Instructions – Parts List
Huskyt 515
Split Manifold Kits
308951B
For pumping two fluids simultaneously or mixing two fluids in the pump
Part No. 241240 polypropylene; split inlet
Part No. 241241 acetal; split inlet
Part No. 241242 KynarR; split inlet
Part No. 241243 polypropylene; split outlet
Part No. 241244 acetal; split outlet
Part No. 241245 KynarR; split outlet
Read warnings and instructions.
9068A
GRACO INC.ąP.O. BOX 1441ąMINNEAPOLIS, MNą55440-1441
Copyright 1999, Graco Inc. is registered to I.S. EN ISO 9001
Installation
Pressure Relief Procedure
WARNING
PRESSURIZED EQUIPMENT HAZARD
The equipment stays pressurized until pressure is
manually relieved. To reduce the risk of serious
injury from pressurized fluid, accidental spray, or
splashing fluid, follow this procedure whenever you
D Are instructed to relieve pressure
D Stop pumping
D Check, clean, or service any system equipment
D Install or clean fluid nozzles
1. Shut off the air to the pump.
2. Open the dispensing valve, if used.
3. Open the fluid drain valve to relieve all fluid
pressure, and have a container ready to catch the
drainage.
4. Acetal Pumps Only: Ground the pump using the
114882 ground screw fastened to the outlet
manifold.
Replacing the Manifolds
1.
2. Remove the four manifold nuts (called out by
Note 1 in the Parts Drawing) and the manifold that
you are going to replace with split manifolds.
3. Install the new o-rings and the new split inlet or
outlet manifolds, and torque the manifold nuts to
80 to 90 in-lb (9 to 10 N-m).
NOTE: Make sure all manifold o-rings are
positioned correctly before you fasten the
manifold.
NOTE: Pumps with duckbill check valves are shipped
with the inlet manifold on top and the outlet manifold
on the bottom. See Inlet and Outlet for Pumps with
Duckbill Check Valves in the Service section of
instruction manual 308981.
Relieve the pressure. See
Pressure Relief Procedure at left.
WARNING
FIRE AND EXPLOSION HAZARD
Never use a polypropylene or KynarR pump with
non-conductive flammable fluids as specified by
your local fire protection code. Consult your fluid
supplier to determine the conductivity or resistivity
of your fluid.
2 308951