This manual provides instructions for the Installation, Operation, and Maintenance of the Goulds Model 3296 “M
Group” Magnetic Drive Process Pump. This manual must be read and understood before installation and start-up.
The design, materials, and workmanship incorporated in the construction of Goulds pumps makes them capable of
giving, trouble-free service. The life and satisfactory service of any mechanical unit, however, is enhanced and
extended by correct application, proper installation, periodic inspection, condition monitoring and careful
maintenance. This instruction manual was prepared to assist operators in understanding the construction and the
correct methods of installing, operating, and maintaining these pumps.
Goulds shall not be liable for physical injury, damage or delays caused by a failure to observe the instructions
for Installation, Operation, and Maintenance contained in this manual.
Warranty is valid only when genuine Goulds parts are used.
Use of the equipment on a service other than stated in the order could nullify the warranty, unless written approval
is obtained in advance from Goulds Pumps, Inc.
Supervision by an authorized Goulds representative is recommended to assure proper installation.
Additional manuals can be obtained by contacting your local Goulds representative or by calling 1-800-446-8537.
THIS MANUAL EXPLAINS
Proper Installation
n
Start Up Procedures
n
Operation Procedures
n
Routine Maintenance
n
Pump Overhaul
n
Troubleshooting
n
Ordering Spare or Repair Parts
n
3296 M Group 6/053
TABLE OF CONTENTS
PAGESECTION
7SAFETY
9GENERAL INFORMATION
11INSTALLATION
19OPERATION
23PREVENTIVE MAINTENANCE
27DISASSEMBLY & REASSEMBLY
1
2
3
4
5
6
55SPARE AND REPAIR PARTS
61APPENDIX
7
8
3296 M Group 6/055
63296 M Group 6/05
IMPORTANT SAFETY NOTICE
To: Our Valued Customers
User safety is a major focus in the design of our products. Following the precautions outlined in this
manual will minimize your risk of injury.
ITT Goulds pumps will provide safe, trouble-free service when properly installed, maintained, and
operated.
Safe installation, operation, and maintenance of ITT Goulds Pumps equipment are an essential end user
responsibility. This Pump Safety Manual identifies specific safety risks that must be considered at all
times during product life. Understanding and adhering to these safety warnings is mandatory to ensure
personnel, property, and/or the environment will not be harmed. Adherence to these warnings alone,
however, is not sufficient — it is anticipated that the end user will also comply with industry and corporate
safety standards. Identifying and eliminating unsafe installation, operating and maintenance practices is
the responsibility of all individuals involved in the installation, operation, and maintenance of industrial
equipment.
Please take the time to review and understand the safe installation, operation, and maintenance guidelines
outlined in this Pump Safety Manual and the Instruction, Operation, and Maintenance (IOM) manual.
Current manuals are available at
your nearest Goulds Pumps sales representative.
www.gouldspumps.com/literature_ioms.html or by contacting
These manuals must be read and understood before installationand star t-up.
For additional information, contact your nearest Goulds Pumps sales representative or visit our Web site at
www.gouldspumps.com.
S-1
SAFETY WARNINGS
Specific to pumping equipment, significant risks bear reinforcement above and beyond normal safety precautions.
WARNING
A pump is a pressure vessel with rotating parts that can be hazard o us. An y press ure vessel can explode,
rupture, or discharge its contents if sufficiently ove r press u r i zed causi n g deat h, personal injury, property
damage, and/or damage to the environment. All necessary measures must be taken to ensure over
pressurization does not occur.
WARNING
Operation of any pumping system with a blocked suction and discharge must be avoided in all cases.
Operation, even for a brief period under these conditions, can cause superheating of enclosed pumpage and
result in a violent explosion. All necessary measures must be taken by the end user to ensure this condition is
avoided.
WARNING
The pump may handle hazardous and/or toxic fluids. Care must be taken to identify the contents of the pump
and eliminate the possibility of exposure, particularly if hazardous and/or toxic. Potential hazards include, but
are not limited to, high temperature, flammable, acidic, caustic, explosive, and other risks.
WARNING
Pumping equipment Instruction, Operation, and Maintenance manuals clearly identify accepted methods for
disassembling pumping units. These methods must be adhered to. Specifically, applying heat to impellers
and/or impeller retaining devices to aid in their removal is strictly forbidden. Trapped liquid can rapidly
expand and result in a violent explosion and injury.
ITT Goulds Pumps will not accept responsibility for physical injury, damage, or delays caused by a failure to
observe the instructions for installation, operation, and maintenance contained in this Pump Safety Manual or the
current IOM available at www.gouldspumps.com/literature.
S-2
SAFETY
DEFINITIONS
Throughout this manual the words WARNING, CAUTION, ELECTRICAL, and ATEX are used to indicate
where special operator attention is required.
Observe all Cautions and Warnings highlighted in this Pump Safety Manual and the IOM provided with
your equipment.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Example:
Pump shall never be operated without coupling guard installed correctly.
CAUTION
Indicates a hazardous situation which, if not avoi ded, could result in minor or moderate injury.
Example: Throttling flow from the suction side may cause cavitation and pump damage.
ELECTRICAL HAZARD
Indicates the possibility of electrical risks if directions are not followed.
Example:Lock out driver power to prevent electric shock, accidental start-up, and physical injury.
When installed in potentially explosive atmospheres, the instructions that follo w the Ex symbol must be
followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there
is any question regarding these requirements or if the equipment is to be modified, please contact an ITT
Goulds Pumps representative before proceeding.
Example:
parts, resulting in a spark and heat generation.
Improper impeller adjustment could cause contact between the rotating and stationary
S-3
GENERAL PRECAUTIONS
WARNING
A pump is a pressure vessel with rotating parts that can be hazardous. Hazardous fluids may be contained by the
pump including high temperature, flammable, acidic, caustic, explosive, and other risks. Operators and
maintenance personnel must realize this and follow safety measures. Personal injuries will result if procedures
outlined in this manual are not followed. ITT Goulds Pumps will not accept responsibility for physical injury,
damage or delays caused by a failure to observe the instructions in this manual and the IOM provided with your
equipment.
WARNING
WARNING
General Precautions
NEVER use heat to disassemble pump due to risk of explosion from tapped liquid.
NEVER APPLY HEAT TO REMOVE IMPELLER. It may explode due to
trapped liquid.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
NEVER operate pump without safety devices installed.
NEVER operate pump without coupling guard correctly installed.
NEVER run pump below recommended minimum flow when dry, or without
prime.
ALWAYS lock out power to the driver befo re per fo rming pump maintenance.
NEVER operate pump with discharge valve closed.
NEVER operate pump with suction valve closed.
DO NOT change service application without approval of an authorized ITT
Goulds Pumps representative.
Safety Apparel:
Insulated work gloves when handling hot bearings or using bearing heater
Heavy work gloves when handling parts with sharp edges, especial l y
impellers
Safety glasses (with side shields) for eye protection
Steel-toed shoes for foot protection when handli ng pa rts, heavy tools, etc.
Other personal protective equipment to protect against hazardous/toxic fluids
Receiving:
Assembled pumping units and their components are heavy. Failure to properly lift
and support equipment can result in serious physical injury and/or equipment
damage. Lift equipment only at specifically identified lifting points or as
instructed in the current IOM. Current manuals are available at
www.gouldspumps.com/literature_ioms.htmlor from your local ITT Goulds
Pumps sales representative. Note: Lifting devices (eyebolts, slings, spreaders, etc.)
must be rated, selected, and used for the entire load being lifted.
Alignment:
WARNING
Shaft alignment procedures must be followed to prevent catastrophic failure of
drive components or unintended contact of rotating parts. Follow coupling
manufacturer’s coupling installation and operation procedures.
S-4
WARNING
CAUTION
General Precautions
Before beginning any alignment procedure, make sure driver power is locked out.
Failure to lock out driver power will result in serious physical injury.
Piping:
Never draw piping into place by forcing at the flan ged con necti on s of t he pump.
This may impose dangerous strains on the unit and cause misalignment between
pump and driver. Pipe strain will adversely effect the operation of the pump
resulting in physical injury and damage to the equipment.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
CAUTION
CAUTION
WARNING
Flanged Connections:
Use only fasteners of the proper size and material.
Replace all corroded fasteners.
Ensure all fasteners are properly tightened and there are no missing fasteners.
Startup and Operation:
When installing in a potentially explosive environment, please ensure that the
motor is properly certified.
Operating pump in reverse rotation may result in contact of metal parts, heat
generation, and breach of containment.
Lock out driver power to prevent accidental start-up and physical injury.
The impeller clearance setting procedure must be followed. Improperly setting
the clearance or not following any of the proper procedures can result in sparks,
unexpected heat generation and equipment damage.
If using a cartridge mechanical seal, the centering clips must be installed and set
screws loosened prior to setting impeller clearance. Failure to do so could result
in sparks, heat generation, and mechanical seal damage.
The coupling used in an ATEX classified environment must be properly certified
and must be constructed from a non-sparking material.
Never operate a pump without coupling guard properly installed. Personal injury
will occur if pump is run without coupling guard.
Make sure to properly lubricate the bearings. Failure to do so may result in excess
heat generation, sparks, and / or premature failure.
The mechanical seal used in an ATEX classified environment must be properly
certified. Prior to start up, ensure all points of potential leakage of process fluid to
the work environment are closed.
Never operate the pump without liquid supplied to mechanical seal. Running a
mechanical seal dry, even for a few seconds, can cause seal damage and must be
avoided. Physical injury can occur if mechanical seal fails.
Never attempt to replace packing until the driver is properly locked out and the
coupling spacer is removed.
WARNING
WARNING
S-5
Dynamic seals are not allowed in an ATEX classified environment.
DO NOT operate pump below minimum rated flows or with suction and/or
discharge valve closed. These conditions may create an explosive hazard due to
vaporization of pumpage and can quickly lead to pump failure and physical injury.
WARNING
WARNING
WARNING
WARNING
WARNING
CAUTION
CAUTION
WARNING
CAUTION
CAUTION
General Precautions
Ensure pump is isolated from system and pressure is relieved before
disassembling pump, removing plu gs, ope ni n g vent or drain valves, or
disconnecting piping.
Shutdown, Disassembly, and Reassembly:
Pump components can be heavy. Proper methods of lifting must be employed to
avoid physical injury and/or equipment damage. Steel toed shoes must be worn at
all times.
The pump may handle hazardous and/or toxic fluids. Observe proper
decontamination procedures. Proper personal protective equipment should be
worn. Precautions must be taken to prevent physical injury. Pumpage must be
handled and disposed of in conformance with applicable environmental
regulations.
Operator must be aware of pumpage and safety precautions to prevent physical
injury.
Lock out driver power to prevent accidental startup and physical injury.
Allow all system and pump components to cool before handling them to prevent
physical injury.
If pump is a Model NM3171, NM3196, 3198, 3298, V3298, SP3298, 4150, 4550,
or 3107, there may be a risk of static electric discharge from plastic parts that are
not properly grounded. If pumped fluid is non-conductive, pump should be
drained and flushed with a conductive fluid under conditions that will not allow
for a spark to be released to the atmosphere.
Never apply heat to remove an impeller. The use of heat may cause an explosion
due to trapped fluid, resulting in severe physical injury and property damage.
Wear heavy work gloves when handling impellers as sharp edges may cause
physical injury.
Wear insulated gloves when using a bearing heater. Bearings will get hot and can
cause physical injury.
S-6
ATEX CONSIDERATIONS and INTENDED USE
Special care must be taken in potentially explosive environments to ensure that the equipment is properly
maintained. This includes but is not limited to:
1. Monitoring the pump frame and liquid end temperature.
2. Maintaining proper bearing lubrication.
3. Ensuring that the pump is operated in the intended hydraulic range.
The ATEX conformance is only applicable when the pump unit is operated within its intended use. Operating,
installing or maintaining the pump unit in any way that is not covered in the Instruction, Operation, and
Maintenance manual (IOM) can cause serious personal injury or damage to the equipment. This includes any
modification to the equipment or use of parts not provided by ITT Goulds Pumps. If there is any question
regarding the intended use of the equipment, please contact an ITT Goulds represe ntative before proceeding.
Current IOMs are available at
Pumps Sales representative.
All pumping unit (pump, seal, coupling, motor and pump accessories) certified for use in an ATEX classified
environment, are identified by an ATEX tag secured to the pump or the baseplate on which it is mounted. A
typical tag would look like this:
www.gouldspumps.com/literature_ioms.htmlor from your local ITT Goulds
The CE and the Ex designate the ATEX compliance. The code directly below these symbols reads as follows:
II = Group 2
2 = Category 2
G/D = Gas and Dust present
T4 = Temperature class, can be T1 to T6 (see Table 1)
Table 1
Max permissible
surface temperature
Code
T1 842 (450) 700 (372)
T2 572 (300) 530 (277)
T3 392 (200) 350 (177)
T4 275 (135) 235 (113)
T5 212 (100) Option not available
T6 185 (85) Option not available
o
F (oC)
The code classification marked on the equipment must be in accordance with the specified area where the
equipment will be installed. If it is not, do not operate the equipment and contact your ITT Goulds Pumps sales
representative before proceeding.
Max permissible
liquid temperature
o
F (oC)
S-7
PARTS
The use of genuine Goulds parts will provide the safest and
most reliable operation of your pump. ITT Goulds Pumps ISO
certification and quality control procedures ensure the parts are
manufactured to the highest quality and safety levels.
Please contact your local Goulds representative for details on
genuine Goulds parts.
The Model 3296 is a sealless frame-mounted
centrifugal pump with an enclosed impeller, that is
driven by a synchronous magnetic coupling, and meets
dimensional standards of ANSI B73.1.
Magnetic Coupling - is a coaxial synchronous type
using rare earth magnets. This concept results in a
compact design and allows the impeller to turn at the
same speed as the motor, (i.e.) there is no slip between
the drive and driven magnets.
Magnets - Two types of rare earth magnets are
available. Neodymium Iron (NdFe), which is used
when pumpage temperatures are less than 250°F
(120°C). For liquid pumpage between 250°F (120°C)
and 425°F (220°C) Samarium Cobalt (SmCo) magnets
are used.
Containment Shell - isolates the pumped liquid from
the atmosphere. Standard material is Hastelloy-C
which provides excellent corrosion and erosion
resistance.
NAMEPLATE INFORMATION
Sleeve Bearings and Thrust Bearings - Goulds
standard bearing material is Pure Sintered Alpha Grade
Silicon Carbide. The sleeve bearings are flexibly
mounted using O-rings.
Impeller - Model 3296 utilizes an enclosed impeller,
hydraulically balanced and keyed to the shaft.
Bearing Frame - the standard configuration is cast
ductile iron with flood oil lubricated ball bearings.
Pure oil mist systems are available as an option. For
protection and reliability of the bearings and the
lubricant, a carbon filled teflon non-contacting
labyrinth seal is provided. On the inboard side a lip
seal is used to prevent leakage of oil into the magnetic
drive assembly.
Casing - is top centerline discharge, self venting type
incorporates a fully confined gasket. 150 lb. ANSI
serrated raised face flanges are standard. The 3296 has
been designed such that there is a metal to metal fit
between the casing and frame adapter.
Every pump has 3 Goulds nameplates that provide
information on your pump. The tags are located on the
casing and bearing frame.
Pump Casing Tag - provides information relative to
the pumps characteristics. The format of pump size
information is: Discharge x Suction - Nominal
Impeller Diameter, (ex.1x1
Bearing Frame Tag - provides information relative to
the type of magnets being used.
3296 M Group 6/059
1
-6)
2
Pump Warning Tag - is permanently fastened to the
bearing frame. It contains precautions to be observed
during the operation, disassembly, maintenance and
reassembly of the pump.
When ordering spare parts you will need to know the
pump model, size, serial number, and the item number
of the required parts. Information can be taken from
the pump casing tag. Item number information can be
found in this manual.
RECEIVING THE PUMP
Inspect the pump as soon as it is received. Make notes
of damaged or missing items on the receipt and freight
bill. File any claims with the transportation company
immediately.
STORAGE REQUIREMENTS
Short Term - (Less than 3 months) Goulds normal
packaging procedure is designed to protect the pump
during shipping. Upon receipt store in a covered and
dry location.
Long Term - (More than 6 months) Preservative
treatment of bearings and machined surfaces will be
required. Rotate shaft several times every 3 months.
Refer to driver and coupling manuals for their long
term storage procedures. Store in a dry covered
location.
HANDLING
!WARNING
s
Failure to properly lift and support equipment
could result in serious injury or damage to pumps.
Use care when moving pumps. Lifting equipment must
be able to adequately support the entire assembly.
Hoist bare pumps, using a sling under the suction
flange and bearing housing.
the pump and driver.
Baseplate mounted units are moved with slings under
Final Piping Check .............................................17
3
SITE/FOUNDATION
A pump should be located near the supply of liquid
and have adequate space for operation, maintenance,
and inspection.
Baseplate mounted pumps are normally grouted to a
concrete foundation, which has been poured on a solid
footing. The foundation must be able to
Fig. 4A
absorb any vibration and to form a permanent, rigid
support for the pumping unit.
The location and size of the foundation bolts are
shown on the outline assembly drawing, provided with
the pump data package.
Foundation bolts commonly used are sleeve type (Fig.
4A) and J type (Fig. 4B). Both designs permit
movement for final bolt adjustment.
Fig. 4B
3296 M Group 6/0511
LEVEL BASEPLATE
1.Place 2 sets of wedges or shims on the foundation,
one set on each side of every foundation bolt. The
wedges should extend .75 in. (20 mm) to 1.5 in.
(40 mm) above the foundation, to allow for
adequate grouting. This will provide even support
for the baseplate once it is grouted.
2.Remove water and/or debris from anchor bolt
holes/sleeves prior to grouting. If the sleeve
Fig. 5A
type bolts are being used, fill the sleeves with rags to
prevent grout from entering.
3.Carefully lower baseplate onto foundation bolts.
4.Level baseplate to within .125 in.(3mm) over the length of
the base and .062 in. (1.5 mm) over the width of the base
by adjusting shims or wedges.
5.Hand tighten bolts.
Fig. 5B
ALIGNMENT AND ALIGNMENT PROCEDURE
!WARNING
s
Before beginning any alignment procedure make
sure driver power is locked out. Failure to lock out
driver power can result in serious personal injury.
The points at which alignment is checked and adjusted
are:
l
Initial Alignment is done prior to operation when
the pump and the driver are at ambient temperature.
l
Final Alignment is done after operation when the
pump and driver are at operating temperature.
Alignment is achieved by adding or removing shims
from under the feet of the driver and shifting
equipment horizontally as needed.
NOTE: Proper alignment is the responsibility of
the installer of the unit.
Accurate alignment of the equipment must be attained.
Trouble-free operation can be accomplished by following these
procedures:.
ALIGNMENT CHECKS
Initial Alignment (Cold Alignment)
l
Before Grouting Baseplate- To ensure alignment can be
obtained.
l
After Grouting Baseplate - To ensure no changes to
alignment have occurred during grouting process.
l
After Connecting Piping -To ensure that pipe strains haven’t
altered alignment. If changes have occurred, alter piping to
remove pipe strains on pump flanges.
Final Alignment (Hot Alignment)
l
After First Run -To obtain correct alignment when both
pump and driver are at operating temperature. Thereafter,
alignment should be checked periodically in accordance with
plant operating and maintenance procedures.
123296 M Group 6/05
ALIGNMENT CRITERIA
Good alignment is achieved when dial indicator
readings as specified in the alignment procedure are
.002 in. (.05 mm) Total Indicated Reading (T.I.R.) or
less when the pump and driver are at operating
temperature (Final Alignment).
MEASUREMENT
1.To ensure accuracy of indicator readings, always
rotate both coupling halves together so indicators
contact the same point on coupling half Y. This
will eliminate any measurement problems due to
runout on coupling half Y.
During the installation phase, however, it is necessary
to set the parallel alignment in the vertical direction to
a different criteria due to differences in expansion rates
of the pump and driver. Table 1 below shows
recommended cold settings for electric motor driven
pumps based on different pumpage temperatures.
Driver manufacturers should be consulted for
recommended cold settings for other types of drivers
(steam turbines, engines, etc.)
Table 1
Cold Settings of Parallel Vertical Alignment
PUMPAGE
TEMPERATURE
50°F (10°C).002in. (.05mm) LOW
150°F (65°C).001in. (.03mm) HIGH
250°F (120°C).005in. (.12mm) HIGH
350°F (175°C).009in. (.23mm) HIGH
425°F (218°C).013in. (.33mm) HIGH
SET DRIVER SHAFT
SET UP
1.Mount two dial indicators on one of the coupling
halves (X) so they contact the other coupling half
(Y) (Fig. 6).
2.Check setting of indicators by rotating coupling
half X to ensure indicators stay in contact with
coupling half Y but do not bottom out. Adjust
indicators accordingly.
2.Take indicator measurements with driver feet hold
down bolts tightened. Loosen hold down bolts
prior to making alignment corrections.
3.Take care not to damage indicators when moving
driver during alignment corrections.
ANGULAR ALIGNMENT
A unit is in angular alignment when indicator A
(Angular indicator) does not vary by more that .002 in.
(.05 mm) as measured at four locations 90° apart.
Vertical Correction (Top to Bottom)
1.Zero indicator A at top dead center (12 o’clock) of
coupling half Y.
2.Rotate indicators to bottom dead center (6
o’clock). Observe needle and record reading.
3.Negative Reading - The coupling halves are
further apart at the bottom than at the top. Correct
by either raising the driver feet at the shaft end
(add shims) or lowering the driver feet at the other
end (remove shims) (Fig. 7A).
Positive Reading - The coupling halves are closer
at the bottom than at the top. Correct by either
lowering the driver feet at the shaft end (remove
shims) or raising the driver feet at the other end
(add shims).
3
Fig. 7A
Fig. 6
4.Repeat steps 1-3 until indicator A reads .002 in
(.05 mm) or less.
3296 M Group 6/0513
Horizontal Correction (Side to Side)
1.Zero indicator A on left side of coupling half Y,
90° from top dead center (9 o’clock).
2.Rotate indicators through top dead center to the
right side, 180° from the start (3 o’clock). Observe
needle and record reading.
3.Negative Reading - The coupling halves are
further apart on the right side than the left. Correct
by either sliding the shaft end of the driver to the
left or the other end to the right.
Positive Reading - The coupling halves are closer
together on the right side than the left. Correct by
either sliding the shaft end of the driver to the
right or the other end to the left (Fig. 7B).
Positive Reading - Coupling half X is higher than
coupling half Y. Correct by adding shims of
thickness equal to half of the indicator reading
from each driver foot (Fig. 8A).
Fig. 8A
NOTE: Equal amounts of shims must be added to
or removed from each driver foot. Otherwise the
vertical angular alignment will be affected.
4.Repeat steps 1 through 3 until indicator P reads
within .002 in. (.05 mm) or less when hot, or per
Table 1 when cold.
Fig. 7B
4.Repeat steps 1 through 3 until indicator A reads
.002 in. (.05 mm) or less.
5.Re-check both horizontal and vertical readings to
ensure adjustment of one did not disturb the other.
Correct as necessary.
PARALLELALIGNMENT
A unit is in parallel alignment when indicator P
(parallel indicator) does not vary by more than .002 in.
(.05 mm) as measured at four points 90° apart at
operating temperature. Note the preliminary cold
setting criteria, Table 1.
Vertical Correction (Top to Bottom)
1.Zero indicator P at top dead center of coupling (12
o’clock) half Y (Fig. 6).
2.Rotate indicator to bottom dead center
(6 o’clock). Observe needle and record reading.
3.Negative Reading - Coupling half X is lower than
coupling half Y. Correct by removing shims of
thickness equal to half of the indicator reading
under each driver foot.
Horizontal Correction (Side to Side)
1.Zero indicator P on the left side of coupling half
Y, 90° from top dead center (9 o’clock).
2.Rotate indicators through top dead center to the
right side, 180° from the start. Observe needle and
record reading (3 o’clock).
3.Negative Reading - Coupling half Y is to the left
of coupling half X. Correct by sliding driver
evenly in the appropriate direction (Fig. 8B).
Positive Reading - Coupling half Y is to the
right of coupling half X. Correct by sliding driver
evenly in the appropriate direction.
Fig. 8B
NOTE: Failure to slide motor evenly will affect
horizontal angular correction.
143296 M Group 6/05
4.Repeat steps 1 through 3 until indicator P reads
.002 in. (.05 mm) or less.
5.Re-check both horizontal and vertical readings to
ensure adjustment of one did not disturb the other.
Correct as necessary.
COMPLETE ALIGNMENT
A unit is in complete alignment when both indicators
A (angular) and P (parallel) do not vary by more than
.002 in. (.05 mm) as measured at four points 90° apart.
Vertical Correction (Top to Bottom)
1.Zero indicators A and P at top dead center
(12 o’clock) of coupling half Y.
2.Rotate indicator to bottom dead center
(6 o’clock). Observe the needles and record the
readings.
Alignment Troubleshooting
PROBLEMPROBABLE CAUSEREMEDY
Cannot obtain horizontal
(Side-to-Side) alignment, angular
or parallel
Cannot obtain vertical (Top to
Bottom) alignment, angular or
parallel
Driver feet bolt bound
Baseplate not leveled
properly, probably twisted.
Baseplate not leveled
properly, probably bowed.
3.Make corrections as outlined previously.
Horizontal Correction (Side to Side)
1.Zero indicators A and P on the left side of
coupling half Y, 90° from top dead center
(9 o’clock).
2.Rotate indicators through top dead center to
the right side, 180° from the start (3 o’clock).
Observe the needle, measure and record the
reading.
3.Make corrections as outlined previously.
4.Recheck both vertical and horizontal readings to
ensure adjustment of one did not disturb the other.
Correct as necessary.
NOTE: With experience, the installer will
understand the interaction between angular and
parallel and will make corrections appropriately.
Table 2
Loosen pump hold down bolts and slide pump and driver
until horizontal alignment is achieved.
Determine which corner(s) of the baseplate are high or low
and remove or add shims at the appropriate corner(s) and
realign.
Determine if center of baseplate should be raised or lowered
and correct by evenly adding or removing shims at the center
of the baseplate.
3
GROUT BASEPLATE
1.Clean areas of baseplate that will contact grout.
Do not use an oil-based cleaner because grout will
not bond to it.
2.Build a dam around foundation (Fig. 9A).
Thoroughly wet foundation.
3.Pour grout slowly through grout holes in
baseplate, until level with the top of the dam. The
use of non-shrink epoxy grout is recommended,
follow manufacturers recommendations. If
cementitious grout is used, remove air by puddling
or with a vibrator (Fig. 9A).
Fig. 9A
3296 M Group 6/0515
4.Allow grout to set.
6.Allow grout to set at least 48 hours.
5.Fill remainder of baseplate with grout. Remove air
as before (Fig. 9B).
Fig. 9B
PIPING
Guidelines for piping are given in the “Hydraulic
Institute Standards” (Edition 14, Centrifugal pump
section) and should be reviewed prior to pump
installation.
1.All piping must be supported independently and
must line up naturally with the pump flanges.
!WARNING
s
Never draw piping into place by forcing at the
flanged connections of the pump. This will impose
dangerous strains on the unit and cause
misalignment between pump and driver. Pipe
strain can adversely effect the operation of the
pump. That could result in serious personal injury
and damage to equipment.
2.Piping runs shall be designed to minimize friction
losses.
3.DO NOT make final connection of piping to pump
until grout has hardened and pump and driver
hold-down bolts have been tightened.
7.Tighten foundation bolts.
Alignment Check
Re-check alignment before continuing, using methods
previously described.
7.Gasket installation and materials must be suitable
for the service.
SUCTION PIPING
Properly installed suction piping is a necessity for
trouble free pump operation. Suction piping should be
flushed BEFORE connection to the pump.
1.Use of elbows close to the pump suction flange
should be avoided. There should be a minimum of
2 pipe diameters of straight pipe between the
elbow and suction inlet. Any elbows used should
be long radius.
2.Size suction pipe one or two sizes larger than
pump suction, with a reducer at suction flange.
Suction piping must never be of smaller diameter
than the pump suction.
3.Reducers, if used, must be eccentric at pump
suction flange with sloping side down.
4.Piping that handles hot liquids requires proper
installation of expansion loops/joints so that linear
expansion of piping will not cause mis-alignment.
5.Piping should be arranged to allow pump flushing
and draining prior to the removal of pump for
servicing.
6.System should be thoroughly cleaned prior to
installation.
4.Suction strainers, when used, must have a net
“free area” of at least three times the suction pipe
area.
5.Separate suction lines are recommended when
more than one pump is operating from the same
source of supply.
163296 M Group 6/05
Suction Lift Conditions
1.Suction pipe must continuously slope upward
towards pump suction to eliminate air pockets.
2.All joints must be air tight.
FINAL PIPING CHECK
After Connecting Piping to the Pump
1.Rotate shaft several times by hand to be sure that
there is no binding and all parts are free.
3.A means of priming the pump must be provided,
such as a foot valve.
Suction Head/Flooded Suction Conditions
1.An isolation valve should be installed in suction
line to permit closing of the line for pump
inspection and maintenance.
2.Piping should be level or slope gradually
downward from source of supply.
3.No portion of piping should extend below pump
suction flange.
4.The suction pipe shall be submerged sufficiently
below the liquid surface to prevent vortices and air
entrainment at the supply.
DISCHARGE PIPING
1.Isolation and check valves should be installed in
discharge line. Locate check valve between
isolation valve and pump which will permit
inspection of check valve. An isolation valve is
required for isolating, priming, regulation of flow,
inspection and maintenance of the pump. A check
valve prevents pump damage due to reverse flow
when driver is turned off.
2.Check alignment, per the alignment procedure
outlined previously to determine absence of pipe
strain. If pipe strain exists, correct piping.
3
2.Increasers, if used, should be placed between
pump and check valves.
3.Cushioning devices should be used to protect
pump from surges and water hammer, if
quick-closing valves are installed in system.
General Considerations ..........................................21
Operating at Reduced Capacity ...................................21
Operating Under Freezing Conditions ..............................21
SHUTDOWN ..................................22
FINAL ALIGNMENT .............................22
4
PREPARATION FOR START-UP
FLUSHING PUMP
The 3296 is flushed with Ethylene Glycol Solution at
the factory to prevent accidental freezing during
shipping or storage at the customers site. Residual
amounts will remain in the pump but if this is a
problem, the 3296 can be flushed out following the
below procedure before pump is installed.
Procedure
3
1.Remove
flush liquid supply.
2.Devise a means of collecting flush liquid as it
drains out the suction nozzle or casing drain if
supplied.
3.Turn flush supply on and run for 5 minutes to
remove Ethylene Glycol residue.
4.When done, raise the coupling end of the pump
(suction flange down) to drain remaining flush
liquid from pump internals. Or, if pump is
equipped with a casing drain plug, remove it to
drain remaining liquid.
" NPT plug (408A) and connect clean
8
!WARNING
s
Failure to properly lift and support equipment
could result in serious injury or damage to pumps.
5.Replace any plugs removed and continue
preparation for start up.
CHECKING ROTATION
!CAUTION
l
Serious damage may result if pump is run in the
wrong rotation.
1.Lock out power to driver.
!WARNING
s
Lock out driver power to prevent accidental
start-up that could result in serious personal
injury.
2.Make sure coupling spacer is removed and
coupling hubs are fastened tightly to the shafts and
are not loose.
3296 M Group 6/0519
NOTE: Pump is shipped with coupling spacer
removed.
3.unlock driver power.
4.Make sure everyone is clear. Jog driver just long
enough to determine direction of rotation.
Rotation must correspond to arrow on bearing
frame.
Pure Oil Mist Lubrication - Pure oil mist is an
optional feature for the 3296. If your pump is equipped
with pure oil mist refer to oil mist generator
manufacturer’s instruction book for proper operation.
!WARNING
s
Operation of the unit without proper lubrication
will cause bearing failure, and pump seizure.
5.Lock out power to driver.
COUPLE PUMP AND DRIVER
!WARNING
s
Lock out driver power to prevent accidental
start-up that could result in serious personal
injury.
Lubricate coupling per manufacturer’s instructions and
install coupling spacer.
INSTALL COUPLING GUARD
Install coupling guard as defined in the appendix.
!WARNING
s
Never operate a pump without a coupling guard
properly installed. Operating pump without a
properly installed coupling guard can result in
serious personal injury.
LUBRICATING BEARINGS
Flood Oil Lubrication - Pumps are shipped without
oil. Fill bearing frame with oil, through filler
connection until oil level reaches center of sight-glass
(Fig A). A high quality turbine type oil, with rust and
oxidation inhibitors should be used as specified in
Table 5.
CONNECT CONDITION
MONITORING DEVICES
Always connect thermocouple to control panel and/or
temperature switch in driver starter. If unit is also
equipped with leak detection and vibration monitoring
systems, these must also be connected. (See Appendix
for wiring diagrams.)
PRIMING PUMP
Never start pump until properly primed (pump casing and
suction piping are full of liquid). Components such as
internal sleeve bearings depend on liquid for lubrication and
will quickly fail if run dry.
Your particular system conditions will dictate method
used to prime pump.
Fig. A
203296 M Group 6/05
STARTING PUMP
1.Make sure suction valve and any recirculation or
cooling lines are open.
2.Fully close or partially open discharge valve as
dictated by system conditions.
3.Start driver.
!CAUTION
l
Immediately observe pressure gauges. If discharge
pressure is not quickly attained - stop driver,
reprime and attempt to restart.
4.Slowly open discharge valve until the desired flow
is obtained.
OPERATION
GENERAL CONSIDERATIONS
Always vary capacity with valve in discharge line.
NEVER throttle flow from suction side.
Driver may overload or magnets de-couple if pumpage
specific gravity (density) is greater than originally
assumed, or rated flow rate is exceeded.
Always operate the pump at or near the rated
conditions to prevent damage resulting from cavitation
or recirculation.
!CAUTION
l
Do not operate above rated temperature range of
magnets as this will weaken or ruin the magnets.
Table 3
Temperature Ratings
Magnetic Types
Neodymium Iron
NdFe
Samarium
Cobalt
SmCo
Drive
Designation
A,B,C,D,E,F250°F (120°C)
AA,BB,CC,DD,
EE,FF
OPERATING AT REDUCED
CAPACITY
Rated
Temperature
425°F (220°C)
!CAUTION
l
Continuous operation against closed discharge
valve will cause pump to overheat. Overheating
the magnetic drive assembly will weaken or ruin
the magnets.
!WARNING
s
Continuous operation against closed discharge
valve may vaporize liquid creating an explosive
hazard due to confined vapor under high pressure
and temperature.
Table 4
Minimum Allowable Flow
Minimum Flow*
60 Hertz50 Hertz
Pump
Group
M
* Based on water with a specific Gravity of 1.0 and
Specific Heat of 1.0
Size
2x3-86032116
3x4-8-112.54023
3x4-8G150753014
1x2-10178.531.6
2x3-108044168
3x4-10H-150-28
1
x3-13-41-8
1
2
2x3-13-80-15
GPMm
3600180029001500
3
/h
OPERATING UNDER
FREEZING CONDITIONS
Exposure to freezing conditions, while pump is idle,
could cause liquid to freeze and damage the pump.
Liquid inside pump should be drained. Liquid inside
cooling coils, if supplied, should also be drained.
4
!WARNING
s
Do NOT operate pump below minimum rated flows or
with discharge valve closed. These conditions may
vaporize liquid creating an explosive hazard due to
confined vapor under high pressure and temperature.
3296 M Group 6/0521
SHUTDOWN
1.Slowly close discharge valve.
2.Shut down and lock out driver to prevent
accidental rotation.
FINAL ALIGNMENT
1.Run the unit under actual operating conditions for
a sufficient length of time to bring the pump and
driver up to operating temperature.
!WARNING
s
When handling hazardous and/or toxic fluids,
skin, eye and respiratory protection are required.
If pump is being drained, precautions must be
taken to prevent injury or environmental
contamination. Pumpage must be handled and
disposed of in conformance with applicable
environmental regulations.
2.Check and reset alignment per alignment
procedure outlined earlier.
3.Reinstall coupling guard per instruction in
appendix.
223296 M Group 6/05
PREVENTIVE MAINTENANCE
GENERAL COMMENTS ...........................23
MAINTENANCE SCHEDULE ........................23
MAINTENANCE OF BEARINGS ......................24
TROUBLESHOOTING ............................25
GENERAL COMMENTS
A routine maintenance program can extend the life of your pump. Well maintained
equipment will last longer and require fewer repairs. You should keep maintenance
records, this will help pinpoint potential causes of problems. A sample form is in
the appendix that can be copied and used for this purpose.
MAINTENANCE SCHEDULE
5
Routine Maintenance
l
Bearing lubrication
l
Temperature monitoring
l
Vibration analysis
l
Discharge pressure
Routine Inspections
l
Check level and condition of oil through sight glass
on bearing frame.
l
Check for unusual noise, vibration, and bearing
temperatures.
l
Inspect pump and piping for leaks.
3 Month Maintenance
l
Check foundation hold down bolts of motor and
pump for tightness.
l
Change oil per section V-C.
l
Check alignment per section III-B.
Yearly Inspections
l
Check pump capacity, pressure, and power. If the
pump performance does not satisfy your process
requirements, the pump should be disassembled and
inspected. Worn parts should be replaced.
3296 M Group 6/0523
MAINTENANCE OF BEARINGS
OIL LUBRICATED BEARINGS
Oil level is measured through sight glass. Oil level
must not fall below center of site glass. An increase in
level may be noted after start up due to oil circulation
within the bearing frame. Change Oil after 200 hours
for new bearings, thereafter every 4000 operating
hours or 6 months, which ever period is shorter.
Change oil every 2000 operating hours under severe
operating conditions, such as high temperature services
[pumpage temperatures in excess of 325°F (160°C)].
We recommend using Table 5 to help determine your
lubricating oil needs.
Table 5
Pumpage Temp. of
325° - 375°F
(160° - 190C°)
with bearing frame cooling
300Synthetic 300
68Synthetic 68
Pumpage Temp. of
greater than 375°F
(190°C)
with bearing frame cooling
Royal Purple Synfilm 68
NOTE: This is a list of oils that meet the lubrication requirements of this pump. It is not intended to be an
endorsement of products listed nor exclude other oils that meet these requirements.
243296 M Group 6/05
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.