Gossen Metrawatt PROFITEST PRCD Operating Instructions

Operating Instructions
PROFITESTPRCD
Adapter for Standards Compliant Testing of PRCDs by Simulating Faults
Important
Read carefully before use!
Please observe the manufacturer‘s details
on the devices under test!
3-349-797-15
5/2.18
8
7
6
4
1
2
10
3
9
Mains Connection
To P R C D O u t le t
To PR C D In l e t (PRCD IN)
5
11
(PRCD OUT)
Fault Selection
Mains disconnect, 1~OFF/3~OFF – For RISO measurement
Mains power on, 1~ON/3~ON – For fault simulation – For RLO measurement
Phase LEDs
Phase Interrupt
Reversed Wires
Orange positions: testing at single-phase PRCDs Green positions: testing at 3-phase PRCDs
Mains
– For tripping test with I
Nom
and measurement of time to trip
Connection
PROFITESTPRCD Operating and Connections Overview
Connections Overview
1 Coupling plug to the outlet of a
3-phase PRCD
2 Earthing contact plug to the outlet of a
single-phase PRCD
3 Probe socket for contacting the on/off
switch on the PRCD
4 Earthing contact socket to the inlet of a
single-phase PRCD
5 Loop for measuring protective conductor
current with a current clamp transformer
6 CEE socket to the inlet of a 3-phase
PRCD
Instrument Overview
7 Mains power cable with earthing contact plug
8 3-phase mains power cable with
CEE outlet (1P+N+PE 16 A-6h)
9 PRCD inlet sockets connected in parallel
to sockets 4 and 6 – for connecting the PROFITEST MXTRA during protective con­ductor and insulation measurements
10 PRCD outlet sockets connected in paral-
lel to plugs 1 and 2 for connecting the PROFITEST MXTRA during protective con­ductor and insulation measurements
11 Five replaceable fuses
2 GMC-I Messtechnik GmbH
!
PROFITESTPRCD Symbols – Scope of Delivery – Table of Contents
Meanings of Symbols on the Instrument 300 V CAT II
Maximum permissible voltage and measuring category between con­nections and ground Warning concerning a point of danger
(attention: observe documentation!) EC mark of conformity
This device may not be disposed of with the trash. Further information regarding the WEEE mark can be accessed on the Internet at www.gossenme­trawatt.com by entering the search term “WEEE”.
Meanings of Symbols in the Operating Instructions
LED L1, L2, L3, N or PE at test adapter
LED on LED off
PRCD LED at the device under test
LED on LED off
Scope of Delivery
1 Test adapter 1 Probe cable with plug-in test probe 1 Set of operating instructions
Table of Contents Page
1 Safety Precautions .................................... 4
2 Applications .............................................. 5
3 Initial Start-Up ........................................... 6
3.1 Testing the LEDs ......................................... 6
3.2 Mains Connection ....................................... 6
3.3 Connecting the PRCD .................................. 6
4 Measurements with the
PROFITEST MXTRA .................................... 6
Measuring Protective Conductor Resistance (Rlo) ....... 7
4.1
4.2
Measuring Insulation Resistance (Riso) ............. 7
4.3
Tripping Test with Nominal Residual Current and
Measurement of Time to Trip ............................... 8
4.4 Varistor Test (PRCD-K) ................................. 8
5 Protective Conductor Current Measurement 9
6 Fault Simulation ...................................... 10
6.1 PRCD-S (single-phase) ............................. 10
6.1.1 Simulated Interruption ....................................... 10
6.1.2 Simulated Wire Reversal .................................... 10
6.1.3 Simulation of PE to Phase – PE-UEXT ................. 10
6.1.4 Contacting the “ON” Key at the PRCD with the Probe 11
6.2 PRCD-K (single-phase) ............................. 11
6.2.1 Simulated Interruption ....................................... 11
6.3 PRCD-S (3-phase) .................................... 12
6.3.1 Simulated Interruption ....................................... 12
6.3.2 Simulated Wire Reversal .................................... 13
6.3.3 Simulation of PE to Phase ................................... 13
7 Characteristic Values .............................. 14
8 Maintenance ........................................... 14
8.1 Housing Maintenance ................................ 14
8.2 Safety Checks............................................ 15
8.2.1
Testing of Protective Conductor Resistance RPE ............15
8.2.2 Testing of Insulation Resistance: ......................... 15
8.2.3 Contact Current Measurement ............................ 16
8.3 Fuse Replacement ..................................... 16
8.4 Return and Environmentally Sound Disposal 16
9
Repair and Replacement Parts Service, Calibration
Center and Rental Instrument Service .................16
10 Product Support ...................................... 16
GMC-I Messtechnik GmbH 3
PROFITESTPRCD Safety Precautions

1 Safety Precautions

The test adapter has been manufactured and tested in accordance with the following safety regulations:
IEC/EN 61010-1 / VDE 0411-1, DIN VDE 0404, IEC/EN 61577 / VDE 0413-2,-4 / DIN EN 61557-16 / VDE 0413-16 (draft) Safety of the operator, as well as that of the test adapter and the PRCD, is only assured when it is used for its intended purpose.
Read the operating instructions carefully and completely before placing your test instrument into service. Follow all instructions contained therein. Make sure that the operating instructions are available to all users of the instrument. Read the operating instructions for the PROFITEST MXTRA as well, in particular the sections con­cerning the R ments, as well as the tripping test.
Tests may only be performed by a qualified electrician, or under the supervision and direction of a qualified electrician. The user must be instructed by a qualified electrician concerning performance and evaluation of the test.
Observe the following safety precautions:
• The instrument may only be connected to electrical systems with a maximum of 230/400 V which comply with applicable safety regulations (e.g. IEC 60346, VDE
0100) and are protected with a fuse or circuit breaker with a maximum rating of 16 A.
• The test adapter may only be used for testing PRCDs.
• No power consuming devices may be connected to the earthing contact and CEE sockets.
• The test adapter may not be used as an extension cord.
• Measurements within electrical systems are prohibited.
• Make certain that the measurement cables are in flawless condition, e.g. no damage to insulation, no cracks in cables or plugs etc.
, R
and time-to-trip measure-
LO
ISO
• When using a test probe with coil cord (PROFITEST MXTRA): Grip the tip of the test probe firmly, for example during insertion into a jack socket. Tensioning at the coil cord may otherwise cause the test probe to snap back resulting in possible injury.
• Insulation resistance can only be mea­sured at voltage-free objects.
• Do not touch the insulation measuring instrument’s test probes (PROFITEST MXTRA) during insulation resistance mea­surements!
• Please observe the manufacturer‘s details on the devices under test!
Fuse Replacement
All fuses for neutral and phase conductors are accessible from the outside (see section
8.3). The fuses may only be replaced when
the instrument is voltage-free, i.e. the instru­ment must be disconnected from mains supply power and may not be connected to a measuring circuit. The fuse type must comply with the specifications in the techni­cal data or the labeling on the instrument (see section 7).
Opening the Instrument / Repairs
The test adapter may only be opened by authorized, trained personnel in order to ensure flawless operation and to assure that the guarantee is not rendered null and void.
Even original replacement parts may only be installed by authorized, trained personnel.
If it can be ascertained that the test adapter has been opened by unauthorized person­nel, no guarantee claims can be honored by the manufacturer with regard to personal safety, measuring accuracy, compliance with applicable safety measures or any con­sequential damages.
4 GMC-I Messtechnik GmbH
Attention!
!
PROFITESTPRCD Applications
The test adapter may not be used:
• If external damage is apparent, for exam­ple if parts which conduct dangerous touch voltage are freely accessible, if its LEDs are defective (voltage at the PRCD IN would no longer be indicated in this case)
• If the seal or sealing lacquer has been removed as the result of repairs or manipulation carried out by a non-autho­rized/certified service provider
• With damaged connection and/or mea­surement cables, e.g. interrupted insula­tion or kinked cable
• If it no longer functions flawlessly
After extraordinary stressing due to transport
In such cases, the test adapter must be removed from operation and secured against unintentional use.

2 Applications

Testing of PRCDs with the Test Adapter by Simulating Faults
The following faults can be simulated with regard to mains supply power to the PRCD:
• Wire reversals
• Failure of individual conductors (undervoltage detection)
• Interference voltage on the protective conductor a) by connecting the phase conductor
to the protective conductor (PE-U
switch setting) or
EXT
b) by touching the “on” key of the
single-phase PRCDs with the probe
The evaluation of the PRCD’s reaction to each respective fault is strictly visual:
• PRCD active or inactive (indicator lamp on the PRCD)
• Fault indication by means of LEDs on the test adapter
In any case, comply with the manu­facturer’s recommendations con­cerning tests to be conducted in accordance with DGUV Provision 3.
Testing of PRCDs with the Test Adapter by Simu­lating Faults and Measuring Protective Conductor and Insulation Resistance, as well as Tripping Current and Time to Trip, using the PROFITEST MXTRA Test Instrument
The following functions are possible after connecting the PROFITEST MXTRA test instru­ment to the test adapter:
• There are three preset test sequences: Single-phase PRCDs: – PRCD-S: 11 test steps – PRCD-K: 4 test steps 3-phase PRCDs: – PRCD-S: 18 test steps
• The test instrument runs through all test steps semi-automatically: Single-phase PRCDs: 10 test steps 3-phase PRCDs: 17 test steps
• Each test step is evaluated and assessed by the user (go/no-go) for later documentation.
• Measurement of the PRCD’s protective conductor resistance using the test instrument’s R that the protective conductor measure-
function. Please note
LO
ment is a modified RLO measurement with ramp sequence for PRCDs, which is only available with the PROFITEST MXTRA test instrument.
• Measurement of the PRCD’s insulation resistance using the test instrument’s R
function.
ISO
• Tripping test with nominal residual cur­rent using the test instrument’s I function.
F
• Measurement of time to trip using the test instrument’s I
function.
ΔN
• Varistor test for PRCD-K: Measurement via ISO ramp
Measuring Protective Conductor Current
Protective conductor current or bias current may result in premature tripping of PRCDs.
For this reason, the protective conductor is led out of the housing as a loop between surface mount sockets 4 and 6. This makes it possible to measure any protective con­ductor current with the help of a current clamp transformer.
GMC-I Messtechnik GmbH 5
Loading...
+ 11 hidden pages