator until the pump starts to cycle. Allow the pump to cycle slowly until all air is pushed out of the lines and the pump is primed.
NOTE: Use lowest possible air pressure to prime, just enough to cycle the pump. If the pump does not prime as expected, turn air pressure DOWN.
10. If you are flushing, run the pump long enough to thoroughly clean the pump and hoses.
11. Close the dispensing valve, if used.
12. Close the bleed-type master air valve.
Pump Shutd
At the end of the work shift and before you check, adjust, clean or repair the system, follow the
Pressure Relief Procedure, page 13.
own
6. Close the fluid drain valve.
7. Turn the air regulator knob to 0. Open all bleed-type master air valves.
8. If the fluid hose has a dispensing device, hold it open.
4
1
334014A
Maintenance
Maintenance
Maintenance Schedule
Establish a p based on the p maintenance or leakage d
reventive maintenance schedule,
ump’s service history. Scheduled
is especially important to prevent spills
ue to diaphragm failure.
Lubrication
Thepumpis to require pump. An in recommend
lubricated at the factory. It is designed
no further lubrication for the life of the
line lubricator is not needed, and is not
ed, under normal operating conditions.
Tighten Threaded Connections
Before e damage, sure all Check fa Althou is to re
Torque
ach use, check all hoses for wear or
and replace as necessary. Check to be
threaded connections are tight and leak-free.
steners. Tighten or retorque as necessary.
gh pump use varies, a general guideline
torque fasteners every two months. See
Instructions, page 16.
Flushing and Storage
• Flush before fluid can dry in the equipment, at the end of the day, before storing, and before repairing equipment.
• Flush at the lowest pressure possible. Check connectors for leaks and tighten as necessary.
• Flush with a fluid that is compatible with the fluid being dispensed and the equipment wetted parts.
Flush the are pumpi damaging
Always flush the pump and relieve the pressure before storing it for any length of time.
pump often enough to prevent the fluid you ng from drying or freezing in the pump and
it. Use a compatible solvent.
334014A 15
Maintenance
Torque Instructions
NOTE: All fast diaphragm joi adhesive patc excessively w operation. R medium-stre threads.
If fluid cover, center diaphragm joint, or manifold fasteners have been loosened, it is important to torque them using the following procedure to improve sealing.
NOTE: Always completely torque the fluid covers and center diaphragm joint before torquing the manifolds.
Start all fl few turns. contacts or less wo torque. R
eners for the fluid covers, center
nt, and manifolds have a thread-locking
h applied to the threads. If this patch is orn, the fasteners may loosen during
eplace screws with new ones or apply
ngth (blue) Loctite or equivalent to the
uid cover or center diaphragm joint screws a
Then turn down each screw just until head
cover. Then turn each screw by 1/2 turn
rkinginacrisscrosspatterntospecified
epeat for manifolds.
Fluid cover, c fasteners: 10
Lubricate air valve fasteners prior to reassembly to prevent galling. Retorque the air valve fasteners in a crisscross pattern to specified torque.
Air valve fasteners: 80in-lb(9.0N•m)
enter diaphragm joint, and manifold 0in-lb(11.3N•m)
Air Valv
e Fasteners
Fluid Covers and Center Diaphragm Joint Manifolds
16 334014A
Dimensions and Mounting
KEY
Dimensions and M
ounting
Aluminum
A
12.7 in (323 mm) 11.8 in (300 mm)
B
14.4 in (366 mm) 12.9 in (328 mm)
C 15.3 in (389 mm) 13.7 in (348 mm)
D
10.9 in (277 mm) 9.5 in (241 mm)
E
1.8 in (46 mm) 1.1 in (28 mm)
F
10.8 in (27
G 21.5 in (546 mm) 20.6 in (523 mm)
4mm)
SST Aluminum and SST
10.7 in (27
2mm)
NOTE: All dimensions are approximate.
H
6.2 in (157 mm)
J
9.4 in (239 mm)
K
15.6 in (396 mm)
L
3/4 npt(f) Air Inlet
M
1 in npt(f) or 1 in. bspt Fluid Inlet (2 for aluminum manifolds; 1 for SST manifolds)
N
1innpt(f) (2 for alum
P
3/4 npt(f) Air Exhaust Port
or 1 in. bspt Fluid Outlet
inum manifolds; 1 for SST manifolds)
334014A
17
Performance Cha
rts
Performance C
Low Pressure S
Operating Air Pressure
100 psi (0.7 MPa, 7.0 bar)
70 psi (0.48 MPa, 4.8 bar)
40 psi (0.28 MPa, 2.8 bar)
20 psi (0.14 MPa, 1.4 bar)
etting
A
B
C
D
harts
(MPa, bar)
PSI
100
(0.70, 7.0)
(0.55, 5.5)
(0.41, 4.1)
(0.28, 2.8)
(0.14, 1.4)
Fluid Pressure
Approximate Cycles per Minute
56 112 168 224 280
80
60
40
20
0
010
(38)
Fluid Flow — gpm (lpm)
A
B
C
D
20
(76)
30
(114)
40
(151)
50
(189)
HowtoReadtheCharts
1. Locate fluid flow rate along bottom of chart.
2. Follow vertical line up to intersection with selected operating air pressure curve.
3. Follow left to scale to read fluid outlet pressure (top chart) or air consumption (bottom chart)
(Nm
scfm
3
/min.)
56 112 168 224 280
75
(2.1)
60
(1.7)
45
(1.3)
30
(0.8)
15
(0.4)
0
010
(38)
Air Consumption
Approximate Cycles per Minute
A
B
C D
20
(76)
Fluid Flow — gpm (lpm)
30
(114)
40
(151)
50
(189)
18 334014A
Performance Cha
rts
High Pressure
Setting
Operating Air Pressure
A
100 psi (0.7 MPa, 7.0 bar)
B
70 psi (0.48 MPa, 4.8 bar)
C
40 psi (0.28 MPa, 2.8 bar)
D
20 psi (0.14 MPa, 1.4 bar)
PSI
(MPa, bar)
200
(1.38, 13.8)
160
(1.10, 11.0)
120
(0.83, 8.3)
(0.55, 5.5)
(0.28, 2.8)
Fluid Pressure
Approximate Cycles per Minute
50 100 150 200 250
80
40
0
010
(38)
Fluid Flow — gpm (lpm)
A
B
C D
20
(76)
30
(114)
40
(151)
50
(189)
How to Read the Charts
1. Locate fluid flow rate along
bottom of chart.
2. Follow vertical line up to
intersection with selected operating air pressure curve.
3. Follow left to scale to read
fluid outlet pressure (top chart) or air consumption (bottom chart)
(Nm
scfm
3
/min.)
50 100 150 200 250
120
(3.4)
96
(2.7)
72
(2.0)
48
(1.4)
24
(0.7)
0
010
(38)
Air Consumption
Approximate Cycles per Minute
A
B
C D
20
(76)
Fluid Flow — gpm (lpm)
30
(114)
40
(151)
50
(189)
334014A 19
Technical Data
Technical Data
US
Maximum fluid working pressure
Air pressure o
Fluid displa
Low Pressure Setting
High Pressure Setting
Air consumpt
Low Pressure Setting 26 scfm
High Pressure Setting 51 scfm
Maximum val
Maximum ai
Maximum free-flow delivery
Maximum p
Maximum suction lift (varies widely based on ball/seat selection and wear, operating speed, material properties, and other variables)
Maximum size pumpable solids 1/8 in 3.2 mm
Recommended cycle rate for continuous use
Recom syst
Air i
Flui
Flui
Wei
mended cycle rate for circulation
ems
nlet size
d inlet size
d outlet size
ght
perating range
cement per cycle
ion
ues with water as media under submerged inlet conditions at ambient temperature:
rconsumption
Low Pressure Setting 59 scfm
High Pressure Setting 95 scfm
Low Pressure Setting
High Pressure Setting
ump speed
Low Pressure Setting
High Pressure Setting
48 lb (aluminum manifolds)
60 lb (SST manifolds)
200 psi 1.4 MPa,14.0 b
20-100 psi 0.14-0.69 MPa
0.17 g 0.64 l
0.20 g 0.76 l
at 70 psi, 20 gpm at 4.8 bar, 76 lpm
0.7 cubic me
1.4 cubic me
1.7 cubic m
2.7 cubic m
50 gpm 189 lpm
46 gpm 174 lpm
280 cpm
225 cpm
16 ft dry,
29 ft wet
93–140 cpm
(in Low or High pressure setting)
20 cpm
(in Low or High pressure setting)
3/4 npt(f)
1 in. npt(f) or 1 in. bspt
1 in. npt(f) or 1 in. bspt
21.8 kg (aluminum manifolds)
27.2 kg (SST manifolds)
Metric
, 1.4-6.9 bar
ters per minute
ters per minute
eters per minute
eters per minute
4.9 m dry
8.8 m wet
ar
20 334014A
Sound Power (measured per ISO-9614–2)
At 70 psi (0.48 MPa, 4.8 bar) and 50 cpm
Low Pressure Setting
High Pressure Setting
At 100 psi (0.7 MPa, 7.0 bar) and full flow
Low Pressure Setting
High Pressure Setting
Sound Pressure (tested3.28ft[1m]fromequipment)
At 70 psi (0.48 MPa, 4.8 bar) and 50 cpm
Low Pressure Setting
High Pressure Setting
At 100 psi (0.7 MPa, 7.0 bar) and full flow
Low Pressure Setting
High Pressure Setting
Wetted parts
Non-wetted external parts aluminum, coated carbon steel
aluminum plus the material(s) chosen for seat, ball,
and diaphragm options.
78 dBa
91 dBa
90 dBa
102 dBa
84 dBa
96 dBa
84 dBa
96 dBa
Technical Data
Fluid Te
mperature Range
NOTICE
Temper operat Operat equipm
Diaphragm/Ball Material Fahrenheit
Santoprene® (SP) -40° to 180°F -40° to 82°C
ature limits are based on mechanical stress only. Certain chemicals will further limit the fluid
ing temperature range. Stay within the temperature range of the most-restricted wetted component.
ing at a fluid temperature that is too high or too low for the components of your pump may cause
ent damage.
Temperature Range
Fluid
Celsius
334014A
21
Graco Standard Husky Pump Warranty
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of five years from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within six (6) years of the date of sale..
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties..
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédac présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés, à la suite de ou en rapport, directement ou indirectement, avec les procédures concernées.
tion du
Graco Information
For the latest information about Graco products, visit www.graco.com. For patent information, see www.graco.com/patents.
To place an order, contact your Graco Distributor or call to identify the nearest distributor.
Phone: 612-623-6921 or Toll Free: 1-800-328-0211 Fax: 612-378-3505
All written and visual data contained in this document reflects the latest product information available at the time of publication.
Graco reserves the right to make changes at any time without notice.
Original Instructions. This manual contains English. MM 334014
International Offices: Belgium, China, Japan, Korea
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2014, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco Headquarters: Minneapolis
www.graco.com
Loading...