Gotham PSDVL2 User Manual

Catalog Number
FEATURES & SPECIFICATIONS
INTENDED USE
For factory installation in Gotham ECOS fi xtures to operate LED arrays.
CONSTRUCTION
Patented integrated test switch/pilot light that requires only one-hole drilling.
U.S. Patent No. 6,522,147.
OPTICS
Operates LED arrays for an initial output of 18% of rated lumens, for 90 minutes upon interruption of normal power.
Low-glare, shadow-free illumination provides excellent visibility for safe building evacuation.
ELECTRICAL
Sealed, maintenance-free, high-temperature nickel-cadmium battery. Ensures long life over a wide range of temperatures.
Polarized battery connector simplifi es maintenance and prevents charger damage due to improper connection.
Pilot light and test switch provide visual and manual means of monitoring system operation.
Automatic battery recharge after 90-minute discharge.
INSTALLATION
Unit can be remote mounted up to half the distance recommended by the LED driver manufacturer or 50 feet, whichever is less.
Unit wired into building circuit in two ways: on night light circuit (permanently energized) or on switchable circuit (unswitched circuit to the battery charger and switched circuit to the fi xture). Unit will strike normally off lamp.
LISTING
UL recognized. Meets UL 924, NFPA 101 (current Life Safety Code), NEC and OSHA illumination standards.
WARRANTY
Five-year total customer satisfaction warranty. (For complete details, see warranty sheet in Product Selection Guide.)
Notes
Type
®
LED Battery Packs
PSDVL2
PSDVL2
ORDERING INFORMATION
PSDVL2
Series
PSDVL2
Lead times will vary depending on options selected. Consult with your sales representative.
Example: PSDVL2
Emergency
Sheet #: PSDVL2
PSDVL2 LED Battery Packs
SPECIFICATIONS
BATTERY
Sealed Nickel-Cadmium
Shelf Expected Optimum Voltage life
PSDVL2 6 3 yrs. 10 yrs. none3 32–100°F (0–38°C)
NOTES: 1 At 77°F (25°C). 2 Optimum ambient temperature range where unit will provide capacity for 90 minutes.
Higher and lower temperatures affect life and capacity. Consult factory for detailed information.
3 Periodic system status test recommended.
1
life1 Maintenance temperature
2
MOUNTING
All dimensions are inches (millimeters).
1-11/16 (43)
3-3/16 (81)
Cross section end view
Length: 17-1/8 (435) Shipping weight: 5.0 lbs. (2.3 kgs.)
ELECTRICAL
Maximum AC input Volts Amps Watts
PSDVL2 120 .27 3.3 277 .25 3.2
INITIAL LUMEN OUTPUT
Lamp Lumens
ECSR 4" 161
ECSR 6" 257
ECSS 4" 163
ECSS 6" 228
Sheet #: PSDVL2