Installation, Operation and Maintenance Instructions
Model 3420
23420 IOM 8/09
FOREWORD
This manual provides instructions for the Installation, Operation, and Maintenance of the Goulds Model 3420/25 Single
Stage Double Suction Pump*. This manual covers the standard product plus common options that are available. For special
options, supplemental instructions are supplied. This manual must be read and understood before installation and start-up.
The design, materials, and workmanship incorporated in the construction of Goulds pumps makes them capable of giving
trouble-free service. The life and satisfactory service of any mechanical unit, however, is enhanced and extended by correct
application, proper installation, periodic inspection, condition monitoring and careful maintenance. This instruction manual
was prepared to assist operators in understanding the construction and the correct methods of installing, operating, and
maintaining these pumps.
ITT - Goulds Pumps shall not be liable for physical injury, damage or delays caused by a failure to observe the
instructions for Installation, Operation, and Maintenance contained in this manual.
When pumping unit is installed in a potentially explosive atmosphere, the instructions after the
followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there is any
question regarding these requirements or if the equipment is to be modified, please contact a Goulds representative
before proceeding.
Warranty is valid only when genuine ITT - Goulds Pumps parts are used.
Use of the equipment on a service other than stated in the order will nullify the warranty, unless written approval is obtained
in advance from ITT - Goulds Pumps.
Supervision by an authorized ITT - Goulds Pumps representative is recommended to assure proper installation.
Additional manuals can be obtained by contacting your local ITT - Goulds Pumps representative or by calling
1-800-446-8537.
* The 3420 is an all English dimension unit and the 3425 is a hard metric design.
A symbol must be
THIS MANUAL EXPLAINS
Proper Installation
n
Start-up Procedures
n
Operation Procedures
n
Routine Maintenance
n
Pump Overhaul
n
Trouble Shooting
n
Ordering Spare or Repair Parts
n
3420 IOM 8/093
43420 IOM 8/09
TABLE OF CONTENTS
PAGESECTION
7SAFETY
11GENERAL INFORMATION
15INSTALLATION
25OPERATION
37PREVENTIVE MAINTENANCE
43DISASSEMBLY & REASSEMBLY
1
2
3
4
5
6
77SPARE AND REPAIR PARTS
99APPENDIX
7
8
3420 IOM 8/095
Industrial Process Pump Safety Manual
IMPORTANT SAFETY NOTICE
To: Our Valued Customers
User safety is a major focus in the design of our products. Following the precautions outlined in this
manual will minimize your risk of injury.
ITT Goulds pumps will provide safe, trouble-free service when properly installed, maintained, and
operated.
Safe installation, operation, and maintenance of ITT Goulds Pumps equipment are an essential end user
responsibility. This Pump Safety Manual identifies specific safety risks that must be considered at all
times during product life. Understanding and adhering to these safety warnings is mandatory to ensure
personnel, property, and/or the environment will not be harmed. Adherence to these warnings alone,
however, is not sufficient — it is anticipated that the end user will also comply with industry and corporate
safety standards. Identifying and eliminating unsafe installation, operating and maintenance practices is
the responsibility of all individuals involved in the installation, operation, and maintenance of industrial
equipment.
Please take the time to review and understand the safe installation, operation, and maintenance guidelines
outlined in this Pump Safety Manual and the Instruction, Operation, and Maintenance (IOM) manual.
Current manuals are available at
your nearest Goulds Pumps sales representative.
These manuals must be read and understood before installation and start-up.
For additional information, contact your nearest Goulds Pumps sales representative or visit our Web site at
www.gouldspumps.com.
www.gouldspumps.com/literature_ioms.html or by contacting
S-1
SAFETY WARNINGS
Specific to pumping equipment, significant risks bear reinforcement above and beyond normal safety precautions.
WARNING
A pump is a pressure vessel with rotating parts that can be hazardous. Any pressure vessel can explode,
rupture, or discharge its contents if sufficiently over pressurized causing death, personal injury, property
damage, and/or damage to the environment. All necessary measures must be taken to ensure over
pressurization does not occur.
WARNING
Operation of any pumping system with a blocked suction and discharge must be avoided in all cases.
Operation, even for a brief period under these conditions, can cause superheating of enclosed pumpage and
result in a violent explosion. All necessary measures must be taken by the end user to ensure this condition is
avoided.
WARNING
The pump may handle hazardous and/or toxic fluids. Care must be taken to identify the contents of the pump
and eliminate the possibility of exposure, particularly if hazardous and/or toxic. Potential hazards include, but
are not limited to, high temperature, flammable, acidic, caustic, explosive, and other risks.
WARNING
Pumping equipment Instruction, Operation, and Maintenance manuals clearly identify accepted methods for
disassembling pumping units. These methods must be adhered to. Specifically, applying heat to impellers
and/or impeller retaining devices to aid in their removal is strictly forbidden. Trapped liquid can rapidly
expand and result in a violent explosion and injury.
ITT Goulds Pumps will not accept responsibility for physical injury, damage, or delays caused by a failure to
observe the instructions for installation, operation, and maintenance contained in this Pump Safety Manual or the
current IOM available at www.gouldspumps.com/literature.
S-2
SAFETY
DEFINITIONS
Throughout this manual the words WARNING, CAUTION, ELECTRICAL, and ATEX are used to indicate
where special operator attention is required.
Observe all Cautions and Warnings highlighted in this Pump Safety Manual and the IOM provided with
your equipment.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Example: Pump shall never be operated without coupling guard installed correctly.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Example: Throttling flow from the suction side may cause cavitation and pump damage.
ELECTRICAL HAZARD
Indicates the possibility of electrical risks if directions are not followed.
Example: Lock out driver power to prevent electric shock, accidental start-up, and physical injury.
When installed in potentially explosive atmospheres, the instructions that follow the Ex symbol must be
followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there
is any question regarding these requirements or if the equipment is to be modified, please contact an ITT
Goulds Pumps representative before proceeding.
Example:
parts, resulting in a spark and heat generation.
Improper impeller adjustment could cause contact between the rotating and stationary
S-3
GENERAL PRECAUTIONS
WARNING
A pump is a pressure vessel with rotating parts that can be hazardous. Hazardous fluids may be contained by the
pump including high temperature, flammable, acidic, caustic, explosive, and other risks. Operators and
maintenance personnel must realize this and follow safety measures. Personal injuries will result if procedures
outlined in this manual are not followed. ITT Goulds Pumps will not accept responsibility for physical injury,
damage or delays caused by a failure to observe the instructions in this manual and the IOM provided with your
equipment.
General Precautions
WARNING
WARNING
NEVER APPLY HEAT TO REMOVE IMPELLER. It may explode due to trapped
liquid.
NEVER use heat to disassemble pump due to risk of explosion from trapped liquid.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
NEVER operate pump without coupling guard correctly installed.
NEVER run pump below recommended minimum flow when dry, or without prime.
ALWAYS lock out power to the driver before performing pump maintenance.
NEVER operate pump without safety devices installed.
NEVER operate pump with discharge valve closed.
NEVER operate pump with suction valve closed.
DO NOT change service application without approval of an authorized ITT Goulds
Pumps representative.
Safety Apparel:
Insulated work gloves when handling hot bearings or using bearing heater
Heavy work gloves when handling parts with sharp edges, especially impellers
Safety glasses (with side shields) for eye protection
Steel-toed shoes for foot protection when handling parts, heavy tools, etc.
Other personal protective equipment to protect against hazardous/toxic fluids
Receiving:
Assembled pumping units and their components are heavy. Failure to properly lift and
support equipment can result in serious physical injury and/or equipment damage. Lift
WARNING
equipment only at specifically identified lifting points or as instructed in the current IOM.
Current manuals are available at
from your local ITT Goulds Pumps sales representative. Note: Lifting devices (eyebolts,
slings, spreaders, etc.) must be rated, selected, and used for the entire load being lifted.
www.gouldspumps.com/literature_ioms.html or
S-4
WARNING
General Precautions
Alignment:
Shaft alignment procedures must be followed to prevent catastrophic failure of drive
components or unintended contact of rotating parts. Follow coupling manufacturer’s
coupling installation and operation procedures.
WARNING
CAUTION
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
Before beginning any alignment procedure, make sure driver power is locked out. Failure
to lock out driver power will result in serious physical injury.
Piping:
Never draw piping into place by forcing at the flanged connections of the pump. This may
impose dangerous strains on the unit and cause misalignment between pump and driver.
Pipe strain will adversely effect the operation of the pump resulting in physical injury and
damage to the equipment.
Flanged Connections:
Use only fasteners of the proper size and material.
Replace all corroded fasteners.
Ensure all fasteners are properly tightened and there are no missing fasteners.
Startup and Operation:
When installing in a potentially explosive environment, please ensure that the motor is
properly certified.
Operating pump in reverse rotation may result in contact of metal parts, heat generation,
and breach of containment.
Lock out driver power to prevent accidental start-up and physical injury.
The impeller clearance setting procedure must be followed. Improperly setting the
clearance or not following any of the proper procedures can result in sparks, unexpected
heat generation and equipment damage.
If using a cartridge mechanical seal, the centering clips must be installed and set screws
loosened prior to setting impeller clearance. Failure to do so could result in sparks, heat
generation, and mechanical seal damage.
WARNING
WARNING
WARNING
CAUTION
The coupling used in an ATEX classified environment must be properly certified and
must be constructed from a non-sparking material.
Never operate a pump without coupling guard properly installed. Personal injury will
occur if pump is run without coupling guard.
Make sure to properly lubricate the bearings. Failure to do so may result in excess heat
generation, sparks, and / or premature failure.
The mechanical seal used in an ATEX classified environment must be properly certified.
Prior to start up, ensure all points of potential leakage of process fluid to the work
environment are closed.
S-5
CAUTION
WARNING
General Precautions
Never operate the pump without liquid supplied to mechanical seal. Running a mechanical
seal dry, even for a few seconds, can cause seal damage and must be avoided. Physical
injury can occur if mechanical seal fails.
Never attempt to replace packing until the driver is properly locked out and the coupling
spacer is removed.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
CAUTION
CAUTION
WARNING
CAUTION
CAUTION
Dynamic seals are not allowed in an ATEX classified environment.
DO NOT operate pump below minimum rated flows or with suction and/or discharge
valve closed. These conditions may create an explosive hazard due to vaporization of
pumpage and can quickly lead to pump failure and physical injury.
Ensure pump is isolated from system and pressure is relieved before disassembling pump,
removing plugs, opening vent or drain valves, or disconnecting piping.
Shutdown, Disassembly, and Reassembly:
Pump components can be heavy. Proper methods of lifting must be employed to avoid
physical injury and/or equipment damage. Steel toed shoes must be worn at all times.
The pump may handle hazardous and/or toxic fluids. Observe proper decontamination
procedures. Proper personal protective equipment should be worn. Precautions must be
taken to prevent physical injury. Pumpage must be handled and disposed of in
conformance with applicable environmental regulations.
Operator must be aware of pumpage and safety precautions to prevent physical injury.
Lock out driver power to prevent accidental startup and physical injury.
Allow all system and pump components to cool before handling them to prevent physical
injury.
If pump is a Model NM3171, NM3196, 3198, 3298, V3298, SP3298, 4150, 4550, or
3107, there may be a risk of static electric discharge from plastic parts that are not
properly grounded. If pumped fluid is non-conductive, pump should be drained and
flushed with a conductive fluid under conditions that will not allow for a spark to be
released to the atmosphere.
Never apply heat to remove an impeller. The use of heat may cause an explosion due to
trapped fluid, resulting in severe physical injury and property damage.
Wear heavy work gloves when handling impellers as sharp edges may cause physical
injury.
Wear insulated gloves when using a bearing heater. Bearings will get hot and can cause
physical injury.
S-6
ATEX CONSIDERATIONS and INTENDED USE
Special care must be taken in potentially explosive environments to ensure that the equipment is properly
maintained. This includes but is not limited to:
1. Monitoring the pump frame and liquid end temperature.
2. Maintaining proper bearing lubrication.
3. Ensuring that the pump is operated in the intended hydraulic range.
The ATEX conformance is only applicable when the pump unit is operated within its intended use. Operating,
installing or maintaining the pump unit in any way that is not covered in the Instruction, Operation, and
Maintenance manual (IOM) can cause serious personal injury or damage to the equipment. This includes any
modification to the equipment or use of parts not provided by ITT Goulds Pumps. If there is any question
regarding the intended use of the equipment, please contact an ITT Goulds representative before proceeding.
Current IOMs are available at
Pumps Sales representative.
All pumping unit (pump, seal, coupling, motor and pump accessories) certified for use in an ATEX classified
environment, are identified by an ATEX tag secured to the pump or the baseplate on which it is mounted. A
typical tag would look like this:
www.gouldspumps.com/literature_ioms.html or from your local ITT Goulds
The CE and the Ex designate the ATEX compliance. The code directly below these symbols reads as follows:
II = Group 2
2 = Category 2
G/D = Gas and Dust present
T4 = Temperature class, can be T1 to T6 (see Table 1)
Table 1
Max permissible
surface temperature
Code
T1 842 (450) 700 (372)
T2 572 (300) 530 (277)
T3 392 (200) 350 (177)
T4 275 (135) 235 (113)
T5 212 (100) Option not available
T6 185 (85) Option not available
o
F (oC)
The code classification marked on the equipment must be in accordance with the specified area where the
equipment will be installed. If it is not, do not operate the equipment and contact your ITT Goulds Pumps sales
representative before proceeding.
Max permissible
liquid temperature
o
F (oC)
S-7
PARTS
The use of genuine Goulds parts will provide the safest and
most reliable operation of your pump. ITT Goulds Pumps ISO
certification and quality control procedures ensure the parts are
manufactured to the highest quality and safety levels.
Please contact your local Goulds representative for details on
genuine Goulds parts.
NAMEPLATE INFORMATION ...........................13
RECEIVING THE PUMP ...............................14
PUMP DESCRIPTION
The model is based on 8 bearing configurations and 15 hydraulic sizes. Groupings are as follows:
GroupDescriptionSizes
SX
MX
M
M
(modified)
—
L
LDS
XL
XXL
Ball radial and duplex ball thrust bearings. Flood oil lube with constant level oiler optional grease
lube. Bearing housings bolt to the casing. Goulds non-metallic labyrinth seals.
Ball radial and duplex ball thrust bearings. Flood oil lube with constant level oiler optional grease
lube. Bearing housings bolt to the casing. Goulds non-metallic labyrinth seals.
Ball radial and duplex ball thrust bearings. Ring oil lube with constant level oiler optional grease
lube. Bearing housing secured with tongue and groove fits and a bearing cap with studs and nuts.
Goulds metallic labyrinth seals.
Same as M group except the shaft is longer to accommodate a wider pump.
Ball radial and duplex ball thrust bearings. Ring oil lube with constant level oiler, optional grease
lube. Bearing housing secured with tongue and groove fits and a bearing cap with studs and nuts.
Goulds metallic labyrinth seals.
Double row roller bearings, both thrust and radial. Ring oil lube with constant level oiler, optional
grease lube. Bearing housing secured with tongue and groove fits and a bearing cap with studs
and nuts. Goulds metallic labyrinth seals.
Double row roller bearings, both thrust and radial. Ring oil lube with constant level oiler, optional
grease lube. Bearing housing secured with tongue and groove fits and a bearing cap with studs
and nuts. Goulds metallic labyrinth seals.
Double row roller bearings, both thrust and radial. Ring oil lube with constant level oiler, optional
grease lube. Bearing housing secured with tongue and groove fits and a bearing cap with studs
and nuts. Goulds metallic labyrinth seals.
Double row roller bearings, both thrust and radial. Ring oil lube with constant level oiler, optional
grease lube. Bearing housing secured with tongue and groove fits and a bearing cap with studs
and nuts. Goulds metallic labyrinth seals.
12 x 14-15
16 x 18-17H
18 x 20-20
16 x 18-30
18 x 20-30
20 x 24-24
20 x 24-30
20 x 24-28
18 x 20-24
24 x 30-32
30 x 30-31
30 x 30-38
30 x 36-42
20x30-42
36x42-52
1
The model 3420 is a horizontal between bearings, enclosed
impeller double suction centrifugal pump.
Casing - The casing is horizontally split. The upper and
lower halves are held together with studs and nuts and/or
capscrews. Flanged suction and discharge connections are
located in the lower half of the casing and conform to ANSI
16.1/16.5 class 125/150. The casing is supported by
integrally cast feet. Separate bearing housings are attached
directly to machined fits in each end of the casing with
capscrews or machined fits secured with bearing caps and
studs and nuts. All sizes have dual volute casings to reduce
radial loads on the shaft. The casings are standard with two
jacking screws, two lifting lugs for the upper half, two
tapered dowel pins for alignment, and a .030 or .016 in. (.75
or .41 mm) non-asbestos parting gasket. The upper half is
3420 IOM 8/097
provided with a vent connection, a priming connection, and
one or two stuffing box seal ring connections. The lower half
is provided with two drain connections, suction and
discharge gauge connections, and stuffing box overflow
connections.
Impeller - The impeller is an enclosed, double suction design
providing axial hydraulic balance. All exterior surfaces are
fully machined. The impeller receives a one or two plane spin
balance as standard. The impeller is keyed to the shaft and
held in place using shaft sleeves and sleeve nuts.
Wear Rings - Casing and impeller wear rings are supplied as
standard to maintain proper running clearances and to
minimize leakage between the suction and discharge
chambers in the casing. Each casing ring is held in place with
a machined hook lock. The impeller rings are held in place
using axial set screws.
Shaft - The shaft is a heavy duty design that minimizes
deflection and vibration. The shaft deflection is a maximum
of .002 in (.051 mm) at the stuffing box face under the worst
operating conditions. The shaft is completely dry with O-ring
seals between the impeller and shaft sleeves and the shaft
sleeves and the sleeve nuts. The standard shaft is AISI 4340
steel with an option for 316 stainless steel.
Shaft Sleeves - Shaft sleeves are standard on all pumps. They
are keyed to the shaft at the impeller and held in place using
sleeve nuts. The sleeve nuts tighten against rotation and are
secured in place with set screws.
Stuffing Box - Non-asbestos packing is standard. The
stuffing box contains a Teflon™ split lantern ring and
renewable stuffing box throat bushings. Tapped openings are
provided for water sealing from either the pump casing or an
outside source. Bypass piping is optional. Two-piece
machined split glands are standard on all packed pumps.
Mechanical Seals - Mechanical seals can be supplied as a
non-standard option. Most seal designs fit in the standard
stuffing box. Goulds does not have its own design gland, so
the gland must be supplied by the seal manufacturer.
Bearings - There are many different bearing configurations
that are offered on the 3420. Specific configurations are
dependent on pump size and group and purchased setup.
Grease lubricated ball, grease lubricated roller, flood oil
lubricated ball, ring oil lubricated ball, and ring oil lubricated
roller bearings are used on various sizes. Oil lubrication is
standard with grease optional. The bearing housings are
sealed with machined labyrinth seals or lip seals.
Baseplates - Fabricated steel bases are standard with a drip
collection chamber and a tapped drain connection. The base
is designed to be grouted and has grout and vent holes.
Soleplates for the pump only or motor only are offered as an
option.
83420 IOM 8/09
NAMEPLATE INFORMATION
Every pump has two or three Goulds nameplates that provide
information about the pump. The tags are located on the
upper half and lower half of the casing.
DescriptionFig. No.Example
Pump Casing Tag - provides information
about the pump’s hydraulic
characteristics. Note the format of the
pump size: Discharge x Suction - Nominal
maximum Impeller Diameter in inches.
(Example: 2x3-8)
(Figs.1&2).
Fig. 1
English
When ordering parts, you will need to identify the pump
model, size, serial number, and the item number of the
required parts. Information can be taken from the pump
casing tags. Item numbers can be found later on in this
manual.
1
Bearing Frame Tag - provides
information on the lubrication system used
(Fig. 3).
ATEX Tag - If applicable, your pump
unit may have the following ATEX tag
affixed to the pump and/or baseplate. See
the Safety section for a description of the
symbols and codes
(Fig. 4).
Fig. 2
Metric
Fig. 3
Fig. 4
3420 IOM 8/099
RECEIVING THE PUMP
Inspect the pump as soon as it is received. Carefully check
that everything is in good order. Make notes of damaged or
missing items on the receipt and freight bill. File any claims
with the transportation company as soon as possible.
Storage Requirements
Short Term: (Less than 6 months): Goulds normal
packaging procedure is designed to protect the pump during
shipping. Upon receipt, store in a covered and dry location.
Long Term: (More than 6 months): Preservative treatment of
bearings and machined surfaces will be required. Rotate shaft
several times every three months. Refer to driver and
coupling manufacturers for their long term storage
procedures. Store in a covered dry location.
Note: Long term storage treatment can be purchased
with the initial pump order.
HANDLING
!WARNING
s
Pump and components are heavy. Failure to properly lift
and support the equipment could result in serious
physical injury, or damage to the pump(s). Steel-toed
shoes must be worn at all times.
Fig. 3A
Use care when moving pumps. Lifting equipment must be
able to adequately support the entire assembly. Hoist a bare
pump or a pump and soleplate unit using a suitable sling,
under the two bearing housings (Fig. 3A). Baseplate mounted
units without motors are moved by supporting the pump with
a sling under the two bearing housings and a sling under the
motor end of the baseplate (Fig. 3B). Baseplate mounted
units with motors are moved with slings attached to the
baseplate lifting lugs. The use of a spreader bar is required so
that the pump is not damaged (Fig 3C).
Final Piping Check ...............................23
3
FOUNDATION
The foundation must be substantial enough to absorb
vibration. (Hydraulic Institute Standards recommends the
foundation weigh at least five [5] times the weight of the
pump unit.) It must form a permanent and rigid support for the
baseplate. This is important in maintaining the alignment of a
flexibly coupled unit.
Foundation bolts of the proper size should be embedded in the
concrete to a depth of eight (8) to twelve (12) inches and
locked with either a hook around a reinforcing bar or
alternatively, a nut and washer at the bottom. The bolts should
have a sleeve around them at least six (6) times the bolt
diameter in length and at least two (2) bolt sizes larger in I.D.
If a nut and washer are used for locking, the washer should
have an O.D. two (2) sizes larger than the sleeve. Foundation
bolts should be sized .125" less than the anchor bolt holes in
the base.
The foundation should be poured to within .75" - 1.5" of
the finished height. (See Fig. 4) Freshly poured foundations
should be allowed to cure for several days before the unit is
set in place and grouted.
Fig. 4
3420 IOM 08/0915
BASEPLATE INSTALLATION PROCEDURE
Industry standard procedures and/or the following
procedure should be followed prior to grouting the
baseplate. The procedure assumes the installer has a basic
knowledge of baseplate and foundation design and
installation methods.
BASEPLATE PREPARATION
1.Inspect all surfaces of the baseplate that will contact
the grout for contamination (rust, oil, grime, etc.)
2.Thoroughly clean all surfaces of the baseplate that will
contact the grout with a cleaner that will not leave any
residue.
NOTE: It may be necessary to sandblast the contact
surfaces and coat with a primer compatible with the
grout. If sandblasting is necessary, remove all the
equipment prior to sandblasting.
LEVEL BASEPLATE
1.Place two sets of wedges or shims on the foundation,
one set on each side of every foundation bolt. The
wedges should extend .75 in. (20 mm) to 1.5 in. (40
mm) above the foundation to allow for adequate
grouting. This will provide even support for the
baseplate once it is grouted.
3.Inspect all machined surfaces for burrs, rust, paint, or
any other type of contamination. If necessary, use a
honing stone to remove any burrs.
FOUNDATION PREPARATION
1.Chip the top of the foundation .50-1.0 in. (13-25 mm)
to remove porous or low strength concrete. If using a
pneumatic hammer, assure that it is not contaminating
the surface with oil, moisture, etc.
2.Remove water and/or debris from the foundation bolt
holes/sleeves. If sleeve type bolts are being used, fill
the sleeves with stuffing material and seal to prevent
grout from entering.
3.Coat the exposed portion of the anchor bolts with a
non-bonding compound to prevent grout from
adhering to the anchor bolts.
4.If recommended by the grout manufacturer, coat the
foundation surface with a compatible primer.
2.Remove water and/or debris from anchor bolt
holes/sleeves prior to grouting. If sleeve type bolts are
being used, fill the sleeves with rags to prevent grout
from entering.
Fig. 6
163420 IOM 08/09
3.Carefully lower the baseplate onto the foundation
bolts.
4.Level the baseplate to within .125 in. (3.2 mm) over
the length of the baseplate and to within .088 in. (1.5
mm) over the width of the baseplate by adjusting the
wedges. If the baseplate has vertical leveling screws,
use the screws to level the base.
5.Hand tighten the foundation bolts.
3
Fig. 7
3420 IOM 08/0917
ALIGNMENT AND ALIGNMENT PROCEDURE
Alignment procedures must be followed to prevent
!
unintended contact of rotating parts. Follow
coupling manufacturer’s installation and operation
procedures.
!WARNING
s
Before beginning any alignment procedure, make sure
driver power is locked out. Failure to lock out driver
power may result in serious physical injury.
To remove guard, refer to coupling guard assembly/
disassembly instructions.
The points at which alignment is checked and adjusted are:
Initial Alignment is done prior to operation when the
•
pump and the driver are at ambient temperature.
Final Alignment is done after operation when the
•
pump and driver are at operating temperature.
Alignment is achieved by adding or removing shims from
under the feet of the driver and shifting equipment
horizontally as needed.
Final Alignment (Hot Alignment)
After First Run - To obtain correct alignment when
•
both pump and driver are at operating temperature.
Thereafter, alignment should be checked periodically
in accordance with plant operating procedures.
NOTE: Alignment check must be made if process
temperature changes, piping changes and or pump
service is performed.
ALIGNMENT CRITERIA
Good alignment is achieved when the dial indicator
readings as specified in the alignment procedure are .002
in. (.05 mm) Total Indicated Reading (T.I.R.) or less when
the pump and driver are at operating temperature (Final
Alignment).
During the installation phase, however, it is necessary to
set the parallel alignment in the vertical direction to a
different criteria due to differences in expansion rates of
the pump and driver. Table 1 shows recommended
preliminary (cold) settings for electric motor driven pumps
based on different pumpage temperatures. Driver
manufacturers should be consulted for recommended cold
settings for other types of drivers (steam turbines, engines,
etc.)
NOTE: Proper alignment is the responsibility of the
installer and user of the unit.
Accurate alignment of the equipment must be attained.
Trouble-free operation can be accomplished by following
these procedures.
ALIGNMENT CHECKS
Initial Alignment (Cold Alignment)
Before Grouting Baseplate - To ensure alignment can
•
be obtained.
After Grouting Baseplate - To ensure no changes have
•
occurred during grouting process.
After Connecting Piping - To ensure pipe strains have
•
not altered alignment. If changes have occurred, alter
piping to remove pipe strains on pump flanges.
Table 1
Cold Setting of Parallel
Vertical Alignment
Pumpage TemperatureSet Driver Shaft
ambientN/A
100°F
200°F
300°F
.000" - .002" HIGH
.002” - .004” HIGH
.004” - .006” HIGH
183420 IOM 08/09
SET UP
1.Mount two dial indicators on the pump coupling half
(X) so they contact the other coupling half (Y) (Figs.
8 & 9).
Fig. 8
Fig. 10
Vertical Correction (Top-to-Bottom)
1.Zero indicator A at top dead center (12 o‘clock) of
coupling half Y.
2.Rotate indicators to bottom dead center (6 o‘clock).
Observe needle and record reading.
3.Negative Reading - The coupling halves are further
apart at the bottom than at the top. Correct by either
raising the driver feet at the shaft end (add shims) or
lowering the driver feet at the other end (remove
shims).
3
Fig. 9
2.Check setting of indicators by rotating coupling half
X to ensure indicators stay in contact with coupling
half Y but do not bottom out. Adjust indicators
accordingly.
MEASUREMENT
1.To ensure accuracy of indicator readings, always
rotate both coupling halves together so indicators
contact the same point on coupling half Y. This will
eliminate any measurement problems due to runout on
coupling half Y.
2.Take indicator measurements with driver feet
hold-down bolts tightened. Loosen hold down bolts
prior to making alignment corrections.
3.Take care not to damage indicators when moving
driver during alignment corrections.
ANGULAR ALIGNMENT
A unit is in angular alignment when indicator A (Angular
indicator) does not vary by more that .002 in. (.05 mm) as
measured at four points 90° apart (Fig. 10).
Positive Reading - The coupling halves are closer at
the bottom than at the top. Correct by either lowering
the driver feet at the shaft end (remove shims) or
raising the driver feet at the other end (add shims).
4.Repeat steps 1-3 until indicator A reads .002 in (.05
mm) or less.
Horizontal Correction (Side-to-Side)
1.Zero indicator A on left side of coupling half Y, 90°
from top dead center (9 o’clock).
2.Rotate indicators through top dead center to the right
side, 180° from the start (3 o’clock). Observe needle
and record reading.
3.Negative Reading - The coupling halves are further
apart on the right side than the left. Correct by either
sliding the shaft end of the driver to the left or the
other end to the right.
Positive Reading - The coupling halves are closer
together on the right side than the left. Correct by
either sliding the shaft end of the driver to the right or
the other end to the left.
4.Repeat steps 1 through 3 until indicator A reads .002
in. (.05 mm) or less.
5.Re-check both horizontal and vertical readings to
ensure adjustment of one did not disturb the other.
Correct as necessary.
3420 IOM 08/0919
PARALLELALIGNMENT
A unit is in parallel alignment when indicator P (parallel
indicator) does not vary by more than .002 in. (.05 mm) as
measured at four points 90° apart at operating temperature.
Note the preliminary vertical cold setting criteria, Table 1.
Vertical Correction (Top-to-Bottom)
1.Zero indicator P at top dead center of coupling (12
o’clock) half Y.
2.Rotate indicator to bottom dead center (6 o‘clock).
Observe needle and record reading.
3.Negative Reading - Coupling half X is lower than
coupling half Y. Correct by removing shims of
thickness equal to half of the indicator reading under
each driver foot.
Positive Reading - Coupling half X is higher than
coupling half Y. Correct by adding shims of thickness
equal to half of the indicator reading from each driver
foot.
NOTE: Equal amounts of shims must be added to or
removed from each driver foot. Otherwise the vertical
angular alignment will be affected.
4.Repeat steps 1 through 3 until indicator P reads within
.002 in. (.05 mm) or less when hot, or per Table 1
when cold.
Horizontal Correction (Side-to-Side)
1.Zero indicator P on the left side of coupling half Y,
90° from top dead center (9 o‘clock).
2.Rotate indicators through top dead center to the right
side, 180° from the start (3 o‘clock). Observe needle
and record reading.
3.Negative Reading - Coupling half Y is to the left of
coupling half X. Correct by sliding driver evenly in
the appropriate direction.
NOTE: Failure to slide motor evenly will affect
horizontal angular correction.
4.Repeat steps 1 through 3 until indicator P reads .002
in. (.05 mm) or less.
5.Re-check both horizontal and vertical readings to
ensure adjustment of one did not disturb the other.
Correct as necessary.
COMPLETE ALIGNMENT
A unit is in complete alignment when both indicators A
(angular) and P (parallel) do not vary by more than .002 in.
(.05 mm) as measured at four points 90 apart.
Vertical Correction (Top-to-Bottom)
1.Zero indicators A and P at top dead center (12
o'clock) of coupling half Y.
2.Rotate indicator to bottom dead center (6 o'clock).
Observe the needles and record the readings.
3.Make corrections as outlined previously.
Horizontal Correction (Side-to-Side)
1.Zero indicators A and P on the left side of coupling
half Y, 90° from top dead center (9 o'clock).
2.Rotate indicators through top dead center to the right
side, 180° from the start (3 o‘clock). Observe the
needle, measure and record the reading.
3.Make corrections as outlined previously.
4.Recheck both vertical and horizontal readings to
ensure adjustment of one did not disturb the other.
Correct as necessary.
NOTE: With experience, the installer will understand
the interaction between angular and parallel and will
make corrections appropriately.
Positive Reading - Coupling half Y is to the right of
coupling half X. Correct by sliding driver evenly in
the appropriate direction.
203420 IOM 08/09
ALIGNMENT TROUBLESHOOTING
ProblemProbable CauseRemedy
Driver feet bolt bound.
Cannot obtain horizontal (Side-to-Side)
alignment, angular or parallel
Cannot obtain vertical (Top-to-Bottom)
alignment, angular or parallel
Baseplate not leveled properly, probably
Baseplate not leveled properly,
probably bowed.
GROUT BASEPLATE
1.Clean areas of baseplate that will contact grout. Do
not use oil-based cleaners because grout will not bond
to it. Refer to grout manufacturers instructions.
2.Build dam around foundation. Thoroughly wet
foundation (Fig. 11).
3.Pour grout through grout hole in baseplate, up to level
of dam. Remove air bubbles from grout as it is poured
by puddling, using a vibrator, or pumping the grout
into place. Non-shrink grout is recommended.
twisted.
Loosen pump hold-down bolts and slide
pump and driver until horizontal alignment is
achieved.
Determine which corner(s) of the baseplate
are high or low and remove or add shims at
the appropriate corner(s) and realign.
Determine if center of baseplate should be
raised or lowered and correct by evenly add
ing or removing shims at the center of the
baseplate.
4.Allow grout to set.
5.Fill remainder of baseplate with grout. Remove air as
before (Fig. 12).
-
3
Flange loads from the piping system, including
!
those from thermal expansion of the piping, must
not exceed the limits of the pump. Casing
deformation can result in contact with rotating parts
and result in excess heat generation, sparks and
premature failure.
Fig. 11
Fig. 12
6.Allow grout to set at least 48 hours.
7.Tighten foundation bolts.
ALIGNMENT CHECK
Re-check alignment before continuing, using methods
previously described.
PIPING
GENERAL
Guidelines for piping are given in the “Hydraulic Institute
Standards” available from: Hydraulic Institute, 30200
Detroit Road, Cleveland, OH 44145-1967 and must be
reviewed prior to pump installation.
3420 IOM 08/0921
A
!WARNING
s
Never draw piping into place by forcing at the flanged
connections of the pump. This may impose dangerous
strains on the unit and cause misalignment between
pump and driver. Pipe strain will adversely effect the
operation of the pump resulting in physical injury and
damage to the equipment.
1.All piping must be supported independently of, and
line up naturally with, the pump flanges.
2.Piping runs should be as short as possible to minimize
friction losses.
3.DO NOT connect piping to pump until grout has
hardened and pump and driver hold-down bolts have
been tightened.
4.It is suggested that expansion loops or joints be
properly installed in suction and/or discharge lines
when handling liquids at elevated temperatures, so
linear expansion of piping will not draw pump out of
alignment.
!WARNING
s
All expansion joints should be properly supported,
anchored, and restrained. Failure to do so may result
in serious physical injury if the expansion joint fails.
5.The piping should be arranged to allow pump flushing
prior to removal of the unit on services handling
corrosive liquids.
6.Carefully clean all pipe parts, valves and fittings, and
pump branches prior to assembly.
straight pipe between the elbow and the pump suction
flange.
3.Use suction pipe one or two sizes larger than the
pump suction, with a reducer at the suction flange.
Suction piping should never be of smaller diameter
than the pump suction.
4.Reducers, if used, should be eccentric, at the pump
suction flange, with sloping side down.
5.Pump must never be throttled on suction side.
6.Suction strainers, when used, must have a net “free
area” of at least three times the suction pipe area.
7.Separate suction lines are recommended when more
than one pump is operating from the same source of
supply.
Suction Lift Conditions
1.Suction pipe must be free from air pockets.
2.Suction piping must slope upwards to pump.
3.All joints must be air tight.
4.A means of priming the pump must be provided, such
as a foot valve.
Suction Head/Flooded Suction Conditions
1.An isolation valve should be installed in the suction
line at least two pipe diameters from the suction to
permit closing of the line for pump inspection and
maintenance.
2.Keep suction pipe free from air pockets.
3.Piping should be level or slope gradually downward
from the source of supply.
SUCTION PIPING
!WARNING
s
NPSHAmust always exceed NPSHRas shown on Goulds
performance curves received with order. Reference
Hydraulic Institute for NPSH and pipe friction values
needed to evaluate suction piping.
Properly installed suction piping is a necessity for
trouble-free pump operation. Suction piping should be
flushed BEFORE connection to the pump.
1.Use of elbows close to the pump suction flange should
be avoided. There should be a minimum of two pipe
diameters of straight pipe between the elbow and
suction inlet. Where used, elbows should be long
radius.
2.If an elbow must be used at the suction flange, it must
be in the vertical position only. If an elbow must be
used in other than a vertical position, it is permissable
only by providing a minimum of two diameters of
4.No portion of the piping should extend below pump
suction flange.
5.The size of entrance from supply should be one or two
sizes larger than the suction pipe.
6.The suction pipe must be adequately submerged
below the liquid surface to prevent vortices and air
entrainment at the supply.
DISCHARGE PIPING
1.Isolation and check valves should be installed in
discharge line. Locate the check valve between
isolation valve and pump, this will permit inspection
of the check valve. The isolation valve is required for
priming, regulation of flow, and for inspection and
maintenance of pump. The check valve prevents
pump or seal damage due to reverse flow through the
pump when the driver is turned off.
2.Increasers, if used, should be placed between pump
and check valves.
223420 IOM 08/09
3.Cushioning devices should be used to protect the
pump from surges and water hammer if quick- closing
valves are installed in system.
FINAL PIPING CHECK
After connecting the piping to pump:
1.Rotate shaft several times by hand to be sure that
there is no binding and all parts are free.
2.Check alignment, per the alignment procedure
outlined previously to determine absence of pipe
strain. If pipe strain exists, correct piping.
3
3420 IOM 08/0923
243420 IOM 08/09
OPERATION
PREPARATION FOR START-UP ..........................25
General Considerations...............................31
Operating at Reduced Capacity ..........................31
Operating Under Freezing Conditions .......................32
SHUTDOWN ......................................32
FINAL ALIGNMENT .................................32
PREPARATION FOR START-UP
When installing in a potentially explosive
!
environment, ensure that the motor is properly
certified.
4
4.Make sure everyone is clear. Jog driver just long
enough to determine the direction of rotation. The
rotation must correspond to the arrow on the pump
casing.
CHECK ROTATION
1.Lock out power to the driver.
!WARNING
s
Lock out driver power to prevent accidental start-up
and physical injury.
All equipment being installed must be properly
!
grounded to prevent unexpected static electric
discharge.
2.Make sure the coupling hubs are securely fastened to
the shafts.
!WARNING
s
Do not jog a coupled pump.
$
Serious injury may result if pump is run in the wrong
direction.
CAUTION
5.Lock out the power to the driver.
COUPLE PUMP & DRIVER
!WARNING
s
Lock out driver power to prevent accidental rotation
and physical injury.
1.Install and lubricate the coupling per the
manufacturer’s instructions.
The coupling used in an ATEX classified
!
environment must be properly certified.
NOTE: Pump is shipped with the coupling hubs
disconnected.
3.Unlock driver power.
3420 IOM 8/0925
2.Install the coupling guard (Fig. 13). Refer to the
Coupling Guard Installation and Disassembly Section
(Appendix I).
The coupling guard used in an ATEX classified
!
environment must be constructed from a
non-sparking material.
!WARNING
s
Never operate a pump without the coupling guard
installed. Personal injury will occur if the pump is run
without the coupling guard.
Leakage of process liquid may result in creating an
!
explosive atmosphere. Ensure the materials of the
pump casing, impeller, shaft, sleeves, gaskets and
seals are compatible with the process liquid.
A build up of gases within the pump, sealing system
!
and or process piping system may result in an
explosive environment within the pump or process
piping system. Ensure process piping system, pump
and sealing system are properly vented prior to
operation.
LUBRICATING BEARINGS
Bearings must be lubricated properly in order to
!
prevent excess heat generation, sparks and
premature failure.
Cooling systems such as those for bearing
!
lubrication, mechanical seal systems, etc, where
provided, must be operating properly to prevent
excess heat generation, sparks and premature
failure.
Rotate shaft by hand to ensure it rotates smoothly
!
and there is no rubbing which could lead to excess
heat generation and or sparks.
Ensure that pump and systems are free of foreign
!
objects before operating and that objects cannot
enter the pump during operation. Foreign objects in
the pumpage or piping system can cause blockage of
flow which can result in excess heat generation,
sparks and premature failure.
Fig. 13
$
Pumps are shipped without oil.
Oil Lubrication: Oil lubricated pumps are not lubricated at
the factory. Constant level oilers are supplied with oil
lubricated pumps. The oiler can be found in the box of
fittings that accompanied the pump during shipment. The
oiler was adjusted to maintain the proper oil level before
leaving the factory. The adjustment should be checked in
case the setting was disturbed during shipment. See Figure
14. The correct dimensions for A and B are given in Table
2. Fill the bearing housing with oil using the oil bottle.
Continue to refill the oil bottle until oil stops draining from
the oiler into the housing. See Table 4 for recommended
oil.
CAUTION
Instructions
1. Remove adjustment
assembly from oiler.
2. Adjust bars to dim. "A".
3. Lock in position.
4. Replace adjust. assem. in
oiler
A
Do not insulate bearing housings as this can result
!
in excess heat generation, sparks and premature
failure.
Check for magnetism on the pump shaft and
!
degauss the shaft if there is any detectable
magnetism. Magnetism will attract ferritic objects to
the impeller, seal and bearings which can result in
excess heat generation, sparks and premature
failure.
Pure/Purge Oil Mist: For pure oil mist, connect the oil
mist system according to the manufacturer's
recommendations. For purge oil mist, connect the oil mist
system per the manufacturers instructions. Fill the pump
with oil as detailed for oil lubrication above. In both cases,
refer to the pump dimensional drawing for the location of
the oil mist connections to the bearing housings. See Table
2 for oil bottle settings and Table 4 for recommended oil.
Fig. 14
263420 IOM 8/09
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.