This manual provides instructions for the Installation, Operation, and Maintenance of the Goulds
Model 3910 Vertical Bearing Frame In-line Process Pump designed to meet the requirements of
the 11th Edition (ISO 13709) of API* Standard 610. This manual covers the standard product
plus common options
supplied. This manual must be read and understood before installation and maintenance.
The design, materials, and workmanship incorporated in the construction of Goulds pumps make them
capable of giving long, trouble-free service. The life and satisfactory service of any mechanical unit,
however, are enhanced and extended by correct application, proper installation, periodic inspection,
condition monitoring, and careful maintenance. This instruction manual was prepared to assist operators
in understanding the construction and the correct methods of installing, operating, and maintaining these
pumps.
ITT - Goulds Pumps shall not be liable for physical injury, damage or delays caused by a failure
to observe the instructions for installation, operation, and maintenance contained in this manual.
When pumping unit is installed in a potentially explosive atmosphere, the instructions after the Ex symbol must be
!
followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there is any
question regarding these requirements or if the equipment is to be modified, please contact a Goulds representative
before proceeding.
that are available. For special options, supplemental instructions are
Warranty is valid only when genuine ITT - Goulds Pumps parts are used.
Use of the equipment on a service other than stated in the order will nullify the warranty, unless written
approval is obtained in advance from ITT - Goulds Pumps.
Supervision by an authorized ITT - Goulds representative is recommended to assure proper installation.
Additional manuals can be obtained by contacting your local ITT - Goulds representative or by calling
1-(800)-446-8537.
THIS MANUAL EXPLAINS
Proper Installation
n
Start-up Procedures
n
Operation Procedures
n
Routine Maintenance
n
Pump Overhaul
n
Troubleshooting
n
Ordering Spare or Repair Parts
n
* American Petroleum Institute
1220 L Street, Northwest
Washington, D.C. 20005
3910-11th IOM 5/085
TABLE OF CONTENTS
PAGE
9SAFETY
13GENERAL INFORMATION
17INSTALLATION
21OPERATION
27PREVENTIVE MAINTENANCE
31DISASSEMBLY & REASSEMBLY
SECTION
1
2
3
4
5
6
61SPARE PARTS
63APPENDICES
I - 63Installation & Disassembly Instructions for Goulds ANSI B15.1 Coupling Guards
A - 63 (Casing Mount Motor Support Only) - All Power Ends Except those with
Optional Air Cooling Package
B - 67 (Casing Mount Motor Support Only) - Power Ends with Optional Air Cooling
Package
II - 71Dial Indicator (Rim-and-Face) Alignment Procedure
III -75Removal and Installation of Back Pull-Out Assembly Using Goulds Back Pull-Out
Removal Device
7
8
3910-11th IOM 5/087
83910-11th IOM 5/08
IMPORTANT SAFETY NOTICE
To: Our Valued Customers
User safety is a major focus in the design of our products. Following the precautions outlined in this
manual will minimize your risk of injury.
ITT Goulds pumps will provide safe, trouble-free service when properly installed, maintained, and
operated.
Safe installation, operation, and maintenance of ITT Goulds Pumps equipment are an essential end user
responsibility. This Pump Safety Manual identifies specific safety risks that must be considered at all
times during product life. Understanding and adhering to these safety warnings is mandatory to ensure
personnel, property, and/or the environment will not be harmed. Adherence to these warnings alone,
however, is not sufficient — it is anticipated that the end user will also comply with industry and corporate
safety standards. Identifying and eliminating unsafe installation, operating and maintenance practices is
the responsibility of all individuals involved in the installation, operation, and maintenance of industrial
equipment.
Please take the time to review and understand the safe installation, operation, and maintenance guidelines
outlined in this Pump Safety Manual and the Instruction, Operation, and Maintenance (IOM) manual.
Current manuals are available at
your nearest Goulds Pumps sales representative.
www.gouldspumps.com/literature_ioms.html or by contacting
These manuals must be read and understood before installationand start-up.
For additional information, contact your nearest Goulds Pumps sales representative or visit our Web site at
www.gouldspumps.com.
S-1
SAFETY WARNINGS
Specific to pumping equipment, significant risks bear reinforcement above and beyond normal safety precautions.
WARNING
A pump is a pressure vessel with rotating parts that can be hazardous. Any pressure vessel can explode,
rupture, or discharge its contents if sufficiently over pressurized causing death, personal injury, property
damage, and/or damage to the environment. All necessary measures must be taken to ensure over
pressurization does not occur.
WARNING
Operation of any pumping system with a blocked suction and discharge must be avoided in all cases.
Operation, even for a brief period under these conditions, can cause superheating of enclosed pumpage and
result in a violent explosion. All necessary measures must be taken by the end user to ensure this condition is
avoided.
WARNING
The pump may handle hazardous and/or toxic fluids. Care must be taken to identify the contents of the pump
and eliminate the possibility of exposure, particularly if hazardous and/or toxic. Potential hazards include, but
are not limited to, high temperature, flammable, acidic, caustic, explosive, and other risks.
WARNING
Pumping equipment Instruction, Operation, and Maintenance manuals clearly identify accepted methods for
disassembling pumping units. These methods must be adhered to. Specifically, applying heat to impellers
and/or impeller retaining devices to aid in their removal is strictly forbidden. Trapped liquid can rapidly
expand and result in a violent explosion and injury.
ITT Goulds Pumps will not accept responsibility for physical injury, damage, or delays caused by a failure to
observe the instructions for installation, operation, and maintenance contained in this Pump Safety Manual or the
current IOM available at www.gouldspumps.com/literature.
S-2
SAFETY
DEFINITIONS
Throughout this manual the words WARNING, CAUTION, ELECTRICAL, and ATEX are used to indicate
where special operator attention is required.
Observe all Cautions and Warnings highlighted in this Pump Safety Manual and the IOM provided with
your equipment.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Example:
Pump shall never be operated without coupling guard installed correctly.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Example: Throttling flow from the suction side may cause cavitation and pump damage.
ELECTRICAL HAZARD
Indicates the possibility of electrical risks if directions are not followed.
Example:Lock out driver power to prevent electric shock, accidental start-up, and physical injury.
When installed in potentially explosive atmospheres, the instructions that follow the Ex symbol must be
followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there
is any question regarding these requirements or if the equipment is to be modified, please contact an ITT
Goulds Pumps representative before proceeding.
Example:
parts, resulting in a spark and heat generation.
Improper impeller adjustment could cause contact between the rotating and stationary
S-3
GENERAL PRECAUTIONS
WARNING
A pump is a pressure vessel with rotating parts that can be hazardous. Hazardous fluids may be contained by the
pump including high temperature, flammable, acidic, caustic, explosive, and other risks. Operators and
maintenance personnel must realize this and follow safety measures. Personal injuries will result if procedures
outlined in this manual are not followed. ITT Goulds Pumps will not accept responsibility for physical injury,
damage or delays caused by a failure to observe the instructions in this manual and the IOM provided with your
equipment.
WARNING
WARNING
General Precautions
NEVER use heat to disassemble pump due to risk of explosion from tapped liquid.
NEVER APPLY HEAT TO REMOVE IMPELLER. It may explode due to
trapped liquid.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
NEVER operate pump without safety devices installed.
NEVER operate pump without coupling guard correctly installed.
NEVER run pump below recommended minimum flow when dry, or without
prime.
ALWAYS lock out power to the driver before performing pump maintenance.
NEVER operate pump with discharge valve closed.
NEVER operate pump with suction valve closed.
DO NOT change service application without approval of an authorized ITT
Goulds Pumps representative.
Safety Apparel:
Insulated work gloves when handling hot bearings or using bearing heater
Heavy work gloves when handling parts with sharp edges, especially
impellers
Safety glasses (with side shields) for eye protection
Steel-toed shoes for foot protection when handling parts, heavy tools, etc.
Other personal protective equipment to protect against hazardous/toxic fluids
Receiving:
Assembled pumping units and their components are heavy. Failure to properly lift
and support equipment can result in serious physical injury and/or equipment
damage. Lift equipment only at specifically identified lifting points or as
instructed in the current IOM. Current manuals are available at
www.gouldspumps.com/literature_ioms.htmlor from your local ITT Goulds
Pumps sales representative. Note: Lifting devices (eyebolts, slings, spreaders, etc.)
must be rated, selected, and used for the entire load being lifted.
Alignment:
WARNING
Shaft alignment procedures must be followed to prevent catastrophic failure of
drive components or unintended contact of rotating parts. Follow coupling
manufacturer’s coupling installation and operation procedures.
S-4
WARNING
CAUTION
General Precautions
Before beginning any alignment procedure, make sure driver power is locked out.
Failure to lock out driver power will result in serious physical injury.
Piping:
Never draw piping into place by forcing at the flanged connections of the pump.
This may impose dangerous strains on the unit and cause misalignment between
pump and driver. Pipe strain will adversely effect the operation of the pump
resulting in physical injury and damage to the equipment.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
CAUTION
CAUTION
WARNING
Flanged Connections:
Use only fasteners of the proper size and material.
Replace all corroded fasteners.
Ensure all fasteners are properly tightened and there are no missing fasteners.
Startup and Operation:
When installing in a potentially explosive environment, please ensure that the
motor is properly certified.
Operating pump in reverse rotation may result in contact of metal parts, heat
generation, and breach of containment.
Lock out driver power to prevent accidental start-up and physical injury.
The impeller clearance setting procedure must be followed. Improperly setting
the clearance or not following any of the proper procedures can result in sparks,
unexpected heat generation and equipment damage.
If using a cartridge mechanical seal, the centering clips must be installed and set
screws loosened prior to setting impeller clearance. Failure to do so could result
in sparks, heat generation, and mechanical seal damage.
The coupling used in an ATEX classified environment must be properly certified
and must be constructed from a non-sparking material.
Never operate a pump without coupling guard properly installed. Personal injury
will occur if pump is run without coupling guard.
Make sure to properly lubricate the bearings. Failure to do so may result in excess
heat generation, sparks, and / or premature failure.
The mechanical seal used in an ATEX classified environment must be properly
certified. Prior to start up, ensure all points of potential leakage of process fluid to
the work environment are closed.
Never operate the pump without liquid supplied to mechanical seal. Running a
mechanical seal dry, even for a few seconds, can cause seal damage and must be
avoided. Physical injury can occur if mechanical seal fails.
Never attempt to replace packing until the driver is properly locked out and the
coupling spacer is removed.
WARNING
WARNING
S-5
Dynamic seals are not allowed in an ATEX classified environment.
DO NOT operate pump below minimum rated flows or with suction and/or
discharge valve closed. These conditions may create an explosive hazard due to
vaporization of pumpage and can quickly lead to pump failure and physical injury.
WARNING
WARNING
WARNING
WARNING
WARNING
CAUTION
CAUTION
WARNING
CAUTION
CAUTION
General Precautions
Ensure pump is isolated from system and pressure is relieved before
disassembling pump, removing plugs, opening vent or drain valves, or
disconnecting piping.
Shutdown, Disassembly, and Reassembly:
Pump components can be heavy. Proper methods of lifting must be employed to
avoid physical injury and/or equipment damage. Steel toed shoes must be worn at
all times.
The pump may handle hazardous and/or toxic fluids. Observe proper
decontamination procedures. Proper personal protective equipment should be
worn. Precautions must be taken to prevent physical injury. Pumpage must be
handled and disposed of in conformance with applicable environmental
regulations.
Operator must be aware of pumpage and safety precautions to prevent physical
injury.
Lock out driver power to prevent accidental startup and physical injury.
Allow all system and pump components to cool before handling them to prevent
physical injury.
If pump is a Model NM3171, NM3196, 3198, 3298, V3298, SP3298, 4150, 4550,
or 3107, there may be a risk of static electric discharge from plastic parts that are
not properly grounded. If pumped fluid is non-conductive, pump should be
drained and flushed with a conductive fluid under conditions that will not allow
for a spark to be released to the atmosphere.
Never apply heat to remove an impeller. The use of heat may cause an explosion
due to trapped fluid, resulting in severe physical injury and property damage.
Wear heavy work gloves when handling impellers as sharp edges may cause
physical injury.
Wear insulated gloves when using a bearing heater. Bearings will get hot and can
cause physical injury.
S-6
ATEX CONSIDERATIONS and INTENDED USE
Special care must be taken in potentially explosive environments to ensure that the equipment is properly
maintained. This includes but is not limited to:
1. Monitoring the pump frame and liquid end temperature.
2. Maintaining proper bearing lubrication.
3. Ensuring that the pump is operated in the intended hydraulic range.
The ATEX conformance is only applicable when the pump unit is operated within its intended use. Operating,
installing or maintaining the pump unit in any way that is not covered in the Instruction, Operation, and
Maintenance manual (IOM) can cause serious personal injury or damage to the equipment. This includes any
modification to the equipment or use of parts not provided by ITT Goulds Pumps. If there is any question
regarding the intended use of the equipment, please contact an ITT Goulds representative before proceeding.
Current IOMs are available at
Pumps Sales representative.
All pumping unit (pump, seal, coupling, motor and pump accessories) certified for use in an ATEX classified
environment, are identified by an ATEX tag secured to the pump or the baseplate on which it is mounted. A
typical tag would look like this:
www.gouldspumps.com/literature_ioms.htmlor from your local ITT Goulds
The CE and the Ex designate the ATEX compliance. The code directly below these symbols reads as follows:
II = Group 2
2 = Category 2
G/D = Gas and Dust present
T4 = Temperature class, can be T1 to T6 (see Table 1)
Table 1
Max permissible
surface temperature
Code
T1 842 (450) 700 (372)
T2 572 (300) 530 (277)
T3 392 (200) 350 (177)
T4 275 (135) 235 (113)
T5 212 (100) Option not available
T6 185 (85) Option not available
o
F (oC)
The code classification marked on the equipment must be in accordance with the specified area where the
equipment will be installed. If it is not, do not operate the equipment and contact your ITT Goulds Pumps sales
representative before proceeding.
Max permissible
liquid temperature
o
F (oC)
S-7
PARTS
The use of genuine Goulds parts will provide the safest and
most reliable operation of your pump. ITT Goulds Pumps ISO
certification and quality control procedures ensure the parts are
manufactured to the highest quality and safety levels.
Please contact your local Goulds representative for details on
genuine Goulds parts.
S-8
GENERAL INFORMATION
PUMP DESCRIPTION ...........................13
NAMEPLATE INFORMATION .....................14
RECEIVING THE PUMP .........................15
Storage Requirements ..........................15
Handling .................................15
PUMP DESCRIPTION
2
The Model 3910 is a vertical bearing frame in-line
centrifugal pump that meets the requirements of API
Standard 610 11th Edition (ISO 13709).
The model is based
pump sizes.
Casing - The casing is a vertical in-line mounted design.
The gasket is fully confined. ANSI Class 300 raised face
serrated flanges are standard; ANSI Class 300 flat face
serrated and ring joint flanges are available.
Impeller - The impeller is fully enclosed and key driven by
the shaft. An impeller nut with locking set screw prevents
axial movement.
Seal Chamber Cover - The Model 3910 seal chamber
cover meets API 682 2nd Edition dimensions for improved
performance of mechanical seals.
on 5 power ends and 27 hydraulic
Power End - Regreasable bearings are standard. The
power end is sealed with labyrinth seals. Pure oil mist
lubrication is optional. Some modifications are required to
convert from grease to oil mist.
Shaft - The standard shaft is machined and ground to
comply with API 610 11th Edition (ISO 13709) criteria.
Bearings - The inboard (radial) bearing carries only radial
load; it is free to float axially in the frame. The outboard
(thrust) bearing is shouldered and locked to the shaft and
retained in the bearing frame to enable it to carry radial and
thrust loads. All fits are precision machined to industry
standards. The inboard bearing is a single row deep groove
ball bearing. The outboard bearing is a duplex angular
contact bearing, which uses a pair of single row angular
contact ball bearings mounted back-to-back.
Motor Support - The fabricated steel motor support is
designed to support the driver and to provide ample access
to both the seal piping and the coupling.
Direction of Rotation - Counterclockwise (left hand) as
viewed from the driver, looking at the pump shaft.
3910-11th IOM 5/0813
NAMEPLATE INFORMATION
Every pump has a Goulds nameplate that provides
information about the pump. The nameplate is located on
the pump casing.
Special tags which provide additional information
(mechanical seal data, etc.) and special tagging required by
customers are located on the pump casing or on the bearing
frame.
The standard nameplate provides information about the
pump’s size, rating, bearings, serial number, hydrostatic
test pressure of pressure containment parts, maximum
allowable working pressure at designated temperature and
construction / customer’s item number. Rating and
hydrostatic test pressure are expressed in English units.
Note the format of pump size: Discharge x Suction Nominal Impeller Diameter in inches, for example, 2x3-13
(Fig. 1A).
The standard nameplate is also available in a version which
expresses the rating and hydrostatic test pressure in metric
units (Fig. 1B).
When ordering spare parts you will need to identify pump
model, size, serial number, and the item number of required
parts. Pump information can be taken from the Goulds
nameplate. Item numbers can be found in this manual.
Fig. 1A
If applicable, your pump unit may have the ATEX tag
affixed to the pump and/or baseplate (Fig. 2). See the
Safety section for a description of the symbols and codes.
Fig. 1B
Fig. 2
143910-11th IOM 5/08
RECEIVING THE PUMP
Inspect the pump as soon as it is received. Carefully check
that everything is in good order. Make notes of damaged or
missing items on the receipt and freight bill. File any claims
with the transportation company as soon as possible.
STORAGE REQUIREMENTS
Short Term (Less than 6 months) Goulds normalpackaging
procedure is designed to protect the pump during shipping. Upon
receipt, store in a covered and dry location.
Long Term (More than 6 months) Preservative treatment
of bearings and machined surfaces will be required. Rotate
shaft several times every 3 months. Refer to driver and
coupling manufacturers for their long term storage
procedures. Store in a covered and dry location.
NOTE: Long term storage treatment may be
purchased with initial pump order.
HANDLING
!WARNING
s
Pump and components are heavy. Failure to properly
lift and support equipment could result in serious
physical injury, or damage to pumps.
Use care when moving pumps. Lifting equipment must be
able to adequately support the entire assembly. Hoist bare
pump using suitable hooks through the holes in the frame
mounted support or suitable slings through the large
openings in the casing mounted support (Fig. 3).
2
Fig. 4
Or with hooks through the holes in the frame mounted
support or with slings through the large openings in the
casing mounted support.
Fig. 3
!WARNING
Units with drivers mounted are moved with slings under
the pump casing and driver (Figs. 4 and 5).
3910-11th IOM 5/0815
s
Units with drivers mounted can be top heavy. Driver
weight could cause the assembled unit to overturn and
could result in serious physical injury, or damage to
pumps.
Fig. 5
163910-11th IOM 5/08
INSTALLATION
GENERAL..................................17
SITE/FOUNDATION............................17
ALIGNMENT AND ALIGNMENT CRITERIA .............18
General Considerations..........................18
Alignment Criteria ............................18
ALIGNMENT TROUBLESHOOTING ..................18
PIPING....................................19
Suction Piping ..............................19
Discharge Piping .............................20
Bypass Piping ..............................20
Auxiliary Piping .............................20
Final Piping Check ............................20
Equipment that will operate in a potentially explosive environment must be installed in accordance with the
!
following instructions.
GENERAL
3
Procedures for installation described within this section are
general in nature. It is assumed that the installer has a basic
knowledge of acceptable methods. More detailed
procedures are described in various publications,
SITE/FOUNDATION
A pump should be located near the supply of liquid and
have adequate space for operation, maintenance, and
inspection. Be sure to allow for crane or hoist service.
Model 3910 in-line pumps are designed to be mounted
directly in the piping. The pump casing has a flat base
which may be mounted on a concrete foundation which has
been poured on a solid footing.
including API Recommended Practice 686/ PIP (Process
Industry Practices) REIE 686, “Recommended Practices
for Machinery Installation and Installation Design.”
Optional casing supports, which provide additional
stability, are also available (Fig. 7).
Fig. 7
If it is intended that the piping support the pumping unit,
piping supports should be properly designed to
accommodate the weight of the pumping unit.
Fig. 6
The foundation must be able to absorb any vibration and to
form a permanent, rigid support for the pumping unit
(Fig. 6). Goulds recommends this mounting method.
3910-11th IOM 5/0817
All equipment being installed must be properly
!
grounded to prevent unexpected static electric
discharge.
ALIGNMENT AND ALIGNMENT CRITERIA
Alignment procedures must be followed to prevent
!
unintended contact of rotating parts. Follow
coupling manufacturer's installation and operation
procedures.
GENERAL CONSIDERATIONS
!WARNING
s
Before beginning any alignment procedure, make sure
driver power is locked out. Failure to lock out driver
power will result in serious physical injury.
To remove coupling guard, refer to coupling guard
installation and disassembly instructions in Appendix I.
The times at which alignment is checked and adjusted are:
Initial Alignment (Cold Alignment) is done prior to
operation when the pump and the driver are at ambient
temperatures.
Final Alignment (Hot Alignment) is done after operation
when the pump and driver are at operating temperatures.
After First Run - To obtain correct alignment when
•
both pump and driver are at operating temperature.
Thereafter, alignment should be checked periodically
in accordance with plant operating procedures.
NOTE: Alignment check must be made if process
temperature changes, piping changes and/or pump
service is performed.
Alignment is achieved by adding or removing shims from
under the flange of the driver and/or shifting driver
horizontally as needed.
NOTE: Proper alignment is the responsibility of the
installer and user of the unit.
Accurate alignment of the equipment must be attained.
Trouble-free operation can be accomplished by achieving
alignment within the levels specified in the following
section.
Three common alignment methods are utilized:
Reverse Dial Indicator method is most common.
•
Laser method is similar to reverse dial indicator
•
method, but uses a laser to obtain the necessary measurements.
Dial Indicator (rim-and-face) method.
•
Follow alignment equipment manufacturer's procedures
when utilizing reverse dial indicator or laser methods. A
detailed procedure for alignment using the dial indicator
(rim-and-face) method is included as Appendix II.
ALIGNMENT CRITERIA
Good alignment is attained when readings as specified in this
section have been achieved with pump and driver at operating
temperatures (final alignment).
Table 2 shows maximum allowable Total Indicator Reading
(T.I.R.) for parallel and angular misalignment.
Table 2
Maximum Allowable
Parallel and Angular Misalignment
Maximum Allowable Misalignment
Group
All
ParallelAngular
0.05 mm
(.002 in.)
[0.125 mm/cm (.0005 in. /in.)
0.03 degrees
of coupling face diameter]
ALIGNMENT TROUBLESHOOTING
ProblemProbable CauseRemedy
Cannot obtain horizontal (Side-to-Side)
alignment, angular or parallel
Driver flange bolt bound
183910-11th IOM 5/08
Loosen motor support hold down bolts and
slide motor support and driver until horizontal alignment is achieved.
PIPING
Guidelines for piping are given in the “Hydraulic Institute
Standards,” available from:
Hydraulic Institute
9 Sylvan Way
Parsippany, NJ 07054
and in API RP 686, and must be reviewed prior to pump
installation.
!WARNING
s
Never draw piping into place by forcing at the flanged
connections of the pump. This may impose dangerous
strains on the unit and cause misalignment between
pump and driver. Pipe strain will adversely affect the
operation of the pump resulting in physical injury and
damage to the equipment.
Flange loads from the piping system, including
!
those from thermal expansion of the piping, must
not exceed the limits of the pump. Casing deformation can result in contact with rotating parts which
can result in excess heat generation, sparks and
premature failure.
1. Piping runs should be as short as possible to minimize
friction losses.
2. It is suggested that expansion loops be properly
designed and installed in suction and/or discharge lines
when handling liquids at elevated tempera- tures, so
thermal expansion of piping will not draw pump out of
alignment.
3. The piping should be arranged to allow pump flushing
prior to removal of the unit on services handling
hazardous liquids.
4. Carefully clean all pipe parts, valves and fittings, and
pump branches prior to assembly.
5. All piping must be supported independently of, and
line up naturally with, the pump flanges. Table 2
shows piping flange alignment criteria.
Bottom of casing should be supported by a solid
6.
foundation or casing feet should be used.
SUCTION PIPING
$
NPSHAmust always exceed NPSHRas shown on
Goulds performance curves received with order.
(Reference Hydraulic Institute for NPSH and pipe
friction values needed to evaluate suction piping).
Properly designed and installed suction piping is a necessity for
trouble-free pump operation. Suction piping should be flushed
BEFORE connection to the pump.
1. Use of elbows close to the pump suction flange should
be avoided. There should be a minimum of two (2)
pipe diameters of straight pipe [five (5) pipe diameters
is preferred] between the elbow and suction inlet.
Where used, elbows should be long radius.
2. Use suction pipe one (1) or two (2) sizes larger than
the pump suction, with a reducer at the suction flange.
Suction piping should never be of smaller diameter
than the pump suction.
3. Reducers, if used, should be eccentric and located at
the pump suction flange with sloping side down.
$
Pump must never be throttled on suction side.
4. A suction screen should be installed prior to initial
start-up and when suction system has been opened for
work. The screen should be of the cone type with a
net area equal to at least three (3) times the cross
sectional area of the suction pipe. The mesh of the
screen should be sized to prevent particles larger than
1.6 mm (1/16 in.) from entering the pump and should
be installed in a spool piece to allow removal for
cleaning. The screen should remain in the system until
periodic inspection shows system is clean.
CAUTION
CAUTION
3
Table 4
Piping Flange Alignment
5. Separate suction lines are recommended when more
than one pump is operating from the same source of
supply.
TypeCriteria
Axial
Parallel
ConcentricFlange bolts should easily install by hand.
In no case should loads on the pump flanges exceed the
limits stated in API Standard 610, 11th Edition (ISO
13709).
3910-11th IOM 5/0819
Flange gasket thickness ± 0.8 mm (.03 in.).
0.001 mm/mm (.001 in./in.) of flange diameter
to a maximum of 0.8 mm (.03 in.).
Suction Lift Conditions
1. Suction pipe must be free from air pockets.
2. Suction piping must slope upwards to pump.
3. All joints must be air tight.
4. A means of priming the pump must be provided.
Suction Head/Flooded Suction Conditions
1. An isolation valve should be installed in the suction
line at least two (2) pipe diameters from the pump
suction to permit closing of the line for pump
inspection and maintenance.
2. Keep suction pipe free from air pockets.
3. Piping should be level or slope gradually downward
from the source of supply.
4. No portion of the piping should extend below pump
suction flange.
5. The size of entrance from supply should be one (1) or
two (2) sizes larger than the suction pipe.
6. The suction pipe must be adequately submerged below
the liquid surface to prevent vortices and air
entrainment at the supply.
DISCHARGE PIPING
Properly designed and installed discharge piping is a
necessity for trouble-free pump operation. Discharge
piping should be flushed BEFORE connection to the pump.
1. Isolation and check valves should be installed in
discharge line. Locate the check valve between
isolation valve and pump; this will permit inspection of
the check valve. The isolation valve is required for
priming, regulation of flow, and for inspection and
maintenance of pump. The check valve prevents pump
or seal damage due to reverse flow through the pump
when the driver is turned off.
2. Increasers, if used, should be placed between pump
and check valves.
3. Cushioning devices should be used to protect the pump
from surges and water hammer if quick-closing valves
are installed in system.
BYPASS PIPING
Systems that require operation at reduced flows for
prolonged periods should be provided with a bypass line
connected from the discharge side (before any valves) to
the source of suction.
A minimum flow orifice can be sized and installed in
bypass line to preclude bypassing excessive flows. Consult
nearest sales office or factory for assistance in sizing
orifice.
An automatic recirculation control valve and/or solenoid
operated valve should be considered if a constant bypass
(i.e. orifice) is not possible.
AUXILIARY PIPING
The mechanical seal must have an appropriate seal
!
flush system. Failure to do so will result in excess heat
generation and seal failure.
Cooling systems such as those for bearing
!
lubrication, mechanical seal systems, etc., where
provided, must be operating properly to prevent
excess heat generation, sparks, and premature
failure.
Sealing systems that are not self purging or self
!
venting, such as plan 23, require manual venting
prior to operation. Failure to do so will result in
excess heat generation and seal failure.
Auxiliary piping may be required for seal chamber cover
cooling, mechanical seal flush or other special features
supplied with the pump. Consult pump data sheet for
specific auxiliary piping recommendations.
If seal chamber cover cooling is required, follow guidelines
listed below.
1. Flows of 4 l/min. (1 GPM) will generally satisfy
cooling requirements.
2. Cooling water pressure should not exceed
7.0 kg/cm
2
(100 psig).
FINAL PIPING CHECK
After connecting the piping to pump:
The Preventive Maintenance section must be
!
adhered to in order to keep the applicable ATEX
classification of the equipment. Failure to follow
these procedures will void the ATEX classification
for the equipment.
Check alignment, per alignment criteria outlined
!
previously, to determine if pipe strain has affected
alignment. If pipe strain exists, correct piping.
203910-11th IOM 5/08
OPERATION
PREPARATION FOR START-UP ....................21
Checking Rotation ............................21
Coupling Pump and Driver ........................21
General Considerations..........................24
Operational Checks............................24
Operating at Reduced Capacity .....................25
Operating Under Freezing Conditions ..................25
SHUTDOWN ................................25
FINAL ALIGNMENT ...........................25
PREPARATION FOR START-UP
4
When installation in a potentially explosive
!
environment, ensure that the motor is properly
certified.
CHECKING ROTATION
$
Serious damage may result if pump is run in the
wrong rotation.
1. Lock out power to driver.
s
!WARNING
Lock out driver power to prevent accidental start-up
and physical injury.
2. Make sure coupling hubs are securely fastened
to shafts.
!WARNING
s
Do NOT jog a coupled pump.
NOTE: Pump is shipped with coupling spacer
removed.
3. Unlock driver power.
4. Make sure everyone is clear. Jog driver just long enough to
determine direction of rotation. Rotation must correspond
to arrow on bearing frame.
CAUTION
5. Lock out power to driver.
COUPLING PUMP AND DRIVER
!WARNING
s
Lock out driver power to prevent accidental rotation
and physical injury.
The coupling used in an ATEX classified environ-
!
ment must be properly certified.
1. Install and lubricate coupling per manufacturer’s
instructions.
The coupling guard used in an ATEX classified
!
environment must be constructed from a nonsparking material.
2. Install coupling guard. Refer to coupling guard
installation instructions in Appendix I.
!WARNING
s
Never operate a pump without coupling guard properly
installed. Refer to Appendix I for coupling guard
installation instructions. Personal injury will occur if
pump is run without coupling guard.
3910-11th IOM 5/0821
LUBRICATING BEARINGS
Bearings musts be lubricated properly in order to
!
prevent excess heat generation, sparks and
premature failure.
Grease Lubrication
Greased lubricated ball bearings are standard on the Model
3910 units.
Sealing systems that are not self purging or self
!
venting, such as plan 23, require manual venting
prior to operation. Failure to do so will result in
excess heat generation and seal failure.
For satisfactory operation, there must be a liquid film
between seal faces to lubricate them. Refer to seal
manufacturer’s drawing for location of taps. Some methods
which may be used to flush/cool the seal are:
The bearings are greased at the factory.
See Preventive Maintenance section for lubrication
recommendations.
Pure Oil Mist Lubrication
Pure oil mist is an optional feature for the Model 3910.
Follow oil mist generator manufacturer’s instructions. The
inlet and outlet connections are located on the side of the
bearing frame.
See Preventive Maintenance section for lubrication
recommendations and connection locations.
!WARNING
s
Operation of the unit without proper lubrication will
cause bearing failure and pump seizure.
SHAFT SEALING WITH
MECHANICAL SEAL
The mechanical seal used in an ATEX classified
!
environment must be properly certified.
Pumps may be shipped with or without mechanical seal
installed. Cartridge type mechanical seals are commonly
used for this model. Cartridge seals are preset at the seal
manufacturer’s facility and require no field settings.
Cartridge seals installed by the user require disengagement
of the holding clips prior to operation, allowing the seal to
slide into place. If the seal has been installed in the pump
by Goulds, these clips have already been disengaged. For
other types of mechanical seals, refer to the seal
manufacturer’s instructions for installation and setting.
Product Flushing - In this arrangement, the pumpage is
•
piped from the casing (and cooled in an external heat
exchanger when required) then injected into seal
chamber.
External Flush - A clean, cool compatible liquid is
•
injected from an outside source directly into seal
chamber. Flushing liquid must be at a pressure 0.35-1.05
2
kg/cm
rate should be 2-8 l/min. (
Other methods may be used which make use of multiple
•
gland connections and/or seal chamber connections.
Refer to documentation supplied with the pump,
mechanical seal reference drawing, and piping diagrams.
(5-15 psi) greater than seal chamber pressure. Injection
1
-2 GPM).
2
PRIMING PUMP
Pumps must be fully primed at all times during
!
operation.
Never start the pump until it has been properly primed.
Several different methods of priming can be used, depending
upon type of installation and service involved.
Suction Supply Above Pump
1. Slowly open the suction valve (Fig. 8).
Connection of Sealing Liquid
The mechanical seal must have an appropriate seal
!
flush system. Failure to do so will result in excess heat
generation and seal failure.
Cooling systems such as those for bearing
!
lubrication, mechanical seal systems, etc., where
provided, must be operating properly to prevent
excess heat generation, sparks, and premature
failure.
2. Open air vents on the suction and discharge piping, casing,
seal chamber, and seal piping, if provided, until all air is
vented and only liquid flows out.
3. Close the vents.
223910-11th IOM 5/08
Fig. 8
Suction Supply Below Pump
A foot valve and outside source of liquid may be used to
prime the pump. Outside source of liquid can come from a
priming pump pressurized discharge line, or other supply
(Fig. 9 and 10).
1. Close discharge valve and open air vents in suction
and discharge piping, casing, seal chamber, and seal
piping, if provided.
2. Open valve in outside supply line until all air is vented
and only liquid flows out.
!WARNING
s
When handling hazardous and/or toxic fluids, proper
personal protective equipment is required. If pump is
being drained, precautions must be taken to prevent
physical injury. Pumpage must be handled and disposed of in conformance with applicable regulations.
3. Close the vents and then the outside supply line.
Other Methods of Priming Pump
Priming by ejector.
•
Fig. 9
Priming by automatic priming pump.
•
START-UP PRECAUTIONS
$
Ensure that pump and systems are free of foreign
!
objects before operating and that objects cannot
enter the pump during operation. Foreign objects in
the pumpage or piping system can cause blockage of
flow which can result in excess heat generation,
sparks, and premature failure.
$
A build up of gases within the pump, sealing system
!
and or process piping system may result in an
explosive environment within the pump or process
piping system. Ensure process piping system, pump,
and sealing system are properly vented prior to
operation.
1. All equipment and personal safety related devices and
controls must be installed and operating properly.
2. To prevent premature pump failure at initial start-up
due to dirt or debris in the pipe system, ensure the
pump can be run continuously at full speed and flow
for 2 to 3 hours.
CAUTION
CAUTION
4
3. Variable speed drivers should be brought to rated
Fig. 10
3910-11th IOM 5/0823
speed as quickly as possible.
4. Variable speed drivers should not be adjusted or
checked for speed governor or overspeed trip settings
while coupled to the pump at initial start-up. If
settings have not been verified, uncouple the unit and
refer to driver manufacturer’s instructions for
assistance.
5. Running a new or rebuilt pump at slow speeds may not
provide enough flow to adequately flush and cool the
wear ring and seal chamber cover bushing.
6. Pumpage temperatures in excess of 93° C (200° F) will
require warm-up of pump prior to operation. Circulate a
small amount of pumpage through the pump until the
STARTING PUMP
casing temperature is within 56° C (100° F) of the
pumpage temperature and evenly heated.
NOTE: Warm-up rate should not exceed 1.4° C
(2.5° F) per minute.
1. Make sure suction valve and any recirculation or
cooling lines are open.
2. Fully close or partially open discharge valve as
dictated by system conditions.
3. Start driver.
$
Immediately observe pressure gauges. If discharge
pressure is not quickly attained, stop driver, reprime,
and attempt to restart.
CAUTION
OPERATION
GENERAL CONSIDERATIONS
$
Always vary capacity with regulating valve in the discharge
line. NEVER throttle flow from the suction side.
Driver may overload if the pumpage specific gravity
(density) is greater than originally assumed, or the
rated flow rate is exceeded.
Always operate the pump at or near the rated
conditions to prevent damage resulting from cavitation
or recirculation.
OPERATIONAL CHECKS
$
The following are minimum operational checks for the
pump only. Consult driver and auxiliary equipment
manufacturers’ literature for additional information.
1. On grease lubricated units, remove grease relief plugs
to verify that grease is present. Replace plugs.
2. On pure oil mist lubricated units, remove viewing port
plugs and assure oil mist is flowing properly. Replace
plugs.
CAUTION
CAUTION
4. Slowly open discharge valve until the desired flow is
obtained.
CAUTION
$
Observe pump for vibration levels, bearing temperature, and excessive noise. If normal levels are
exceeded, shut down and resolve.
3. Check bearing temperatures using a pyrometer or other
accurate temperature measuring device. Monitor
bearing temperature frequently during initial operation
to determine if a bearing problem exists as well as to
establish normal bearing operating temperature.
4. On units equipped with auxiliary piping, assure that
proper flows have been established and that equipment
is operating properly.
5. Establish baseline vibration readings to determine
normal running conditions. If it is determined that the
unit is running rough, consult factory.
6. Monitor all gauges to ensure pump is running at or
near rating and that suction screen (when used) is not
clogged.
!
OPERATING AT REDUCED
CAPACITY
!WARNING
s
Do NOT operate pump below minimum rated flows or
with discharge valve closed. These conditions may
create an explosive hazard due to vaporization of
pumpage and can quickly lead to pump failure and
physical injury.
243910-11th IOM 5/08
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.