Goulds Pumps 3311 User Manual

Installation, Operations, and Maintenance Instructions
Model 3311
TABLE OF CONTENTS
3 SAFETY INSTRUCTIONS 1
5 APPLICATION 2
7 SYSTEM LAYOUT 3
12 UNPACKING, HANDLING, STORAGE 4
14 PUMP INSTALLATION 5
17 STARTING AND STOPPING PROCEDURES 6
19 MAINTENANCE, DISASSEMBLY, ASSEMBLY 7
30 LOCATING TROUBLES 8
31 SECTIONAL DRAWING / PARTS LIST 9
Please note: Only trained and skilled operating personnel are allowed to install and operate this
pump or pump set. Compliance with these operating instructions and all applicable rules and regulations must be ensured.
If you fail to comply with these operating instructions:
people may be put at risk
the pump or pump set may be damaged
the manufacturer shall not be held liable for damage caused by non-compliance.
2
1 Safety Instructions
1.1 Safety instructions
This manual gives basic instructions which must be observed during installation, operation and maintenance of the pump.
It is therefore imperative that this manual be read by the installer and the responsible personnel or operators prior to installation and commissioning. It must always be available on site.
Within this manual, safety instructions are marked with safety symbols.
Safety symbol to ISO 3864-B.3.1
This general hazard symbol highlights information non­compliance with which could cause a risk to personal safety.
Safety symbol to ISO 3864-B.3.6
This symbol refers to electrical hazards.
CAUTION
This word gives warning of a hazard to the machine.
Signs affixed to the machine, e.g.
- arrow indicating the direction of rotation
- symbols indicating fluid connections
must be visible and kept legible.
1.2 Qualification and training of
operating personnel
The personnel responsible for operation, maintenance, inspection and assembly must be properly trained and qualified.
The responsibilities of the operating personnel must be exactly defined by the plant operator. If the staff does not have the necessary knowledge, they must be trained and instructed, which may be performed by the machine manufacturer or the supplier on behalf of the plant operator, if required. Moreover, the plant operator is to make sure that the contents of this manual are fully understood by the operating personnel.
1.3 Hazards in the event of non-
compliance with the safety instructions
Non-compliance with the safety instructions may cause a risk to personnel as well as to the environment and the machine. Non-compliance may result in a loss of any right to claim damages.
For example, non-compliance may involve the following hazards:
- failure of important functions of the equipment;
- failure of specified maintenance and repair procedures;
- electrical, mechanical and chemical hazards affecting
personal safety;
- leakage of environmentally damaging substances.
1.4 Safety at work
When operating the pump, the safety instructions contained in this manual, the relevant national accident prevention regulations and any other service and safety instructions issued by the plant operator must be observed.
3
1.5 Safety instructions relevant to
operation
- If hot or cold machine components involve hazards, the
customer must ensure these components are guarded against accidental contact.
- Guards for moving parts (e.g. coupling) must not be
removed from the machine while in operation.
- Any leakage of hazardous (e.g. explosive, toxic, hot)
fluids (e.g. from the shaft seal) must be drained away so as to prevent any risk to personal safety or the environment. Statutory regulations must be complied with.
- Hazards resulting from electricity must be prevented.
Local regulations must be complied with.
1.6 Safety instructions relating to
maintenance, inspection and assembly work
It shall be the plant operator's responsibility to ensure that all maintenance, inspection and assembly work is performed by authorized and qualified personnel who have adequately familiarized themselves with the subject matter by studying this manual in detail.
Any work on the machine shall only be performed when it is not operating and has been properly secured from starting. Always lock out power to the driver before performing pump maintenance. The procedure for stopping the machine described in this manual must be followed.
Pumps which handle hazardous fluids must be decontaminated.
On completion of work all safety and protective equipment must be re-installed and made operative again.
Prior to restarting the machine, the instructions listed under sub-section 6.4 "Checks before first start-up" must be observed.
1.7 Unauthorized alterations and
production of spare parts
Any modification to the machine is permissible only after consultation with Gould’s Pumps.
Using genuine spare parts and accessories authorized by the manufacturer is in the interest of safety. Use of other parts may exempt the manufacturer from any liability.
1.8 Unauthorized use
Goulds Pumps, inc. will not be liable for any damages or delay caused by failure to comply with the provisions of this instruction manual. The pump is not to be operated at speeds, working pressures, discharge pressures or temperatures higher than, nor used with liquids other than, stated in the original order acknowledgement or the conditions of service for which it was quoted without written permission from Goulds Pumps.
4
2 Application
2.1 Limitation of use
Operation of the pump must be limited to the application and operating conditions stated by the purchaser and confirmed on the manufacturer's data sheet. The pump is covered by warranty under Gould’s Pumps’ conditions of sale.
2.2 Wrong use
Operate the pump only for the application stated on
the data sheet. Operation outside these limits of product application will increase the risk to personal safety and the environment.
CAUTION
Do not exceed the density stated on the data sheet as
this could cause a motor overload condition.
Do not operate the pump outside its characteristic
curve so as to avoid pump or motor damage.
2.3 Accessories
The accessories supplied with the pump are indicated on the data sheet. Other accessories may be mounted to the pump or the pump set only after Gould’s Pumps' prior consent.
2.4 Design and working principle
The 3311 high pressure pump of the Goulds multi-stage line is a horizontal multi-stage ring-section type centrifugal pump.
It meets the technical requirements according to DIN ISO 5199 / EN 25199.
The pump casings are held together by external tie bolts and sealed against the atmosphere by O-rings.
The axial thrust is balanced by a hydraulic balancing device consisting of a disc/drum combination. An additional lift-off device is available and intended for special applications. The balancing liquid flows back through an external line to the suction casing.
Suction nozzle: axial or radial.
In the case of radial suction nozzle orientation, the suction casing pump feet assembly allows adaptation to the installation requirements by rotating the casing.
Bearings: Oil-lubricated anti-friction bearing on the discharge side; suction side sleeve bearing lubricated by the liquid handled or oil-lubricated anti-friction bearing.
Shaft seal: Packed stuffing box or mechanical seal according to DIN
24960.
Drive: Depending on its design, the pump is either driven from the discharge side or the suction side, by a customary electric motor or turbine. The direction of rotation is counter-clockwise for discharge side drive, and clockwise for suction side drive, when viewed from drive end.
2.5 Applications
- M unici pal water supply:
Pumping stations, treatment plants, booster units.
- Water treatment:
Filtration, reverse osmosis.
- Pumps for industrial purposes:
General water supply, cold water, boiler feed installations, hot water, pumping of organic and inorganic solutions, high-pressure gas washing; power water generation plants, purifying and cleaning plants, desalinization plants.
- Power supply:
Small and medium-sized thermal stations, waste incineration installations.
5
2.6 Nameplate Information
Every pump has a Goulds nameplate that provides information about the pump. The tags are located on the pump casing.
When ordering parts, you will need to identify the pump model, size, serial number, and the item number of the required parts. Information can be taken from the pump casing tags. Item numbers can be found later in this manual.
Pump Casing Tag – provides information about the pump’s hydraulic characteristics. Note the format of the pump size: Discharge x Suction – Nominal maximum Impeller Diameter in inches. (Example: 2x3-7)
6
3 System Layout
3.1 Pipework
3.1.1 General
In short discharge lines, the nominal diameter should be such that the piping resistance is only a small proportion of the discharge head. For long pipelines, the most cost­effective solution should be determined on a case-by-case basis.
Flow velocity guidelines:
Suction line: v max. 3 m/s
Discharge line: v
Abrupt cross-section transitions or sharp bends should be avoided. Flow disturbances must be kept to a minimum when making necessary branches.
Unfavorable pipework layouts may impair the performance of the pump, especially on the suction side (e.g. bends in several planes in front of the suction nozzle).
1.5 to 2.5 m/s
s
4 to 6 m/s
D
The pipework must be independently supported and
positioned such that no excessive forces and moments are exerted on the pump flanges.
Excessive loads could result in leakage and be
hazardous to personnel.
CAUTION
If hot water is handled, excessive pipework loads and
moments can cause a misalignment of the coupling between pump and driver, thus reducing the operating safety of the unit.
Once the flange bolts have been released, the flanges must not yield more than the amount corresponding to the gasket thickness, nor must they be out of parallel nor bear against each other under stress. Check that the flange gaskets do not extend into the interior of the pipe. All pipe components, valves and fittings and the pump nozzles should be thoroughly cleaned before assembly.
Air-relief valves and drain valves must be installed in the suction and discharge lines.
In order to prevent the formation of air pockets,
- a feed line (supply source above the pump) should
slope gradually downward towards the pump;
- a suction line (supply source below the pump) should
gradually rise to the pump.
Shut-off valves must be installed in the suction and discharge lines and in all pipelines connecting the pump with the liquid system.
The valves enable the pump to be depressurized and dismantled without having to drain the system. Flow regulation at constant speed is permissible from the discharge side only.
CAUTION
The pipes should have at least the nominal diameter of
the pump nozzles. Where this is not possible, it should be ensured that the flow velocity in the suction or feed line does not exceed 2 - 3 m/s.
Flange seals must not extend into the interior of the
pipework.
Clean the pipework prior to pump installation.
Support the pipelines so as to prevent distortion of
pump components.
Avoid rough cross-section transitions and sharp bends.
Eccentric reducers must be used in the event of
different nominal diameters.
In the event of unfavorable suction conditions, stead y
flow should be ensured over a length of 15 x suction nozzle diameter upstream from the suction nozzle.
Shut-off valves in the suction or discharge line must
be fully open during operation and must never be used to control the flow.
7
3.1.2 Suction or feed line
A suction line should rise to the pump and a feed line should slope gradually downward towards the pump.
Feed operation suction operation
Reducers mounted must be eccentric to eliminate the possibility of air pockets being formed.
CAUTION
The strainer is for starting purposes only. Solids which
are smaller than the mesh size will not be retained by the strainer.
However, such small particles may collect in the
lateral area of the impeller near the clearances, in particular if their concentration is high.
In order to prevent clogging, it is recommended that
the customer provide a sedimentation tank or a larger flushable fine strainer upstream from the pump.
Design:
Conical strainer with perforated plate support body with external fine screen, mesh size 0.5 mm, of corrosion­resistant material. The fine screen can be removed after several months of operation, once there are no more deposits.
For new conical strainers supplied by Gould’s Pumps the pressure loss can be calculated as follows:
Hv
2
v
ζ
=
g2
in m
v = medium flow velocity in reference cross-section, in m/s ζ = 4, loss coefficient for new conical strainers
Eccentric reducer
If the liquid is contaminated, a filter should be fitted upstream from the pump whose free-space sectional area should be three times the pipe cross-sectional area.
8
1 Pump suction nozzle / flange 2 Pipe section for strainer 3 Conical strainer (installed with its tip against flow direction) 4 Feed line 5 Differential pressure measuring instrument
Feed line with conical strainer
Determining the strainer pressure loss
Example:
Feed line = DN 125 Flow rate 80 m³/h ζ = 4 v = 1.81 m/s in the feed line
Hv =
2
4
81.1
81.92
276.3
4
62.19
66.0
==
m
The suction line must be leak-proof and it must be possible to release all air. The suction opening of the suction line should be well below the liquid level, and a foot valve with a strainer should be used. The foot valve must be far enough from the bottom to avoid excessive inlet losses which could impair performance.
3.1.3 Vacuum equalizing pipe
If the pump draws from a system or tank under vacuum, an equalizing pipe must be installed connecting the vent connection at the suction casing or the highest point of the suction line to a point above the maximum liquid level in the suction tank.
- The line should be fitted with a shut-off valve which
should only be closed for maintenance work on the pump.
To assist in starting the pump, we also recommend that a pipeline, which can be shut off, be installed between the first stage and the equalizing line.
1 Eccentric reducer (suction operation) or concentric reducer (feed operation) 2 Shut-off valve 3 Suction line 4 Bend 5 Foot valve 6 Feed line 7 Non-return valve 8 Control valve
Pump installation
A shut-off valve should be installed in the feed line; it is to be closed for maintenance work.
It should be installed such that air pockets cannot form in the spindle cap, i.e. with the spindle in a horizontal position or pointing vertically downward.
a Equalizing line b Additional line 1 Shut-off valve 2 Shut-off valve (vacuum-tight)
Vacuum operation
3.1.4 Discharge line
For flow control, install a shut-off valve as close to the pump nozzle as possible. It is recommended that a non­return valve be installed between pump nozzle and shut­off valve, thus protecting the pump against reverse rotation and also the pump and the foot valve against water hammer that may occur in the event of sudden shut­down.
9
3.1.5 Minimum flow line
The minimum flow line (or bypass line) should be used if operation with the discharge side shut-off valve closed is possible. The minimum flow valve ensures that a sufficient rate is automatically returned to the suction side tank.
The minimum flow rate is shown on the curves or the data sheet.
Size t = 140 °C or lower t > 140 °C
2x3-7 20 % of Q
2.5x4-8 20 % of Q 4x5-11 25 % of Q
25 % of Q
BEP
25 % of Q
BEP
25 % of Q
BEP
BEP BEP BEP
Should exact calculation be required, please contact Gould’s Pumps.
CAUTION
Up to the shut-off or non-return valve, the line should
be designed to suit the nominal pressure of the discharge line, afterwards in accordance with the design pressure of the feedwater/suction tank.
Permissible velocity in the minimum flow line: 7 to 10
m/s.
If an automatic device (bypass non-return valve) is
used, ensure that even in the case of trouble, liquid can be returned through the minimum flow line.
Frequent checks are recommended. Early replacement
of the minimum flow valve (which is exposed to heavy wear) will prevent energy losses.
The minimum flow valve should be installed near the
pump discharge nozzle, upstream from the discharge shut-off valve.
A non-return valve should be installed in the
minimum flow nozzle or the minimum flow line.
For repair or overhaul work on the pump or the bypass
non-return valve, a shut-off valve must be installed in the minimum flow line (c).
a Feed line b Discharge line c Bypass line 1 Bypass non-return valve 2 Conical strainer
Minimum flow control
3.1.6 Balancing line
The balancing line connects the discharge side shaft sealing casing with the suction casing. There is no throttling or shut-off device in this line, which serves to hydraulically balance the pump.
The balancing line can also be returned by the customer to the feed tank or the feed line.
3.1.7 Venting during pump priming
Before starting the set, the pump and the suction line must be completely vented and filled with the liquid handled. To bleed the air, several holes with plugs have been provided. Similar holes may be used in the pip ework. The shut-off valve in the suction or supply line must be fully open.
10
3.1.8 Cooling
Cooling is required if the temperature of the liquid handled exceeds 110 °C, if a packed stuf fing box is used, or 140 °C if a mechanical seal is installed. For this purpose the pump is equipped with a shaft sealing casing which can be cooled. The connecting points for the cooling lines are on the shaft sealing casing. The customer should provide either an open circuit, i.e. a cooling water return line to the drain system, or a closed circuit including a return to the cooling circuit to be provided.
3.1.9 Drain line, leakage water line
The pump has connections for leakage water and drain lines.
3.1.10 Pressure monitoring
In order to monitor the pressures upstream and downstream from the pump, the installation of measuring points in the pipeline is recommended.
3.2 Electrical connections
The electrical connection for the driving motor must be in compliance with the relevant rules and requirements.
11
4 Unpacking, Handling, Storage
4.1 Safety measures
4.4 Handling
The pump or the pump set must be lifted as shown below:
Do not lift heavy equipment overhead of personnel.
A safe distance must be kept when lifting and moving
the equipment.
Use only approved and suitable lifting equipment.
The length of the lifting equipment should be such
that the pump or the set are lifted in horizontal position.
Do not attempt to lift the pump or the pump set using
eyebolts on pump components.
CAUTION
Do not remove protection covers from the pump
nozzles, as they prevent contamination of the pump.
4.2 Unpacking
Do not unpack the pump until it has been carefully checked for damage that may have occurred in transit. Report any damage on the counterfoil or delivery note.
Claims must be made immediately on the carrier or the transport insurance.
4.3 Intermediate storage
If the pump or the pump set is not to be installed immediately it should be stored in a clean, dry and vibration-free room.
The packing should be checked for damage on a monthly basis.
Lifting the pump
Lifting the pump / motor / baseplate assembly
12
4.5 Preservation
Usually, only iron pumps are preserved.
4.5.1 Removal of preservation
To remove the preservative coating, the pump should be filled and drained several times using appropriate agents, e.g. solvent naphta, diesel oil, or an alkaline detergent. Flush with water, if necessary.
The pump must be installed and put into operation immediately afterwards.
4.5.2 Re-preservation
If the pump has been supplied preserved and is to be stored, a new preservative coating should be applied after six months.
For suitable preservatives, contact Goulds Pumps.
13
5 Pump Installation
5.1 Prerequisites
Prior to the installation of the pump, the storage and handling instructions in Section 4 must have been complied with.
5.2 Safety measures
The pipework must be properly installed. Fluid
leakage during operation may cause health hazards or environmental damage.
The shut-off valves in the suction or feed line and in
the discharge line must be closed.
All internal rules and guidelines must be complied
with.
Hot components must have contact guards.
Disconnect power to the equipment so as to eliminate
electrical shock hazards!
5.3 General
5.3.1 Fitting tools
Standard tools and lifting equipment are used. These should be available at the customer's end.
5.3.2 Permissible environment
The ambient temperature range should be from
- 20 °C to + 60 °C.
The atmospheric humidity should be low in order to avoid corrosion.
5.3.3 Space utilization
The space required by the pump or the pump set can be seen from the table of dimensions and the arrangement drawing.
Clear and easy access to the shut-off and regulating valves and the measuring instruments must be ensured.
5.3.4 Installation position
3311 pumps are installed in horizontal position.
5.3.5 Preparatory checks
The foundation of the pump must be level and have a minimum of vibration. The consistency of the concrete should at least correspond to BN15, DIN 1045.
We recommend using a baseplate.
Prior to installation checks should be made with regard to:
- possible damage to the pump or the pump set that may
have occurred in transit
- ease of running (check that the shaft is free to rotate by
hand)
- the foundation dimensions.
5.3.6 Foundation
Prior to placing the pump set on the foundation which should be well set, the following preparatory work must be carried out:
- roughen and clean foundation surface
- remove shuttering/cores from the anchor holes
- clean and blow out the anchor holes
- check the positions and dimensions of the anchor holes
against the arrangement drawing.
Alternatively: If the baseplate is fastened by means of heavy load plugs:
- Scribe and drill plug holes
- Clean plug holes and blow them out
- Inse rt heavy l oad plugs
14
Loading...
+ 30 hidden pages