Gossen Metrawatt METRATESTER 5 3P User guide

Operating Instructions
METRATESTER 5+3P
Workshop Test Panel for Testing Devices per DIN VDE 0701-0702 and DIN VDE 0104
3-349-414-03
7/5.13
1 NETZ-VDE switch (mains-VDE) 2 Measuring selector switch: L1-L2-L3 3 Connector socket/terminal for DUT
phase conductor (parallel to test sockets)
4 Connector socket/terminal for DUT pro-
tective conductor (parallel to test sockets)
5 Connector socket/terminal for
conductive parts of the DUT for testing for the absence of voltage in accordance with DIN VDE 0701–0702, and for contact current measurement for protection class II devices
6 Measuring function selector switch for
METRATESTER 5+ 7 Contact surface for finger contact 8 Plug connector for mains cables 9 Mains / emergency stop switch,
12 RCD (residual current circuit beaker)
4*25 A, 0.03 A 13 Three circuit breakers, B16 A 14 Polarity reversing switch 15 CEE socket, 3P+N+PE, 32 A, 230/400 V
max. 16 A !
16 Fuse, T 0.1/250G 17 CEE socket, 3P+N+PE, 16 A, 230/400 V 18 Earthing contact outlet 19 Mains indicator lamps, L1-L2-L3 20 Test sockets, L1-L2-L3-N-PE 21 Probe cable with clip / test probe 22 Mains cable with earthing contact plug
and coupling socket 23 Mains cable with CEE 16 A, 5-pole
mains plug and coupling socket
undervoltage trigger can be locked at
zero setting 10 “Durchgang” (continuity) indicator lamp 11 Connector sockets for continuity test
with max. 33 V AC
2 GMC-I Messtechnik GmbH
Table of Contents Page
1 Applications ....................................................................................................................4
2 Safety Precautions .........................................................................................................4
3 Standard Equipment and Accessories ............................................................................6
4
Connecting the Test Case to the Mains and Testing the Mains Connection ..........................6
4.1 Connecting the Test Case ................................................................................................................. 6
4.2 Testing Protective Conductor Potential ............................................................................................... 6
4.3 Measuring Line Voltage .................................................................................................................... 7
5 Connecting the DUT to the Test Case ............................................................................. 8
5.1 Protection Class I Devices ................................................................................................................. 8
5.2 Protection Class II and III Devices ...................................................................................................... 9
5.3 Devices with Single or Multi-Phase Connection without Plug ............................................................... 9
5.4 Stationary Devices for Protective Conductor Testing via the Supply Mains .......................................... 10
5.5 Data Processing Equipment ............................................................................................................ 10
5.6 Extension Cables with the VL2 E Accessory ..................................................................................... 11
5.7 Setting the Switches at the Test Case .............................................................................................. 11
5.8 Setting the Switches at the Device Under Test ................................................................................. 11
6 Testing Devices in Accordance with DIN VDE 0701-0702 ............................................12
6.1 Measuring Protective Conductor Resistance for Protection Class I Devices ......................................... 12
6.2 Measuring Insulation Resistance ..................................................................................................... 13
6.3 Measuring Protective Conductor Resistance ..................................................................................... 15
6.3.1 Equivalent Leakage Current ............................................................................................................ 15
6.3.2 Differential Current Measurement for Protection Class I Devices ........................................................ 16
6.4 Measuring Contact Current ............................................................................................................. 17
6.4.1 Contact Current Measurement – Differential Current ........................................................................17
6.4.2 Testing in Accordance with the Direct Method ................................................................................. 17
6.5 Measuring Load Current and Voltage at the Consumer ..................................................................... 18
7 Testing Extension Cables with the VL2 E Accessory ....................................................19
7.1 DIN VDE Tests for Extension Cables ................................................................................................. 19
7.2 Function Test for Extension Cables .................................................................................................. 19
8 Continuity Test with Extra-Low Voltage ........................................................................ 20
9 Display and Indicators at the Test Instruments ............................................................20
9.1 Indication of Errors and Limit Values ................................................................................................ 20
10 Technical Data ..............................................................................................................21
10.1 Test case ...................................................................................................................................... 21
10.2 METRATESTER 5 + Test Instrument ................................................................................................. 22
11 Maintenance – Recalibration ........................................................................................ 25
11.1 Housing Maintenance ..................................................................................................................... 25
11.2 Recalibration .................................................................................................................................. 25
11.3 Periodic Self-Test of the Connector Cable for Protective Conductor Continuity .................................... 26
11.4 Testing the Integrated RCD (residual current circuit breaker) ............................................................. 26
GMC-I Messtechnik GmbH 3
11.5 Fuse Replacement .......................................................................................................................... 26
11.6 Return and Environmentally Sound Disposal ..................................................................................... 26
12 Repair and Replacement Parts Service
Calibration Center * and Rental Instrument Service .....................................................27
13 Product Support ............................................................................................................28

1 Applications

The portable test case, manufactured in accordance with “guidelines for equipment required for electrical installation operations”, is intended for use by qualified electricians for measuring and testing electrical devices after repair or modifications, as well as for periodic testing, in accordance with DIN VDE 0701-0702. According to these regulations, protective conductor resistance, insulation resistance, differential current, contact current and equivalent leakage current must be measured, and testing for the absence of voltage must be executed at user accessible conductive parts at data processing equipment and office machines.
Further applications for the substantiation of correct functioning of electrical equipment include the measurement of operating voltage and current consumption at devices under test. Beyond this, the protective conductor at the mains connection can be tested for the absence of voltage and line voltage can be measured. Extension cables can be tested after connecting the VL2 E accessory.

2 Safety Precautions

The test case is equipped with a METRATESTER 5+ test instrument, and has been manufactured and tested in accordance with the following regulations: IEC 61010-1,
DIN EN 61010-1, VDE 0411-1 “Regulations for electronic testers and controllers,
Part 1: safety measures for electronic measuring instruments”
and DIN VDE 0404 “Devices for technical safety testing of electrical equipment, part 1:
General requirements, and part 2: Devices for periodic testing”
If used for its intended purpose, safety of the test case and of the user is assured. Their safety is however not guaranteed, if the test case is used improperly or handled carelessly.
In order to maintain flawless technical safety conditions, and to assure safe use, it is imperative that you read these operating instructions thoroughly and carefully before placing the test case into service, and that you follow all instructions contained herein.
4 GMC-I Messtechnik GmbH
Observe the following safety precautions:
Attention!
!
• Measurements within electrical systems are prohibited!
The test case may only be connected to 230/400 V mains system with 50 Hz and a 16 A fuse via the 5-pole (23) or 3-pole (22) mains cable.
• In order to avoid undesired shutdown in the event of a defective device under test, the mains outlets should be separately fused if at all possible! A defect in the DUT may trip the mains power RCD (residual current circuit breaker), and thus cause a service interruption. If DUTs are being tested which cannot be disconnected from the mains intermittently, an RCD (residual current circuit breaker) can also trip the power supply circuit (test per section 6.4.1). The manufacturer of the test case assumes no liability for loss of data or other damage which results from its use.
• Be prepared for the occurrence of unexpected voltages at devices under test. For example, capacitors may be dangerously charged.
• If the test case is connected via the earthing contact mains adapter, phase conductor L1 may be connected to the N safety socket if poled accordingly! If this is the case, reverse polarity of the plug at the mains adapter (see section 4.1).
• Before connecting the device under test to the test case, subject it to a thorough visual inspection first. Devices under test with visibly damaged insulation must be repaired before metrological testing is performed.
• If the test case and/or its connector cables demonstrate visible damage, no longer function, have been stored for a lengthy period of time under unfavorable conditions or have been subjected to excessive stress during transport, it must be assumed that hazard-free operation is no longer possible. If this is the case, remove the test case from service and secure it against inadvertent use, for example by locking it up.
The NETZ-VDE switch (2) may only be set to the “NETZ” (mains) position after devices under test with a protective conductor have passed the protective conductor test.
For reasons of safety, the device under test must be turned off before switching to “Netz” (mains), so that dangerous devices under test (e.g. a circular saw) can only be switched on intentionally.
• Due to the fact that the test case is laid out in accordance with DIN VDE 0404, the “PE” safety socket and the “PE” contacts in the outlet may only be connected to the mains protective conductor after the NETZ-VDE switch has been set to the “Netz” (mains) position.
• In order to assure compliance with technical safety requirements, the test case may only be repaired by a qualified electrician, who is preferably employed by the manufacturer.
Before opening the test case in order to carry out repairs, it must be disconnected from the mains by pulling the plug from the electrical outlet.
• Disconnect the test case from the mains whenever work is interrupted and secure it against unauthorized use, for example by locking the cover.
• Use recommended accessories only!
GMC-I Messtechnik GmbH 5
Meaning of Symbols on the Instrument
!
Warning concerning a source of danger (attention: observe documentation!)
EC label of conformity
This device may not be disposed of with the trash. Further information regarding the WEEE mark can be accessed on the Internet at www.gossenmetrawatt.com by entering the search term WEEE.

3 Standard Equipment and Accessories

Scope of Delivery
1 test case 2 mains cables (Schuko and CEE16A) 1 measurement cable with test probe, 1 alligator clip 1 set of operating instructions
Accessories
SECU-cal 10 calibration adapter (M662A) VL2 E test adapter for testing cables (Z745W)

4 Connecting the Test Case to the Mains and Testing the Mains Connection

4.1 Connecting the Test Case

Set the switches as follows before connecting to the mains: Set the NETZ–VDE switch (1) to “NETZ”, set the METRATESTER 5 + measuring function selector switch (6) to “250 V”, set the polarity reversing switch (14) to “1”, set the L1-L2-L3
measuring selector switch (2) to “L1” and then connect the test case to the mains. Set the mains switch (9) and the RCD (residual current circuit breaker) (12) to “EIN” (on). According to the manufacturer, the emergency stop switch may generate minor humming noises with the U coil in certain armature positions. If this is the case, quickly turn the emergency stop switch on and off several times. When connected via the 5-pole CEE mains adapter (23), indicator lamps L1, L2 and L3 (19) must light up, and when connected via the earthing contact mains adapter (22), only indicator lamp L1 should light up. Mains polarity is tested for this type of connection, i.e. if lamp L1 does not light up, the polarity of the earthing contact plug must be reversed in the mains outlet.
If this is not the case, immediately disconnect the test case from the mains.
The fault at the mains connection or the test case must be eliminated before executing any tests.

4.2 Testing Protective Conductor Potential

Touch the contact surface (7) with your finger, and touch a grounded object at the same time (e.g. a water pipe). The PE indicator lamp may not light up! If this is the case, potential between the protective conductor at the mains plug (22/23) and the contact surface (7) is  100 V.
6 GMC-I Messtechnik GmbH
When connected via the 5-pole CEE mains plug (23), indicator lamps L1, L2 and L3 (19)
Note!
Attention!
!
Note!
must light up. When connected via the earthing contact mains adapter (22), only indicator lamp L1 should light up. Mains polarity is tested for this type of connection, i.e. if lamp L1 does
not light up, the polarity of the earthing contact plug must be reversed in the mains outlet. If this is not the case, immediately disconnect the test case from the mains. The fault at the mains connection
or the test case must be eliminated before executing any further tests. If the PE signal lamp lights up when you touch the contact surface (7), potential between the protective conductor at the mains plug (22/23) and the contact surface (7) is  25 V, i.e. the protective conductor is conducting voltage.
Depending upon handling, potential transfer may occur which causes the PE signal lamp to light up. For example, this could be the case if you touch a device under test with the NETZ-VDE switch (1) in the “VDE” position, thus creating a capacitive voltage divider.
If, while testing protective conductor potential, you determine that the mains protective conductor is conducting voltage, no measurements may be performed with the test case. If this is the case, potentially dangerous voltage is also present at the user accessible earthing contacts at the outlets, the “PE” socket (20) and the jack (4). Immediately disconnect the test case from the mains and arrange to have the fault eliminated at the mains connection. Voltage in the mains protective conductor also results in incorrect measured values when testing for the absence of voltage in accordance with DIN VDE 0701-0702 (see section 6.4.1).

4.3 Measuring Line Voltage

Set the measuring function selector switch (6) to “250 V~”.
• If connected via the 5-pole CEE mains adapter, set the measuring selector switch (2) to the L1, L2 and L3 settings, one after the other, and if connected via the earthing contact mains adapter set the switch to L1 and read the measured value from the LCD panel for each switch setting. Line voltage must always lie within the permissible range of 207 to 253 V.
If line voltage is present, values are displayed at the with the measuring function selector switch (6) in each of its respective positions, even if no device under test has been connected. The display of such numbers indicates that line voltage is present, regardless of the position to which the measuring function selector switch (6) has been set. If the selector switch has been set to “250 V~”, these numbers represent the actual line voltage value. In all other detented switch positions – if no device under test has been connected – these numbers do not represent actual measured values.
If the test case has been connected via the earthing contact mains adapter, all tests and measurements can be performed except tests at 3-phase current devices under mains operating conditions.
GMC-I Messtechnik GmbH 7

5 Connecting the DUT to the Test Case

Mains Connection Sockets
Switch the DUT on!
Either
Depending upon its plug, con­nect the DUT to one of the out­lets, or to the connector sockets in the case of loose wire ends.
It is absolutely mandatory to execute the tests in the order in which they are specified here!
1 Visual inspection 2 Measurement of protective conductor resistance for protection class I devices 3 Measurement of insulation characteristics if technically feasible, i.e. if the DUT does not
include any electrically actuated, all-pole switches: – Insulation resistance followed by protective conductor or equivalent leakage current – Otherwise: leakage current during operation, differential current, protection class I
devices
Contact current for protection class II devices Safety extra-low voltage (only at point of connection of safety extra-low voltage
generated in the DUT) 4 Function Test 5 Labeling inspection 6 Documentation

5.1 Protection Class I Devices

8 GMC-I Messtechnik GmbH

5.2 Protection Class II and III Devices

Connect the DUT, for example to the earthing contact outlet, or to the connec­tor sockets in the case of loose wire ends.
Switch the DUT on!
Mains Connection Sockets
To Accessible Metal Parts
Either
Mains Connection Sockets
Switch the DUT on!
Either

5.3 Devices with Single or Multi-Phase Connection without Plug

GMC-I Messtechnik GmbH 9
Loading...
+ 19 hidden pages