Gorman-Rupp Pumps PA6A60-4045D User Manual

Page 1
ACDE
PUBLICATION NUMBER OM−04402
January 29, 1996
Rev. F 01-11-05
SERIES PUMPS
(Including 60-Series Pump End)
THE GORMAN-RUPP COMPANY D MANSFIELD, OHIO
GORMAN-RUPP OF CANADA LIMITED D ST. THOMAS, ONTARIO, CANADA Printed in U.S.A.
www.gormanrupp.com
ECopyright by the Gorman-Rupp Company
Page 2
The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Page 3
OM−04402 PA SERIES PUMPS

INTRODUCTION

Thank You for purchasing a Gorman-Rupp Prime-
AireT priming-assisted pump. Read this manual carefully to learn how to safely install and operate your pump. Failure to do so could result in personal injury or damage to the pump.
A set of manuals accompanies your pump. Each set consists of three parts; the Installation/Opera­tion Manual contains essential information on in­stalling and operating the pump. However, since pump installations are seldom identical, some of the information only summarizes general recom­mendations and practices required to inspect, po­sition, and arrange the pump and piping.
The Parts List Manual provides a performance curve, pump model cross-section drawing, and parts list for your pump.
The Maintenance and Repair Manual provides troubleshooting and maintenance instructions re­quired to properly diagnose operational problems, and to service the pump components.
This pump is a PA Series, priming-assisted centrif­ugal model. The unit is designed for handling non­volatile, non-flammable liquids containing speci­fied entrained solids.
Because pump installations are seldom identical, this manual cannot possibly provide detailed in­structions and precautions for every aspect of each specific application. Therefore, it is the re­sponsibility of the owner/installer of the pump to ensure that applications not addressed in this manual are performed only after establishing that neither operator safety nor pump integrity are com­promised by the installation. Pumps and related equipment must be installed and operated ac­cording to all national, local and industry stan­dards.
If there are any questions regarding the pump which are not covered in this manual or in other lit­erature accompanying the unit, please contact your Gorman-Rupp distributor or the Gorman­Rupp Company:
The Gorman-Rupp Company
P.O. Box 1217
Mansfield, Ohio 44901−1217
Phone: (419) 755−1011
or:
Gorman-Rupp of Canada Limited
70 Burwell Road
St. Thomas, Ontario N5P 3R7
Phone: (519) 631−2870
CONTENTS
SAFETY − SECTION A INSTALLATION − SECTION B
PREINSTALLATION INSPECTION PAGE B − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
POSITIONING PUMP PAGE B − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SUCTION AND DISCHARGE PIPING PAGE B − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SUCTION LINES PAGE B − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISCHARGE LINES PAGE B − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ALIGNMENT PAGE B − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATION − SECTION C
OPERATION OF MOTOR DRIVEN UNITS PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATION OF ENGINE DRIVEN UNITS PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATIONAL CHECKS (All Models) PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STOPPING (Motor Driven Units) PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STOPPING (Non-Auto-Start Engine Driven Units) PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STOPPING (Auto-Start Engine Driven Units) PAGE C − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERIODIC CHECKS (All Models) PAGE C − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERIODIC CHECKS (Engine Driven Units) PAGE C − 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COLD WEATHER PRESERVATION (All Models) PAGE C − 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PAGE I − 1INTRODUCTION
Page 4
OM−04402PA SERIES PUMPS
RECORDING MODEL AND
WARRANTY INFORMATION
SERIAL NUMBERS
Please record the model and serial number for your Gorman-Rupp Prime-AireT priming-assisted pump in the spaces provided below. Your Gorman­Rupp distributor needs this information when you require parts or service.
Model:
Serial Number:
The following are used to alert personnel to procedures which require special attention, to those which could damage equipment, and to those which could be dangerous to personnel:
Immediate hazards which WILL result in severe personal injury or death. These instructions describe the procedure re­quired and the injury which will result from failure to follow the procedure.
The warranty provided with your Prime-AireT pri­ming-assisted pump is part of Gorman-Rupp’s support program for customers who operate and maintain their equipment as described in this and the other accompanying literature. Please note that should the equipment be abused or modified to change its performance beyond the original fac­tory specifications, the warranty will become void and any claim will be denied.
Hazards or unsafe practices which COULD result in minor personal injury or product or property damage. These instructions de­scribe the requirements and the possible damage which could result from failure to follow the procedure.
Hazards or unsafe practices which COULD result in severe personal injury or death. These instructions describe the procedure required and the injury which could result from failure to follow the procedure.
NOTE
Instructions to aid in installation, operation, and maintenance or which clarify a procedure.
PAGE I − 2 INTRODUCTION
Page 5
PA SERIES PUMPS
OM−04402

SAFETY - SECTION A

This information applies to Prime AireR Series pumps. Refer to the manual ac­companying the engine or power source before attempting to begin oper­ation.
Because pump installations are seldom identical, this manual cannot possibly provide detailed instructions and pre­cautions for each specific application. Therefore, it is the owner/installer’s re­sponsibility to ensure that applications not addressed in this manual are per­formed only after establishing that nei­ther operator safety nor pump integrity are compromised by the installation.
Before attempting to open or service the pump:
1. Familiarize yourself with this man­ual.
2. Shut down the engine and discon­nect the positive battery cable, or lock out incoming power to the mo­tor and take precautions to ensure that the pump will remain inopera­tive.
3. Allow the pump to completely cool if overheated.
4. Check the temperature and make sure the pump is cool before open­ing any covers, plates, or plugs.
5. Close the suction and discharge valves.
6. Vent the pump slowly and cau­tiously.
7. Drain the pump.
ing away from the unit to prevent injury during automatic operation. Disconnect the positive battery cable before per­forming any maintenance. Failure to do so may result in serious personal injury.
This pump is designed to handle most non-volatile, non-flammable liquids containing specified entrained solids. Do not attempt to pump volatile, corro­sive, or flammable liquids which may damage the pump or endanger person­nel as a result of pump failure.
Use lifting and moving equipment in good repair and with adequate capacity to prevent injuries to personnel or dam­age to equipment. Attach lifting equip­ment to the lifting device fitted to the pump. If chains or cable are wrapped around the pump to lift it, make certain that they are positioned so as not to damage the pump, and so that the load will be balanced. The bail is intended for use in lifting the pump assembly only. Suction and discharge hoses and pip­ing must be removed from the pump be­fore lifting.
After the pump has been installed, make certain that the pump and all piping or hose connections are tight, properly supported and secure before operation.
If the pump is equipped with the auto­matic starting system, it is subject to au­tomatic restart. Keep hands and cloth-
Do not operate the pump against a closed discharge valve. If operated
PAGE A − 1SAFETY
Page 6
against a closed discharge valve, pump components will deteriorate, and the liquid could come to a boil, build pres­sure, and cause the pump casing to rup­ture or explode. Momentary closure of a discharge valve is acceptable only when required for startup or shutdown procedures.
Do not remove plates, covers, gauges, pipe plugs, or fittings from an over­heated pump. Vapor pressure within the pump can cause parts being disen­gaged to be ejected with great force. Al­low the pump to cool completely before servicing.
PA SERIES PUMPSOM−04402
Make sure the pump is level. Lower jack stands and chock the wheels, if so equipped. Use caution when positioning the skid-mounted unit to prevent damage to the fuel tank.
Do not operate an internal combustion engine in an explosive atmosphere. When operating an internal combustion engine in an enclosed area, make sure exhaust fumes are piped to the outside. These fumes contain carbon monoxide, a deadly gas that is colorless, tasteless and odorless.
This pump is may be used to handle ma­terials which could cause illness through direct exposure or emitted fumes. Wear adequate protective cloth­ing when working on the pump or pip­ing.
Do not operate the pump without guards in place over the rotating parts. Ex­posed rotating parts can catch clothing, fingers or tools, causing severe injury to personnel.
Fuel used by internal combustion en­gines presents an extreme explosion and fire hazard. Make certain that all fuel lines are securely connected and free of leaks. Never refuel a hot or run­ning engine. Avoid overfilling the fuel tank. Always use the correct type of fuel.
Never tamper with the governor to gain more power. The governor establishes safe operating limits that should not be exceeded. Refer to the Performance Curve in the Parts List Manual for the maximum continuous operating speed for this pump.
PAGE A − 2 SAFETY
Page 7
PA SERIES PUMPS OM−04402
INSTALLATION − SECTION B
Review all SAFETY information in Section A.
Since pump installations are seldom identical, this section offers only general recommendations and practices required to inspect, position, and ar­range the pump and piping.
Most of the information pertains to a standard static lift application where the pump is positioned above the free level of liquid to be pumped.
If installed in a flooded suction application where the liquid is supplied to the pump under pressure, some of the information such as mounting, line configuration, and priming must be tailored to the specific application. Since the pressure supplied to the pump is critical to performance and safety, be sure to limit the incoming pressure to 50% of the maximum permissible operating pressure as shown on the pump performance curve.
Only operate this pump in the direction in­dicated by the arrow on the pump body and on the accompanying decal. Other­wise, the impeller could become loosened from the shaft and seriously damage the pump.
d. Check levels and lubricate as necessary. Re-
fer to LUBRICATION in the Maintenance and Repair Manual and perform duties as in­structed.
e. If the pump has been stored for more than 12
months, some of the components or lubri­cants may have exceeded their maximum shelf life. These must be inspected or re- placed to ensure maximum pump service.
For further assistance, contact your Gorman-Rupp distributor or the Gorman-Rupp Company.
PREINSTALLATION INSPECTION
The pump assembly was inspected and tested be­fore shipment from the factory. Before installation, inspect the pump for damage which may have oc­curred during shipment. Check as follows:
a. Inspect the pump for cracks, dents, damaged
threads, and other obvious damage.
b. Check for and tighten loose attaching hard-
ware. Since gaskets tend to shrink after dry­ing, check for loose hardware at mating sur­faces.
c. Carefully read all tags, decals, and markings
on the pump assembly, and perform all duties indicated. Note that the pump shaft rotates in the required direction.
If the maximum shelf life has been exceeded, or if anything appears to be abnormal, contact your Gorman-Rupp distributor or the factory to deter­mine the repair or updating policy. Do not put the pump into service until appropriate action has been taken.
Battery Installation (Engine Driven Units)
Unless otherwise specified on the pump order, the engine battery is not included with engine driven units.
Refer to the information accompanying the battery and/or electrolyte solution for activation and charg­ing instructions.
Before installing the battery, clean the positive and negative cable connectors, and the battery termi­nals. Secure the battery by tightening the holddown brackets. The terminals and clamps may be coated with petroleum jelly to retard corro­sion. Connect and tighten the positive cable first, then the negative cable.
PAGE B − 1INSTALLATION
Page 8
OM−04402 PA SERIES PUMPS
POSITIONING PUMP
Use lifting and moving equipment in good repair and with adequate capacity to prevent injuries to personnel or dam­age to equipment. Attach lifting equip­ment to the lifting device fitted to the pump. If chains or cable are wrapped around the pump to lift it, make certain that they are positioned so as not to damage the pump, and so that the load will be balanced. The bail is intended for use in lifting the pump assembly only. Suction and discharge hoses and pip­ing must be removed from the pump be­fore lifting.
Lifting
Use lifting and moving equipment with a capacity of at least 5 times the weight of the pump, not in­cluding the weight of any customer installed ac­cessories. Customer-installed equipment such as suction and discharge piping must be removed before attempting to lift. Contact the factory or the Pump Specification Data Sheet for the approxi­mate weight of your pump.
If the pump has been mounted on a moveable base, make certain the base is stationary by setting the brake and blocking the wheels before attempt­ing to operate the pump.
If the pump has been mounted on a mov­able base, do not attempt to operate the pump unless the unit is level. Be sure the leveling stands are positioned on a solid surface, and the wheels are chocked.
SUCTION AND DISCHARGE PIPING
Pump performance is adversely effected by in­creased suction lift, discharge elevation, and fric­tion losses. See the Performance Curve in the Parts List Manual to be sure your overall application al­lows pump to operate within the safe operation range.
Materials
Either pipe or hose maybe used for suction and discharge lines; however, the materials must be compatible with the liquid being pumped. If hose is used in suction lines, it must be the rigid-wall, rein­forced type to prevent collapse under suction. Us­ing piping couplings in suction lines is not recom­mended.
Line Configuration
The pump assembly can be seriously damaged if the chains or cables used to lift and move the unit are improperly wrapped around the pump.
Mounting
Locate the pump in an accessible place as close as practical to the liquid being pumped. Level mount­ing is essential for proper operation. The pump may have to be supported or shimmed to provide for level operation and eliminate vibration.
For engine driven units, the pump must be posi- tioned as level as possible to ensure sufficient lubri­cation and fuel supply to the engine.
PAGE B − 2 INSTALLATION
Keep suction and discharge lines as straight as possible to minimize friction losses. Make mini­mum use of elbows and fittings, which substan­tially increase friction loss. If elbows are necessary, use the long-radius type to minimize friction loss.
Connections to Pump
Before tightening a connecting flange, align it ex­actly with the pump port. Never pull a pipe line into place by tightening the flange bolts and/or cou­plings.
Lines near the pump must be independently sup­ported to avoid strain on the pump which could
Page 9
PA SERIES PUMPS OM−04402
cause excessive vibration, decreased bearing life, and increased shaft and seal wear. If hose-type lines are used, they should have adequate support to secure them when filled with liquid and under pressure.
Gauges
The pump is drilled and tapped for installing dis­charge pressure and vacuum suction gauges. It is recommended that gauges be installed to monitor pump performance. Seal the gauge threads with pipe dope to ensure an airtight seal. Follow the sealant manufacturer’s recommendations when selecting and applying the pipe dope. The pipe dope should be compatible with the liquid being pumped.
SUCTION LINES
To avoid air pockets which could affect pump prim­ing, the suction line must be as short and direct as possible. When operation involves a suction lift, the line must always slope upward to the pump from the source of the liquid being pumped; if the line slopes down to the pump at any point along the suction run, air pockets will be created.
larger than the solids handling capability of the pump.
Consult the pump Specification Data Sheet or the factory for the solids handling capabilities of your pump.
Sealing
Since even a slight leak will affect priming, head, and capacity, especially when operating with a high suction lift, all connections in the suction line should be sealed with pipe dope to ensure an air­tight seal. Follow the sealant manufacturer’s rec­ommendations when selecting and applying the pipe dope. The pipe dope should be compatible with the liquid being pumped.
Suction Lines In Sumps
If a single suction line is installed in a sump, it should be positioned away from the wall of the sump at a distance equal to 1 1/2 times the diame­ter of the suction line.
If there is a liquid flow from an open pipe into the sump, the flow should be kept away from the suc­tion inlet because the inflow will carry air down into the sump, and air entering the suction line will re­duce pump efficiency.
Fittings
Suction lines should be the same size as the pump inlet. If reducers are used in suction lines, they should be the eccentric type, and should be in­stalled with the flat part of the reducers uppermost to avoid creating air pockets. Valves are not nor­mally used in suction lines, but if a valve is used, install it with the stem horizontal to avoid air pock­ets.
Strainers
Be certain to use the strainer furnished with the pump; any spherical solids which pass through the strainer will also pass through the pump itself.
If a strainer not furnished with the pump is installed by the pump user, make certain that the total area of the openings in the strainer is at least three or four times the cross section of the suction line, and that the openings will not permit passage of solids
If it is necessary to position inflow close to the suc­tion inlet, install a baffle between the inflow and the suction inlet at a distance 1-1/2 times the diameter of the suction pipe. The baffle will allow entrained air to escape from the liquid before it is drawn into the suction inlet.
If two suction lines are installed in a single sump, the flow paths may interact, reducing the efficiency of one or both pumps. To avoid this, position the suction inlets so that they are separated by a dis­tance equal to at least 3 times the diameter of the suction pipe.
Suction Line Positioning
The depth of submergence of the suction line is
critical to efficient pump operation. Figure B−1
shows recommended minimum submergence vs. velocity.
Although not recommended, the vacuum assisted priming feature allows the pump to be operated
PAGE B − 3INSTALLATION
Page 10
OM−04402 PA SERIES PUMPS
temporarily in a slurping" application with varying water levels.
NOTE
The pipe submergence required may be reduced
by installing a standard pipe increaser fitting at the end of the suction line. The larger opening size will reduce the inlet velocity. Calculate the required submergence using the following formula based on the increased opening size (area or diameter).
Figure B−1. Recommended Minimum Suction Line Submergence vs. Velocity
DISCHARGE LINES
Siphoning
Do not terminate the discharge line at a level lower than that of the liquid being pumped unless a si­phon breaker is used in the line. Otherwise, a si­phoning action causing damage to the pump could result.
Valves
This pump is designed with a check valve in the discharge line.
If a throttling valve is desired in the discharge line, use a valve as large as the largest pipe to minimize friction losses. Never install a throttling valve in a suction line.
With high discharge heads, it is recommended that a throttling valve be installed in the discharge line to protect the pump from excessive shock pres­sure and reverse rotation when it is stopped.
If the application involves a high discharge head, gradually close the discharge throttling valve before stopping the pump.
ALIGNMENT
Engine Driven Units
The alignment of the pump, air compressor and engine is critical for trouble-free mechanical opera-
PAGE B − 4 INSTALLATION
Page 11
PA SERIES PUMPS OM−04402
tion. Refer to the Maintenance and Repair Manual for detailed alignment information.
Basic and Motor Driven Units
The alignment of the pump and its power source is critical for trouble-free mechanical operation. In either a flexible coupling or V-belt driven system, the driver and pump must be mounted so that their shafts are aligned with and parallel to each other. It is imperative that alignment be checked after the pump and piping are installed, and before opera­tion.
NOTE
Check Rotation, Section C, before final alignment of the pump.
When mounted at the Gorman-Rupp factory, driver and pump are aligned before shipment. Misalign­ment will occur in transit and handling. Pumps must be checked and realigned before operation. Before checking alignment, tighten the foundation bolts. The pump casing feet and/or pedestal feet, and the driver mounting bolts should also be tightly secured.
Most couplings require a specific gap or clearance between the driving and the driven shafts. Refer to the coupling manufacturer’s service literature.
Align spider insert type couplings by using calipers to measure the dimensions on the circumference of the outer ends of the coupling hub every 90 de­grees. The coupling is in alignment when the hub ends are the same distance apart at all points (see Figure B−2).
Figure B−2. Alignment of V-Belt Driven Pumps
Align non-spider type couplings by using a feeler gauge or taper gauge between the coupling halves every 90 degrees. The coupling is in alignment when the hubs are the same distance apart at all points (see Figure B−3).
When checking alignment, disconnect the power source to ensure that the pump will remain inoperative.
Adjusting the alignment in one direction may alter the alignment in another direc­tion. Check each procedure after altering alignment.
Coupled Drives
When using couplings, the axis of the power source must be aligned to the axis of the pump shaft in both the horizontal and vertical planes.
Figure B−3. Alignment of V-Belt Driven Pumps
Check parallel adjustment by laying a straightedge across both coupling rims at the top, bottom, and side. When the straightedge rests evenly on both halves of the coupling, the coupling is in horizontal parallel alignment. If the coupling is misaligned, use a feeler gauge between the coupling and the straightedge to measure the amount of misalign­ment.
PAGE B − 5INSTALLATION
Page 12
OM−04402 PA SERIES PUMPS
V-Belt Drives
When using V-belt drives, the power source and the pump must be parallel. Use a straightedge along the sides of the pulleys to ensure that the pul­leys are properly aligned (see Figure B−4). In drive systems using two or more belts, make certain that the belts are a matched set; unmatched sets will cause accelerated belt wear.
MISALIGNED:
SHAFTS
NOT PARALLEL
MISALIGNED:
SHAFTS
NOT IN LINE
ALIGNED: SHAFTS
PARALLEL AND
SHEAVES IN LINE
Figure B−4. Alignment of V-Belt Driven Pumps
Tighten the belts in accordance with the belt manu­facturer’s instructions. If the belts are too loose, they will slip; if the belts are too tight, there will be excessive power loss and possible bearing failure. Select pulleys that will match the proper speed ra­tio; overspeeding the pump may damage both pump and power source.
Do not operate the pump without a guard in place over the rotating parts. Exposed rotating parts can catch cloth­ing, fingers, or tools, causing severe in­jury to personnel.
Refer to the information which follows for installa­tion details for the liquid level sensing system pro­vided with your pump.
Float Switch Installation
The Float Switch autostart system employs either a single or double float switch, where a bulb raises or lowers (floats) with the liquid level, thus activating an enclosed miniature switch. The floats are equipped with a socket type connector that plugs into a matching receptacle on the auto-start control box.
Standard floats are equipped with 50 feet (15,2 m) of cable.
When installing the floats, note the following:
a. Be sure to provide sufficient room in the wet
well or sump so that floats do not get ob­structed or drawn into the suction line. If a flex­ible suction hose is used, it may be extended to lay along the bottom of the wet well or sump and the float can be attached to the hose above the point where it bends along the bot­tom. Direct the suction line toward the flow, and the float(s) away from the flow. If a stand­pipe is available, attach the float switch cable to the standpipe in the sump at the approxi­mate desired liquid level.
b. In a single float system, the cable can be teth-
ered to the suction line or standpipe approxi­mately 6 inches (152 mm) above the float. This setting allows approximately 9 inches (229 mm) of liquid rise between pump start/ stop. The start/stop interval may be increased by extending the float end of the cable. The liquid level in the sump will increase approxi­mately 8 inches (203 mm) between start/stop intervals for every 6 inches (152 mm) of cable increase.
c. If a double float switch system is used, posi-
AUTO-START
The standard pump is equipped with an auto-start
tion the Start" float at the desired high water level in the sump, and the Stop" float at the desired low water level in the pump.
control system which allows the pump to start and stop as the liquid level in the wet well or sump rises and falls.
d. Refer to Figure B−5 for additional float switch
data.
PAGE B − 6 INSTALLATION
Page 13
PA SERIES PUMPS OM−04402
ENGINE
CONTROL
BOX
ON
(Emptying)
OFF
(Filling)
OPERATING
CABLE
TETHER
RANGE
(See Table Below)
POINT
OFF
(Emptying)
1.25" Pipe (Not Furnished)
ON
(Filling)
Figure B−5. Float Switch Data
Submersible Transducer Installation
The Electronic Pressure Switch (EPS) autostart system employs a submersible transducer level sensor with 75 feet (22,9 m) of signal cable con­nected to the EPS.
The transducer sensor converts pressure to an electrical signal proportional to liquid level. This electrical signal is distributed to the digital display on the EPS through a scaling circuit which con­verts the electrical signal to feet of water".
3.0
(0.9)
2.5
(.76)
2.0
(0.6)
1.5
(.46)
1.0
(0.3)
0.5
(.15)
1.0
(0.3)
APPROXIMATE FREE CORD LENGTH IN FT. (M)
2.0
(0.6)
3.0
(0.9)
c. Allow slack in the signal cable so that the sen-
sor weight does not pull on the connection.
d. The wet well or sump must be vented to atmo-
sphere.
e. The EPS is scaled in feet of water column. If
the measured medium is other than 1.0 spe­cific gravity, the reading on the EPS should be divided by the specific gravity of the mea­sured medium to obtain the actual level.
4.0
(1.2)
When installing the transducer sensor, note the fol­lowing:
a. Handle the signal cable and transducer sen-
sor with care during installation. Carefully lower the sensor into the wet well or sump; do not drop it to the bottom. To avoid clogging, suspend the sensor off the bottom.
b. Be sure to provide sufficient room in the wet
well or sump so that the sensor does not get drawn into the suction line. To prevent this, a flexible suction hose may be extended to lay along the bottom of the wet well or sump. The sensor can then be attached to the hose above the point where it bends along the bot­tom. See Figure B−6 for a typical installation.
f. Thoroughly clean the sensor after each use
to prevent clogging.
Do not disassemble the transducer sensor or loosen the compression nut at the signal cable entry. This will void warranty. There are no user-serviceable parts inside. Do not nick or cut the jacket of the signal cable; this will cause leakage and void warranty. Connect the signal cable only to the EPS terminals for this purpose and to no other power source.
PAGE B − 7INSTALLATION
Page 14
OM−04402 PA SERIES PUMPS
SUCTION
DISCHARGE
LINE
LINE
SIGNAL CABLE
(ATTACH TO
SUCTION LINE)
SUCTION
SUBMERSIBLE
TRANSDUCER
(DOWNSTREAM
FROM SUCTION)
STRAINER
Figure B−6. Submersible Transducer AutoStart Pump Installation
Transducer Connections
The submersible transducer sensor cable is facto­ry-equipped with a female connector which mates with a male connector on the back of the EPS con­trol. If removal or replacement of the female con-
FLOW
nector is required, reconnect the cable to the con­nector as shown in Figure B−7.
Once the connections are made, simply plug the female connector into the male connector on the back of the EPS, and refer to Section C for opera­tional procedures.
PAGE B − 8 INSTALLATION
Page 15
PA SERIES PUMPS OM−04402
+ BATT
BATT
SHIELD
MOTOR
RUN
+
+ TEMP
RELAY
TRANSDUCER
SHD −V +VSIG
SHIELD
BLACK
A
MALE
TRANSDUCER
CONNECTOR
FEMALE
TRANSDUCER
CONNECTOR
RED
WHITE
TRANSDUCER
RELAY
B
HORN
RELAY
CAUTION−
THIS COVER PLATE MUST
SENSOR
CABLE
BE INSTALLED FOR PROPER
CONTROL OPERATION
Figure B−7. Back Side of Transducer Showing Sensor Cable Connections
PAGE B − 9INSTALLATION
Page 16
PA SERIES PUMPS
OM−04402
OPERATION − SECTION C
Review all SAFETY information in Section A.
Follow the instructions on all tags, labels and decals attached to the pump.
This pump is designed to handle most non-volatile, non-flammable liquids containing specified entrained solids and corrosives. Do not attempt to pump volatile, corrosive, or flammable liquids which may damage the pump or endan­ger personnel as a result of pump fail­ure.
Pump speed and operating condition points must be within the continuous per­formance range shown on the Perfor­mance Curve in the separate Parts List Manual.
OPERATION OF ELECTRIC MOTOR DRIVEN UNITS
Component Function
The control box contains the following hand-oper­ated switches and controls:
D The control handle operates the control
box circuit breakers. In the OFF position, the control handle opens the circuit breakers to interrupt incoming power through the con­trol box and prevent pump operation. In the ON position, it closes the circuit breakers to permit pump operation. The circuit breakers will open or trip" automatically in the event of a short circuit overload current. When tripped, move the control handle to OFF and back to ON to reset the circuit breakers.
D The selector switch controls the mode of
operation. In the OFF position, it prevents all operation of the pump. In the HAND posi­tion, it allows the pump to run continuously. In the AUTO position, it allows the pump to be controlled automatically by the float switch liquid level control system.
D The reset pushbutton resets the motor over-
load after it has been TRIPPED by an over­load. The overload relay will trip automatical­ly if the current drawn by the motor exceeds design specifications. Allow 10 seconds for the relay to cool after tripping before press­ing the reset.
If replacing the heater pack, press the reset button to set the relay.
Control Box Function
If the circuit breaker trips, do not reset it immedi-
The control box is provided to facilitate operation of the pump. It contains controls for starting and stop­ping the pump, and the low voltage circuitry used for operating the automatic liquid level system.
The control box provides overload pro­tection and power control. Do not con­nect the pump motor directly to the in­coming power lines.
OPERATION PAGE C − 1
ately. Wait at least ten minutes before resetting the control handle back to the ON position. If the over­load unit continues to trip, operational problems ex­ist.
The pump motor will restart as soon as the RESET pushbutton is pressed, un­less the selector switch is in the OFF po­sition. Turn the selector switch to OFF
NOTE
Page 17
OM−04402 PA SERIES PUMPS
and move the control handle to OFF be­fore approaching the pump.
D The liquid level system operates in conjunc-
tion with the 3-position switch (HAND-OFF­AUTO) supplied as part of the system. After the float(s) have been installed as de­scribed in INSTALLATION, Section B, pump operation may be automatically con­trolled for filling or dewatering functions.
D The green run light indicates the pump is
running. The light will be energized when the 3-position switch is in the HAND position or when the pump is running with the switch in the AUTO position.
Always terminate incoming power to the control box before investigating control box circuitry prob­lems.
Always terminate power to the control box before performing service func­tions.
To check electric motor rotation, remove V-belts, couplings, or otherwise disconnect the pump from the motor before checking motor rotation. Operate the motor independently while observing the direc­tion of the motor shaft, or cooling fan.
If rotation is incorrect on a three-phase motor, have a qualified electrician interchange any two of the three phase wires to change direction.
Priming
The pump will begin to prime upon startup. The air in the suction line will be discharged from the educ­tor discharge line. Complete priming is indicated by a positive discharge pressure reading.
If full priming is not achieved, the discharge check valve may be malfunctioning. If this occurs, shut down the pump and consult the separate Mainte-
nance and Repair manual for further details.
OPERATION OF ENGINE DRIVEN UNITS
Before Starting
Power through the control box may be terminated by moving the control handle to the OFF position, thereby opening the circuit breakers. This stops the pump, but does not terminate incoming power through the field wiring connected to the control box.
Rotation
The correct direction of pump rotation is indicated by an arrow on the pump body or accompanying decals. If the pump is operated in the wrong direc­tion, the impeller could become loosened from the shaft and seriously damage the pump.
The pump must operate in the direction in­dicated by the arrow on the pump, or ac­companying decals. Reverse rotation could damage the pump and adversely af­fect performance.
Check the fuel level and oil levels in the engine, air compressor, pump bearings and seal housing.
Make sure the pump is level. Lower the jack stands and chock the wheels, if so equipped.
Make sure the pump is level. Lower jack stands and chock the wheels, if so equipped. Use caution when positioning the skid-mounted unit to prevent damage to the fuel tank.
Check to ensure that all guards are in place.
Do not operate the pump without guards in place over the rotating parts. Ex­posed rotating parts can catch clothing, fingers or tools, causing severe injury to personnel.
OPERATIONPAGE C − 2
Page 18
PA SERIES PUMPS
OM−04402
Close the pump drain.
Manual Starting
Consult the engine operation manual before at­tempting to start the unit.
Manual Starting (Deutz Powered Units)
On initial start-up, set the engine speed at the half­throttle position. Turn the keyswitch on the control box to the START" position until the engine starts. Release the key and the switch will return to the RUN" position.
After the engine starts and the unit is fully primed, adjust the engine RPM until the desired flow rate is achieved.
Automatic Starting
If the pump is equipped with the auto­matic starting system, it is subject to au­tomatic restart. Keep hands and cloth­ing away from the unit to prevent injury during automatic operation. Disconnect the positive battery cable before per­forming any maintenance. Failure to do so may result in serious personal injury.
Consult the engine operation manual before at­tempting to start the unit.
Automatic Starting (Deutz Powered Units)
If the unit is equipped with the autostart control sys­tem, install the float(s) as described in INSTALLA- TION, Section B.
Pump speed and operating condition points must be within the continuous per­formance range shown on the curve in the separate Parts List Manual accompanying the pump.
Manual Starting (John Deere Powered Units)
On initial start-up, set the engine speed at the half­throttle position. Turn the key switch on the control box to the MANUAL" position, then press and hold the ENTER" button until the engine starts.
After the engine starts and the unit is fully primed, adjust the engine RPM until the desired flow rate is achieved.
Follow the procedures outlined for manual starting and throttle adjustment, then turn the key to the AUTO START" position.
NOTE
For security purposes, the key can be removed with the switch in the AUTO START" position.
Press and hold the white AUTO" button on the control panel until the red AUTO" light illuminates. The auto-start system is now armed.
NOTE
The unit can continue to be started manually with the keyswitch in the AUTO START" position by pressing the white MAN" button on the control. The Single Lightning Bolt" light on the control will illu­minate in conjunction with an audible alarm before the unit starts. The unit can then be stopped manu­ally by pressing the OFF/SET" button.
Pump speed and operating condition points must be within the continuous per­formance range shown on the curve in the separate Parts List Manual accompanying the pump.
OPERATION PAGE C − 3
In the auto-start mode, the Single Lightning Bolt" light will illuminate in conjunction with an audible alarm when the liquid level in the sump or wet well rises and activates the float(s). The light will blink and the alarm will sound for approximately 8 sec­onds before the unit starts.
Page 19
OM−04402 PA SERIES PUMPS
When the liquid level in the sump or wet well is suffi­ciently pumped down, the unit will automatically shut down.
NOTE
If the keyswitch is moved to the OFF" position while in the auto-start mode, the engine will stop. However, the auto-start process will continue as soon as the keyswitch is moved back to the AUTO START" position. To cancel the auto-start process, press the OFF/SET" button.
The control panel is equipped with high oil temper­ature, low oil pressure, V-belt and start failure (3 at­tempts) safety shutdowns. If any of these problems occur, the red Double Lightning Bolt" light will illu­minate to indicate a system fault. When the prob­lem is corrected, press the OFF/SET" button to re­set the control.
NOTE
The OFF/SET" button has dual functionality when in program mode. If necessary, consult the factory for details on programming functions.
The unit can be started manually with the key­switch in the AUTO START" position by pressing the white MAN" button. The Single Lightning Bolt" light will illuminate in conjunction with an au­dible alarm before the unit starts.
before the unit starts. When the liquid is sufficiently pumped down, the unit will automatically shut down.
The unit can be stopped while in the AUTO" mode by moving the key switch to the OFF" position.
NOTE
If the key switch is moved to the OFF" position while in the AUTO" mode, the engine will stop. However, the auto-start process will continue as soon as the key switch is moved back to the AUTO" position.
The control panel is equipped with high oil temper­ature, low oil pressure, engine overspeed and en­gine overcrank safety shutdowns. If any of these problems occur, the engine will not start. When the problem is corrected, turn the key switch to the OFF" position to reset the control.
Priming
The pump will begin to prime upon startup. The air in the suction line will be discharged from the educ­tor discharge line. Complete priming is indicated by a positive discharge pressure reading.
If full priming is not achieved, the discharge check valve may be malfunctioning. If this occurs, shut down the pump and consult the separate Mainte- nance and Repair manual for further details.
Stop the unit manually by pressing the OFF/SET" button.
Automatic Starting (John Deere Powered Units With Float System)
If the unit is equipped with the autostart control sys­tem, install the float(s) as described in INSTALLA- TION, Section B.
Follow the procedures outlined for manual starting and adjust the throttle to the desired flow rate. Turn the key switch to OFF", then move it to the AUTO" position.
The pump will start automatically when the liquid level in the sump or wet well increases and the float(s) rise to the on" position. An alarm will sound and the control box will begin a countdown display
Routine Operation (All Engine Driven Models)
Do not operate an internal combustion engine in an explosive atmosphere. When operating an internal combustion engine in an enclosed area, make sure exhaust fumes are piped to the outside. These fumes contain carbon monoxide, a deadly gas that is colorless, tasteless and odorless.
Adjust the engine speed to achieve the desired output. Do not exceed the factory set engine speed and system operating pressure. Do not operate
OPERATIONPAGE C − 4
Page 20
PA SERIES PUMPS
OM−04402
below the recommended operating speed (if appli­cable).
Never tamper with the governor to gain more power. The governor establishes safe operating limits that should not be exceeded. Refer to the Performance Curve in the separate Parts List Manual for the maximum continuous operating speed for this pump.
Operation In Extreme Heat (Engine Driven Auto-Start Units)
OPERATIONAL CHECKS (All Models)
Leakage
Once the pump is fully primed, no leakage should be visible at pump mating surfaces, or at pump connections or fittings. Keep all line connections and fittings tight to maintain maximum pump effi­ciency.
Pump Vacuum Check
Read the vacuum gauge with the pump primed and at operation speed. Shut off the pump. The vacuum gauge reading will immediately drop pro­portionate to static suction lift, and should then sta­bilize. If the vacuum reading falls off rapidly after stabilization, an air leak exists. Before checking for the source of the leak, check the point of installa­tion of the vacuum gauge.
The safety shutdown system will automatically stop the unit if engine operating temperature ex­ceeds design limits. If engine over-temperature shutdown occurs, allow the unit to cool before re­starting.
If engine overheating continues, check the engine lubricant level and viscosity. Consult the engine operation manual for the recommended lubricant for operation in extreme heat.
If the unit is being operated in the automatic mode, adjust the float(s) to allow shorter run and longer cooling periods, if possible.
This pump is equipped with automatic liquid level controls, and is subject to automatic restart. Keep hands and clothing away from the unit to prevent injury during automatic operation. Dis­connect the battery before performing any maintenance. Failure to do so may result in serious personal injury.
Eductor Discharge Line
Check the eductor discharge line for liquid bypass. If bypass occurrs, shut down the pump. Refer to the Maintenance and Repair Manual, disassemble and clean the float and valve assembly inside the priming chamber.
Liquid Temperature And Overheating
Overheating can occur if operated with the valves in the suction or discharge lines closed. Operating against closed valves could bring the liquid to a boil, build pressure, and cause the pump to rup­ture or explode. If overheating occurs, stop the pump immediately and allow it to completely cool before servicing it. Approach any over-heated
pump cautiously.
Do not remove plates, covers, gauges, pipe plugs, or fittings from an over­heated pump. Vapor pressure within the pump can cause parts being disen­gaged to be ejected with great force. Al­low the pump to completely cool before servicing.
OPERATION PAGE C − 5
Page 21
OM−04402 PA SERIES PUMPS
Strainer Check
Check the strainer regularly, and clean it as neces­sary. The strainer should also be checked if pump flow rate begins to drop. Monitor and record the vacuum suction gauge readings regularly to detect strainer blockage.
Never introduce air or steam pressure into the pump casing or piping to remove a blockage. This could result in personal injury or damage to the equipment. If backflushing is absolutely neces­sary, liquid pressure must be limited to 50% of the maximum permissible operating pressure shown on the pump performance curve.
STOPPING (Electric Motor Driven Units)
Never halt the flow of liquid suddenly. If the liquid being pumped is stopped abruptly, damaging shock waves can be transmitted to the pump and piping system. Close all connecting valves slowly.
After stopping the pump, lock out incomming pow­er to ensure that the pump will remain inoperative.
STOPPING (Auto-Start Engine Driven Units)
Manual Stopping (Deutz Powered Units)
In the manual mode, reduce the throttle speed slowly, and allow the engine to idle briefly before switching the HAND-OFF-AUTO switch to ‘OFF’.
If the application involves a high discharge head, gradually close the discharge throttling valve before stopping the pump.
After stopping the pump, close and lock the control panel cover, or disconnect the positive battery cable to ensure that the pump will remain inopera­tive.
Manual Stopping (John Deere Powered Units)
Never halt the flow of liquid suddenly. If the liquid being pumped is stopped abruptly, damaging shock waves can be transmitted to the pump and piping system. Close all connecting valves slowly.
STOPPING (Non-Auto-Start Engine Driven Units)
Never halt the flow of liquid suddenly. If the liquid being pumped is stopped abruptly, damaging shock waves can be transmitted to the pump and piping system. Close all connecting valves slowly.
Reduce the throttle speed slowly and allow the en­gine to idle briefly before stopping.
If the application involves a high discharge head, gradually close the discharge throttling valve before stopping the pump.
After stopping the pump, switch off the engine igni­tion and remove the key to ensure that the pump will remain inoperative.
In the manual mode, reduce the throttle speed slowly, and allow the engine to idle briefly before switching the engine key switch to ‘OFF’.
If the application involves a high discharge head, gradually close the discharge throttling valve before stopping the pump.
After stopping the pump, close and lock the control panel cover, or disconnect the positive battery
cable to ensure that the pump will remain inopera­tive.
Automatic Stopping
In the automatic mode, the pump will stop when the liquid in the wet well or sump lowers and acti­vates the Off" float switch(s). The pump will restart automatically when the liquid rises and activates the On" float switch(s).
OPERATIONPAGE C − 6
Page 22
PA SERIES PUMPS
OM−04402
Safety Shutdown System
The unit is equipped with a safety system to auto­matically shut down the engine under certain con­ditions. The engine will automatically shut down:
1. If the engine exceeds its safe operating tem­perature.
2. If the engine oil pressure drops below design limits.
3. If the engine fails to start within a pre-set peri­od of time.
4. If the engine speed exceeds the safe operat­ing range.
5. If the engine fan belt breaks (Deutz powered units).
Lights on the control panel will indicate which of the safety features has caused the engine to shut down.
PERIODIC CHECKS (All Models)
Seal Cavity And Bearing Lubrication
Both the seal and bearing cavities were fully lubri­cated at the factory. Check the lubrication levels before startup, and regularly thereafter as indi­cated in the Maintenance and Repair Manual. When lubrication is required, use only SAE No. 30 non-detergent oil.
Bearing Temperature Check
Bearings normally run at higher than ambient tem­peratures because of heat generated by friction. Temperatures up to 160_F (71_C) are considered normal for bearings, and they can operate safely to at least 180_F (82_C).
Checking bearing temperatures by hand is inaccu­rate. Bearing temperatures can be measured ac­curately by placing a contact-type thermometer against the housing. Record this temperature for future reference.
Should any of the safety features cause the engine to shut down, the cause must be determined and corrected before putting the unit back into service. The engine will not restart until the key switch has been returned to the ‘OFF’ position for at least 10 seconds.
All safety shutdown features are pre-set at the fac­tory for optimum performance and safety; do not attempt to adjust these settings.
Never disconnect any of the safety shut­down features; this will void the warran­ty and could result in serious damage to the unit and/or injury to personnel. Safe­ty shutdown features are pre-set at the factory; do not attempt to adjust any of the settings. Determine the cause of shutdown before putting the unit back into service. Consult the factory for ad­ditional information.
A sudden increase in bearing temperatures is a warning that the bearings are at the point of failing to operate properly. Make certain that the bearing lubricant is of the proper viscosity and at the cor­rect level (see LUBRICATION in the Maintenance and Repair Manual). Bearing overheating can also be caused by shaft misalignment and/or excessive vibration.
When pumps are first started, the bearings may seem to run at temperatures above normal. Con­tinued operation should bring the temperatures down to normal levels.
PERIODIC CHECKS (Engine Driven Units)
Engine Fuel Filter
Consult the manual accompanying the engine, and change the fuel filter periodically as indicated. If operated under extremely dusty and/or humid conditions, change the filter more frequently. Irreg­ular performance and loss of power usually indi­cate a dirty fuel filter.
OPERATION PAGE C − 7
Page 23
OM−04402 PA SERIES PUMPS
Engine Oil
The engine was lubricated for test at the factory. However, always check the lubrication level before startup.
Consult the manual accompanying the engine, and change the oil filter periodically as indicated. If operated under extremely dusty conditions, change the filter more frequently.
Air Compressor
The air compressor was lubricated for test at the factory. However, always check the lubrication lev­el before startup.
Check the compressor V-belts regularly for exces­sive wear and proper tension. Refer to the manual accompanying the air compressor for v-belt ad­justment procedures.
Consult the manual accompanying the air com­pressor and preform all duties and checks as indi­cated.
Drive Belt
Check the drive belt regularly for excessive wear and proper tension. Refer to the separate Mainte- nance and Repair manual for belt replacement and adjustment procedures.
COLD WEATHER PRESERVATION (All Models)
In below freezing conditions, drain the pump to prevent damage from freezing. Also, clean out any solids by flushing with a hose. Operate the pump for approximately one minute; this will remove any remaining liquid that could freeze the pump rotat­ing parts. If the pump will be idle for more than a few hours, or if it has been pumping liquids con­taining a large amount of solids, drain the pump, and flush it thoroughly with clean water. To prevent large solids from clogging the drain port and pre­venting the pump from completely draining, insert a rod or stiff wire in the drain port, and agitate the liquid during the draining process. Clean out any remaining solids by flushing with a hose.
OPERATIONPAGE C − 8
Page 24
PA SERIES PUMPS
TROUBLESHOOTING − SECTION D
Review all SAFETY information in Section A.
Before attempting to open or service the pump:
1. Familiarize yourself with this manual.
2. Shut down the engine and discon­nect the positive battery cable, or lock out incoming power to the motor and take precautions to ensure that the pump will remain inoperative.
3. Allow the pump to completely cool if overheated.
4. Check the temperature and make sure pump is cool before opening any covers, plates, or plugs.
5. Close the suction and discharge valves.
6. Vent the pump slowly and cautiously.
7. Drain the pump.
OM−04402
TROUBLE POSSIBLE CAUSE PROBABLE REMEDY
PUMP FAILS TO PRIME
PUMP STOPS OR FAILS TO DELIVER RATED FLOW OR PRESSURE
Discharge check valve contami­nated, damaged, or unable to seat.
Air compressor head 180_ out. Consult factory.
Air leak in suction line. Correct leak.
Lining of suction hose collapsed. Replace suction hose.
Leaking or worn seal or pump gasket. Check pump vacuum. Replace
Suction lift or discharge head too high. Check piping installation and install
Air compressor damaged or belts bro­ken.
Strainer clogged. Check strainer and clean if neces-
Ecuctor clogged. Check and clean eductor.
Air leak in suction line. Correct leak.
Lining of suction hose collapsed. Replace suction hose.
Leaking or worn seal or pump gasket. Check pump vacuum. Replace
Clean or replace check valve.
leaking or worn seal or gasket.
bypass line if needed. See INSTAL- LATION.
Check and repair/replace.
sary.
leaking or worn seal or gasket.
TROUBLESHOOTING PAGE D − 1
Page 25
OM−04402
TROUBLE POSSIBLE CAUSE PROBABLE REMEDY
PA SERIES PUMPS
PUMP STOPS OR FAILS TO DELIVER RATED FLOW OR PRESSURE (cont.)
PUMP REQUIRES TOO MUCH POWER
Strainer clogged.
Discharge check valve clogged.
Suction intake not submerged at proper level or sump too small.
Impeller or other wearing parts worn or damaged.
Discharge head too high.
Suction lift too high.
Pump speed too slow. Check engine output; consult en-
Belt or flexible coupling broken. Check and replace as necessary.
Pump speed too high. Check engine output.
Extreme ambient temperature. Reduce pump output.
Discharge head too low. Fuel filter clogged. Check & replace often in extreme
Check strainer and clean if neces­sary.
Check and clean check vavle.
Check installation and correct submergence as needed.
Replace worn or damaged parts. Check that impeller is properly centered and rotates freely.
Free impeller of debris.Impeller clogged.
Install bypass line.
Measure lift w/vacuum gauge. Re­duce lift and/or friction losses in suction line.
gine operation manual.
Adjust discharge valve.
operating conditions.
PUMP CLOGS FREQUENTLY
EXCESSIVE NOISE
Dilute if possible.Liquid solution too thick.
Check and replace as required.Fuel contaminated.
Pump or jack shaft bearing(s) frozen. Disassemble, check and replace
bearing(s) as required..
Discharge flow too slow.
Suction check valve or foot valve clogged or binding.
Liquid solution too thick.
Cavitation in pump. Reduce suction lift and/or friction
Pumping entrained air.
Impeller clogged or damaged.
Open discharge valve fully to in­crease flow rate, and run engine at maximum governed speed.
Clean valve.
Dilute if possible.
losses in suction line. Record vac­uum and pressure gauge readings and consult local representative or factory.
Locate and eliminate source of air bubble.
Secure mounting hardware.Pump or drive not securely mounted.
Clean out debris; replace damaged parts.
TROUBLESHOOTINGPAGE D − 2
Page 26
PA SERIES PUMPS
TROUBLE POSSIBLE CAUSE PROBABLE REMEDY
OM−04402
BEARINGS RUN TOO HOT
Bearing temperature is high, but within limits.
Low or incorrect lubricant.
Suction and discharge lines not prop­erly supported.
Excessive tension on drive belt.
Check bearing temperature regu­larly to monitor any increase.
Check for proper type and level of lubricant.
Check piping installation for proper support.
Align drive properly.Drive misaligned.
Check belt tension. Adjust as required.
TROUBLESHOOTING PAGE D − 3
Page 27
For U.S. and International Warranty Information,
Please Visit www.grpumps.com/warranty
or call:
U.S.: 419−755−1280
International: +1−419−755−1352
For Canadian Warranty Information,
Please Visit www.grcanada.com/warranty
or call:
519−631−2870
THE GORMAN-RUPP COMPANY D MANSFIELD, OHIO
GORMAN-RUPP OF CANADA LIMITED D ST. THOMAS, ONTARIO, CANADA
Loading...