Pressure, Level & Temperature Transmitters & Transducers
INSTALLATION MANUAL
TABLE OF CONTENTS
1.1 Product Description
1.2 Warning
1.3 Unpacking/Inspection
1.4 Using this manual
2.1 Mounting/process connection
2.2 Power Supply
2.3 Wiring/Grounding
2.4 Environment
Maintenance
Return Information
Pressure, Level & Temperature Transmitters &
Transducers
1. INTRODUCTION
1.1 Product Description
Model 216/316 is a Low Range High line Differential Pressure Transducer with ranges as
low as 2.5 WCD to 200 PSID and digitally corrected accuracy up to +- 0.05% FSO. These are often used for measuring fluid flow across a primary device such as an orifice plate but can also be used for other differential pressure applications.
1.2 Warning
Pressurized vessels and associated equipment are potentially dangerous. The product
described in the guide should be operated only by personnel trained in the procedures
that will assure safety to themselves, to others, to the equipment, and to the product.
Specific warnings are noted as in specific installation/operation sections.
1.3 Unpacking and Inspection
All models covered in this manual are carefully tested, inspected and packed. Upon
receipt of the shipment thoroughly inspect the transducer. If you see any visible signs of
obvious shipping damage, notify the freight company immediately.
1.4 Using this manual
This manual is intended to help the end user install, maintain, and provide general
service of GP:50 Model 216/316 Low Range High Line Differential Pressure Transducer.
The user should have a general understanding of current loops & general instrument
control. All aforementioned models are precision instruments and should be given the
same care as any other precision instrument during installation and operation.
2. INSTALLATION
2.1 Mounting/Process Connection
Model 216/316 is a position sensitive device and its orientation may cause zero shift if
mounted differently from the orientation the unit was calibrated in (standard orientation
has the pressure ports in the horizontal position). Although this is the case, once
determined, this shift can be adjusted for using the zero adjustment screw on the unit. It
is also noted the lower the pressure range the greater the orientation shift. The standard
process connections is ¼ NPT F but can be ordered with optional pressure ports.
Consult factory for availability. Installation of the device shall be in accordance with
industry standard pipe fitting requirements for this size. During installation or removal
torque should only be applied at the wrench flats provided on the pressure port. As a
general rule of thumb, the device shall be wrench-tight to avoid leakage from the
process connection.
Ensure media is compatible with 316 stainless steel (standard material, optional materials
available) check part number to verify wetted material to avoid premature corrosion of the
diaphragm. This can cause performance degradation and eventual sensor failure.