PRODUCT CONFIGURATION
QSE MAG FLOWMETER
The QSE Mag Series is a dependable highly accurate
electromagnetic owmeter designed for ow and usage
monitoring in commercial applications.
The NorylTM housing and ow tube offer a lightweight, easyto-install Mag Meter that is resistant to heat (210°F [99°C])
and compatible with many water-based liquid solutions.
The QSE Mag Meter monitors ow rate and total ow in a
wide variety of applications including: HVAC, Turf/ Irrigation
and other water reclamation applications.
FEATURES / BENEFITS
• Low investment and operating costs
• ± 0.5% Accuracy of Reading (from 0.25 fps to 15 fps
[0.08 to 4.6 m/s])
• Wide turndown ratio of 60:1
• Non-intrusive, no moving parts to wear out,
maintenance, repair costs low and tolerates high flows
without damage
• The slightly modified bore permits unobstructed flow
and minimizes flow disturbances and straight pipe
requirements
PRODUCT IDENTIFIER
QSE = Electro-Magnetic Flow Meter
SIZE
FITTING
2
05 = 1/2” (15 mm)
07 = 3/4” (20 mm)
10 = 1” (25 mm)
15 = 1-1/2” (40 mm)
20 = 2” (50 mm)
30 = 3” (80 mm) (Flange only)
40 = 4” (100 mm) (Flange only)
3
NPT = NPT (Male) (½” to 2” Only)
BSP = BSPP (Male) (ISO 228) (½” to 2” Only)
FAP = ANSI Flange - Polymer (3” & 4” Only)
FAS = ANSI Flange - Steel (3” & 4” Only)
FDS = DIN Flange - Steel (3” & 4” Only)
ELECTRONIC CHOICE
09 = 2-Button Integral Display, Field Congurable (Cumulative,
Batch & Rate) and Integral Pulse Transmitter (Open Collector
Square Wave), Includes Four Strain Reliefs
QB = Integral Pulse Transmitter (Open Collector Square Wave),
Includes Four Strain Reliefs
COMMUNICATION CHOICE
Q1 = Integrates with Any Electronic Choice QSI Module:
Blue Tooth®, Coil/Digital Pulse Input, Pulse Output (Flow or
Energy & Scalable), RS485 (MODbus RTU), Temperature Inputs,
BTU Calculator. Energy Use Computation Note: Energy Use
Computation Requires Temperature Sensor Probes (Select
Probes Below)
Q2 = Integrates with Any Electronic Choice QSI Module:
Blue Tooth®, Coil/Digital Pulse Input, Pulse Output (Flow or
Energy & Scalable), Data Logger, Temperature Inputs, BTU
(Heat) Calculator. Energy Use Computation Note: Energy Use
Computation Requires Temperature Sensor Probes (Select
Probes Below)
Q3 = Integrates with Any Electronic Choice QSI Module:
Blue Tooth®, Coil/Digital Pulse Input, Pulse Output (Scalable),
Data Logger, 4-20mA.
XX = No Communication Suite
TEMPERATURE SENSOR PROBES
1 = Integrates with QSI Communications Choice for Energy
Use Computation (2ea) 1" (25 mm) Long Temperature Sensor
Probes w/Cables (10 ft. [3 m]) (Customer Installed), Used with
1/2" through 2" Meters
2 = Integrates with QSI Communications Choice for Energy
Use Computation (2ea) 2" (50 mm) Long Temperature Sensor
Probes w/Cables (10 ft. [3 m]) (Customer Installed), Used with
3" and 4" Meters
X = No Temperature Probes
1
4
5
6
• 7 line sizes (½” to 4”) ½”, ¾”, 1”, 1-½”, 2”, 3", & 4”
• Housing ported with “Thermal Well Supports” for
sensors (Energy Management)
• Compatible with GPI 09 Electronics Display or
FLOMEC QSI I/O Board
PACKAGING (Auto Select)
A = 1/2" - 2" Meters
B = 3" Meter
C = 4" Meter
1 2 3 4 5 6 7
>>>> QSE 30 FAP 09 Q1 2 B
7
© 2018 Great Plains Industries, Inc. All Rights Reserved.
SPECIFICATIONS
Fitting
Type:
Recommeded Plastic
Flange Bolt Torque:
Pipe Sizes: 1/2”, 3/4”, 1”, 1-1/2”, 2”, 3”, 4”
Pressure Rating: 150 psi @ 73 F (10 bar @ 23 C)
Velocity: 0.25 to 15 fps (0.08 to 4.57 m/s)
Flow: 1/2” (05) 0.16 - 10 GPM (0.63 - 38 L/min)
Accuracy
±0.5% of Reading between 0.25 fps and 15 fps (0.08 m/s and 4.57 m/s)
(Reference Owner's Manual for complete accuracy and
uncertainty specications)
NPT, BSP, ANSI Flanged, DIN Flanged
1/2” to 2” - NPT (Male), BSPP (Male) (ISO 228)
3” & 4” 150# ANSI Flanged - Polymer Flange
3” & 4” ANSI Flanged - Steel Flange
3” & 4” DIN Flanged - Steel Flange
25 ft.-lbs. (33.9 Nm)
3/4” (07) 0.3 - 20 GPM (1.27 - 76 L/min)
1” (10) 0.6 - 40 GPM (2.52 - 151 L/min)
1-1/2” (15) 1.3 - 80 GPM (5.05 - 303 L/min)
2” (20) 2.5 - 150 GPM (9.47 - 568 L/min)
3” (30) 5 - 300 GPM (19 - 1136 L/min)
4” (40) 10 - 600 GPM (38 - 2271 L/min)
APPLICATIONS
Operating Temperature
Range:
1/2"-2": 32 F to 210 F (0 C to 99 C)
3"-4": 32 F to 180 F (0 C to 82 C)
Ambient Temperature Range: 0 F to 140 F (-18 C to 60 C)
Typical
K-Factor:
1/2” (05) 4347 PPG (1158.5 Pulses/L)
3/4” (07) 1937 PPG (511.8 Pulses/L)
1” (10) 1089 PPG (287.7 Pulses/L)
1-1/2” (15) 484.1 PPG (127.9 Pulses/L)
2” (20) 400 PPG (105.7 Pulses/L)
3” (30) 121 PPG (32.0 Pulses/L)
4” (40) 68.1 PPG (18.0 Pulses/L)
Power
Supply:
Externally Powered
Voltage Supply (Min): 12V (dc or ac)
Voltage Supply (Max): 30V (dc or ac)
Consumption:
Wetted
Materials:
Max current consumption (QSE with QSB): 75mA
Max current consumption (QSE with QSI): 150mA
Body Noryl
TM
Electrodes 316L SS
Seals EPDM O-Rings
Frequency
Range:
All Sizes
10 Hz Minimum - 1,000 Hz Maximum
(with 09 Display)
10 Hz Minimum - 3,000 Hz Maximum
(with Blind Pulse Out)
Calibration Report: Standard
N.I.S.T. Available
• Agriculture Irrigation
• Turf Irrigation Systems
• Micro Irrigation Systems
• HVAC
• EMS (Energy Management
Systems)
• BAS (Building Automation
Systems)
160.0
140.0
120.0
100.0
80.0
Pressure PSIG
60.0
40.0
20.0
0.0
50 70 90 110 130 150 170 190 210
(10) (21) (32) (43) (54) (66) (77) (88) (99)
• Chilled water
• Domestic water (hot and cold
APPROVALS
• Energy sub-metering
(BTU hot and cold)
• Process (blow down,
make up, boiler feed, etc.)
NEMA 6P
(pending)
IP67
Derated Pressure Curve for QSE (Pressure vs Temperature)
Derated Pressure
Temperature °F (°C)
Service & Warranty: For technical assistance, warranty replacement or repair contact your
FLOMEC® or GPI® distributor: In North or South America: 888-996-3837 / FLOMEC.net
Outside North or South America: +61 2 9540 4433 / FLOMEC.net
11.0
9.7
8.3
6.9
5.5
Pressure bar
4.1
2.8
1.4
0.0
05/18 IND-1060-QSE