Gossen Metrawatt PROFITEST PRCD Operating Instructions

Operating Instructions
PROFITESTPRCD
Adapter for Standards Compliant Testing of PRCDs by Simulating Faults
Important
Read carefully before use!
Please observe the manufacturer‘s details
on the devices under test!
3-349-797-15
5/2.18
8
7
6
4
1
2
10
3
9
Mains Connection
To P R C D O u t le t
To PR C D In l e t (PRCD IN)
5
11
(PRCD OUT)
Fault Selection
Mains disconnect, 1~OFF/3~OFF – For RISO measurement
Mains power on, 1~ON/3~ON – For fault simulation – For RLO measurement
Phase LEDs
Phase Interrupt
Reversed Wires
Orange positions: testing at single-phase PRCDs Green positions: testing at 3-phase PRCDs
Mains
– For tripping test with I
Nom
and measurement of time to trip
Connection
PROFITESTPRCD Operating and Connections Overview
Connections Overview
1 Coupling plug to the outlet of a
3-phase PRCD
2 Earthing contact plug to the outlet of a
single-phase PRCD
3 Probe socket for contacting the on/off
switch on the PRCD
4 Earthing contact socket to the inlet of a
single-phase PRCD
5 Loop for measuring protective conductor
current with a current clamp transformer
6 CEE socket to the inlet of a 3-phase
PRCD
Instrument Overview
7 Mains power cable with earthing contact plug
8 3-phase mains power cable with
CEE outlet (1P+N+PE 16 A-6h)
9 PRCD inlet sockets connected in parallel
to sockets 4 and 6 – for connecting the PROFITEST MXTRA during protective con­ductor and insulation measurements
10 PRCD outlet sockets connected in paral-
lel to plugs 1 and 2 for connecting the PROFITEST MXTRA during protective con­ductor and insulation measurements
11 Five replaceable fuses
2 GMC-I Messtechnik GmbH
!
PROFITESTPRCD Symbols – Scope of Delivery – Table of Contents
Meanings of Symbols on the Instrument 300 V CAT II
Maximum permissible voltage and measuring category between con­nections and ground Warning concerning a point of danger
(attention: observe documentation!) EC mark of conformity
This device may not be disposed of with the trash. Further information regarding the WEEE mark can be accessed on the Internet at www.gossenme­trawatt.com by entering the search term “WEEE”.
Meanings of Symbols in the Operating Instructions
LED L1, L2, L3, N or PE at test adapter
LED on LED off
PRCD LED at the device under test
LED on LED off
Scope of Delivery
1 Test adapter 1 Probe cable with plug-in test probe 1 Set of operating instructions
Table of Contents Page
1 Safety Precautions .................................... 4
2 Applications .............................................. 5
3 Initial Start-Up ........................................... 6
3.1 Testing the LEDs ......................................... 6
3.2 Mains Connection ....................................... 6
3.3 Connecting the PRCD .................................. 6
4 Measurements with the
PROFITEST MXTRA .................................... 6
Measuring Protective Conductor Resistance (Rlo) ....... 7
4.1
4.2
Measuring Insulation Resistance (Riso) ............. 7
4.3
Tripping Test with Nominal Residual Current and
Measurement of Time to Trip ............................... 8
4.4 Varistor Test (PRCD-K) ................................. 8
5 Protective Conductor Current Measurement 9
6 Fault Simulation ...................................... 10
6.1 PRCD-S (single-phase) ............................. 10
6.1.1 Simulated Interruption ....................................... 10
6.1.2 Simulated Wire Reversal .................................... 10
6.1.3 Simulation of PE to Phase – PE-UEXT ................. 10
6.1.4 Contacting the “ON” Key at the PRCD with the Probe 11
6.2 PRCD-K (single-phase) ............................. 11
6.2.1 Simulated Interruption ....................................... 11
6.3 PRCD-S (3-phase) .................................... 12
6.3.1 Simulated Interruption ....................................... 12
6.3.2 Simulated Wire Reversal .................................... 13
6.3.3 Simulation of PE to Phase ................................... 13
7 Characteristic Values .............................. 14
8 Maintenance ........................................... 14
8.1 Housing Maintenance ................................ 14
8.2 Safety Checks............................................ 15
8.2.1
Testing of Protective Conductor Resistance RPE ............15
8.2.2 Testing of Insulation Resistance: ......................... 15
8.2.3 Contact Current Measurement ............................ 16
8.3 Fuse Replacement ..................................... 16
8.4 Return and Environmentally Sound Disposal 16
9
Repair and Replacement Parts Service, Calibration
Center and Rental Instrument Service .................16
10 Product Support ...................................... 16
GMC-I Messtechnik GmbH 3
PROFITESTPRCD Safety Precautions

1 Safety Precautions

The test adapter has been manufactured and tested in accordance with the following safety regulations:
IEC/EN 61010-1 / VDE 0411-1, DIN VDE 0404, IEC/EN 61577 / VDE 0413-2,-4 / DIN EN 61557-16 / VDE 0413-16 (draft) Safety of the operator, as well as that of the test adapter and the PRCD, is only assured when it is used for its intended purpose.
Read the operating instructions carefully and completely before placing your test instrument into service. Follow all instructions contained therein. Make sure that the operating instructions are available to all users of the instrument. Read the operating instructions for the PROFITEST MXTRA as well, in particular the sections con­cerning the R ments, as well as the tripping test.
Tests may only be performed by a qualified electrician, or under the supervision and direction of a qualified electrician. The user must be instructed by a qualified electrician concerning performance and evaluation of the test.
Observe the following safety precautions:
• The instrument may only be connected to electrical systems with a maximum of 230/400 V which comply with applicable safety regulations (e.g. IEC 60346, VDE
0100) and are protected with a fuse or circuit breaker with a maximum rating of 16 A.
• The test adapter may only be used for testing PRCDs.
• No power consuming devices may be connected to the earthing contact and CEE sockets.
• The test adapter may not be used as an extension cord.
• Measurements within electrical systems are prohibited.
• Make certain that the measurement cables are in flawless condition, e.g. no damage to insulation, no cracks in cables or plugs etc.
, R
and time-to-trip measure-
LO
ISO
• When using a test probe with coil cord (PROFITEST MXTRA): Grip the tip of the test probe firmly, for example during insertion into a jack socket. Tensioning at the coil cord may otherwise cause the test probe to snap back resulting in possible injury.
• Insulation resistance can only be mea­sured at voltage-free objects.
• Do not touch the insulation measuring instrument’s test probes (PROFITEST MXTRA) during insulation resistance mea­surements!
• Please observe the manufacturer‘s details on the devices under test!
Fuse Replacement
All fuses for neutral and phase conductors are accessible from the outside (see section
8.3). The fuses may only be replaced when
the instrument is voltage-free, i.e. the instru­ment must be disconnected from mains supply power and may not be connected to a measuring circuit. The fuse type must comply with the specifications in the techni­cal data or the labeling on the instrument (see section 7).
Opening the Instrument / Repairs
The test adapter may only be opened by authorized, trained personnel in order to ensure flawless operation and to assure that the guarantee is not rendered null and void.
Even original replacement parts may only be installed by authorized, trained personnel.
If it can be ascertained that the test adapter has been opened by unauthorized person­nel, no guarantee claims can be honored by the manufacturer with regard to personal safety, measuring accuracy, compliance with applicable safety measures or any con­sequential damages.
4 GMC-I Messtechnik GmbH
Attention!
!
PROFITESTPRCD Applications
The test adapter may not be used:
• If external damage is apparent, for exam­ple if parts which conduct dangerous touch voltage are freely accessible, if its LEDs are defective (voltage at the PRCD IN would no longer be indicated in this case)
• If the seal or sealing lacquer has been removed as the result of repairs or manipulation carried out by a non-autho­rized/certified service provider
• With damaged connection and/or mea­surement cables, e.g. interrupted insula­tion or kinked cable
• If it no longer functions flawlessly
After extraordinary stressing due to transport
In such cases, the test adapter must be removed from operation and secured against unintentional use.

2 Applications

Testing of PRCDs with the Test Adapter by Simulating Faults
The following faults can be simulated with regard to mains supply power to the PRCD:
• Wire reversals
• Failure of individual conductors (undervoltage detection)
• Interference voltage on the protective conductor a) by connecting the phase conductor
to the protective conductor (PE-U
switch setting) or
EXT
b) by touching the “on” key of the
single-phase PRCDs with the probe
The evaluation of the PRCD’s reaction to each respective fault is strictly visual:
• PRCD active or inactive (indicator lamp on the PRCD)
• Fault indication by means of LEDs on the test adapter
In any case, comply with the manu­facturer’s recommendations con­cerning tests to be conducted in accordance with DGUV Provision 3.
Testing of PRCDs with the Test Adapter by Simu­lating Faults and Measuring Protective Conductor and Insulation Resistance, as well as Tripping Current and Time to Trip, using the PROFITEST MXTRA Test Instrument
The following functions are possible after connecting the PROFITEST MXTRA test instru­ment to the test adapter:
• There are three preset test sequences: Single-phase PRCDs: – PRCD-S: 11 test steps – PRCD-K: 4 test steps 3-phase PRCDs: – PRCD-S: 18 test steps
• The test instrument runs through all test steps semi-automatically: Single-phase PRCDs: 10 test steps 3-phase PRCDs: 17 test steps
• Each test step is evaluated and assessed by the user (go/no-go) for later documentation.
• Measurement of the PRCD’s protective conductor resistance using the test instrument’s R that the protective conductor measure-
function. Please note
LO
ment is a modified RLO measurement with ramp sequence for PRCDs, which is only available with the PROFITEST MXTRA test instrument.
• Measurement of the PRCD’s insulation resistance using the test instrument’s R
function.
ISO
• Tripping test with nominal residual cur­rent using the test instrument’s I function.
F
• Measurement of time to trip using the test instrument’s I
function.
ΔN
• Varistor test for PRCD-K: Measurement via ISO ramp
Measuring Protective Conductor Current
Protective conductor current or bias current may result in premature tripping of PRCDs.
For this reason, the protective conductor is led out of the housing as a loop between surface mount sockets 4 and 6. This makes it possible to measure any protective con­ductor current with the help of a current clamp transformer.
GMC-I Messtechnik GmbH 5
Attention!
!
PROFITESTPRCD Initial Start-Up

3 Initial Start-Up

See the connections overview on page 2 for all connection variants.

3.1 Testing the LEDs

Before performing any measurements, the LEDs should be tested for correct function­ing.
Single-Phase Mains Connection
Insert the earthing contact plug into the
earthing contact mains outlet, remove it, rotate it 180° and insert it again.
When connected with correct polarity, the PRCD IN L1 LED must light up, and when rotated 180° the PRCD IN L1 and PRCD IN PE LEDs must light up simultaneously.
3-Phase Mains Connection
Insert the CEE plug into the CEE outlet. The PRCD IN L1, L2 and L3 LEDs must light up. If any of the phase conductors are con­nected to the neutral conductor, i.e. L1-N,
L2-N or L3-N, N lights up instead Lx. If any of the phase conductors are connected to protective earth, i.e. L1-PE, L2-PE or L3-PE, PE lights up instead of Lx.

3.2 Mains Connection

The test adapter must be connected to the mains for fault simulation, as well as for indi­cation by means of the phase LEDs.
Connect the test adapter to the mains
via the single or 3-phase mains power cable. Refer to the characteristic values on page 14 for nominal mains values.

3.3 Connecting the PRCD

The respective PRCD must be connected to the test adapter for all tests.
Connecting a Single-Phase PRCD
Insert the earthing contact inlet plug from
the PRCD into the earthing contact out­let (4) at the test adapter.
Insert the earthing contact plug (2) from
the test adapter into the outlet coupling socket at the PRCD.
Example of a Single-Phase PRCD
Connecting a 3-Phase PRCD
Insert the CEE inlet plug from the PRCD
into the CEE outlet (6) at the test adapter.
Insert the CEE plug (1) from the test
adapter into the CEE outlet coupling socket at the PRCD.
Single-Phase Mains Connection For correct phase connection, the earthing contact plug must inserted into the mains outlet such that only the PRCD IN L1 LED lights up. The PRCD IN PE LED lights up as well in the case of polarity reversal.
6 GMC-I Messtechnik GmbH
4 Measurements with the
PROFITEST MXTRA
In order to perform protective conductor mea­surements (Rlo) at
MXTRA
, the test adapter must remain connected to the mains. The test adapter can remain connected to the mains for protective conductor measurements conducted at PRCDs whose protective conduc­tor is not switched, as well as for insulation mea­surements (Rins) with the
type S PRCDs
PROFITEST MXTRA
with the
PROFITEST
Attention!
!
PROFITESTPRCD Measurement with the PROFITEST MXTRA

4.1 Measuring Protective Conductor Resistance (Rlo)

As opposed to the usual default setting for low-resistance measurements, the device under test does not have to be discon­nected from all sources of voltage in this case. Depending on the PRCD, the rotary selector switches have to be set to the ON and the 1~ ON or 3~ ON positions, in order to be able to activate the PRCD and switch the protective conductor through.
Example of a Single-Phase PRCD
Activate the PRCD.Perform the measurement as described
in the operating instructions for the
PROFITEST MXTRA
(section 12.2 as of V10).

4.2 Measuring Insulation Resistance (Riso)

The right-hand rotary selector switch must be set to the mains disconnect position: 1~ OFF or 3~ OFF.
In order to perform the insulation mea-
surement (Rins), connect the PROFITEST MXTRA test instrument, via the measuring adapter, to socket 9 for the cable at the mains side and to socket 10 for the cable at the test object’s outlet side.
Example, Single-Phase PRCD OUT Sockets
Before performing protective conductor
measurements, execute an offset mea­surement to assure that the test adapter’s connector contacts are not in­cluded in the measurement results.
Insert the respective test plug into the
appropriate socket at the test adapter to this end: 2 to 4 or 1 to 6.
Start the offset measurement at the
PROFITEST MXTRA
Connect the PRCD as described in sec-
tion 3.3.
Connect the PROFITEST MXTRA test instru-
ment to sockets 9 and 10 via the 2-pole measuring adapter.
GMC-I Messtechnik GmbH 7
.
Connect the PRCD as described in sec-
tion 3.3.
Single-phase PRCD: Connect the
PROFITEST MXTRA test instrument, via the 2-pole measuring adapter, to the PRCD IN / OUT L1, N and PE sockets, one after the
other.
Note!
PROFITESTPRCD Measurement with the PROFITEST MXTRA
Perform the measurement as described
in section 11 of the operating instruc­tions for the PROFITEST MXTRA .
3-phase PRCD: MXTRA
suring adapter, to the
Connect the
PROFITEST
test instrument, via the 2-pole mea-
PRCD IN / OUT
L1, L2,
L3, N and PE sockets, one after the other.
4.3 Tripping Test with Nominal Residual Cur­rent and Measurement of Time to Trip
If you operate your test adapter at an electrical system with a 30 mA breaker, the mains RCCB may be tripped during the tripping test (tripping current and time to trip) instead of the PRCD. In this case the
In order to prevent an upstream RCD (also non-selevtive RCD) from being tripped and to ensure that the actual tripping current and/or the correct time-to-trip are deter­mined, we recommend the following proce­dure:
Connect the PROFITEST MXTRA test instru-
ment via the 2-pole measuring adapter with pole (L1) to L1 (PRCD-OUT) and with pole (PE) to N (PRCD-IN). Observe the correct polarity between earthing contact plug and PRCD!
Refer to the operating instructions for the
PROFITEST MXTRA regarding performance of the measurement Type K PRCD, section 7.3.2 Type S PRCD, section 7.3.3
MAINS L1
LED goes out.
:

4.4 Varistor Test (PRCD-K)

During this measurement, the voltage is ascertained at which the varistor becomes conductive, thus checking the varistor for correct functioning as well. Measurement can be performed by means of an ISO ramp, or with a fixed test voltage of 50 V.
As a prerequisite for this measurement, the device under test must be switched on.
Connect the PROFITEST MXTRA test instru-
ment to the PE IN and PE OUT sockets via the 2-pole measuring adapter.
Perform the measurement as described
in the operating instructions for the PROF- ITEST MXTRA (section 11).
The evaluation of the measured varistor re­sistance depends on the manufacturer’s specifications (PRCD-K from Kopp: e.g. 12 to 22 V according to Kopp).
Note on Kopp Test Specification: PRCD-K (Varistor in Protective Earth Circuit)
Test Sequence by Kopp:
1.) Connect operating voltage (e. g. 230 V/ 50 Hz) and 24 V AC voltage source.
2.) Select resistance (R) depending on the residual current of the PRCD-K:
For PRCD-K with In = 30 mA R = 220 Ω/1 W.
For PRCD-K with In = 10 mA R = 620 Ω/0.5 W.
3.) Switch on PRCD-K by pressing the ON button.
4.) Press key <T> circuit is functioning properly.
device must trip PE
The shutdown test of the PRCD-K stipulated by KOPP at this point is performed in connection with the testing of the RCD pro­tection device with a continuously rising resi­dual current until the device is tripped.
8 GMC-I Messtechnik GmbH
PROFITESTPRCD Measurement with the PROFITEST MXTRA
5 Protective Conductor Current
Measurement
Connect the PRCD as described in sec-
tion 3.3.
Switch mains power on by turning the
right-hand rotary selector switch to the 1~ ON or 3~ ON position depending on
the number of phases.
Single-phase PRCD: Tur n t he left-hand ro-
tary selector switch to the first ON posi­tion in the orange area for single-phase interruption.
3-phase PRCD: Turn t he left-hand rotary se-
lector switch to the first ON position in the green area for 3-phase interruption.
Enclose the external protective conduc-
tor loop (5) with the jaws of the current clamp transformer.
Read the measured value for protective
conductor current at the current clamp transformer.
Protective conductor current should not exceed 3.5 mA.
Example of a Single-Phase PRCD
GMC-I Messtechnik GmbH 9
Note!
PROFITESTPRCD Fault Simulation

6 Fault Simulation

6.1.2 Simulated Wire Reversal

If you operate your test adapter at an electrical system with a 30 mA breaker, the mains RCCB may be tripped during the tripping test (trip­ping current and time to trip) instead of the PRCD. In this case the MAINS
L1 LED goes out.

6.1 PRCD-S (single-phase)

Switch mains power on by
turning the right-hand rotary selector switch to the 1~ ON position.

6.1.1 Simulated Interruption

Start with the left-hand rotary se-
lector switch in the first ON position in the orange area for single-phase interrup­tion.
Switch through the positions, one after
the other, in the clockwise direction (ta­ble from top to bottom).
Turn the left-hand rotary selector
switch to the L1-PE position in the orange area for single-phase wire reversal.
Instead of the
L1 LED
, the
PE LED
must light up.
It must not be possible to activate the PRCD when this fault is simulated.
Rotary Switch
Step
7
6.1.3 Simulation of PE to Phase – PE-U
Te st Adapter
L1 LED
PE LED
PRCD
LED
Action
It must not be possible to activate the PRCD.
EXT
Set the left-hand rotary selector switch
to the PE-U
position.
EXT
The L1 LED and the PE LED PE light up. It must not be possible to activate the PRCD when this fault is simulated.
Rotary Switch
Step
1
2
3
4
5
6
10 GMC-I Messtechnik GmbH
Te st Adapter
L1 LED
PE LED
PRCD
Action
LED
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
8
Step
Rotary Switch
Te st Adapter
L1 LED
PE LED
PRCD
Action
LED
It must not be possi­ble to activate the PRCD.
PROFITESTPRCD Fault Simulation

6.1.4 Contacting the “ON” Key at the PRCD with the Probe

Turn the left-hand rotary selector switch
to the first ON position in the orange area for single-phase interruption.
The L1 LED must light up.
Activate the PRCD.Plug the probe into the PROBE socket
and contact the ON key at the PRCD with the test probe.
The PRCD is tripped. It must not be possible to activate the PRCD
as long as the probe is in contact with the
ON key at the PRCD.

6.2 PRCD-K (single-phase)

Switch mains power on by
turning the right-hand rotary selector switch to the 1~ ON position.

6.2.1 Simulated Interruption

Start with the left-hand rotary se-
lector switch in the first ON position in the orange area for single-phase interrup­tion.
Switch through the positions, one after
the other, in the clockwise direction (ta­ble from top to bottom).
Rotary Switch
Step
1
2
3
4
Te st Adapter
L1 LED
PE LED
PRCD
Action
LED
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Rotary Switch
Step
9
Contact “ON” key at PRCD with test probe.
10
Tes t Adapter
L1 LED
PE LED
PRCD
LED
Action
Activate the PRCD.
The PRCD is tripped. It must not be possible to reac­tivate it.
Due to its design, the following tests are omitted for the PRCD-K:
– PE interruption – Simulated wire reversal – Simulation of PE to phase – Contacting the “ON” key at PRCD with
the test probe
Step 11: see section entitled “Protective
Conductor Current Measurement” on page 9.
GMC-I Messtechnik GmbH 11
Note!
PROFITESTPRCD Fault Simulation

6.3 PRCD-S (3-phase)

Switch mains power on by
turning the right-hand rotary selector switch to the 3~ ON position.

6.3.1 Simulated Interruption

Start with the left-hand rotary se-
lector switch in the first ON position in the green area for single-phase interruption.
Switch through the positions, one after
the other, in the clockwise direction (ta­ble from top to bottom).
Conductor Interruption Using a 3-Phase PRCD from Kopp as an Example
Rotary Switch
Step
1
2
3
4
5
6
7
Test A d a pte r L1
LED
L2 LED
L3 LEDN LED
PE LED
PRCD
Action
LED
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Activate the PRCD.
8
9
10
Regarding step 8: The N LED also lights up due to star connection, although N is interrupted!
The PRCD is tripped. It must not be possible to reactivate it.
Activate the PRCD.
The PRCD is tripped. It must not be possible to reactivate it.
Tripping performance may deviate from this example in the case of PRCDs from other manufacturers – adhere to the manufacturer’s test instructions!
12 GMC-I Messtechnik GmbH
PROFITESTPRCD Fault Simulation

6.3.2 Simulated Wire Reversal

Turn the left-hand rotary selector
switch to the L1-N position in the green area for 3-phase wire reversal.
Switch through the positions, one after
the other, in the clockwise direction (ta­ble from top to bottom).
It must not be possible to activate the PRCD when any of these faults is simulated.
Rotary Switch
Step
Test Ada p t e r L1
LED
L2 LED
L3 LEDN LED
PE LED
PRCD LED
11
12
13
14
15
16

6.3.3 Simulation of PE to Phase

Set the left-hand rotary selector switch
to the PE-U It must not be possible to activate the PRCD when this fault is simulated.
Rotary Switch
Step
17
EXT
Test Ada p t e r L1
LED
position.
L2
L3
LED
LEDN LED
PE LED
PRCD LED
Action
It must not be possible to activate the PRCD.
It must not be possible to activate the PRCD.
It must not be possible to activate the PRCD.
It must not be possible to activate the PRCD.
It must not be possible to activate the PRCD.
It must not be possible to activate the PRCD.
Action
It must not be possible to activate the PRCD.
Step 18: see section entitled “Protective
Conductor Current Measurement” on
page 9.
GMC-I Messtechnik GmbH 13
Note!
PROFITESTPRCD Characteristic Values – Maintenance

7 Characteristic Values

Measurements with Protective conductor current measurement Measuring range:
Measurements with PROFITEST MXTRA as accessory:
Protective conductor measurement Measuring range:
Insulation measurement Measuring range:
Connections
Test O u t let s
Earth contact CEE 3P+N+PE 16 A 400 V
Test Plug
Earth contact CEE 3P+N+PE 16 A 400 V
METRACLIP 61
as accessory:
0 ... 30 mA AC
0.1 Ω ... 6 Ω, see technical data on
function of the
R
LO
PROFITEST MXTRA
50 kΩ ... 500 MΩ, see technical data on R
function of the
ISO
PROFITEST MXTRA
1P+N+PE, 16 A, 230 V
1P+N+PE, 16 A, 230 V
Ambient Conditions
Operating temperature Storage temperature -20 ... + 60 °C Relative humidity
Mechanical Design
Test adapter protection IP 40 per DIN VDE
Dimensions Housing (Wx HxD):
Weight Approx. 2.4 kg (with
-5 ... + 50 °C
Max. 75%, no condensation allowed
0470, part 1, connections: IP 20
approx. 24 x 17.5 x 11 cm (without connector cable, with surface mount sockets) Mains connector cable length with plug: earthing contact/ approx. 97/100 cm Connector cable length with test plug: earthing contact/CEE to PRCD: approx. 57/ 60 cm
connector cable)
CEE:
Power Supply
Nominal line voltage 230/400 V 50 Hz Mains connection
Throughput rating
Power consumption Earth contact: < 2 VA
Electrical Safety
Measurement category 300 V CAT II
Pollution degree 2 Fuse links 5 ea. FF315mA/500V
14 GMC-I Messtechnik GmbH
Earthing contact plug: 230 V 1P+N+PE 16 A or CEE plug: 230/400 V 3P+N+PE 16 A Earth contact: CEE: 30 VA
CEE: < 4 VA
10 VA

8 Maintenance

8.1 Housing Maintenance

No special maintenance is required. Keep outside surfaces clean and dry. Use a slightly dampened cloth for cleaning. Avoid the use of solvents, cleansers and abrasives.
If the test adapter has not been used for a long period of time, the switches may demonstrate increased contact resistance depending upon storage conditions. If this is the case, actuate the switches several times.
PROFITESTPRCD Maintenance
The fuses may only be replaced when the instrument is voltage-free, i.e. the instrument must be disconnected from mains supply power and may not be connected to a mea­suring circuit. The fuse type must comply with the specifications in the technical data or the labeling on the device.
8.2 Safety Checks
Testing in Compliance with DGUV Provision 3
Subject your test adapter to regular safety checks. The test adapter has been designed in con­formity with standards IEC 61010 and VDE 0404 as a safety class I and II test instrument. The testing of protective conductor, insula­tion resistance as well as contact current is described in the following subchapters.
8.2.1 Testing of Protective Conductor
Resistance R
Connection and/or Contacting of PRCD Adapter Single-phase (230 V)
The protective conductor resistance test is performed between the PE contact of the mains socket (earthing contact plug (7)) and the PE contact PRCD IN (both earthing con­tact outlet (4) and 4 mm parallel PE jack (9)).
Testing of Single-phase Connection
Turn the right rotary selector switch of
the PRCD adapter to position 1~ON. Turn the left rotary selector switch to any
position*.
Apart from the exceptional positions indi­cated below, a protective conductor resis­tance of R to the design of the PRCD adapter.
* The following positions in which errors
• Conductor interruption:
PE
are simulated for measuring purposes
must be exempt from this test:
PE (orange), PE (green=3P) → >30MΩ
PE
<2Ω is admissible. This is due
• Reversed conductors: L1-PE (orange), L1-PE (green), L2-PE (green), L3-PE (green) >30MΩ
• Voltage on protective conductor: PE-Uext (green/orange) approx.1.5 MΩ
Connection and/or Contacting of PRCD Adapter 3-phase (400 V)
The protective conductor resistance test is performed between the PE contact of the mains plug (CEE plug (8)) and the PE con­tact PRCD IN (both CEE socket (6) and 4 mm parallel PE jack (9)).
Testing of 3-phase Connection
Turn the right rotary selector switch of
the PRCD adapter to position 3~ON.
Turn the left rotary selector switch to any
position*.
Apart from the exceptional positions indi­cated below, a protective conductor resis­tance of R to the design of the PRCD adapter.
<2Ω is admissible. This is due
PE
* The following positions in which errors
are simulated for measuring purposes must be exempt from this test:
• Conductor interruption: PE (orange), PE (green=3P) → >30MΩ
• Reversed conductors: L1-PE (orange), L1-PE (green), L2-PE (green), L3-PE (green) >30MΩ
• Voltage on protective conductor: PE-Uext (green/orange) approx.1.5 MΩ

8.2.2 Testing of Insulation Resistance:

The test is performed in the respective selector switch position 1~ON and/or 3~ON on short-circuited contacts L-N and/or L N (for earthing contact and/or CEE plugs) of
• mains power cables (7) and/or (8)
PRCD OUT
connection cables (2) and/or (1)
PRCD IN sockets (4) and/or (6)
against PE in each case.
The usual limit values apply in these cases.
123
-
GMC-I Messtechnik GmbH 15
N L L3 L2 L1
PROFITESTPRCD Maintenance – Addresses

8.2.3 Contact Current Measurement

The measurement of contact current is per­formed on the screw connections of the PRCD IN sockets with standard limit values (IB<0.5mA).

8.3 Fuse Replacement

All fuses for neutral and phase conductors are accessible from the outside. The fuses may only be replaced when the instrument is voltage-free, i.e. the instrument must be disconnected from mains supply power and may not be connected to a mea­suring circuit. The respective fuse type must comply with the specifications in the techni­cal data or the labeling on the device.

8.4 Return and Environmentally Sound Disposal

The device is a category 9 product (monitor­ing and control instrument) in accordance with ElektroG (German electrical and elec­tronic device law). This device is subject to the RoHS directive. Furthermore, we make reference to the fact that the current status in this regard can be accessed on the Internet at
www.gossenmetrawatt.com by entering the search term WEEE.
In accordance with WEEE 2012/ 19/EU and ElektroG, we identify our electrical and electronic devices with the symbol in accor­dance with DIN EN 50419 which is shown at the right. Devices identified with this symbol may not be disposed of with the trash.
Please contact our service department regarding the return of old devices (see address next page).
9 Repair and Replacement Parts
Service, Calibration Center and Rental Instrument Service
If required lease contact:
GMC-I Service GmbH Service Center Thomas-Mann-Strasse 16-20 90471 Nürnberg
Germany
Phone: +49-911-817718-0 Fax: +49-911-817718-253 e-mail service@gossenmetrawatt.com www.gmci-service.com
This address is only valid in Germany. Please contact our representatives or sub­sidiaries for service in other countries.

10 Product Support

If required please contact:
GMC-I Messtechnik GmbH
Product Support Hotline
Phone: +49-911-8602-0 Fax: +49 911 8602-709 e-mail:
support@gossenmetrawatt.com
Edited in Germany • Subject to change without notice • PDF version available on the Internet
GMC-I Messtechnik GmbH Südwestpark 15 90449 Nürnberg
Germany
Phone: +49 911 8602-111 Fax: +49 911 8602-777 e-mail: info@gossenmetrawatt.com www.gossenmetrawatt.com
Loading...