Goulds Pumps 3910 User Manual

Installation, Operation and Maintenance
Model 3910 11th Edition (ISO 13709)
FOREWORD
This manual provides instructions for the Installation, Operation, and Maintenance of the Goulds Model 3910 Vertical Bearing Frame In-line Process Pump designed to meet the requirements of
the 11th Edition (ISO 13709) of API* Standard 610. This manual covers the standard product plus common options
The design, materials, and workmanship incorporated in the construction of Goulds pumps make them capable of giving long, trouble-free service. The life and satisfactory service of any mechanical unit, however, are enhanced and extended by correct application, proper installation, periodic inspection, condition monitoring, and careful maintenance. This instruction manual was prepared to assist operators in understanding the construction and the correct methods of installing, operating, and maintaining these pumps.
ITT - Goulds Pumps shall not be liable for physical injury, damage or delays caused by a failure to observe the instructions for installation, operation, and maintenance contained in this manual.
When pumping unit is installed in a potentially explosive atmosphere, the instructions after the Ex symbol must be
!
followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there is any question regarding these requirements or if the equipment is to be modified, please contact a Goulds representative before proceeding.
that are available. For special options, supplemental instructions are
Warranty is valid only when genuine ITT - Goulds Pumps parts are used.
Use of the equipment on a service other than stated in the order will nullify the warranty, unless written approval is obtained in advance from ITT - Goulds Pumps.
Supervision by an authorized ITT - Goulds representative is recommended to assure proper installation.
Additional manuals can be obtained by contacting your local ITT - Goulds representative or by calling 1-(800)-446-8537.
THIS MANUAL EXPLAINS
Proper Installation
n
Start-up Procedures
n
Operation Procedures
n
Routine Maintenance
n
Pump Overhaul
n
Troubleshooting
n
Ordering Spare or Repair Parts
n
* American Petroleum Institute
1220 L Street, Northwest
Washington, D.C. 20005
3910-11th IOM 5/08 5
TABLE OF CONTENTS
PAGE
9 SAFETY
13 GENERAL INFORMATION
17 INSTALLATION
21 OPERATION
27 PREVENTIVE MAINTENANCE
31 DISASSEMBLY & REASSEMBLY
SECTION
1
2
3
4
5
6
61 SPARE PARTS
63 APPENDICES
I - 63 Installation & Disassembly Instructions for Goulds ANSI B15.1 Coupling Guards
A - 63 (Casing Mount Motor Support Only) - All Power Ends Except those with
Optional Air Cooling Package
B - 67 (Casing Mount Motor Support Only) - Power Ends with Optional Air Cooling
Package
II - 71 Dial Indicator (Rim-and-Face) Alignment Procedure
III -75 Removal and Installation of Back Pull-Out Assembly Using Goulds Back Pull-Out
Removal Device
7
8
3910-11th IOM 5/08 7
8 3910-11th IOM 5/08
IMPORTANT SAFETY NOTICE
To: Our Valued Customers
User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury.
ITT Goulds pumps will provide safe, trouble-free service when properly installed, maintained, and operated.
Safe installation, operation, and maintenance of ITT Goulds Pumps equipment are an essential end user
responsibility. This Pump Safety Manual identifies specific safety risks that must be considered at all
times during product life. Understanding and adhering to these safety warnings is mandatory to ensure personnel, property, and/or the environment will not be harmed. Adherence to these warnings alone, however, is not sufficient — it is anticipated that the end user will also comply with industry and corporate safety standards. Identifying and eliminating unsafe installation, operating and maintenance practices is the responsibility of all individuals involved in the installation, operation, and maintenance of industrial equipment.
Please take the time to review and understand the safe installation, operation, and maintenance guidelines outlined in this Pump Safety Manual and the Instruction, Operation, and Maintenance (IOM) manual. Current manuals are available at your nearest Goulds Pumps sales representative.
www.gouldspumps.com/literature_ioms.html or by contacting
These manuals must be read and understood before installation and start-up.
For additional information, contact your nearest Goulds Pumps sales representative or visit our Web site at
www.gouldspumps.com.
S-1
SAFETY WARNINGS
Specific to pumping equipment, significant risks bear reinforcement above and beyond normal safety precautions.
WARNING
A pump is a pressure vessel with rotating parts that can be hazardous. Any pressure vessel can explode, rupture, or discharge its contents if sufficiently over pressurized causing death, personal injury, property damage, and/or damage to the environment. All necessary measures must be taken to ensure over pressurization does not occur.
WARNING
Operation of any pumping system with a blocked suction and discharge must be avoided in all cases. Operation, even for a brief period under these conditions, can cause superheating of enclosed pumpage and result in a violent explosion. All necessary measures must be taken by the end user to ensure this condition is avoided.
WARNING
The pump may handle hazardous and/or toxic fluids. Care must be taken to identify the contents of the pump and eliminate the possibility of exposure, particularly if hazardous and/or toxic. Potential hazards include, but are not limited to, high temperature, flammable, acidic, caustic, explosive, and other risks.
WARNING
Pumping equipment Instruction, Operation, and Maintenance manuals clearly identify accepted methods for disassembling pumping units. These methods must be adhered to. Specifically, applying heat to impellers and/or impeller retaining devices to aid in their removal is strictly forbidden. Trapped liquid can rapidly expand and result in a violent explosion and injury.
ITT Goulds Pumps will not accept responsibility for physical injury, damage, or delays caused by a failure to observe the instructions for installation, operation, and maintenance contained in this Pump Safety Manual or the current IOM available at www.gouldspumps.com/literature.
S-2
SAFETY
DEFINITIONS
Throughout this manual the words WARNING, CAUTION, ELECTRICAL, and ATEX are used to indicate where special operator attention is required.
Observe all Cautions and Warnings highlighted in this Pump Safety Manual and the IOM provided with
your equipment.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Example:
Pump shall never be operated without coupling guard installed correctly.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Example: Throttling flow from the suction side may cause cavitation and pump damage.
ELECTRICAL HAZARD
Indicates the possibility of electrical risks if directions are not followed.
Example: Lock out driver power to prevent electric shock, accidental start-up, and physical injury.
When installed in potentially explosive atmospheres, the instructions that follow the Ex symbol must be
followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there is any question regarding these requirements or if the equipment is to be modified, please contact an ITT Goulds Pumps representative before proceeding.
Example: parts, resulting in a spark and heat generation.
Improper impeller adjustment could cause contact between the rotating and stationary
S-3
GENERAL PRECAUTIONS
WARNING
A pump is a pressure vessel with rotating parts that can be hazardous. Hazardous fluids may be contained by the pump including high temperature, flammable, acidic, caustic, explosive, and other risks. Operators and maintenance personnel must realize this and follow safety measures. Personal injuries will result if procedures outlined in this manual are not followed. ITT Goulds Pumps will not accept responsibility for physical injury, damage or delays caused by a failure to observe the instructions in this manual and the IOM provided with your equipment.
WARNING
WARNING
General Precautions
NEVER use heat to disassemble pump due to risk of explosion from tapped liquid.
NEVER APPLY HEAT TO REMOVE IMPELLER. It may explode due to trapped liquid.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
NEVER operate pump without safety devices installed.
 
NEVER operate pump without coupling guard correctly installed.
NEVER run pump below recommended minimum flow when dry, or without prime.
ALWAYS lock out power to the driver before performing pump maintenance.
NEVER operate pump with discharge valve closed.
NEVER operate pump with suction valve closed.
DO NOT change service application without approval of an authorized ITT Goulds Pumps representative.
Safety Apparel:
Insulated work gloves when handling hot bearings or using bearing heater Heavy work gloves when handling parts with sharp edges, especially
impellers
Safety glasses (with side shields) for eye protection Steel-toed shoes for foot protection when handling parts, heavy tools, etc. Other personal protective equipment to protect against hazardous/toxic fluids
Receiving:
Assembled pumping units and their components are heavy. Failure to properly lift and support equipment can result in serious physical injury and/or equipment damage. Lift equipment only at specifically identified lifting points or as instructed in the current IOM. Current manuals are available at
www.gouldspumps.com/literature_ioms.html or from your local ITT Goulds
Pumps sales representative. Note: Lifting devices (eyebolts, slings, spreaders, etc.) must be rated, selected, and used for the entire load being lifted.
Alignment:
WARNING
Shaft alignment procedures must be followed to prevent catastrophic failure of
drive components or unintended contact of rotating parts. Follow coupling manufacturer’s coupling installation and operation procedures.
S-4
WARNING
CAUTION
General Precautions
Before beginning any alignment procedure, make sure driver power is locked out.
Failure to lock out driver power will result in serious physical injury.
Piping:
Never draw piping into place by forcing at the flanged connections of the pump. This may impose dangerous strains on the unit and cause misalignment between
pump and driver. Pipe strain will adversely effect the operation of the pump resulting in physical injury and damage to the equipment.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
CAUTION
CAUTION
WARNING
Flanged Connections:
Use only fasteners of the proper size and material.
Replace all corroded fasteners.
Ensure all fasteners are properly tightened and there are no missing fasteners.
Startup and Operation:
When installing in a potentially explosive environment, please ensure that the
motor is properly certified.
Operating pump in reverse rotation may result in contact of metal parts, heat
generation, and breach of containment.
Lock out driver power to prevent accidental start-up and physical injury.
The impeller clearance setting procedure must be followed. Improperly setting the clearance or not following any of the proper procedures can result in sparks,
unexpected heat generation and equipment damage.
If using a cartridge mechanical seal, the centering clips must be installed and set screws loosened prior to setting impeller clearance. Failure to do so could result
in sparks, heat generation, and mechanical seal damage.
The coupling used in an ATEX classified environment must be properly certified
and must be constructed from a non-sparking material.
Never operate a pump without coupling guard properly installed. Personal injury will occur if pump is run without coupling guard.
Make sure to properly lubricate the bearings. Failure to do so may result in excess
heat generation, sparks, and / or premature failure.
The mechanical seal used in an ATEX classified environment must be properly certified. Prior to start up, ensure all points of potential leakage of process fluid to
the work environment are closed.
Never operate the pump without liquid supplied to mechanical seal. Running a mechanical seal dry, even for a few seconds, can cause seal damage and must be
avoided. Physical injury can occur if mechanical seal fails.
Never attempt to replace packing until the driver is properly locked out and the coupling spacer is removed.
WARNING
WARNING
S-5
Dynamic seals are not allowed in an ATEX classified environment.
DO NOT operate pump below minimum rated flows or with suction and/or discharge valve closed. These conditions may create an explosive hazard due to
vaporization of pumpage and can quickly lead to pump failure and physical injury.
WARNING
WARNING
WARNING
WARNING
WARNING
CAUTION
CAUTION
WARNING
CAUTION
CAUTION
General Precautions
Ensure pump is isolated from system and pressure is relieved before disassembling pump, removing plugs, opening vent or drain valves, or disconnecting piping.
Shutdown, Disassembly, and Reassembly:
Pump components can be heavy. Proper methods of lifting must be employed to avoid physical injury and/or equipment damage. Steel toed shoes must be worn at all times.
The pump may handle hazardous and/or toxic fluids. Observe proper decontamination procedures. Proper personal protective equipment should be worn. Precautions must be taken to prevent physical injury. Pumpage must be handled and disposed of in conformance with applicable environmental regulations.
Operator must be aware of pumpage and safety precautions to prevent physical injury.
Lock out driver power to prevent accidental startup and physical injury.
Allow all system and pump components to cool before handling them to prevent physical injury.
If pump is a Model NM3171, NM3196, 3198, 3298, V3298, SP3298, 4150, 4550, or 3107, there may be a risk of static electric discharge from plastic parts that are not properly grounded. If pumped fluid is non-conductive, pump should be drained and flushed with a conductive fluid under conditions that will not allow for a spark to be released to the atmosphere.
Never apply heat to remove an impeller. The use of heat may cause an explosion due to trapped fluid, resulting in severe physical injury and property damage.
Wear heavy work gloves when handling impellers as sharp edges may cause physical injury.
Wear insulated gloves when using a bearing heater. Bearings will get hot and can cause physical injury.
S-6
ATEX CONSIDERATIONS and INTENDED USE
Special care must be taken in potentially explosive environments to ensure that the equipment is properly maintained. This includes but is not limited to:
1. Monitoring the pump frame and liquid end temperature.
2. Maintaining proper bearing lubrication.
3. Ensuring that the pump is operated in the intended hydraulic range.
The ATEX conformance is only applicable when the pump unit is operated within its intended use. Operating, installing or maintaining the pump unit in any way that is not covered in the Instruction, Operation, and Maintenance manual (IOM) can cause serious personal injury or damage to the equipment. This includes any modification to the equipment or use of parts not provided by ITT Goulds Pumps. If there is any question regarding the intended use of the equipment, please contact an ITT Goulds representative before proceeding. Current IOMs are available at Pumps Sales representative.
All pumping unit (pump, seal, coupling, motor and pump accessories) certified for use in an ATEX classified environment, are identified by an ATEX tag secured to the pump or the baseplate on which it is mounted. A typical tag would look like this:
www.gouldspumps.com/literature_ioms.html or from your local ITT Goulds
The CE and the Ex designate the ATEX compliance. The code directly below these symbols reads as follows:
II = Group 2 2 = Category 2 G/D = Gas and Dust present T4 = Temperature class, can be T1 to T6 (see Table 1)
Table 1
Max permissible
surface temperature
Code
T1 842 (450) 700 (372)
T2 572 (300) 530 (277)
T3 392 (200) 350 (177)
T4 275 (135) 235 (113)
T5 212 (100) Option not available
T6 185 (85) Option not available
o
F (oC)
The code classification marked on the equipment must be in accordance with the specified area where the equipment will be installed. If it is not, do not operate the equipment and contact your ITT Goulds Pumps sales representative before proceeding.
Max permissible
liquid temperature
o
F (oC)
S-7
PARTS
The use of genuine Goulds parts will provide the safest and most reliable operation of your pump. ITT Goulds Pumps ISO certification and quality control procedures ensure the parts are manufactured to the highest quality and safety levels.
Please contact your local Goulds representative for details on genuine Goulds parts.
S-8
GENERAL INFORMATION
PUMP DESCRIPTION ...........................13
NAMEPLATE INFORMATION .....................14
RECEIVING THE PUMP .........................15
Storage Requirements ..........................15
Handling .................................15
PUMP DESCRIPTION
2
The Model 3910 is a vertical bearing frame in-line centrifugal pump that meets the requirements of API
Standard 610 11th Edition (ISO 13709).
The model is based pump sizes.
Casing - The casing is a vertical in-line mounted design. The gasket is fully confined. ANSI Class 300 raised face serrated flanges are standard; ANSI Class 300 flat face serrated and ring joint flanges are available.
Impeller - The impeller is fully enclosed and key driven by the shaft. An impeller nut with locking set screw prevents axial movement.
Seal Chamber Cover - The Model 3910 seal chamber cover meets API 682 2nd Edition dimensions for improved performance of mechanical seals.
on 5 power ends and 27 hydraulic
Power End - Regreasable bearings are standard. The power end is sealed with labyrinth seals. Pure oil mist lubrication is optional. Some modifications are required to convert from grease to oil mist.
Shaft - The standard shaft is machined and ground to
comply with API 610 11th Edition (ISO 13709) criteria.
Bearings - The inboard (radial) bearing carries only radial load; it is free to float axially in the frame. The outboard (thrust) bearing is shouldered and locked to the shaft and retained in the bearing frame to enable it to carry radial and thrust loads. All fits are precision machined to industry standards. The inboard bearing is a single row deep groove ball bearing. The outboard bearing is a duplex angular contact bearing, which uses a pair of single row angular contact ball bearings mounted back-to-back.
Motor Support - The fabricated steel motor support is designed to support the driver and to provide ample access to both the seal piping and the coupling.
Direction of Rotation - Counterclockwise (left hand) as viewed from the driver, looking at the pump shaft.
3910-11th IOM 5/08 13
NAMEPLATE INFORMATION
Every pump has a Goulds nameplate that provides information about the pump. The nameplate is located on the pump casing.
Special tags which provide additional information (mechanical seal data, etc.) and special tagging required by customers are located on the pump casing or on the bearing frame.
The standard nameplate provides information about the pump’s size, rating, bearings, serial number, hydrostatic test pressure of pressure containment parts, maximum allowable working pressure at designated temperature and construction / customer’s item number. Rating and hydrostatic test pressure are expressed in English units. Note the format of pump size: Discharge x Suction ­Nominal Impeller Diameter in inches, for example, 2x3-13 (Fig. 1A).
The standard nameplate is also available in a version which expresses the rating and hydrostatic test pressure in metric units (Fig. 1B).
When ordering spare parts you will need to identify pump model, size, serial number, and the item number of required parts. Pump information can be taken from the Goulds nameplate. Item numbers can be found in this manual.
Fig. 1A
If applicable, your pump unit may have the ATEX tag affixed to the pump and/or baseplate (Fig. 2). See the Safety section for a description of the symbols and codes.
Fig. 1B
Fig. 2
14 3910-11th IOM 5/08
RECEIVING THE PUMP
Inspect the pump as soon as it is received. Carefully check that everything is in good order. Make notes of damaged or missing items on the receipt and freight bill. File any claims with the transportation company as soon as possible.
STORAGE REQUIREMENTS
Short Term (Less than 6 months) Goulds normalpackaging
procedure is designed to protect the pump during shipping. Upon receipt, store in a covered and dry location.
Long Term (More than 6 months) Preservative treatment of bearings and machined surfaces will be required. Rotate shaft several times every 3 months. Refer to driver and coupling manufacturers for their long term storage procedures. Store in a covered and dry location.
NOTE: Long term storage treatment may be purchased with initial pump order.
HANDLING
! WARNING
s
Pump and components are heavy. Failure to properly lift and support equipment could result in serious physical injury, or damage to pumps.
Use care when moving pumps. Lifting equipment must be able to adequately support the entire assembly. Hoist bare pump using suitable hooks through the holes in the frame mounted support or suitable slings through the large openings in the casing mounted support (Fig. 3).
2
Fig. 4
Or with hooks through the holes in the frame mounted support or with slings through the large openings in the casing mounted support.
Fig. 3
! WARNING
Units with drivers mounted are moved with slings under the pump casing and driver (Figs. 4 and 5).
3910-11th IOM 5/08 15
s
Units with drivers mounted can be top heavy. Driver weight could cause the assembled unit to overturn and could result in serious physical injury, or damage to pumps.
Fig. 5
16 3910-11th IOM 5/08
INSTALLATION
GENERAL..................................17
SITE/FOUNDATION............................17
ALIGNMENT AND ALIGNMENT CRITERIA .............18
General Considerations..........................18
Alignment Criteria ............................18
ALIGNMENT TROUBLESHOOTING ..................18
PIPING....................................19
Suction Piping ..............................19
Discharge Piping .............................20
Bypass Piping ..............................20
Auxiliary Piping .............................20
Final Piping Check ............................20
Equipment that will operate in a potentially explosive environment must be installed in accordance with the
!
following instructions.
GENERAL
3
Procedures for installation described within this section are general in nature. It is assumed that the installer has a basic knowledge of acceptable methods. More detailed procedures are described in various publications,
SITE/FOUNDATION
A pump should be located near the supply of liquid and have adequate space for operation, maintenance, and inspection. Be sure to allow for crane or hoist service.
Model 3910 in-line pumps are designed to be mounted directly in the piping. The pump casing has a flat base which may be mounted on a concrete foundation which has been poured on a solid footing.
including API Recommended Practice 686/ PIP (Process Industry Practices) REIE 686, “Recommended Practices for Machinery Installation and Installation Design.”
Optional casing supports, which provide additional stability, are also available (Fig. 7).
Fig. 7
If it is intended that the piping support the pumping unit, piping supports should be properly designed to accommodate the weight of the pumping unit.
Fig. 6
The foundation must be able to absorb any vibration and to form a permanent, rigid support for the pumping unit (Fig. 6). Goulds recommends this mounting method.
3910-11th IOM 5/08 17
All equipment being installed must be properly
!
grounded to prevent unexpected static electric discharge.
ALIGNMENT AND ALIGNMENT CRITERIA
Alignment procedures must be followed to prevent
!
unintended contact of rotating parts. Follow coupling manufacturer's installation and operation procedures.
GENERAL CONSIDERATIONS
! WARNING
s
Before beginning any alignment procedure, make sure driver power is locked out. Failure to lock out driver power will result in serious physical injury.
To remove coupling guard, refer to coupling guard installation and disassembly instructions in Appendix I.
The times at which alignment is checked and adjusted are:
Initial Alignment (Cold Alignment) is done prior to operation when the pump and the driver are at ambient temperatures.
Final Alignment (Hot Alignment) is done after operation when the pump and driver are at operating temperatures.
After First Run - To obtain correct alignment when
both pump and driver are at operating temperature. Thereafter, alignment should be checked periodically in accordance with plant operating procedures.
NOTE: Alignment check must be made if process temperature changes, piping changes and/or pump service is performed.
Alignment is achieved by adding or removing shims from under the flange of the driver and/or shifting driver horizontally as needed.
NOTE: Proper alignment is the responsibility of the installer and user of the unit.
Accurate alignment of the equipment must be attained. Trouble-free operation can be accomplished by achieving alignment within the levels specified in the following section.
Three common alignment methods are utilized:
Reverse Dial Indicator method is most common.
Laser method is similar to reverse dial indicator
method, but uses a laser to obtain the necessary mea­surements.
Dial Indicator (rim-and-face) method.
Follow alignment equipment manufacturer's procedures when utilizing reverse dial indicator or laser methods. A detailed procedure for alignment using the dial indicator (rim-and-face) method is included as Appendix II.
ALIGNMENT CRITERIA
Good alignment is attained when readings as specified in this section have been achieved with pump and driver at operating temperatures (final alignment).
Table 2 shows maximum allowable Total Indicator Reading (T.I.R.) for parallel and angular misalignment.
Table 2
Maximum Allowable
Parallel and Angular Misalignment
Maximum Allowable Misalignment
Group
All
Parallel Angular
0.05 mm
(.002 in.)
[0.125 mm/cm (.0005 in. /in.)
0.03 degrees
of coupling face diameter]
ALIGNMENT TROUBLESHOOTING
Problem Probable Cause Remedy
Cannot obtain horizontal (Side-to-Side) alignment, angular or parallel
Driver flange bolt bound
18 3910-11th IOM 5/08
Loosen motor support hold down bolts and slide motor support and driver until hori­zontal alignment is achieved.
PIPING
Guidelines for piping are given in the “Hydraulic Institute Standards,” available from:
Hydraulic Institute 9 Sylvan Way Parsippany, NJ 07054
and in API RP 686, and must be reviewed prior to pump installation.
! WARNING
s
Never draw piping into place by forcing at the flanged connections of the pump. This may impose dangerous strains on the unit and cause misalignment between pump and driver. Pipe strain will adversely affect the operation of the pump resulting in physical injury and damage to the equipment.
Flange loads from the piping system, including
!
those from thermal expansion of the piping, must not exceed the limits of the pump. Casing deforma­tion can result in contact with rotating parts which can result in excess heat generation, sparks and premature failure.
1. Piping runs should be as short as possible to minimize friction losses.
2. It is suggested that expansion loops be properly designed and installed in suction and/or discharge lines when handling liquids at elevated tempera- tures, so thermal expansion of piping will not draw pump out of alignment.
3. The piping should be arranged to allow pump flushing prior to removal of the unit on services handling hazardous liquids.
4. Carefully clean all pipe parts, valves and fittings, and pump branches prior to assembly.
5. All piping must be supported independently of, and line up naturally with, the pump flanges. Table 2 shows piping flange alignment criteria.
Bottom of casing should be supported by a solid
6. foundation or casing feet should be used.
SUCTION PIPING
$
NPSHAmust always exceed NPSHRas shown on Goulds performance curves received with order. (Reference Hydraulic Institute for NPSH and pipe friction values needed to evaluate suction piping).
Properly designed and installed suction piping is a necessity for trouble-free pump operation. Suction piping should be flushed BEFORE connection to the pump.
1. Use of elbows close to the pump suction flange should be avoided. There should be a minimum of two (2) pipe diameters of straight pipe [five (5) pipe diameters is preferred] between the elbow and suction inlet. Where used, elbows should be long radius.
2. Use suction pipe one (1) or two (2) sizes larger than the pump suction, with a reducer at the suction flange. Suction piping should never be of smaller diameter than the pump suction.
3. Reducers, if used, should be eccentric and located at the pump suction flange with sloping side down.
$
Pump must never be throttled on suction side.
4. A suction screen should be installed prior to initial start-up and when suction system has been opened for work. The screen should be of the cone type with a net area equal to at least three (3) times the cross sectional area of the suction pipe. The mesh of the screen should be sized to prevent particles larger than
1.6 mm (1/16 in.) from entering the pump and should be installed in a spool piece to allow removal for cleaning. The screen should remain in the system until periodic inspection shows system is clean.
CAUTION
CAUTION
3
Table 4
Piping Flange Alignment
5. Separate suction lines are recommended when more than one pump is operating from the same source of supply.
Type Criteria
Axial
Parallel
Concentric Flange bolts should easily install by hand.
In no case should loads on the pump flanges exceed the
limits stated in API Standard 610, 11th Edition (ISO
13709).
3910-11th IOM 5/08 19
Flange gasket thickness ± 0.8 mm (.03 in.).
0.001 mm/mm (.001 in./in.) of flange diameter to a maximum of 0.8 mm (.03 in.).
Suction Lift Conditions
1. Suction pipe must be free from air pockets.
2. Suction piping must slope upwards to pump.
3. All joints must be air tight.
4. A means of priming the pump must be provided.
Suction Head/Flooded Suction Conditions
1. An isolation valve should be installed in the suction line at least two (2) pipe diameters from the pump suction to permit closing of the line for pump inspection and maintenance.
2. Keep suction pipe free from air pockets.
3. Piping should be level or slope gradually downward from the source of supply.
4. No portion of the piping should extend below pump suction flange.
5. The size of entrance from supply should be one (1) or two (2) sizes larger than the suction pipe.
6. The suction pipe must be adequately submerged below the liquid surface to prevent vortices and air entrainment at the supply.
DISCHARGE PIPING
Properly designed and installed discharge piping is a necessity for trouble-free pump operation. Discharge piping should be flushed BEFORE connection to the pump.
1. Isolation and check valves should be installed in discharge line. Locate the check valve between isolation valve and pump; this will permit inspection of the check valve. The isolation valve is required for priming, regulation of flow, and for inspection and maintenance of pump. The check valve prevents pump or seal damage due to reverse flow through the pump when the driver is turned off.
2. Increasers, if used, should be placed between pump and check valves.
3. Cushioning devices should be used to protect the pump from surges and water hammer if quick-closing valves are installed in system.
BYPASS PIPING
Systems that require operation at reduced flows for prolonged periods should be provided with a bypass line connected from the discharge side (before any valves) to the source of suction.
A minimum flow orifice can be sized and installed in bypass line to preclude bypassing excessive flows. Consult nearest sales office or factory for assistance in sizing orifice.
An automatic recirculation control valve and/or solenoid operated valve should be considered if a constant bypass (i.e. orifice) is not possible.
AUXILIARY PIPING
The mechanical seal must have an appropriate seal
!
flush system. Failure to do so will result in excess heat generation and seal failure.
Cooling systems such as those for bearing
!
lubrication, mechanical seal systems, etc., where provided, must be operating properly to prevent excess heat generation, sparks, and premature failure.
Sealing systems that are not self purging or self
!
venting, such as plan 23, require manual venting prior to operation. Failure to do so will result in excess heat generation and seal failure.
Auxiliary piping may be required for seal chamber cover cooling, mechanical seal flush or other special features supplied with the pump. Consult pump data sheet for specific auxiliary piping recommendations.
If seal chamber cover cooling is required, follow guidelines listed below.
1. Flows of 4 l/min. (1 GPM) will generally satisfy cooling requirements.
2. Cooling water pressure should not exceed
7.0 kg/cm
2
(100 psig).
FINAL PIPING CHECK
After connecting the piping to pump:
The Preventive Maintenance section must be
!
adhered to in order to keep the applicable ATEX classification of the equipment. Failure to follow these procedures will void the ATEX classification for the equipment.
Check alignment, per alignment criteria outlined
!
previously, to determine if pipe strain has affected alignment. If pipe strain exists, correct piping.
20 3910-11th IOM 5/08
OPERATION
PREPARATION FOR START-UP ....................21
Checking Rotation ............................21
Coupling Pump and Driver ........................21
Lubricating Bearings ...........................22
Shaft Sealing ...............................22
Priming Pump ..............................22
Start-up Precautions ...........................23
STARTING PUMP .............................24
OPERATION ................................24
General Considerations..........................24
Operational Checks............................24
Operating at Reduced Capacity .....................25
Operating Under Freezing Conditions ..................25
SHUTDOWN ................................25
FINAL ALIGNMENT ...........................25
PREPARATION FOR START-UP
4
When installation in a potentially explosive
!
environment, ensure that the motor is properly certified.
CHECKING ROTATION
$
Serious damage may result if pump is run in the wrong rotation.
1. Lock out power to driver.
s
! WARNING
Lock out driver power to prevent accidental start-up and physical injury.
2. Make sure coupling hubs are securely fastened to shafts.
! WARNING
s
Do NOT jog a coupled pump.
NOTE: Pump is shipped with coupling spacer removed.
3. Unlock driver power.
4. Make sure everyone is clear. Jog driver just long enough to determine direction of rotation. Rotation must correspond to arrow on bearing frame.
CAUTION
5. Lock out power to driver.
COUPLING PUMP AND DRIVER
! WARNING
s
Lock out driver power to prevent accidental rotation and physical injury.
The coupling used in an ATEX classified environ-
!
ment must be properly certified.
1. Install and lubricate coupling per manufacturer’s instructions.
The coupling guard used in an ATEX classified
!
environment must be constructed from a non­sparking material.
2. Install coupling guard. Refer to coupling guard installation instructions in Appendix I.
! WARNING
s
Never operate a pump without coupling guard properly installed. Refer to Appendix I for coupling guard installation instructions. Personal injury will occur if pump is run without coupling guard.
3910-11th IOM 5/08 21
LUBRICATING BEARINGS
Bearings musts be lubricated properly in order to
!
prevent excess heat generation, sparks and premature failure.
Grease Lubrication
Greased lubricated ball bearings are standard on the Model 3910 units.
Sealing systems that are not self purging or self
!
venting, such as plan 23, require manual venting prior to operation. Failure to do so will result in excess heat generation and seal failure.
For satisfactory operation, there must be a liquid film between seal faces to lubricate them. Refer to seal manufacturer’s drawing for location of taps. Some methods which may be used to flush/cool the seal are:
The bearings are greased at the factory.
See Preventive Maintenance section for lubrication recommendations.
Pure Oil Mist Lubrication
Pure oil mist is an optional feature for the Model 3910. Follow oil mist generator manufacturer’s instructions. The inlet and outlet connections are located on the side of the bearing frame.
See Preventive Maintenance section for lubrication recommendations and connection locations.
! WARNING
s
Operation of the unit without proper lubrication will cause bearing failure and pump seizure.
SHAFT SEALING WITH MECHANICAL SEAL
The mechanical seal used in an ATEX classified
!
environment must be properly certified.
Pumps may be shipped with or without mechanical seal installed. Cartridge type mechanical seals are commonly used for this model. Cartridge seals are preset at the seal manufacturer’s facility and require no field settings. Cartridge seals installed by the user require disengagement of the holding clips prior to operation, allowing the seal to slide into place. If the seal has been installed in the pump by Goulds, these clips have already been disengaged. For other types of mechanical seals, refer to the seal manufacturer’s instructions for installation and setting.
Product Flushing - In this arrangement, the pumpage is
piped from the casing (and cooled in an external heat exchanger when required) then injected into seal chamber.
External Flush - A clean, cool compatible liquid is
injected from an outside source directly into seal chamber. Flushing liquid must be at a pressure 0.35-1.05
2
kg/cm rate should be 2-8 l/min. (
Other methods may be used which make use of multiple
gland connections and/or seal chamber connections. Refer to documentation supplied with the pump, mechanical seal reference drawing, and piping diagrams.
(5-15 psi) greater than seal chamber pressure. Injection
1
-2 GPM).
2
PRIMING PUMP
Pumps must be fully primed at all times during
!
operation.
Never start the pump until it has been properly primed. Several different methods of priming can be used, depending upon type of installation and service involved.
Suction Supply Above Pump
1. Slowly open the suction valve (Fig. 8).
Connection of Sealing Liquid
The mechanical seal must have an appropriate seal
!
flush system. Failure to do so will result in excess heat generation and seal failure.
Cooling systems such as those for bearing
!
lubrication, mechanical seal systems, etc., where provided, must be operating properly to prevent excess heat generation, sparks, and premature failure.
2. Open air vents on the suction and discharge piping, casing, seal chamber, and seal piping, if provided, until all air is vented and only liquid flows out.
3. Close the vents.
22 3910-11th IOM 5/08
Fig. 8
Suction Supply Below Pump
A foot valve and outside source of liquid may be used to prime the pump. Outside source of liquid can come from a priming pump pressurized discharge line, or other supply (Fig. 9 and 10).
1. Close discharge valve and open air vents in suction and discharge piping, casing, seal chamber, and seal piping, if provided.
2. Open valve in outside supply line until all air is vented and only liquid flows out.
! WARNING
s
When handling hazardous and/or toxic fluids, proper personal protective equipment is required. If pump is being drained, precautions must be taken to prevent physical injury. Pumpage must be handled and dis­posed of in conformance with applicable regulations.
3. Close the vents and then the outside supply line.
Other Methods of Priming Pump
Priming by ejector.
Fig. 9
Priming by automatic priming pump.
START-UP PRECAUTIONS
$
Ensure that pump and systems are free of foreign
!
objects before operating and that objects cannot enter the pump during operation. Foreign objects in the pumpage or piping system can cause blockage of flow which can result in excess heat generation, sparks, and premature failure.
$
A build up of gases within the pump, sealing system
!
and or process piping system may result in an explosive environment within the pump or process piping system. Ensure process piping system, pump, and sealing system are properly vented prior to operation.
1. All equipment and personal safety related devices and controls must be installed and operating properly.
2. To prevent premature pump failure at initial start-up due to dirt or debris in the pipe system, ensure the pump can be run continuously at full speed and flow for 2 to 3 hours.
CAUTION
CAUTION
4
3. Variable speed drivers should be brought to rated
Fig. 10
3910-11th IOM 5/08 23
speed as quickly as possible.
4. Variable speed drivers should not be adjusted or checked for speed governor or overspeed trip settings while coupled to the pump at initial start-up. If settings have not been verified, uncouple the unit and refer to driver manufacturer’s instructions for assistance.
5. Running a new or rebuilt pump at slow speeds may not provide enough flow to adequately flush and cool the wear ring and seal chamber cover bushing.
6. Pumpage temperatures in excess of 93° C (200° F) will require warm-up of pump prior to operation. Circulate a small amount of pumpage through the pump until the
STARTING PUMP
casing temperature is within 56° C (100° F) of the pumpage temperature and evenly heated.
NOTE: Warm-up rate should not exceed 1.4° C (2.5° F) per minute.
1. Make sure suction valve and any recirculation or cooling lines are open.
2. Fully close or partially open discharge valve as dictated by system conditions.
3. Start driver.
$
Immediately observe pressure gauges. If discharge pressure is not quickly attained, stop driver, reprime, and attempt to restart.
CAUTION
OPERATION
GENERAL CONSIDERATIONS
$
Always vary capacity with regulating valve in the discharge line. NEVER throttle flow from the suction side.
Driver may overload if the pumpage specific gravity (density) is greater than originally assumed, or the rated flow rate is exceeded.
Always operate the pump at or near the rated conditions to prevent damage resulting from cavitation or recirculation.
OPERATIONAL CHECKS
$
The following are minimum operational checks for the pump only. Consult driver and auxiliary equipment manufacturers’ literature for additional information.
1. On grease lubricated units, remove grease relief plugs to verify that grease is present. Replace plugs.
2. On pure oil mist lubricated units, remove viewing port plugs and assure oil mist is flowing properly. Replace plugs.
CAUTION
CAUTION
4. Slowly open discharge valve until the desired flow is obtained.
CAUTION
$
Observe pump for vibration levels, bearing tempera­ture, and excessive noise. If normal levels are exceeded, shut down and resolve.
3. Check bearing temperatures using a pyrometer or other accurate temperature measuring device. Monitor bearing temperature frequently during initial operation to determine if a bearing problem exists as well as to establish normal bearing operating temperature.
4. On units equipped with auxiliary piping, assure that proper flows have been established and that equipment is operating properly.
5. Establish baseline vibration readings to determine normal running conditions. If it is determined that the unit is running rough, consult factory.
6. Monitor all gauges to ensure pump is running at or near rating and that suction screen (when used) is not clogged.
!
OPERATING AT REDUCED CAPACITY
! WARNING
s
Do NOT operate pump below minimum rated flows or with discharge valve closed. These conditions may create an explosive hazard due to vaporization of pumpage and can quickly lead to pump failure and physical injury.
24 3910-11th IOM 5/08
Loading...
+ 56 hidden pages