Gossen MetraWatt R2900 Operating Instructions Manual

Page 1
Operating Instructions
R2900
Compact Controller, 96 x 96 mm
3-349-203-15
3/3.03
Page 2
Contents Page Page
Safety Features and Precautions . . . . . . . . . . . . . . . . 3
Repair and Replacement Parts Service . . . . . . . . . . . . 4
Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Device Identification . . . . . . . . . . . . . . . . . . . . . . . . . 5
Data Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Mechanical Installation / Preparation . . . . . . . . . . . . . 6
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . 8
Performance After Activating Auxiliary Voltage . . . . . 10
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operating Flowchart,
“Discontinuous-Action Controller” . . . . . . . . . . . . . . 12
Operating Flowchart, “Discontinuous-Action Controller”
with Differential Control . . . . . . . . . . . . . . . . . . . . . . 13
Operating Flowchart, “Continuous-Action and Step-Action Controllers” . . . 14 Operating Flowchart, “Cont.-Action and
Step-Action Controller” with Diff. Control . . . . . . . . . 15
Off / Manual Operation . . . . . . . . . . . . . . . . . . . . . . 16
Manual Operation with Binary Input . . . . . . . . . . . . . 17
PWR Out Offset with Binary Input . . . . . . . . . . . . . . . 17
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Saving and Loading Device Settings: . . . . . . . . . . . . 21
Differential Controller . . . . . . . . . . . . . . . . . . . . . . . . 21
Slave Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Controller Sorts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Configuration of the Controller with Continuous Output
(desig. A7 and A8) . . . . . . . . . . . . . . . . . . . . . . . . . 23
Parameters Configuration . . . . . . . . . . . . . . . . . . . . 24
Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Self-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Manual Self-Tuning . . . . . . . . . . . . . . . . . . . . . . . . .28
Setpoint Ramps . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Heating Circuit Monitoring . . . . . . . . . . . . . . . . . . . .32
Limit Value Monitoring . . . . . . . . . . . . . . . . . . . . . . .33
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . .36
Meanings of symbols on the instrument:
Indicates EC conformity
Continuous doubled or reinforced insulation
Warning concerning a source of danger Attention: observe documentation!
Functional earth terminal, earthing for functional purposes only (no safety function)
2 GOSSEN METRAWATT GMBH
Page 3

Safety Features and Precautions

The R2900 controller is manufactured and tested in accordance with safety regulations IEC 61010-1 / DIN EN 61010-1 / VDE 0411-1. If used for its intended purpose, safety of the user and of the device is assured.
Read the operating instructions completely and carefully before using the device, and follow all instructions included therein. The operating instructions should be made available to all users.
Observe the following safety precautions:
The device may only be connected to electrical systems which comply with the specified nominal range of
use (see circuit diagram and serial plate), and which are protected with a fuse or circuit breaker with a maximum nominal current rating of 16 A.
The installation must include a switch or a circuit breaker which serves as a disconnecting device.
The controller may not be used:
If visible damage is apparent – If it no longer functions flawlessly – After lengthy periods of storage under unfavorable conditions (e.g. humidity, dust, temperature) In such cases the device must be removed from service and secured against any possible inadvertent use.

Maintenance

Housing
No special maintenance is required for the housing. Keep outside surfaces clean. Use a slightly dampened cloth for cleaning. Avoid the use of solvents, cleansers and abrasives.
Repair and Parts Replacement
Repairs and the replacement of parts conducted at a live open instrument may only be carried out by trained personnel who are familiar with the dangers involved.
GOSSEN METRAWATT GMBH 3
Page 4

Repair and Replacement Parts Service

When you need service, please contact:
GOSSEN METRAWATT GMBH Service-Center Thomas-Mann-Strasse 20 90471 Nürnberg • Germany Phone +49-(0)-911-8602-410/256 Fax +49-(0)-911-8602-253 E-Mail service@gmc-instruments.com
This address is only valid in Germany. Please contact our representatives or subsidiaries for service in other countries.

Product Support

When you need support, please contact:
GOSSEN METRAWATT GMBH Product Support Hotline Phone +49-(0)-911-8602-112 Fax +49-(0)-911-8602-709 E-Mail support@gmc-instruments.com
4 GOSSEN METRAWATT GMBH
Page 5

Device Identification

Electronic controller with self-tuning and 2nd setpoint, front panel dimensions: 96 x 96 mm Controller Types
2 / 3-step controller with heating current monitoring / step-action controller 2 transistor outputs 2 / 3-step controller with heating current monitoring 1
2 / 3-step controller with heating current monitoring 1
2 / 3-step controller with heating current monitoring / step-action controller 2 relay outputs Step-action controller with repeater / 3-step controller 2 transistor outputs Step-action controller with repeater / 3-step controller 2 relay outputs Cont.-action contr. / step-action contr. / 3-step contr. w. heat current monit. 1 continuous output and 2 transistor outputs Cont.-action contr. / step-action contr. / 3-step contr. w. heat current monit. 1 continuous output and 2 relay outputs
Measuring Ranges
Input Thermocouple, configurable Type J, L –18 ... 850 °C / 0 ... 1562 °F
Type K –18 ... 1200 °C / 0 ... 2192 °F Type S, R –18 ... 1770 °C / 0 ... 3218 °F Type B 0 ... 1820 °C / 32 ... 3308 °F (especially 600 °C) Type N –18 ... 1300 °C / 0 ... 2372 °F
Resistance thermometer Pt 100 – 100 ... 500 °C / –148 ... 932 °F Input Standard signal, configurable 0 / 2 Both measurement inputs can be mutually
st
measurement input same as B1, 2nd same as B2, can be configured for slave controller B4
1
configured as per B1 for differential controller.B3
... 10 V or 0 / 4 ... 20 mA B2
Auxiliary Voltage AC 110 ... 230 V C1 Limit Contacts None
Two 2 relay outputsD0D1
Data Interface None
RS 485 or RS 232 (internally selectable)
Configuration Default settings
Configure per customer requirements
Operating German / English Instructions French / Italian
None
st
switching point: transistor output
nd
2
switching point: relay output
st
switching point: relay output
nd
2
switching point: transistor output
R2900
A1 A2
A3
A4 A5 A6 A7 A8
B1
F0 F1 K0 K9 L0 L1 L2
GOSSEN METRAWATT GMBH 5
Page 6

Data Interface

Refer to operating instructions 3-349-204-15 for detailed information regarding the data interface.

Mechanical Installation / Preparation

The R2900 controller is intended for installation to a control panel. The installation location should be vibration-free to the greatest possible extent. Aggressive vapors shorten the service life of the
96
5
96
50
Variants
A1 ... A6, D0, F0
controller. Requirements set forth in VDE 0100 must be observed during the performance of all work. Work on the device may only be carried out by trained personnel who are familiar with the dan­gers involved.
Set the housing into the panel cutout from the front, and secure it from behind at the left and right-hand sides with the two included screw clamps. Typical tightening torque amounts to 10 Ncm, and a value of 20 Ncm should not be exceeded.
+0,8
92
In general, unobstructed air circulation must be assured when one or several devices are installed. The ambient temperature under­neath the devices may not exceed 50 °C.
+0.8
92
Panel Cutout
Figure 1, Housing Dimensions and Panel Cutout
6 GOSSEN METRAWATT GMBH
Variant A7, A8 or D1, or
570
F1
Page 7
1
2
Securing the two screw clamps at the right and left-hand sides of the housing:
Push in direction 1 all the way up to the limit stop – Push in direction 2 all the way up to the limit stop
Figure 2, Securing the Housing
GOSSEN METRAWATT GMBH 7
Page 8

Electrical Connection

Binary In-
put
Transistor Output for Controlling SSRs 110 - 230
A1, A2, A5, A7
A3, A4, A6, A8
+ I + II
1 234 56 789
I
II
Switching Output Heating Current Transf.
11 12 13 14 15 16 17 18 19
A1, A3, A5, A7
A2, A4, A6, A8
Auxiliary
Voltage
V
NL
A1, A2, A3,
A4, A7, A8
B1, B3, B4 B3
A5, A6
Repeater
10 V
10 V
B2 B4
20 mA
20 mA
Sensor 1 Sensor 2
21 22 23 24
A1 A2
D1
A7, A8
25 26 27 28 29
+CB A
10V / 20 mA GND TxD RxD
F1
Alarms Continuous Output RS 232 / RS 485
8 GOSSEN METRAWATT GMBH
Page 9
EN 55022 requires the following warning as regards electromagnetic compatibility:
Warning
This is a class A device. It may cause radio interference in residential surroundings. If this is the
case, the operator may be required to implement appropriate corrective measures.
Connectors: Screw terminals for wire with a cross section of 1.5 square mm or
two-core wire-end ferrules with a cross-section of 2 x 0.75 square mm
Tighten screws with a manual screwdriver only! Tightening torque for all screw termi­nals: max. 0.6 Nm
Figure 3, Connector Terminal Positions
GOSSEN METRAWATT GMBH 9
Page 10

Performance After Activating Auxiliary Voltage

LED Segment Test
U/M Software Version
B Designation
A Designation
Current Configuration
CnF2
approx. 2 s
D Designation
approx. 1.5 s
Current Configuration
CnF1
Actual Value
approx. 1.5 s
Setpoint or oFF
10 GOSSEN METRAWATT GMBH
Page 11

Operation

Actual value or parameter value
Setpoint / heating current /
manipulating factor / 2nd actual
value or parameter designation
I
II
A1 A2
W2
Switching output I active
Switching output II active
Alarm(s) active
Setpoint 2 active
Shift displays, levels and values (see operating flow chart)
Off / manual operation
R2900GOSSEN METRAWATT
Up and down scrolling keys for value selection
Select: off / manual
Figure 4, Controls
Value Selection
The selected value can be changed using the up and down scrolling keys. The selected value is saved to memory and becomes active after 2.5 seconds, or after pressing the key. The display goes dark briefly to indicate activation of the selected value.
GOSSEN METRAWATT GMBH 11
automatic operation
Page 12

Operating Flowchart, “Discontinuous-Action Controller”

Off
Actual
I
II
A1 A2
W2
PARAMETER LEVEL
Param. Value
Param. Value
(page 24)
I II
A1 A2
W2
I II
A1 A2
W2
Automatic Operation
Actual
Setpoint
I II
A1 A2
W2
Setpoint can only be selected here for
fixed setpoint controllers.
Actual
I Heat
Only appears when heating current monitoring is activated.
CONFIGURATION
(page 18)
Press key briefly. Press and hold key until
the display is switched. Press and hold both keys until
the display is switched.
OPERATING LEVEL
I II
A1 A2
W2
I
II
A1 A2
W2
Actual
M. Factor
I II
A1 A2
W2
I II
A1 A2
W2
Extended oper­ating level when configured as differential con­troller see page 13
12 GOSSEN METRAWATT GMBH
Page 13

Operating Flowchart, “Discontinuous-Action Controller” with Differential Control

Off
Actual Diff.
I
II
A1 A2
W2
PARAMETER LEVEL
Param. Value
Parameter Value
Actual Diff.
Diff. Set-
(page 24)
I II
A1 A2
W2
I
II
A1 A2
W2
Automatic Operation
I II
A1 A2
W2
Differential setpoint can only be selected here.
Act. Val. 1
Act. Val. 2
CONFIGURATION
Press key briefly. Press and hold key until
the display is switched. Press and hold both keys until
the display is switched.
OPERATING LEVEL
I II
A1 A2
W2
Only appears when heating current monitoring is activated.
Actual Diff.
I Heat
(page 18)
I
II
A1 A2
W2
I II
A1 A2
W2
I
II
A1 A2
W2
Actual Diff.
M. Factor
I II
A1 A2
W2
GOSSEN METRAWATT GMBH 13
Page 14

Operating Flowchart, “Continuous-Action and Step-Action Controllers”

Manual Operation
Act. Val.
M. Factor
PARAMETER LEVEL
Param. Value
Param. Value
I II
A1 A2
W2
(page 24)
I II
A1 A2
W2
I
II
A1 A2
W2
Automatic Operation
Act. Val.
Setpoint
I
II
A1 A2
W2
Setpoint can only be selected here for fixed setpoint controllers.
CONFIGURATION
Press key briefly. Press and hold key until
the display is switched. Press and hold both keys until
the display is switched.
(page 18)
II
A1 A2
W2
OPERATING LEVEL
Act. Val.
M. Factor
I
I II
A1 A2
W2
Extended operating level when configured as differential con­troller, see page 15
Only for step-action controllers with
designation A5, A6
I
II
A1 A2
W2
14 GOSSEN METRAWATT GMBH
Page 15

Operating Flowchart, “Cont.-Action and Step-Action Controller” with Diff. Control

Manual Operation
Actual Diff.
I II
A1 A2
W2
PARAMETER LEVEL
Param. Value
Param.Value
(page 24)
I II
A1 A2
W2
I
II
A1 A2
W2
Automatic Operation
Actual Diff.
Diff. Set-
I II
A1 A2
W2
Differential setpoint can only be selected here.
Act. Val. 1
Act. Val. 2
CONFIGURATION
(page 18)
Press key briefly. Press and hold key until
the display is switched. Press and hold both keys until
the display is switched.
OPERATING LEVEL
I II
A1 A2
W2
Only for step-action controllers with designation A5, A6
Actual Diff.
M. Factor
I
II
A1 A2
W2
I II
A1 A2
W2
I II
A1 A2
W2
GOSSEN METRAWATT GMBH 15
Page 16

Off / Manual Operation

OPERATING LEVEL, DISCONTINUOUS-ACTION CONTROLLER
–No alarm function – No indication of errors
Alarm function and error indication identical to automatic operat-
ing mode.
The actuator outputs are controlled with the and keys
and not by the controller function.
Switching between manual and automatic modes is bumpless in
both directions.
Continuous-action controller:
Manipulating factor is displayed in %. Values are changed with the and keys, and are forwarded immediately to the control outputs.
Step-action controller:
Switching output I (more) or II (less) is triggered directly by pressing the or key. If posi­tion acknowledgement is utilized (designations A5 and A6), the measured position is displayed as a percentage, and bars are displayed for all other designations.
Off
Act. Val.
I II
A1 A2
W2
The actuator outputs are inactive
as long as the keys are not acti­vated.
–When the or key is
activated, switching output I (“heat”) or II (“cool”) is triggered directly.
OPERATING LEVEL, CONTINUOUS-ACTION
STEP-ACTION CONTROLLERS
Manual Operation
Act. Val.
M. Factor
I
II
A1 A2
W2
16 GOSSEN METRAWATT GMBH
Page 17

Manual Operation with Binary Input

Switching to manual operation is possible via the binary input (terminals 5 and 6). This is distinguished from off / manual operation with the key as follows:
Bumpless switching to manual operation with all controller sorts The last manipulating factor is “frozen” for step-action controllers as well. – The last switching status is retained for limit transducers. – Operation and display are identical to automatic operation, except that the LED lights up and the
manipulating factor can be changed in the manipulating factor display with the and keys.
When configured as a step-action or a continuous-action controller (controller sort set to 2 through 5), the
Y St parameter must be set to 0.
The “alarm 2” configuration digit must be set to a value of 8 ... F to this end (see also CnF2 on page 20).

PWR Out Offset with Binary Input

When configured as a step-action or a continuous-action controller (controller sort set to 2 through 5), control quality can be significantly improved by means of PWR out offset where abrupt load fluctuations prevail.
When the contact at the binary input is closed, the controller’s manipulating factor is increased by an
amount equaling Y St.
It is reduced by the same value when the contact is opened. – No function during self-tuning –Where Y St = 0, the binary input activates manual operation (see above). The “alarm 2” configuration digit must be set to a value of 8 ... F to this end (see also CnF2 on page 20).
Example: If a machine requires an average of 70% heating power during production operation, but only 10% during idle
time, the difference of Y ST is set to 60%, and the binary input is only activated during production.
GOSSEN METRAWATT GMBH 17
Page 18

Configuration

(continued on page 20)
Controller Sort Alarm 1
Code Code
Limit transducer Actuator Absolute 2-step controller, heat *) Relative 2-step controller, cooling *) Absolute 3-step controller *) Relative 3-step controller, water cooling Absolute Step-action controller Relative
*) Settings for continuous-action controller: see page 23
I
II
A1 A2
W2
I
II
A1 A2
W2
Relative
Absolute Relative Absolute Relative Absolute Relative Absolute Relative Absolute
Actuation
Suppression
Inactive
Active
Inactive
Active
Inactive
Active
Inactive
Active
Contact
NO contact
NC contact
NO contact
NC contact
Heating Cir­cuit Monitor-
ing
Inactive
Active
Gray highlighting: default setting K0
18 GOSSEN METRAWATT GMBH
Page 19
1)
Sensor / Continuous Output2) Unit of Measure Sensor type
1)
Code U/M
°C
°C
°C
°C
°C
°C
Output Range 2)Output Quantity 2)Code Type Design Condition
°F
°F
°F
°F
°F
°F
0 ... 20 mA
0 ... 10 V
4 ... 20 mA
2 ... 10 V
0 ... 20 mA
0 ... 10 V
4 ... 20 mA
2 ... 10 V
0 ... 20 mA
0 ... 10 V
4 ... 20 mA
2 ... 10 V
Actual value (step-action
controller)
Manipulating
factor
(cont.-action
controller)
Select output
quantity
with Cont
(see also page
23)
(no function)
Saving and loading device settings:
see page 21
1) Switching to and from °C and °F is only effective for designations B1, B3 and B4.
2) Only effective for designations A7 and A8
I
II
A1 A2
W2
I
II
A1 A2
W2
J
L
K
B
S
R
N
1 ° Display
0,1 ° Display
0 ... 20 mA / 0 ... 10 V
4 ... 20 mA / 2 ... 10 V
Thermo-
couple
Pt 100
Std.
signal
For measurement
input 1 with
designation B1, B4
For both
measurement inputs
with designation B3
For measurement
input 1 with
designation B2
GOSSEN METRAWATT GMBH 19
Page 20
Configuration
Function, Measurement Input 2 Standard Sig-
(continued)
nal 2
Code B3 B4 B4 Code
Fixed setpoint contr. (int. setpoint)
Differential Fixed setpoint Absolute
Absolute
Absolute
Absolute
Slave controller
Fixed setpoint
controller
Slave controller
0 ... 20 mA
0 ... 10 V
4 ... 20 mA
2 ... 10 V
Relative
Relative
Relative
Relative
Relative Absolute Relative Absolute Relative Absolute Relative Absolute
Actuation sup­pression
Inactive
Active
Inactive
Active
Inactive
Active
Inactive
Active
Alarm 2
Contact Binary input
NO contact
Setpoint 2 delete!!!
NC contact
NO contact
Manual / automatic or PWR out off-
NC contact
set
I II
A1 A2
W2
I II
A1 A2
W2
Gray highlighting: default setting K0
20 GOSSEN METRAWATT GMBH
Page 21

Saving and Loading Device Settings:

Code Function Comment
Current settings
User-defined default settings If settings have not already been saved with d in the past, the factory default settings or a configuration per customer specifications (K9) is loaded.
1)
Factory default settings
The configuration digits and all parameter s except for the interface address Addr
1)
are saved as user-defined default settings.
1)
are loaded.
1)
are loaded.
A configuration per customer specifications (K9) is stored here, and is overwritten in the process. All entries, including self-tuning and calibration results, are overwritten in the process.

Differential Controller

Actual value difference, i.e. 1
Parameters: see page 24
st
actual value – 2nd actual value, is regulated to the selected differential set-
point. – The differential setpoint can be set within a range of ± one half of the measuring range. – Limit value monitoring is relative to actual value difference, and not the two actual values. – If an attempt is made at the operating level to change the differential setpoint (display mode: 1

Slave Controller

The external setpoint which is applied to the 2
value / 2
nd
actual value), no appears briefly at the bottom display.
Parameters: see page 24
nd
measurement input replaces the internal setpoint.
st
actual
The setpoint ramp function (see page 31) is retained. – After switching to setpoint 2 via the binary input, the controller becomes a fixed setpoint controller using set-
point 2 (SP 2). – Upper and lower limits for the external setpoint are scaled with the rn L and rn H parameters
nd
(2
measurement input, standard signal for designation B4).
–The SP L and SP H parameters limit the external setpoint for control and display purposes. If an attempt is made at the operating level to change the setpoint (display mode: actual value / setpoint),
no appears briefly at the bottom display.
GOSSEN METRAWATT GMBH 21
Page 22

Controller Sorts

Code Controller Sort Comment
Limit transducer
Actuator
2-step controller, “heat” A harmonic-free PDPI control algorithm regulates switching output I in order to increase / 2-step controller, “cooling”
3-step controller
3-step controller, water cooling
Step-action controller
Switching output I is active where actual value < current setpoint, and switching output II is active where actual value > current setpoint + dbnd. Switching hysteresis is equal to HYST. Switching status changes are possible once per tc. Read-out of a constant actuating signal to switching output I where YST > 0, or switching output II where YST< 0. The actuating cycle is equal to at least tc. No alarm functions.
decrease the actual value. The actuating cycle is equal to at least tc.
A harmonic-free PDPI control algorithm regulates switching output I in order to increase the actual value, or switching output II in order to decrease the actual value. The actuating cycle is equal to at least tc. The dead band dbnd suppresses switching back and forth between “heating” and “cooling” if no lasting deviation occurs. The manipulating factor at switching output II is adapted to the non-linear performance char­acteristics of a water cooler. The actuating cycle is equal to tc. A harmonic-free PDPI control algorithm regulates switching output I or II in order to increase or decrease the actual value. The duration of the actuating impulse is equal to tc. The dead band dbnd is symmetric to the setpoint.
Parameters: see page 24
22 GOSSEN METRAWATT GMBH
Page 23

Configuration of the Controller with Continuous Output (desig. A7 and A8)

• Continuous output = actual value (“sensor U/M / continuous output” configuration digit = 0, 1, 2, 3)
The controller sorts demonstrate the same performance characteristics as with designations A1 to A4.
Read-out of the actual value (actual value difference for differential controllers) is scaled with the rn L
and rn H parameters.
• Continuous output = manipulating factor (“sensor U/M / continuous output” configuration digit = 4, 5, 6, 7)
Switching output I is inactive.
The various continuous controller sorts result from the “controller sort” configuration digit:
Code Controller Sort Comment
Limit transducer
Actuator Read-out of a manipulating factor which can be adjusted with parameter Y St. Continuous controller with falling char­acteristic curve Continuous controller with rising char­acteristic curve
Split range controller
, No practically relevant function
• Continuous output = “select with Cont” (“sensor U/M / continuous output” configuration digit = 8, 9, A, b)
Cont Cont. Output Comment
The read-out is scaled with the rn L and rn H parameters (the current differential setpoint for differ-
Current setpoint
“Cooling” manip. factor
ential controllers). The controller sorts demonstrate the same performance characteristics as with designations A1 to A4. Negative manipulating factors are read out continuously, and switching output II remains inactive. Controller sort = 4: split range controller with inverted output performance
Read-out of a manipulating factor which can be adjusted with the Y H parameter where actual value < setpoint
A harmonic-free PDPI control algorithm regulates the continuous output every
0.5 seconds. An output filter assures smoothest possible actuating signal char­acteristics. tc is used to set the time constant for an additional actual value filter.
Continuous controller with falling characteristic curve for positive manipulating factors (increase actual value). Negative manipulating factors are read out via switching output II (decrease actual value). The actuating cycle for switching output II has a duration of at least tc. The dead band dbnd suppresses rapid switching back and forth between the continuous output and switching output II if no lasting deviation occurs.
GOSSEN METRAWATT GMBH 23
Page 24

Parameters Configuration

X1 = lower range limit, X2 = upper range limit,
Parameter Display Range Default Comment
Upper limit value for relay A1
Lower limit value for relay A1
Upper limit value for relay A2
oFF, 1 ... MR oFF, X1 ... X2
oFF oFF
Lower limit value for relay A2
Setpoint 2 SP L ... SP H X1
Ramp for rising setpoints oFF, 1 ... MR per min. oFF
Ramp for falling setpoints oFF, 1 ... MR per min. oFF
Heating current setpoint (see Balancing)
Auto, oFF, 0.1 ... A H oFF
Proportional band heating 0.1 ... 999.9% 10.0
Proportional band cooling 0.1 ... 999.9% 10.0 Only with 3-step controllers
Dead band 0 ... MR 0 Not with 2-step controllers
Path delay time 0 ... 9999 s 100
Read-out cycle time 0.5 ... 600.0 s 10.0
Motor run-time
Switching hysteresis
5 ... 5000 s 60
0 ... 1.5% MR 0.5%MR
Maximum setpoint SP L ... X2 X2
Minimum setpoint X1 ... SP H X1
Maximum manipulating factor –100 ... 100 % 100
Actual value correction (see Balancing)
Decimal point position 9999, 999
(Auto), –MR/4 ... +MR / 4 0
9, 9999, 9999 9999 Only with designation B2
Upper range limit, standard signal rn L ... 9999 100
Lower range limit, standard signal –1500 ... rnH 0
MR = X2 – X1
Relative (= default config.) Absolute
Not with step-action control-
1)
lers
4)
Only with step-action control-
5)
lers For limit value monitoring and limit transducers
Only with designations B1, B3 and B4
Only with designations B2, B4, A7 and A8
2)
3)
24 GOSSEN METRAWATT GMBH
Page 25
Parameter Display Range Default Comment
Upper range limit, heating current (see Balancing)
Calibration, position acknowledge­ment
Manipulating factor for actuator mode, or for PWR out offset
1.0 ... 99.9 A 42.7
See Balancing
–100 ... 100% 0
Not with step-action control-
1)
lers Only with step-action control-
lers with position acknowl-
6)
edgement
Sensor error manipulating factor –100 ... 100% 0
Continuous signal
Interface address 0 ... 250 250 Only with designation F1
1)
Only where:“controller sort” conf iguration digit 6 and designation ≠ A5, A6
2)
Only where:“controller sort” configu ration digit = 4 or 5
3)
Only where:“controller sort” configuration digit = 0, 4, 5 or 6
4)
Additional actual value filter for continuous-action controllers (controller sort = 2 or 3), tc = time constant
5)
Only where:“controller sort” configuration digit = 6
6)
Only where:“controller sort” configuration digit = 6 and designation = A5, A6
See page 23 0
Only for designations A7 and A8
Parameters Pb 1 through Addr are disabled for the operator during self-tuning.
GOSSEN METRAWATT GMBH 25
Page 26

Balancing

Thermocouple Correction (parameter: CAL)
The correction value is selected in °C or °F. The displayed correction value is added to the measured temper- ature.
Cable Compensation for Pt 100 with 2-Wire Connection (parameter: CAL)
The correction value can be determined automatically in the “Off / manual operation” mode: – Short circuit the sensor at the measuring point.
–Set the CAL value to Auto. Measured cable resistance is converted to temperature change and is entered as the CAL value. Balancing can also be performed manually if the sensor temperature is known:
CAL = known sensor temperature – displayed temperature value
Scaling for Heating Current Monitoring (parameter: A H)
The default setting for the GTZ 4121 is 42.7 A. If the GTZ 4121 current transformer is not used for acquiring heating current, the current value must be selected at which the utilized transformer generates an output volt­age of 10 V DC.
Calibrating the Position Acknowledgement Display (parameter: Y100, Y0)
Calibration is performed in the manual operating mode at the parameter level with the device configured as a step-action controller (“controller sort” configuration digit = 6):
1. Select parameter Y 100. The stored value appears at first: a standardized value between 0 and 255.
The scroll up key controls switching output I directly (more), and the currently measured actuator
position appears at the display. The scroll up key must be pressed and held until the displayed value
no longer fluctuates. The displayed value is saved to memory.
2. Select parameter Y0.
Same procedure as for parameter Y100. In this case, the scroll down key must be pressed and
held. It controls switching output II directly (less). Y100 must be greater than Y0! The Y100 and Y0 parameters are displayed only in the automatic operating mode.
26 GOSSEN METRAWATT GMBH
Page 27

Self-Tuning

Self-tuning is used to achieve optimized controller dynamics, i.e. parameters Pb 1, Pb 11, tu and tc are determined. Read-out cycle time tc is not changed during self-tuning.
We recommend for tc a value of tu/12 to guarantee satisfactory controller
Start
Slow Blinking
Abort
Current
Current
Current
or
The controller is switched to the automatic operating mode after self-tuning has been successfully com-
pleted. – In the case of 3-step controllers (controller sorts 4 and 5), cooling is activated if the upper limit value is
exceeded in order to prevent overheating. Self-tuning then performs an oscillation test around the set-
point.
Sequence
The setpoint which is active when tuning is started remains valid and can no longer be changed (slave
controllers: changing external setpoints are only displayed). – Activation or deactivation of setpoint 2 does not – Selected setpoint ramps are not taken into consideration. – If started at the operating point (actual value approximates the setpoint value), overshooting cannot be
avoided.
Abort
Self-tuning can be aborted at any time with the keys (automatic operating mode), or by
switching to manual / off with the key. – If an error occurs during self-tuning, the controller no longer reads out an actuating signal. Self-tuning
must be aborted in this case.
Additional information regarding error messages upon request.
I II
dynamics. When controlling contactors, tc should be adequately increased.
A1 A2
Preparation
W2
Complete configuration must be performed before – The setpoint value is adjusted to the value which is required after
I II
A1 A2
W2
self-tuning.
Start
Briefly press the keys simultaneously at the operating level (auto-
self-tuning is started.
matic or manual / off operating mode) in order to trigger self-tuning. Self­tuning cannot be started in the “actuator” or “limit transducer” mode.
tun1...tun8 blinks at the display at all operating levels during self-tuning.
become effective.
GOSSEN METRAWATT GMBH 27
Page 28

Manual Self-Tuning

Preparation
Complete configuration (page 18) and parameter settings (page 24) must first be entered for use of the con-
troller. – The actuators should be deactivated with the off / manual operation function (page 16). –A recorder must be connected to the sensor and adjusted appropriately to prevailing circuit dynamics and
the setpoint.
In the case of differential controllers, the actual value difference must be recorded. – For 3-step or split range controllers, on and off-time must be recorded for switching output I or the contin-
uous output (e.g. with an additional recorder channel or a stopwatch). – Configure as limit transducer (controller sort = 0). – Set read-out cycle time to the minimum value: tc = 0.5. If possible, deactivate manipulating factor limiting. YH = 100. Reduce (or increase) the setpoint so that overshooting and undershooting do not cause any impermissible
values.
Performing the Actuation Test
dbnd = MR Setting for 3-step and split range controllers (switching output II may not be triggered)
dbnd = 0 Setting for step-action controllers (switching output II must be triggered)
Start the recorder. – Activate the actuators with automatic operation. – Record two overshoots and two undershoots.
The actuation test is now complete for 2-step, continuous-action and step-action controllers. Continue as follows for 3-step and split range controllers:
–Set dbnd to 0 in order to cause further overshooting with active switching output II. Record two over-
shoots and two undershoots. –Record on-time T
and off-time TII at switching output I or the continuous output for the last oscillation.
I
Parameters Pb 1, Pb 11, tu and tc are determined by means of manual self-tuning in order to maintain optimized controller dynamics. An actua­tion test or an oscillation test is performed to this end.
28 GOSSEN METRAWATT GMBH
Page 29
t
x
P
x
ss
dbnd = 0dbnd = MR
(3-step and split range controllers only)
T
I
T
II
Evaluating the Actuation Test
Apply a tangent to the curve at the intersection of the actual value and the setpoint, or at the cut-off point
of the output. – Measure time t. Measure oscillation amplitude x
, or overshooting for step-action controllers x.
ss
Parameter Values
Parameter
2-step controller 3-step controller Continuous-action
tu 1.5 tc tu / 12 Pb 1 (x Pb 11 Pb 1
1) When controlling contactors, tc should be adequately increased.
/ MR) 100 % (xss / MR) 200 % (x / MR) 50 %
ss
(T
/ TII)–Pb 1 (TI / TII)–
I
controller
∆t ∆t – (tY / 4)
1)
Split range
controller
Step-action
controller
tY / 100
If manipulating factor limiting was active, the proportional band must be corrected:
YH positive: Pb 1 multiply by 100% / YH YH negative: Pb 11 multiply by –100% / YH
GOSSEN METRAWATT GMBH 29
Page 30
Performing the Oscillation Test
If an actuation test is not possible, for example if neighboring control loops influence the actual value too greatly, if switching output II must be active in order to maintain the actual value (cooling operating point), or if optimization is required directly to the setpoint for any given reason, control parameters can be determined by means of sustained oscillation. However, calculated values for tu may be very inaccurate in this case under certain circumstances. – Preparation as described above. The test can be performed without a recorder if the actual value is
observed at the display, and if times are measured with a stopwatch. – dbnd = 0 Setting for 3-step, split range and step-action controllers – Activate the actuators with automatic operation, and start the recorder if applicable. Record several oscilla-
tions until they become uniform in size. –Measure oscillation amplitude x –Record on-time T
and off-time TII at switching output I or the continuous output for the oscillations.
I
.
ss
x
ss
T
T
I
II
Evaluating the Oscillation Test
Parameter Values
Parameter
1)
tu
2-step controller 3-step controller
tc tu / 12 Pb 1 x
100 %
ss
MR
Pb 11 Pb 1
1) If either TI or TII is significantly greater than the other, value tu is too large.
2) When controlling contactors, tc should be adequatel y increased.
xss TII 100 %
MR (T
+ TII)
I
(T
/ TII)–Pb 1 (TI / TII)–
I
Continuous-action
controller
0.3 (TI + TII)0,2 • (TI + TII – 2tY)
2)
200 %
x
ss
MR
Split range
controller
xss TII 200 %
MR (T
+ TII)
I
Step-action
controller
tY / 100
50 %
x
ss
MR
Correction with manipulating factor limiting YH positive: Pb 1 multiply by 100% / YH
YH negative: Pb 11 multiply by –100% / YH
30 GOSSEN METRAWATT GMBH
Page 31
Correction for step-action controllers in the event that TI or TII is smaller than tY:
tY
Multiply Pb 1 by , if T
tY tYtY
T
T
I
is smaller, or by , if TII is smaller.
I
I
TII T
II
The value for tu is very inaccurate in this case. It should be optimized in the closed loop control mode.
Closed Loop Control Mode
The closed loop control mode is started after self-tuning has been completed: – Configure the desired control algorithm with controller sort.
–Adjust the setpoint to the required value. – The dead band can be increased from dbnd = 0 for 3-step, split range and step-action controllers if con-
trol of switching output I (or the continuous output) and II changes too rapidly, for example due to an
unsteady actual value.

Setpoint Ramps

Function Parameters SPuP and SPdn cause a gradual temperature change
Activation – When auxiliary power is switched on
Setpoint display The targeted setpoint is displayed (not the currently valid setpoint) with a blinking r at
Limit values Relative limit values make reference to the ramp, not the targeted setpoint. As a rule, no
(rising / falling) in degrees per minute.
– When the current setpoint is changed – When setpoint 2 is activated – After switching from manual to automatic operation
the left-hand digit.
alarm is triggered for this reason.
GOSSEN METRAWATT GMBH 31
Page 32

Heating Current Monitoring

FunctionHeating current is acquired with an external transformer (e.g. GTZ 4121).
AMPS current setpointHeater phase current is entered for this parameter. AMPS can be set to Auto for automatic adjustment
An alarm is triggered if the current setpoint is fallen short of by more than 20% with acti­vated heat (control output I active), or if current is not “off” when the heat is switched off. The alarm is not triggered until heating current is high enough when output I is active, or when current drops to zero when output I is inactive. Monitoring is inactive if the controller is switched to oFF, as well as in the case of contin- uous and step-action controllers.
with the heater switched on. The measured current value is saved to memory.

Heating Circuit Monitoring

Function– Can be set to active or inactive with the “alarm” configuration digit
(see Configuration).
– Without external transformer, without additional parameters – Assumes correct optimization of tu and Pb 1 control parameters,
i.e. heating circuit monitoring must be activated before self-tuning is started. In the event of manual optimization or subsequent adaptation of control parameters, the lower limit value for the tu parameter must be observed:
minimum tu =
∆ϑ
Dt = maximum temperature rise during actuation
– Error message LE appears after approximately 2 times tu, if heat remains on at
100% and measured temperature rise is too small.
– Monitoring is not active:
where controller sort = limit transducer, actuator or step-action controller during self-tuning with standard signal input (designation B2) where manipulating factor limiting YH < 20%
Pb 1 MR
50% ∆ϑ
Dt
32 GOSSEN METRAWATT GMBH
Page 33

Limit Value Monitoring

Alarm Relay n, NO Contact Alarm Relay n, NC Contact
Hysteresis (HYSt)
ALnL ALnH
ALnL ALnH
Actual ValueSetpoint
n = 1, 2
Relative Limit Values Absolute Limit Values
Actuation suppression: Alarm suppression remains inactive during actuation (configuration digit “alarms 1 and 2”) until temperature has exceeded the lower limit value for the first time. During cooling, suppression is active until temperature has fallen below the upper limit value for the first time. Suppression is active when auxiliary power is activated, if the current setpoint is changed or setpoint 2 is activated, or if switching takes place from off to automatic operation.

Alarms

Blinking Display
(at operating level only)
Heating current Heating current monitoring LED A1 blinks Alarm output A1 and
Actual value Limit value monitoring 1 LED A1 blinks Alarm output A1 and
Actual value Limit value monitoring 2 LED A2 blinks Alarm output A2 and
1)
Only for designation D1
2)
In the case of designation D0 and config uration as a 2-step controller
The display is switched to the operating level 30 seconds after value selection has been completed during configuration or parameter setting.
Error Message Source Display Response Comment
LED A1 are activated
LED A1 are activated
LED A2 are activated
1)
NO / NC contact selected in configuration digits
1)
“alarms 1 and 2” LED blinks at all levels
2)
GOSSEN METRAWATT GMBH 33
Page 34

Error Messages

Responses in the event of an error:
1. Alarm output A1 is activated, output performance is determined by the “alarm 1” configuration digit
(see Configuration on page 18).
In the case of designation D0 and configuration as a 2-step controller, read-out takes place at switching
output II. The LED lights up when relay contact II is closed and/or transistor output II is active.
2. LED A1 blinks at all levels. The (blinking) error message only appears at the operating level: in the event of
faulty measured values at the display, at which the error-free measured value is otherwise displayed (SE H,
SE L, CE and YE) when other error messages appear in the upper display.
3. The display is switched to the operating level 30 seconds after value selection has been completed during
configuration or parameter setting.
4. Exceptions and additional information are included in the following table:
Display
sensor error high
sensor error low
current error
y error
Error Message Source Response
Broken sensor or actual value greater than up-
Ctr. Sort Manipulating Factor Read-Out
per range limit
2 or 3-step
Sensor polarity reversed or actual value less than lower range limit
Current transformer has reversed polarity, is un­suitable or defective Position ackn. incorrectly calibrated, Y100 Y0
Step On/off ctr. Actuator No response to error
Same as heating current monitoring alarm Continues to control temperature
No
response to error 3
YSE = –100/0/100% YSE –100/0/100%
–100/0/100%
If the controller has settled in:
last “plausible” manipulating
factor, if not: YSE
YSE
Remedy
1
2
Self-tuning cannot be
no tune
started (controller sort: “actuator” or “limit
No response to error Error message is not cleared until key is pressed
transducer”)
34 GOSSEN METRAWATT GMBH
Page 35
Display
Error Message Source Response
Remedy
Disturbance in
tune error 2
self-tuning sequence in steps 1 through 13 (step
Control outputs I and II inactive Self-tuning must be aborted.
4
2 in this case)
Control outputs I and II inactive. Error message is not cleared until key is pressed and held. Control outputs I and II inactive. The parameter level is disabled.
Control outputs I and II inactive 7
5
6
loop error
parameter error
digital error
Measured temperature rise is too small with heat on at 100% Parameter not within permissible limits Error detected by digital component monitoring Hardware error de-
analog error
tected by analog compo-
Control outputs I and II inactive 7
nent monitoring
Remedies
1. Eliminate sensor error.
2. Inspect current transformer.
3. Check for correct connection of the position acknowledgement potentiometer and re-calibrate.
4. Avoid disturbances which impair the self-tuning sequence, e.g. sensor errors.
5. Close the control loop: Check the sensor, the actuators and the heater for correct functioning.
Check sensor-heater assignments (wiring).
Correctly optimize control parameters tu and Pb 1.
6. Restore default configuration and default parameters, and then reconfigure, or load user-defined default
settings.
7. Arrange for repair at authorized service center.
GOSSEN METRAWATT GMBH 35
Page 36

Technical Data

Annual mean relative humidity, no condensation 75% Ambient temperature
Nominal range of use Operating range Storage range
Aux. Voltage Nominal Ranges of Use Power Consumption Nominal Value Voltage Frequency
AC 110 V / AC 230 V
Relay Output Floating, normally open contact Switching capacity AC/DC 250 V, 2 A, 500 VA / 50 W Service life > 2•105 switching cycles at nominal load Interference suppression Utilize external RC element (100 - 47 nF)
Transistor output suitable for commercially available semiconductor relays (SSR) Switching Status Open-Circuit Voltage Output Current
Active (load 800 ) < DC 17 V 10 ... 15 mA Inactive < DC 17 V < 0.02 mA Overload limit Short-circuit, continuous interruption
Electrical Safety
Safety class II, panel-mount device, DIN EN 61010-1 section 6.50.4 Fouling factor 1, per DIN EN 61010-1 section 3.7.3.1 and IEC 664 Overvoltage category II, per DIN EN 61010 appendix J and IEC 664 Operating voltage 300 V per DIN EN 61010 EMC requirements IEC/EN 61326
For complete technical data refer to the following data sheet: order no. 3-349-202-03
Printed in Germany • Subject to change without notice
AC 95 V ... 253 V 48 Hz ... 62 Hz
at contactor
0 °C ... + 50 °C 0 °C ... + 50 °C
–25 °C ... + 70 °C
Max. 10 VA typically 6 W
GOSSEN METRAWATT GMBH Thomas-Mann-Str. 16-20 90471 Nürnberg, Germany
Phone +49-(0)-911-8602-0 Fax +49-(0)-911-8602-669 E-mail info@gmc-instruments.com www.gmc-instruments.com
Loading...