•Safety glasses (with side shields) for eye protection,
especially in machine shop areas
•Steel-toed shoes for foot protection when handling
parts, heavy tools, etc.
•Other personal protective equipment to protect
against hazard/toxic fluids
Coupling Guards:
•Never operate a pump without a V-belt guard
properly installed
Flanged Connections:
•Never force piping to make a connection with a
pump
• Use only fasteners of the proper size and material
• Ensure there are no missing fasteners
• Beware of corroded or loose fasteners
Operation:
•Do not operate below minimum rated flow, or with
discharge valves closed
•Do not open vent or drain valves, or remove plugs
while system is pressurized
Maintenance Safety:
• Always lockout power
• Ensure pump is isolated from system and pressure
is relieved before disassembling pump, removing
plugs, or disconnecting piping
•Use proper lifting and supporting equipment to
prevent serious injury
• Observe proper decontamination procedures
• Know and follow company safety regulations
• Never apply heat to remove impeller
• Observe all cautions and warnings highlighted in
pump instruction manual
Safety Definitions
These pumps have been designed for saf e and reliable operation when properly used and maintained in accordance
with instructions contained in this manual. A pum p is a pressure containing device with rotating parts that can be
hazardous. Operators and maintenance personnel must realize this and follow safety meas ures. Goulds pumps
shall not be liable for physical injury, damage or delays caused by a failure to observe the instructions in this manual.
The following symbols are used to denote special attention:
Electrical Hazard. Particular care must be taken when electrical power source to the equipment is
energized.
Warning. O perating procedure, prac tice etc which, if not c orrect ly followed, could result in personal injury or
loss of life
Caution. Operating procedure, practice etc which if not followed could result in dam age or destruction of
equipment
ATEX. If equipment is to be installed in a potentially explosive atmosphere and these procedures are not
followed, personal injury or equipment damage from an explosion may
FOREWORD
When pumping unit is installed in a potentially explosive atmosphere, the instructions after the Ex symbol
please contact a Goulds representative before proceeding.
This manual provides instructions for the Installation, operation, and maintenance of the
Goulds Axial Flow (AF) pump model. This manual covers the standard product. For special
options, supplemental instructions are supplied. This manual must be read and understood before installation and start-up.
The design, materials and workmanship incorporated in the construction of Goulds pumps
makes them capable of giving long, trouble-free service. The life and satisfactory service of any
mechanical unit, however, is enhanced and extended by correct application, proper installation,
periodic inspection, condition monitoring and careful maintenance. This instruction manual was
prepared to assist operators in understanding the construction and the correct methods of
installing, operating, and maintaining these pumps.
Goulds shall not be liable for physical injury, damage or delays caused by a failure to
observe the instructions for Installation, Operation, and Maintenance contained i n thi s
manual.
Warranty is valid only when genuine Goulds parts are used.
Use of the equipment on a service other than stated in the order will nullify the warranty,
unless written approval is obtained in advance from Goulds Pumps, Inc.
Supervision by an authorized Goulds representative is recommended to assure proper
installation.
Additional manuals can be obtained by contacting your local Goulds representative or by
calling 1-800-446-8537.
THIS MANUAL EXPLAINS
Proper Installation
Start-up Procedures
Operation Procedures
Routine Maintenance
Pump Overhaul
Trouble shooting
Order Spare or Repair Parts
must be followed. Personal injury and/or equipment damage may occur if these instructions are not
followed. If there is any question regarding these requirements or if the equipment is to be modified,
AF (42-66) IOM 3
4
General Precautions
potentially explosive environment.
Never apply heat to remove impeller. It may explode due to trapped
liquid
Never use heat to disassemble pump due to risk of explosion from
trapped liquid
Never operate pump without coupling guard correctly installed
Never operate pump beyond the rated conditions to which the pump was
sold
Never start pump without proper prime, or proper liquid level in self
priming pumps
Never run pump below recommended minimum flow or when dry
Always lock out power to the driver before performing pump maintenance
Never operate pump without safety devices installed
Never operate pump with discharge valve closed
Never operate pump with suction valve closed
Do not change conditions of service without approval of an authorized
Goulds representative
Explosion Prevention
In order to reduce the possibility of accidental explosions in atmospheres containing explosive gasses
and/or dust, the instructions under the ATEX symbol must be closely followed. ATEX certification is a
directive enforced in Europe for non-electrical and electrical equipment installed in Europe. ATEX
requirements are not restricted to Europe, and are useful guidelines for equipment installed in any
Special ATEX considera ti ons
All installation and operation instructions in this manual must be strictly adhered to. In addition, care must be taken to
ensure that the equipment is properly maintained. This includes but is not limited to:
1. monitoring the pump frame and liquid end temperature
2. maintining proper bearing lubrication
3. ensuring that the pump is operated in the intended hydraulic range
AF (42-66) IOM
ATEX Identification
Temperature in Celsius
Temperature in Celsius
T1
T3
T4
T5
For a pumping unit (pump, seal, coupling, motor and pump accessories) to be certified for use in an ATEX classified
environment, the proper ATEX identification must be present. The ATEX tag will be secured to the pump or the
baseplate on which it is mounted. A typical tag will look like this:
II 2 G/D X
The CE and the Ex designate the ATEX compliance. The code directly below these symbols reads as follows:
II ------------ Group 2
2 ------------- Category 2
G/D ------------ Gas and Dust present
X ------------ Temperature class, can be T1 to T6 (see following table)
Maximum Process Temperature to achieve desired T rating
T Rating per EN 1127-1 Maximum Surface
450 410
T2
300 260
200 165
135 100
100 65
Maximum Process
T6
The code classification marked on the equipment should be in accordance with the specified area where the
equipment will be installed. If it is not, please contact your ITT/Goulds representative before proceeding.
85 50
Intended Use
The ATEX conformance is only applicable when the pump unit is operated within its intended use. All instructions
within this manual must be followed at all times. Operating, installing or maintaining the pump unit in any way that is
not covered in this manual can cause serious personal injury or damage to the equipment. This includes any
modification to the equipment or use of parts not provided by ITT/Goulds. If there is any question regarding the
intended use of the equipment please contact an ITT/Goulds representative before proceeding.
GENERAL PRECAUTIONS.............................................................................. 9
DEFINITIONS
Axial flow pumps are pressure-containing devices with
rotating parts that can be hazardous. It has been
designed for safe and reliable operation when properly
used and maintained in accordance with instructions
contained in this manual. It is not to be operated at
speeds, working pressures, discharge pressures, or
temperatures higher than, nor used with liquids other
than stated in the original order acknowledgement,
without written permission of ITT Industries, Gould’s
Pumps, Inc. Operators and maintenance personnel
must realize this and follow safety measures. ITT
Industries, Gould’s Pumps, Inc. shall not be liable for
physical injury, damage or delays caused by a failure to
observe the instructions in this manual.
Throughout this manual, the words Warning, Caution,
and Note are used to indicate procedures or situations
which require special operator attention:
WARNING
Warning is used to indicate the presence of a
hazard which can cause severe personal injury,
death or substantial property damage if the warning
is ignored.
CAUTION
Caution is used to indica te the presence of a hazard
which will or can cause minor personal injury or
property damage if the warning is ignored.
NOTE: Operating procedure, condition, etc. that is
essential to observe.
EXAMPLES
WARNING
Pump shall never be operated without V-belt or
coupling guard installed correctly.
CAUTION
Obstructions to flow or pipe fowling may cause
cavitation and pump damage.
NOTE: Proper alignment is essential for long pump
life.
GENERAL PRECAUTIONS
WARNING
Personal injury will result if procedures outli n ed in
this manual are not followed.
•Never apply heat to remove the impeller. It may
explode due to trapped liquid.
•Never use heat to disassemble pump due to risk of
explosion from trapped liquid.
•Never operate pump without V-belt or coupling
guard correctly installed.
•Never operate pump beyond the rated conditions
to which the pump was sold.
•Never start pump without proper prime (sufficient
liquid in pump casing).
•Never run the pump < 75% or > 115% of the Best
Efficiency Point (B.E.P.), AF pumps are unstable in
these regions.
•Always lock out power to the driver before
performing maintenance.
•Never operate pump without safety devices
installed.
• Never operate pump with suction valve closed.
• Never operate pump with discharge valve closed.
• Do not change conditions of service without
approval of an authorized Gould’s representative
AF (42-66) IOM 9
THIS PAGE
INTENTIONALLY
LEFT BLANK
AF (42-66) IOM
10
2
GENERAL INFORMATION
GENERAL .................................................................................................... 11
NAME PLATE INFORMATION .................................................................... 12
RECEIVING THE PUMP .............................................................................. 13
INSTALLATION AND OPERATION CHECKLIST ........................................ 13
GENERAL
This instruction manual is intended to assist those
involved with the installation, operation and
maintenance of Gould’s pumps. It is recommended
that this manual be thoroughly reviewed prior to
installing or performing any work on the pump or
motor.
The design, material and workmanship incorporated
into the construction of Gould’s pumps makes them
capable of giving long, trouble-free service. The life
and satisfactory service of any mechanical unit,
however, are enhanced and extended by periodic
inspection and careful maintenance. Keep this
instruction manual handy for reference. Further
information can be obtained by contacting Gould’s
Pumps, Ashland Operations, East Centre St., Ashland,
PA 17921 or your local representative.
Gould’s Pumps will not be liable for any damages or
delay caused by failure to comply with the provisions of
this instruction manual. This pump is not to be
operated at speeds, working pressures, discharge
pressures, or temperatures, nor used on liquids other
than stated in the original order acknowledgment
without written permission of Gould’s Pumps.
PUMP DESCRIPTION
The AF pump generates flow by the thrust or lift
action of the rotating axial vanes of the impeller. It
provides high flow rates and low heads which are
ideal for re-circulation, evaporator, and generator
cooling systems. The AF utilizes an elbow to direct
the flow through the suction and out the discharge
end of the pump. The pump accommodates top or
end suction configurations using either the LMR or
LM bearing arrangement. The LMR is for top
suction and the LM is for end suction.
Arrangements are as follows:
Elbow – AF elbows are fabricated with 150# flat
face suction and discharge flanges. They come
with fabricated feet for mounting to a sub-base or
without feet to be mounted directly in the piping.
The elbows have a built in stuffing box and a rear
flange for mounting the power end to the elbow.
There are also adjusting lugs for aligning the shaft
to the stuffing box.
Casing – The AF comes with a casing or spool piece to
simplify impeller installation and alignment. The casing
bolts to the elbow and shrouds the impeller. It has a gasket
or o-ring seal between it and the elbow. Adjusting lugs on
the elbow center the casing relative to the impeller.
Power End - The power end is made up of the bearing
housing, bearings, locknuts, lock washers, labyrinth oil
seals, shaft, shaft sleeve (w/packing), oil slinger, keys,
shaft, and shaft washer.
Stuffing Box – The stuffing box is integral with the elbow
and provides a mounting surface for a mechanical seal or
cylindrical bore with flush ports and gland face for packing.
The standard packed box includes (5) rings of packing and
(2) lantern rings to seal the shaft area. (2) flush ports are
provided for lubrication. The innermost flush port is used
with process flow and the outermost port for water flush. A
special alternate packing arrangement is available that
includes a throat bushing and additional ring of packing
near the gland (see the attached addendum). A gland is
used for packing adjustment.
AF (42-66) IOM 11
Shaft Sleeve – If packing is specified, a
replaceable wear sleeve is provided with the power
end. The sleeve is keyed to prevent rotation. The
stuffing box can also be modified to accept a
mechanical seal if required.
Impeller - The impeller is cast with (4) fixed vanes
at 0 or +5 degrees, CW or CCW rotation, and top
or end suction. The impeller bore is stepped for
easy assembly to the shaft. It is held in place with
a key, shaft washer, and bolts. It has a cover plate
and o-rings to prevent corrosion and allow for easy
impeller replacement. The impeller is dynamically
balanced (two plane) per ISO 1940 to a quality
grade G-16.
Shaft – The shaft is cantilevered into the elbow to
eliminate the need for internal bearings. It is sized
for minimal deflection, high critical speed, and
extreme corrosion resistance. The shafts are
stepped for easy assembly with the impeller. The
shaft comes with a replaceable sleeve when used
with stuffing boxes.
Bearings - The inboard radial bearing absorbs shaft radial
loads and aligns the pump shaft. It is a spherical roller
bearing. The outboard thrust bearing absorbs impeller
thrust loads and comes as either back-to-back angular
contacts or a single taper roller bearing, depending on
pump size. Lubrication is by flood oil or grease, depending
on customer requirements.
Oil-Cooling (Optional ) – An oil-cooling coil is available on
all sizes, it is installed in the bottom of the bearing housing
and circulates water to cool the oil bath. Generally, it is
used when process temperatures cause excessive heat
build up in the bearing housing and/or bearings.
Configurations and Drives – The 42”, 1200mm, 54”, 60”,
and 66”pumps are usually gear driven and come on a
subbase as standard. They can also be pipe mounted with
a drive shaft to a motor on a separate subbase.
NAMEPLATE INFORMATION
Every Gould’s pump has a nameplate that provides
information about the pump, including hydraulic
characteristics. The nameplate for the AF is located on the
bearing housing. Note the format of the pump size:
Discharge X Suction - Impeller Diameter in inches or
millimeters (Example 42” X 42”-42” or 1200mm X
1200mm-1200mm, see Fig. 1). When ordering spare
parts you will need to identify pump model, size, serial
number, and the item number of required parts.
Information can be found in this manual.
12 AF (42-66) IOM
COMPLETE
INITIAL
DESCRIPTION
PAGE NO.
Manual read and understood
1~54
Level foundation
15
Level subbase
16
Check motor rotation ---CW _____ ---CCW _____
28
Component rough alignment complete
21~26
V-belt tension and alignment per drive mfgr.
21,22
Coupling alignment per cplg mfgr.
22
Piping installed and alignment rechecked
19, 20
Mech. seal adjusted per mfgr.
Mfgrs Mnl
Seal flush lines connected
41
Impeller alignment and clearance set ______ Inch/Side
27
Pump shaft-free turning
30
Bearing lubrication
30, 38
V-belt or coupling guards installed
9, 22,30
Motor electrical connections
Mfgrs Man’l
2
!
RECEIVING THE PUMP
Inspect the pump as soon as it is received.
Carefully check that everything is in good order.
Make notes of damaged or missing items on the
receipt and freight bill. File any claims with the
transportation company as soon as possible.
STORAGE REQUIREMENTS
Short Term: (Less than 6 months) Gould’s normal
packaging is via a skid. It is designed to protect
the pump during shipping only. Upon receipt, store
in a covered and dry location.
Long Term: (More than 6 months) Gould’s longterm packaging via crating. Preservative treatment
of bearings and machined surfaces is required.
Rotate the shaft several times every 3 months.
Refer to drive manufacturer's instruction manual
for their long-term storage procedures. Store in a
covered dry location
Note: Long-term storage treatment can be
purchased with initial p u mp order.
UNCRATING/DE-SKIDDING
Care should be taken when uncrating or de-skidding
pumps. If shipment is not delivered in proper order, and in
accordance with the bill of lading, note the damage or
shortage on both the receipt and freight bill. Make any
claims to the transportation company promptly. Instruction
books and sheets are included in the shipment - DO NOT
DISCARD.
LIFTING THE PUMP/SUB-BASE
WARNING
Pump and components are heavy. Failure to properly
lift and support equipment could result in serious
physical injury or damage to pumps.
Use care when moving pumps. Lifting equipment must be
able to adequately support the entire assembly. Lift
assembled unit by the lifting holes found in the sub-base.
If the motor, sheaves, and guard are in place, be sure that
the lifting cable or chain clears these components. If
necessary remove the guard or use a spreader bar to
prevent damage. In case the motor ships separate use the
eyebolts or lifting lugs found on the motor to hoist it into
place on the sub-base.
INSTALLATION AND OPERATION CHECKLIST
AF (42-66) IOM 13
THIS PAGE
INTENTIONALLY
LEFT BLANK
14 AF (42-66) IOM
Equipment that will operate in a potentially
accordance with the following instructions.
All equipment being installed must be
maintenance purposes.
3
INSTALLATION
PREPARATION FOR INSTALLATION ........................................................ 15
AF units are usually shipped completely assembled.
Check all bolts and nuts on the entire unit and make
sure they are securely tightened. If necessary, install
and adjust drive components per manufacturer’s
recommendations
explosive environment must be installed in
properly grounded to prevent unexpected
static electric discharge. If not, a static
electric discharge may occur when the pump
is drained and disassembled for
AF pump shall be located in a clean, dry area free from
flooding. The area should provide adequate space for
operation, maintenance, inspection and repair,
considering complete disassembly and handling of
equipment. The pump should have a supply of clean
liquid for packing or mechanical seal lubrication. The
pump should be positioned to provide the most efficient
pipeline system.
The AF pumps covered by these instructions may be
designed to hang in the piping system, furnished with
spring loaded sub-base bolts, or have a sub-base
designed to be anchor bolted and grouted to the
foundation.
The foundation must be substantial enough to absorb
any vibration and form a permanent, rigid support for the
pumping unit to the degree that there shall not be any
adverse movement or settling over a long period of time.
Foundations for anchor bolted and grouted sub-bases
are typically concrete with anchor bolts cast in to secure
the pump.
LOCATION/FOUNDATION
The most commonly used foundation bolts are the
sleeve-type (Fig 2 and J type Fig. 3)
AF (42-66) IOM 15
SHIMS OR WEDGES
SHIMS OR WEDGES
Both designs permit movement for final bolt
adjustment. Anchor bolts should be located in the
concrete by a template dimensioned from the pump
installation drawing. The top of the sleeve-type bolt
should be temporarily sealed with waste material to
prevent concrete from entering during the concrete
pouring operation. Foundation bolts are located
according to the bolt hole dimensions shown on the
installation drawing. Bolt size is based on hole size,
they should be 1/8” to ¼” under the sub-base hole size.
For information on spring mounted sub-bases, see the
following section under spring mounted bases.
SUB-BASE LEVELING
GROUTED BASE
When the unit is received with the pump and driver
mounted to the sub-base, it should be placed on the
foundation and the coupling halves or V-belts
disconnected (Fig. 4). The coupling should not be
reconnected until all realignment operations have been
completed. A recommended coupling alignment
procedure is included in the following sections.
Fig. 4
Fig. 5
1. The sub-base should be supported on rectangular
metal blocks or on metal wedges having a slight
taper. There should be support blocks or wedges
on both sides of each foundation bolt. A gap of
about 3/4" to 1-1/2' should be allowed between the
sub-base and the foundation for grouting (Fig. 5).
2. Adjust the metal supports or wedges until the
shafts of the pump and driver and sub-base are
level. Check the coupling faces, as well as the
suction and discharge flanges of the pump, for
horizontal and vertical position by means of a level.
Check also for any internal rubbing in the pump.
Correct, if necessary, by adjusting the supports or
wedges under the sub-base as required. In most
cases, factory alignment will be regained by
shimming under the sub-base alone. Provisions
must be made to support the discharge piping
independently from the pump to prevent excessive
loads and maintain pump-driver alignment.
3. The sub-base should be level to within .125 in. (3
mm) over the length of the base and .0875 in. (1.5
mm) over the width of the base. Bases anchored
with conventional foundation bolts use shims on
both sides of the anchor bolts to level the base.
The bolts which secure the pump sub-base to the
foundation should be 1/8” – 1/4” less in diameter
than the holes in the sub-base (hole size is shown
on the certified installation drawing).
4. Clean outside areas of sub-base that will contact
grout. Do not use oil-based cleaners because
grout will not bond to it. Refer to grout
manufacturer's instructions.
5. Build a dam around foundation and thoroughly wet
the foundation (Fig. 6).
16 AF (42-66) IOM
Fig.10
SPRING
POCKETS
Fig. 8
BOLT
BASEPLATE
GROU
DAM
GROUT
FOUNDATION
Fig. 6
BOLT
BASEPLATE
DAM
GROUT
FOUNDATION
Fig. 7
3
SPRING MOUNTED BASE
Fig. 8 shows a V-belt driven AF pump on a spring
mounted sub-base. Sub-bases supported by spring
pockets assure that the pump remains level,
regardless of vertical movement due to thermal pipe
expansion during operation.
6. Pour grout through the grout holes in the sub-base,
up to level of dam. Remove air bubbles from grout
as it is poured by puddling, using a vibrator, or
pumping the grout into place. Non-shrink grout is
recommended.
7. Allow grout to set.
8. Fill remainder of sub-base with grout. Remove air
as before (Fig. 7)
9. Allow grout to set at least 48 hours.
10. Tighten foundation bolts.
Fig. 8
The following is a brief description of the spring pocket
components and their function (see Fig. 9). The
adjusting screw is used to compress or relax the
spring. Turning the screw causes the adjusting screw
nut assembly to move vertically and change the
amount of force the spring exerts against the spring
retainer, which is fastened to the sub-base. The stop
nut is to limit the vertical up motion of the sub-base in
case part of the load is removed from the pump unit
AF (42-66) IOM 17
Fig. 9
Fig. 9
1/16”
FLANGE
BOLTS
BLOCKS
Spring Size
Wire Size
Spring Rate
Adjusting Screw Size
Load Change per Full Turn
1
.812”
1140 #/in.
1-1/2”-6 UNC
190 #
2
.750”
760 #/in.
1-1/2”-6 UNC
127 #
3
.532”
560 #/in.
1-1/2”-6 UNC
93 #
4
1.00”
1000 #/in.
2”-4-1/2 UNC
222 #
5
.375”
133 #/in.
¾”-10 UNC
13 #
Table 1
!
when the system is cold. The jam nut keeps the stop
nut from turning during normal operation when the subbase has been pushed down from the thermal
expansion. The adjusting screw holder is a bearing
surface for the end of the adjusting screw and serves
to hold the end of the screw in a fixed location.
The adjusting screw was lubricated at the factory but
should be re-lubricated with heavy protective grease
during the pump installation. The springs and other
parts should be coated with an agent to protect the
surface from corrosion, and a heavy lubricant should
be applied to the adjusting screw holder pocket.
The following steps are used to set the springs and
level the sub-base:
1. Place blocks under the sub-base, near each spring
holder, and position the sub-base level on the blocks.
A small gap (approx. 1/16" or 1.6 mm) should exist
between the flange of the vertical pipe and the pump
elbow with the gasket in place (Fig. 10).
allow the required horizontal motion without having the
adjusting screw nut assembly hit the walls of the spring
holder. Make sure there is sufficient clearance
between the adjusting screw holder and the bottom of
the sub-base for vertical thermal expansion, this
clearance is usually shown on the pump installation
drawing.
NOTE: Each spring carries a share of the unit load
but generally do not carry equal loads. Each
holder has a small "window” to check the spring
coil spacing, which is an indication of the relative
load on the spring. The ins tallation drawing may
indicate the approximate number of turns required
for each spring loca tion, especially if the unit uses
more than (4) springs. If necessary refer to table 1
for spring rate information.
4. Turn the adjusting screws until the bottom of the
sub-base just clears each block. Next adjust each
screw evenly until the pump flange and gasket are less
than 1/32” (0.8 mm) away from the pipe flange.
Careful adjustment is necessary to keep the pump
level and obtain better weight distribution on the
springs. After the springs have been loaded and
adjusted, the base should be off the support blocks
and level.
5. Check the alignment of the impeller and the pump
elbow. If necessary, correct the alignment by adjusting
the springs or by using shims.
NOTE: If the flange gap is over 1/32” (0.8 mm), turn
the adjusting screws a uniform amount to close the
gap. For a gap of 1/32” (0.8 mm) or less, omit this
step.
Fig. 10
2. Install several flange bolts to help maintain
alignment of the flanges.
6. Tighten the vertical pipe flange bolts, recheck the
alignment and connect the horizontal pipe flange to the
elbow. The pump unit should be level and there
should not be any rubbing of the impeller in the elbow
when the shaft is turned by hand.
WARNING
Do not tighten bolts.
3. Position the adjusting screw holders, while the
adjusting screw end is seated in the hole, in the
direction of the horizontal thermal expansion. This will
18 AF (42-66) IOM
Never draw piping into place by
damage to the equipment.
3
!
7. Run each stop nut down to make light contact with
the spring retainer. Lock in place by turning the
jam nut down tight against the stop nut.
8. Inspect each spring holder to check the gap
between the coils of the spring. There must be
enough total gap to accommodate the downward
thermal expansion of the system without having
them compressed solid.
NOTE: Pumps with oil lubrication should be
checked for oil level while thermal expansion is
taking place. It may be necessary to add oil to the
bearing housing to provide the proper oil level to
the higher bearing. A line parallel with the subbase deck through the pr o p er oil level line will
show the correct level at the highest end of the
bearing housing. A hori zontal line back from that
point will establish the proper level mark on the
sight gauge.
The system should be operated at normal temperature
before the adjusting screw holders are grouted in
place. Some customers operate their units with the
adjusting screw holders ungrouted.
If it becomes necessary to remove a spring assembly
from a spring pocket, for safety the following steps
should be strictly adhered to:
1. Make sure the spring is relaxed. If the spring
cannot be relaxed with the adjusting screw, the safest
method is to pry off the Plexiglas cover and cut the
coils using a torch.
2. Remove the bolts or cap screws, which fasten
the spring retainer to the holder and lift out the entire
assembly.
3. When the pump is connected to the system and
a spring is removed, there should be support under the
sub-base near the spring location until the spring has
been replaced and adjusted. Distortion of the subbase will affect the pump alignment, and the weight of
the components is more likely to cause distortion when
the pump is connected to the rigid pipe system.
4. If a spring is replaced while the system is hot,
the stop nut should not be set until the system is cold.
The springs must be allowed to push the base back to
its cold position.
An optional grease filled spring pocket is shown in
figure 11. The difference between the standard pocket
and the grease filled pocket is the addition of a grease
fitting and grease seal. Adjustment and setting of the
grease filled pocket are identical.
Fig. 11
GENERAL
forcing at the flanged connections of
the pump. This may impose
dangerous strains on the unit and
cause misalignment between pump
and driver. Pipe strain will adversely
effect the operation of the pump
resulting in physical injury and
Guidelines for piping are given in the “Hydraulic
Institutes Standards” available from: Hydraulic
Institute, 30200 Detroit Road, Cleveland OH 441451967 and must be reviewed prior to pump installation.
AF (42-66) IOM 19
CONNECTION OF PIPI NG
WARNING
Never draw piping into place by forcing at the
flanged connections of the pump. This may
impose dangerous strains on the unit and cause
misalignment between the pu m p and driver. Pipe
strain will adversely affect the operation of the
pump resulting in physical injury and damage to
the equipment.
1. All piping must be supported independently of, and
line up with the pump flanges.
2. Piping runs should be as short as possible to
minimize friction losses
!
3. DO NOT connect piping to the pump until the
pump and driver hold-down bolts have been
tightened.
4. It is suggested that expansion loops or joints be
properly installed in suction and /or discharge lines
when handling liquids at elevated temperatures, so
linear expansion of piping will not draw pump out
of alignment.
5. The piping should be arranged to allow pump
flushing prior to removal of the unit on services
handling corrosive liquids.
6. Carefully clean all pipe parts, valves and fittings,
and pump branches prior to assembly.
SUCTION AND DISCHARGE P IPING
WARNING
NPSHA must always exceed NPSHR as shown on
Goulds performance curves received with order.
(Reference Hydraulic Institute for NPSH and pipe
friction values needed to evaluate suction piping
Properly installed suction piping is a necessity for
trouble-free pump operation. Suction piping should be
flushed BEFORE connection to the pump.
1. Use of elbows close to the pump suction flange
should be avoided. There should be a minimum of
2 pipe diameters of straight pipe between the
elbow and suction inlet. Where used, elbows
should be long radius.
2. Use suction pipe one or two sizes larger than the
pump suction, with a reducer at the suction flange.
Suction piping should never be of smaller diameter
than the pump suction.
3. To prevent suction cavitation, horizontal reducers
should be eccentric with the sloping side down and
concentric for vertical applications.
5. Pump must never be throttled on suction side.
7. Separate suction lines are recommended when
more than one pump is operating from the same
source of supply.
Suction lift conditions
1. Suction pipe must be free from air pockets.
2. Suction piping must slope upwards to pump.
3. All joints must be airtight.
Suction head/Flooded suction conditions
1. An isolation valve should be installed in the suction
line at least two pipe diameters from the suction to
permit closing of the line for pump inspection and
maintenance.
2. Keep suction pipe free from air pockets.
3. Piping should be level or slope gradually
downward from the source of supply.
4. No portion of the piping should extend below pump
suction flange.
5. The size of entrance from supply should be one or
two sizes larger than the suction pipe.
6. The suction pipe must be adequately submerged
below the liquid surface to prevent vortices and air
entrainment at the supply.
Discharge piping
1. Isolation and check valves should be installed in
discharge line. Locate the check valve between
isolation valve and pump, this will permit inspection
of the check valve. The isolation valve is required
for priming, regulation of flow, and for inspection
and maintenance of pump. The check valve
prevents pump or seal damage due to reverse flow
through the pump when the driver is turned off.
2. Increasers, if used, should be placed between
pump and check valves.
3. Cushioning devices should be used to protect the
pump from surges and water hammer if quickclosing valves are installed in system.
Final Piping Check
1. Rotate shaft several times by hand to be sure that
there is no binding and all parts are free.
2. Check alignment, per the impeller alignment
procedure outlined on pg. 28 to determine
absence of pipe strain. If pipe strain exists, correct
the piping.
20 AF (42-66) IOM
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.