VL2 E Test Adapter
For Testing Devices and Cables 
in Combination with DIN VDE 0701-0702 Test Instruments
• In order to assure compliance with technical safety requirements, the 
test adapter may only be repaired by a qualified electrician, who is 
preferably employed by the manufacturer.
• If the test adapter and/or its connector cables demonstrate visible 
damage, no longer function or have been stored for a lengthy period 
of time under unfavorable conditions, it must be assumed that 
hazard-free operation is no longer possible. Remove the test adapter 
from service and secure it against inadvertent use.
2 Applications
The test adapter is intended for the performance of measurements and 
testing at electrical devices and extension cables with CEE plug 
connectors in combination with test instruments in accordance with the 
following standards: 
DIN VDE 0701-0702:2008 (testing after repair and for periodic testing)
3-349-242-15
7/11.12
(1) Surface mounted test plug: CEE 3P+N+PE 32 A 400 V 
(2) Surface mounted test plug: CEE 3P+N+PE 16 A 400 V 
(3) Surface mounted test plug: CEE 1P+N+PE 16 A 230 V 
(4) Surface mounted inlet test plug: 1P+N+PE 16 A 230 V 
(5) Connector socket for probe cable from the DIN VDE test instrument, 
for testing cables only 
(6) Surface mounted earth contact test outlet: 1P+N+PE 16 A 230 V 
(7) Earth contact connector cable for connection to test sockets at 
DIN VDE test instruments 
(8) Surface mounted test outlet: CEE 3P+N+PE 32 A 400 V 
(9) Surface mounted test outlet: CEE 3P+N+PE 16 A 400 V
(10) Surface mounted test outlet: CEE 1P+N+PE 16 A 230 V 
(11) Rotary selector switch for cable function tests 
(12) Surface mounted earth contact test plug: 1P+N+PE 16A 230 V
1 Safety Precautions
The test adapter has been manufactured and tested in accordance with 
the following regulation: 
DIN VDE 0411/IEC 348 
“Regulations for electronic testers and controllers, 
part 1: safety measures for electronic measuring instruments”
Safety is only assured for the user and the test adapter when used for its 
intended purpose in combination with DIN/VDE 0701-0702 test 
instruments. In order to maintain flawless technical safety conditions, and 
to assure safe use, it is imperative that you read these operating 
instructions thoroughly and carefully before placing the test adapter into 
service, and that you follow all instructions contained herein.
• Measurements within electrical systems are prohibited!
The VL2 E test adapter may only be connected via its cable (7) to the socket of an external DIN VDE 0701-0702 test instrument for tests without 
line voltage. If it is connected, for example, to a test panel with a „VDEMAINS“ switch-over, the switch must be set to the „VDE“ position, otherwise the RCCB of the supplying system might trigger.
• Be prepared for the occurrence of unexpected voltages at devices 
under test (e.g. due to charged capacitors).
• Before connecting the device under test to the test adapter, subject it 
to a thorough visual inspection first. Damaged devices under test 
must be repaired prior to testing.
• Only extension cables which have been plugged into the test outlets 
at the test adapter may be connected to the surface mount plugs on 
the test adapter for testing.
3 Connecting the Test Adapter to a DIN VDE 0701-0702 Test Instrument
➭ The test adapter’s earth contact plug may only be plugged into the 
earth contact outlet at a DIN VDE 0701-0702 test instrument which is 
identified as the test socket.
Testing Extension Cables
➭ Additionally plug the test instrument’s probe into the SL socket (5).
4 Connecting a Device Under Test to the Test Adapter
After the visual inspection has been passed and before plugging the 
device under test into the appropriate connectors, all functions must be 
activated, making sure, for example, that thermostat contacts are closed 
etc. Always measure protective conductor resistance first for safety class I 
devices under test, because the measurement of insulation resistance 
and equivalent leakage current is not possible without a properly 
functioning protective conductor.
This measurement is of special importance for function testing as well, 
because a defective or reversed protective conductor may represent a 
hazard for the user!
5 Testing Devices
The following tests in accordance with DIN VDE must be performed in 
consideration of the operating instructions for the utilized test instrument.
Automatic test sequences in combination with test adapter VL2 E 
are only possible with SECUTEST S2 N+, SECUSTAR FM 
or SECULIFE SB
5.1 Measuring Protective Conductor Resistance
➭ When testing devices: Connect the probe cable to the housing of the 
DUT, making sure that good contact is established.
➭ When testing extension cables: Plug the test instrument’s probe into the 
SL socket (5). Connect the plug and the socket of the extension cable 
under test to the corresponding surface mount plug and surface 
mount outlet on the test adapter.
➭ Perform testing in accordance with the operating instructions included 
with the test instrument.
➭ Read the measured value and compare it with permissible values per 
DIN VDE 0701-0702.
The connector cable must be shaken back and forth, section by 
section over its entire length, during measurement (for 
permanently installed devices only in so far as the connector 
cable is accessible during maintenance, modification or testing).

VL2 E Test Adapter
For Testing Devices and Cables 
in Combination with DIN VDE 0701-0702 Test Instruments
Compensation of Test Adapter Connector Cable Resistance
Cable resistance amounts to 0.07 . This value must be subtracted from  
the displayed measured value for measurements in extreme ranges. 
A resistance value of 0.3  may not be exceeded for devices under test 
with cable lengths of up to 5 meters. A value of 0.3 , plus 0.1  for each 
additional 7.5 meters, applies for lengths of greater than 5 meters.
5.2 Measuring Insulation Resistance
During this test, L1, L2, L3 and N are measured against PE (rotary 
selector switch set to position 1).
➭ Perform testing in accordance with the operating instructions included 
with the test instrument.
➭ Read the measured value and compare it with permissible values per 
DIN VDE 0701-0702. When testing extension cables, a value of 2 M  
should not be significantly fallen short of.
If there is any uncertainty about applying insulation voltage, for 
example with electronic devices, or, in the case of safety class I 
devices, if there is no assurance that all components subjected to 
line voltage will be taken into account by the measurement, the 
DUT must be tested using a leakage current measuring method 
with a suitable test instrument.
5.3 Measuring Equivalent Leakage Current
➭ Perform testing in accordance with the operating instructions included 
with the test instrument.
➭ Read the measured value and compare it with permissible values per 
DIN VDE 0701-0702.
6 Function Test for Extension Cables
➭ Select insulation measurement at the test instrument. 
➭ Set the test adapter’s rotary selector switch to position 2. 
➭ Read the measured value.
The adapter may indicate a value ranging from 0  in the event of a  
short-circuit of all wires to infinite (display overrange) in the event of a 
wire interruption. Owing to the good insulation of undamaged cables 
a test value of 7 M with a tolerance of 10% has been established for 
this efficient test method. 
All values in the range from 6.3 to 7.7 M therefore indicate that testing 
has been passed. 
If a fault has been detected, the precise fault type such as shortcircuit or interruption of wires, reversed wiring and/or inadequate 
insulation must be evaluated.
The following characteristics can be tested with this procedure:
➭ Testing of AC cables for short-circuiting and continuity 
➭ Additional testing of 3-phase cables and caravan cables for reversed 
wiring of L1, L2, L3 and N (clockwise rotation)
Do not touch the plug-in contacts of the plugs of long connection 
cables after testing. They could be electrically charged.
When using the adapter with SECUTEST S2N+, the error message 
„Visual test failed“ appears if the test has not been passed.
7 Characteristic Values
Nominal Range of Use
Maximum voltage
Maximum current
Electrical Safety
Safety class I 
Measuring category I for insulation resistance measurement,
Ambient Conditions
Storage temperature – 20 C ... + 60 C 
Operating temperature – 10 C ... + 50 C 
Accuracy range 0 C ... + 50 C 
Relative humidity Max. 75%, no condensation allowed 
Elevation Max. 2000 m 
Deployment Indoors; outdoors only within the specified 
Mechanical Design
Protection Housing: IP 40 per DIN VDE 0470, part 1
Dimensions W x H x D: approx. 330 x 230 x 145 mm 
Weight Approx. 1.7 kg
For measuring insulation resistance: 600 V DC 
For measuring equivalent leakage current: 230 V AC
For measuring protective conductor resist.:10 A DC/AC
300 V CAT II for all other measurements
ambient conditions
Terminals: IP 20
8 Maintenance
Self-Test
Self-testing for protective conductor continuity at the connector cable is 
performed automatically for all VDE tests.
Housing
No special maintenance is required for the housing. Keep outside 
surfaces clean. Use a slightly dampened cloth for cleaning. Avoid the use 
of cleansers, abrasives and solvents.
9 Repair and Replacement Parts Service
Calibration Center* and Rental Instrument Service
When you need service, please contact:
GMC-I Service GmbH 
Service Center 
Thomas-Mann-Str. 20 
90471 Nuremberg, Germany 
Phone +49 911 817718-0 
Fax  +49 911 817718-253 
E-Mail service@gossenmetrawatt.com 
www.gmci-service.com
This address is only valid in Germany. Please contact our representatives 
or subsidiaries for service in other countries.
* DAkkS Calibration Laboratory for Measured Electrical Quantities: 
D–K–1580-01-01, accredited per DIN EN ISO/IEC 17025:2005
Accredited measured quantities: direct voltage, direct current values, 
DC resistance, alternating voltage, alternating current values, AC active power, 
AC apparent power, DC power, capacitance, frequency and temperature.
10 Product Support
When you need service, please contact:
GMC-I Messtechnik GmbH
Product Support Hotline
Phone +49 911 8602-0 
Fax  +49 911 8602-709 
E-Mail support@gossenmetrawatt.com
Edited in Germany • Subject to change without notice • A pdf version is available on the internet
GMC-I Messtechnik GmbH 
Südwestpark 15 
90449 Nürnberg •
 Germany
Phone +49 911 8602-111 
Fax +49 911 8602-777 
E-Mail info@gossenmetrawatt.com 
www.gossenmetrawatt.com