Gossen Metrawatt U1289, U1389, U1387, U1281, U1381 User guide

Page 1
Operating Instructions
ENERGYMETER|MID Electronic Active Energy Meters U1281/U1289/U1381/U1387/U1389
MAIN PISTRIBUTION – PRODUCTION
© Gossen Metrawatt GmbH Edited in Germany • Subject to change without notice / Errors excepted • A pdf version is available on the Internet
All trademarks, registered trademarks, logos, product names and company names are the property of their respective owners.
Gossen Metrawatt GmbH
Südwestpark 15 90449 Nürnberg Germany
Phone +49 911 8602-0 Fax +49 911 8602-669 E-Mail info@gossenmetrawatt.com www.gossenmetrawatt.com
3-349-618-15
5/4.22
Page 2

1 Safety Precautions – Symbols

– Check the specified nominal voltage on the serial plate
before placing the instrument into service. – Observe the maximum voltage of the pulse output. – Make sure the connector cables are not damaged, and
that they are voltage-free while wiring the instrument. – If it can be assumed that safe operation is no longer pos-
sible, the instrument must be immediately removed from
service (disconnect input voltage!). Safe operation can no
longer be relied upon if the instrument demonstrates visi-
ble damage.
The device may not be placed back into operation until
troubleshooting and repair have been performed, and
calibration and dielectric strength have been tested and
approved at our factory or an authorized service center. – Voltage conducting parts may be exposed if the cover is
opened.
If balancing, maintenance or repair of a live open instru-
ment is required, work may only be carried out by trained
personnel who are familiar with the dangers involved.
Capacitors inside the instrument may be dangerously
charged, even after it has been disconnected from all
power sources. – After the instrument has once again been closed subse-
quent to repair or maintenance work, insulation must be
tested with high-voltage in accordance with the values
specified in the technical data.
2 Gossen Metrawatt GmbH
Page 3
Meaning of Symbols on the Instrument
!
M111948
EB
8
11
DE MTP 11 B 001 MI-003 Prototype test certificate
Total insulation, Safety Class II device
Warning concerning a source of danger (Attention, observe documentation!)
This device may not be disposed of with the trash. Fur­ther information regarding the WEEE mark can be accessed on the Internet at www.gossenmetrawatt.com by entering the search term ’WEEE’.
Metrology label with year (M11) and registration number of the indicated authoring for module D. Duration of Calibration validity country specific
Label with seal from federally approved test authority
(for recalibration only)
Tamper-proof sealing
The manufacturer‘s lead seal for calibration protection is located at the back of the instrument.
Tamper-proof sealing for the terminal cover can be attached either at the left or right-hand side of the terminal cover.
Gossen Metrawatt GmbH 3
Page 4

2 Serial Plate – Terminals

Type designation
U
N
f
N
LED constant
Year of manufacture
Accuracy class
CT: Current transformer transformation ratio
VT: Voltage transformer transformation ratio
Serial number
Pulse outpput
I
MIN
-I
N
(I
MAX
)
External auxiliary
Reverse Action Lock
The values of CT, VT and S on the serial plate can be / are calibrated
Operating
Bus connection
temperature range
voltage
Circuit Symbols
4-L
3-L
2-L
Y
V
U12/U1389:
U1387:
U12/U1381:
4 Gossen Metrawatt GmbH
Page 5
Voltage Voltage Voltage
Current Current Current
L3L2L1 N
S0
CurrentCurrentCurrent
Inputs
2.5 mm
2
with wire end ferrules or
16 mm
2
without wire end ferrule

2 x 1.5 mm
2
without wire end ferrule
Voltage:
Current:
2.5 mm
2
with wire end furrule or

2 x 1.5 mm
2
without wire end ferrule
Auxiliary voltage
H
BUS
Enable key
24 V
10%
(Feature H1)
Pulse
output
H
12 3 4 5 6 78 9112021222324
+
Tighten screws by hand only! Tightening torque
Note:
Observe the wiring diagram in the terminal cover
Attention:
!
for current terminals (No. 1, 3, 4, 6, 7 and 9) = 2 Nm
for all other terminals (No. 2, 5, 8, 11, 20 to 24) = 0.4 Nm
Gossen Metrawatt GmbH 5
Page 6

3 Pulse Output – Bus Interfaces

R
L
+
20
21
U
t
External Voltage Source
Energy Import
max. 40 V
R
L
20
21
U
t
AC/DC
Energy Import
max. 375 V
~
24 V DC
I = max. 100 mA
I = max. 27 mA
U
U
External Voltage Source
Standard pulse duration: 30 ms + 5%, Interpulse period: > 30 ms Pulse duration V7/V8: 130 ms + 5%, Interpulse period: > 130 ms
Pulse rates fix V1/V3 Direct
Transformer
CT = VT = 1 (Q0) 1000 CT, VT progr. (Q1) 1000 CTxVT; CT, VT fix (Q9)
1 10
11 100
101 1000
1001 10 000 10001  100000 1000011000 000
underligned values are default values in as-delivered condition
The interface descriptions for the active energy meters are available on the Internet under www.gossenmetrawatt.com.
6 Gossen Metrawatt GmbH
1000puls./kWh
f (primary) f (primary)
1000puls./kWh 100 pulses/kWh
10 pulses/kWh
1 pulses/kWh 0,1 pulses/kWh 0,01 puls./kWh
V7
V8 fix V9 Programmable V2/V4 U1281 / U1289
100 — 1 1000
U1381 / U1387 / U1389
puls./kWh puls./kWh
f (secondary)
100
1000
100
1000
1

1000

100 10000
1

1000
—1  1000 pulses/kWh —0,1  100 pulses/kWh —0,01  10 pulses/kWh —1  1000 pulses/MWh —0,1  100 pulses/MWh — 0,01 10 pulses/MWh

10000puls./kWh

10000
pulses/kWh
puls./kWh
Page 7

4 Display and Control Panel

4.1 Test LED

The test LED is located between the LCD and the serial plate. The higher the measured power value, the higher the blink rate. If all currents are lower than the starting current, the LED lights up permanently.
LED Constant
U128x: 10 000 pulses/kWh U138x: 100 000 pulses/kWh

4.2 Resolution of Energy Import Main Display (Large Characters)

Meter Feature
U1281, U1289 123456.7 23456.78 kWh
Q0 or Q9 1 10 12345.67 2345.678 kWh
Q9
U138x
Q1
*
For calibratable main displays (Q0 or Q9), the calibration reading indicates an additional digit after the decimal point. Therefore, the leading digit is omitted in the case of 7-digit presentation.
CTxVT
CTxVT
min.
max.
11 100 123456.7 23456.78 kWh
101 1000 1234567 234567.8 kWh
1001 10000 12345.67 2345.678 MWh
10001 100000 123456.7 23456.78 MWh
100001 1000000 1234567 234567.8 MWh
1 10 123456.7 kWh
11 100 1234567 kWh
101 1000 12345.67 MWh
1001 10000 123456.7 MWh
10001 100000 1234567 MWh
Standard Reading
Calibration Reading *
Unit
Gossen Metrawatt GmbH 7
Page 8

4.3 Meanings of Symbols on the LCD

Main display (active energy Etot* in kWh or MWh)
Auxiliary display (instantaneous power Pmom*)
Error: alternating error code and instantaneous power
* U138x: CT and VT are taken into consideration
U
8 Gossen Metrawatt GmbH
Main display
if Correct connection:
Continously lit phase symbols
Phase failure:
Symbol for affected phase is cleared from display.
Incorrect phase sequence:
Phase symbols blink in the following order: 3-2-1.
Negative power:
Respective phase symbol blinks.
4 quadrant display of instantaneous power: posi­tive or negative active power P, positive or nega­tive reactive power Q.
For bus connection: appears when the meter transmits a data packet.
is not/cannot be calibrated,
U
is displayed.
Page 9
Key Symbols for Parameters Configuration
Key and 2
nd
key bit blanked:
Parameters CT, VT or S0 configurable according to fea­tures, can be disabled with enable key. Key displayed with one key bit: Parameters CT, VT or S0 disabled, can be changed after activating enable key.
Key blanked, 2
nd
key bit displayed:
Parameters CT, VT or S0 (which are / can be calibrated) are preset at the factory, can be queried in the display mode, other values can be set.
Key with 2
nd
key bit displayed: parameters (which can be /
are calibrated) are preset at the factory, other values are disabled with enable key and can be reset after cancel­ling the disable function.
Values which are preset at the factory are specified addi­tionally on the serial plate in as-delivered condition.
Symbols Adjustable
parameters
CT, VT S0
CT, VT S0 CT, VT V2/V4 and Q0/Q9
Disabled parameters
CT, VT Q1 S0 V2, V4
CT, VT S0 S0 CT, VT V2/V4 and Q0/Q9
Fixed/ calibrated parameters
S0
S0, CT, VT V1/V3 and Q0/Q9 S0, CT, VT V7/V8/V9 and Q0
Feature
Q1 V2, V4
Q1 and V1/V3/V7/V8/V9
Q1 and V1/V3/V7/V8/V9
Gossen Metrawatt GmbH 9
Page 10

4.4 Key Operation


Querying parameter values CT, VT and S0
Apart from the LCD test, the menu key located between LCD and serial plate serves to query current paramter val­ues and, in the case of active energy meters with special features, to change parameters (provided that the enable key has been activated before). The sequence can be seen from the figure on the right. If no key is pressed for 2 minutes, the display returns auto­matically to the standard setting.
Parameters can be changed in the following instruments:
Parameters CT, VT for U138x with feature Q1, parameters S0 for U128x/U138x with feature V2/V4
a) Enabling parameter modifications
The enable key serves to enable or disable paramter changes. It is located below the terminal cover and is acti­vated with a pointed object (e. g. ballpen).
Pressing the key for the first time activates operating mode „Change parameters“ (key off):
Renewed activation disables operating mode „Change parameters“ (key on):
If the key is not activated for approx. 2 minutes, operating mode „Change parameters“ is automatically aborted and blocked. The key is displayed again:
10 Gossen Metrawatt GmbH
Page 11
b) Changing parameter values
Briefly press the enable key first, as described under
Item a) (activates operating mode „Change parame­ters“).
Press and hold the menu key once until the read-out
test is displayed.
Repeatedly press the menu key until the parameter to
be changed appears at the display.
Press and hold the menu key until the parameter value
at the digit with the highest value (on the far left-hand side) blinks.
You can increase the value of the blinking digit by
pressing the menu key (fast scroll when key is held). If the key is not activated for a few seconds, the selected digit is stored and the entry cursor moves one digit to the right. The selected value is stored when the digit with the lowest value (on the far right-hand side) stops blinking.
Press the menu key several times until the standard dis-
play appears.
Press the enable key once more. This disables operat-
ing mode „Change parameter values“.
Query and Configuration of LON-Bus (Feature W1) M-Bus (Feature W2) and L-Bus (Feature W3)
The interface descriptions for the active energy meters with bus connection are available on the internet under www.gossenmetrawatt.com.
Gossen Metrawatt GmbH 11
Page 12
00013.8
10
kVArh
VAr
123456.7
1
234
kWh
kW
100
Ct
1
V
t
1000
PER
888888.8
8
888888.8
kWh
kWh
0200
Ct
0002
V
t
M
1000
PER
kWh
Auto
Auto
Auto
kWh
S0
M
M
M
m
m
001000.0
0
000010.0
kWh
kWh
m
m
Primary energy
Secondary energy
Calibration
m
Standard
Read-out test
M
Auto
0001.00 0000
V
er
Firmware version
Pulse rate
vt
ct
m m
...
M
Auto
Read-Out
S0
AutoAutoAuto Auto Auto
U138x with Feature Q1
U138x with Feature Q1
Feature V2/V4
Parameter modifications only after enabling
bus-specific menus see interface descriptions
0.100
seC
S0
m
Auto
Pulse duration
Setup range
0.030 ...
3.000 s
read-out
Auto
M
Feature V2/V4
0.100
seC
S0
Setup range see chapter 3
12 Gossen Metrawatt GmbH
Page 13
Key
Auto Automatic scrolling ct Transformation ratio current m Press the menu key briefly M Press and hold the menu key Q1 Feature: Transformation ratios programmable S0 Pulse rate S0 output vt Transformation ratio voltage V2/V4 Feature: rate programmable V9 S0 rate customized
00049.90
00F0Hzz00
m m
...
m
M
Auto
Multifunctional display Feature M1 M2 M3 Reactive energy kVArh —• • Phase voltage U1N, U2N, U3N •—• Delta voltage U12, U23, U13 •—• Current I1, I2, I3 •—• Active power P1, P2, P3, Ptot •—• Reactive power Q1, Q2, Q3, Qtot •—• Apparent power S1, S2, S3, Stot •—• Power factor PF1, PF2, PF3, PFtot •—• Frequency F •—•
Gossen Metrawatt GmbH 13
Page 14

5 Error Messages – Reset

Read-out
If an error occurs, the respective error code and instanta­neous power are displayed alternately.
Error Code Meaning Cause/Remedy
E0VHi1
E0VHi 2
E0VHi 3
E01Hi1
E0 1Hi 2
E 01Hi 3
E 0SYnc
E0 EnErgY E 0cALib E 0AnALog
Reset
In the event of malfunction or or after eliminating an error, the device can be reset briefly by disconnecting auxiliary power or supply power.
Maximum value for U1 exceeded
Maximum value for U2 exceeded
Maximum value for U3 exceeded
Maximum value for I1 exceeded
Maximum value for I2 exceeded
Maximum value for I3 exceeded
Frequency measuring error
Meter defective Balancing required DC offset too high
Meter connected to direct voltage
Send meter to repair department
14 Gossen Metrawatt GmbH
Page 15

6 Product Support

+49 911 8602-0
Montag – Thursday: Friday:
You can also e-mail to:
support.industrie@gossenmetrawatt.com
8:00 a.m. – 4:00 p.m. 8:00 a.m. – 2:00 p.m.

7 Declaration of Conformity

The product fulfills all requirements of applicable EU direc­tives and national regulations. We confirm this with the CE mark. The CE Declaration of Conformity is available for download from our website. Search for your product in our Download Center for this purpose:
https://www.gmc-instruments.de/en/
services/download-center/
Gossen Metrawatt GmbH 15
Page 16

8 Repair and Recalibration

Note for Test Laboratories
Directly measuring meters (U128X): In as-delivered condition, screw terminals 2, 5 and 8 are tightened in order to establish contact between current and voltage inputs. If isolated voltage supply is required for tests, the screw ter­minals can be released (remove screw cover, release screws, pull insulating sleeves over contact pins in the ter­minals and connect simulator voltage).
Calibration Reading
For testing and calibration purposes the energy values can be displayed with a higher resolution. Press the menu key, as shown in the flowchart in chapter 4.4. Refer to chapter
4.2 for the type and feature dependant resolutions.
Recalibration by our federally approved test authority EB-8 is possible at any time.
GMC-I Service GmbH Service Center Beuthener Straße 41 90471 Nürnberg • Germany Phone +49 911 817718-0 E-Mail service@gossenmetrawatt.com www.gmci-service.com
This address is only valid in Germany. Please contact our representatives or subsidiaries for ser-
vice in other countries.
16 Gossen Metrawatt GmbH