This Installation, Operation, and Maintenance
manual is designed to help you achieve the best
performance and longest life from your GormanRupp pump.
This pump is a 10 Series, semi-open impeller, selfpriming centrifugal model with a suction check
valve. The pump is designed for handling corrosive
liquids containing specified entrained solids, residues and slurries. The basic material of construc-
The Gorman-Rupp CompanyorGorman-Rupp of Canada Limited
P.O. Box 121770 Burwell Road
Mansfield, Ohio 44901-1217St. Thomas, Ontario N5P 3R7
The following are used to alert maintenance personnel to procedures which require special attention, to
those which could damage equipment, and to those which could be dangerous to personnel:
tion for wetted parts is type 316 stainless steel.
for information or technical assistance on the power source, contact the power source manufacturer’s local dealer or representative.
If there are any questions regarding the pump or
its application which are not covered in this manual or in other literature accompanying this unit,
please contact your Gorman-Rupp distributor, or
write:
Immediate hazards which WILL result in
severe personal injury or death. These
instructions describe the procedure required and the injury which will result
from failure to follow the procedure.
Hazards or unsafe practices which
COULD result in severe personal injury
or death. These instructions describe
the procedure required and the injury
which could result from failure to follow
the procedure.
Hazards or unsafe practices which COULD
result in minor personal injury or product
or property damage. These instructions
describe the requirements and the possible damage which could result from failure
to follow the procedure.
NOTE
Instructions to aid in installation, operation, and
maintenance or which clarify a procedure.
PAGE I − 1INTRODUCTION
Page 5
10 SERIES
SAFETY - SECTION A
This information applies to 10 Series basic pumps. Gorman-Rupp has no control over or particular knowledge of the
power source which will be used. Refer
to the manual accompanying the power
source before attempting to begin operation.
OM−00711−04
After the pump has been installed, make
certain that the pump and all piping or
hose connections are tight, properly
supported and secure before operation.
Before attempting to open or service the
pump:
1. Familiarize yourself with this manual.
2. Disconnect or lock out the power
source to ensure that the pump will
remain inoperative.
3. Allow the pump to completely cool
if overheated.
4. Check the temperature before
opening any covers, plates, or
plugs.
5. Close the suction and discharge
valves.
6. Vent the pump slowly and cautiously.
7. Drain the pump.
Do not operate the pump against a
closed discharge valve for long periods
of time. If operated against a closed discharge valve, pump components will
deteriorate, and the liquid could come
to a boil, build pressure, and cause the
pump casing to rupture or explode.
Do not remove plates, covers, gauges,
pipe plugs, or fittings from an overheated pump. Vapor pressure within the
pump can cause parts being disengaged to be ejected with great force. Allow the pump to cool before servicing.
This pump is designed to handle corro-
sive liquids containing specified entrained solids, residues and slurries. Do
not attempt to pump volatile or flammable liquids which may damage the
pump or endanger personnel as a result
of pump failure.
This pump is designed to pump materials which could cause serious illness or
injury through direct exposure or
emitted fumes. Wear protective clothing, such as rubber gloves, face mask,
and rubber apron, as necessary before
disassembling the pump or piping.
PAGE A − 1SAFETY
Page 6
10 SERIESOM−00711−04
Overheating may produce dangerous
fumes. Use extreme caution when venting the pump, or when removing covers,
plates, plugs, or fittings.
Do not operate the pump without
shields and/or guards in place over the
drive shafts, belts, and/or couplings, or
other rotating parts. Exposed rotating
parts can catch clothing, fingers, or
tools, causing severe injury to personnel.
Never run this pump backwards. Be certain that rotation is correct before fully
engaging the pump.
PAGE A − 2SAFETY
Page 7
10 SERIESOM−00711−04
INSTALLATION − SECTION B
Review all SAFETY information in Section A.
Since pump installations are seldom identical, this
section offers only general recommendations and
practices required to inspect, position, and arrange the pump and piping.
Most of the information pertains to a standard
static lift application where the pump is positioned
above the free level of liquid to be pumped.
If installed in a flooded suction application where
the liquid is supplied to the pump under pressure,
some of the information such as mounting, line
configuration, and priming must be tailored to the
OUTLINE DRAWING
specific application. Since the pressure supplied
to the pump is critical to performance and safety,
be sure to limit the incoming pressure to 50% of the
maximum permissible operating pressure as
shown on the pump performance curve (see Section E, Page 1).
For further assistance, contact your Gorman-Rupp
distributor or the Gorman-Rupp Company.
Pump Dimensions
See Figure B−1 for the approximate physical dimensions of this pump.
Figure B−1. Pump Model 16A22−B
PREINSTALLATION INSPECTION
The pump assembly was inspected and tested before shipment from the factory. Before installation,
inspect the pump for damage which may have occurred during shipment. Check as follows:
a. Inspect the pump for cracks, dents, damaged
threads, and other obvious damage.
b. Check for and tighten loose attaching hard-
ware. Since gaskets tend to shrink after drying, check for loose hardware at mating surfaces.
PAGE B − 1INSTALLATION
Page 8
OM−00711−0410 SERIES
c. Carefully read all tags, decals, and markings
on the pump assembly, and perform all duties
indicated. Note that the pump shaft rotates in
the required direction.
Only operate this pump in the direction indicated by the arrow on the pump body
and on the accompanying decal. Otherwise, the impeller could become loosened
from the shaft and seriously damage the
pump.
d. Check levels and lubricate as necessary. Re-
fer to LUBRICATION in the MAINTENANCEAND REPAIR section of this manual and perform duties as instructed.
e. If the pump has been stored for more than 12
months, some of the components or lubricants may have exceeded their maximum
shelf life. These must be inspected or re-placed to ensure maximum pump service.
damaged if the chains or cables used to lift
and move the unit are improperly wrapped
around the pump.
Mounting
Locate the pump in an accessible place as close as
practical to the liquid being pumped. Level mounting is essential for proper operation.
The pump may have to be supported or shimmed
to provide for level operation or to eliminate vibration.
Clearance
A minimum clearance of 18 inches in front of the
cover plate is required to permit removal of the cover and easy access to the pump interior.
SUCTION AND DISCHARGE PIPING
Pump performance is adversely effected by increased suction lift, discharge elevation, and friction losses. See the performance curve on Page
E-1 to be sure your overall application allows pump
to operate within the safe operation range.
If the maximum shelf life has been exceeded, or if
anything appears to be abnormal, contact your
Gorman-Rupp distributor or the factory to determine the repair or updating policy. Do not put the
pump into service until appropriate action has
been taken.
POSITIONING PUMP
Lifting
Use lifting equipment with a capacity of at least
3550 pounds (1610 kg). This pump weighs approximately 706pounds (320 kg), not including
the weight of accessories, base and power source.
Customer installed equipment such as suction and
discharge pipingmust be removed before attempting to lift.
The pump assembly can be seriously
Materials
Either pipe or hose maybe used for suction and
discharge lines; however, the materials must be
compatible with the liquid being pumped. If hose is
used in suction lines, it must be the rigid-wall, reinforced type to prevent collapse under suction. Using piping couplings in suction lines is not recommended.
Line Configuration
Keep suction and discharge lines as straight as
possible to minimize friction losses. Make minimum use of elbows and fittings, which substantially increase friction loss. If elbows are necessary,
use the long-radius type to minimize friction loss.
Connections to Pump
Before tightening a connecting flange, align it exactly with the pump port. Never pull a pipe line into
place by tightening the flange bolts and/or couplings.
PAGE B − 2INSTALLATION
Page 9
10 SERIESOM−00711−04
Lines near the pump must be independently supported to avoid strain on the pump which could
cause excessive vibration, decreased bearing life,
and increased shaft and seal wear. If hose-type
lines are used, they should have adequate support
to secure them when filled with liquid and under
pressure.
Gauges
Most pumps are drilled and tapped for installing
discharge pressure and vacuum suction gauges. If
these gauges are desired for pumps that are not
tapped, drill and tap the suction and discharge
lines not less than 18 inches (457,2 mm) from the
suction and discharge ports and install the lines.
Installation closer to the pump may result in erratic
readings.
SUCTION LINES
To avoid air pockets which could affect pump priming, the suction line must be as short and direct as
possible. When operation involves a suction lift, the
line must always slope upward to the pump from
the source of the liquid being pumped; if the line
slopes down to the pump at any point along the
suction run, air pockets will be created.
Fittings
three or four times the cross section of the suction
line, and that the openings will not permit passage
of solids larger than the solids handling capability
of the pump.
This pump is designed to handle up to 2 1/2 inch
(63,5 mm) diameter spherical solids.
Sealing
Since even a slight leak will affect priming, head,
and capacity, especially when operating with a
high suction lift, all connections in the suction line
should be sealed with pipe dope to ensure an airtight seal. Follow the sealant manufacturer’s recommendations when selecting and applying the
pipe dope. The pipe dope should be compatible
with the liquid being pumped.
Suction Lines In Sumps
If a single suction line is installed in a sump, it
should be positioned away from the wall of the
sump at a distance equal to 1-1/2 times the diameter of the suction line.
If there is a liquid flow from an open pipe into the
sump, the flow should be kept away from the suction inlet because the inflow will carry air down into
the sump, and air entering the suction line will reduce pump efficiency.
Suction lines should be the same size as the pump
inlet. If reducers are used in suction lines, they
should be the eccentric type, and should be installed with the flat part of the reducers uppermost
to avoid creating air pockets. Valves are not normally used in suction lines, but if a valve is used,
install it with the stem horizontal to avoid air pockets.
Strainers
If a strainer is furnished with the pump, be certain
to use it; any spherical solids which pass through a
strainer furnished with the pump will also pass
through the pump itself.
If a strainer is not furnished with the pump, but is
installed by the pump user, make certain that the
total area of the openings in the strainer is at least
If it is necessary to position inflow close to the suction inlet, install a baffle between the inflow and the
suction inlet at a distance 1-1/2 times the diameter
of the suction pipe. The baffle will allow entrained
air to escape from the liquid before it is drawn into
the suction inlet.
If two suction lines are installed in a single sump,
the flow paths may interact, reducing the efficiency
of one or both pumps. To avoid this, position the
suction inlets so that they are separated by a distance equal to at least 3 times the diameter of the
suction pipe.
Suction Line Positioning
The depth of submergence of the suction line is
critical to efficient pump operation. Figure B−2
shows recommended minimum submergence vs.
velocity.
PAGE B − 3INSTALLATION
Page 10
OM−00711−0410 SERIES
NOTE
The pipe submergence required may be reduced
by installing a standard pipe increaser fitting at the
end of the suction line. The larger opening size will
reduce the inlet velocity. Calculate the required
submergence using the following formula based
on the increased opening size (area or diameter).
Figure B−2. Recommended Minimum Suction Line Submergence vs. Velocity
DISCHARGE LINES
Siphoning
Do not terminate the discharge line at a level lower
than that of the liquid being pumped unless a siphon breaker is used in the line. Otherwise, a siphoning action causing damage to the pump
could result.
Valves
If a throttling valve is desired in the discharge line,
use a valve as large as the largest pipe to minimize
friction losses. Never install a throttling valve in a
suction line.
A check valve in the discharge line is normally recommended, but it is not necessary in low discharge head applications.
With high discharge heads, it is recommended that
a throttling valve and a system check valve be installed in the discharge line to protect the pump
from excessive shock pressure and reverse rotation when it is stopped.
If the application involves a high discharge
head, gradually close the discharge
throttling valve before stopping the pump.
Bypass Lines
Self-priming pumps are not air compressors. During the priming cycle, air from the suction line must
be vented to atmosphere on the discharge side. If
the discharge line is open, this air will be vented
through the discharge. However, if a check valve
has been installed in the discharge line, the discharge side of the pump must be opened to atmospheric pressure through a bypass line installed be-
PAGE B − 4INSTALLATION
Page 11
10 SERIESOM−00711−04
tween the pump discharge and the check valve. A
self-priming centrifugal pump will not prime if
there is sufficient static liquid head to hold the discharge check valve closed.
Except in certain specific applications (to
NOTE
The bypass line should be sized so that it does not
affect pump discharge capacity; however, the bypass line should be at least 1 inch (25,4 mm) in diameter to minimize the chance of plugging.
prevent flooding during service of an automatic air release valve in a below-ground
lift station), if a manual shut-off valve is installed anywhere in a bypass line, it must
be a full-opening, ball-type valve to pre-
vent plugging by solids.
In low discharge headapplications (less than 30
feet (9,1 m)), it is recommended that the bypass
line be run back to the wet well, and located 6
inches below the water level or cut-off point of the
low level pump. In some installations, this bypass
outline may be terminated with a six-to-eight foot
(1,8 to 2,4 m) length of 1-1/4 inch (31,8 mm) I.D.
smooth-bore hose; air and liquid vented during
the priming process will then agitate the hose and
break up any solids, grease, or other substances
likely to cause clogging.
A manual shut-off valve should not be
installed in any bypass line. A manual
shut-off valve may inadvertently be left
closed during operation. A pump which
has lost prime may continue to operate
without reaching prime, causing dangerous overheating and possible explosive rupture of the pump casing. Personnel could be severely injured.
A bypass line that is returned to a wet well
must be secured against being drawn into
the pump suction inlet.
It is also recommended that pipe unions be installed at each 90_ elbow in a bypass line to ease
disassembly and maintenance.
In high discharge head applications (more than
30 feet (9,1 m), an excessive amount of liquid may
be bypassed and forced back to the wet well under
the full working pressure of the pump; this will reduce overall pumping efficiency. Therefore, it is
recommended that a Gorman-Rupp Automatic
Air Release Valve be installed in the bypass line.
Gorman-Rupp Automatic Air Release Valves are
reliable, and require minimum maintenance. See
Automatic Air Release Valves in this section for
installation and theory of operation of the Automatic Air Release Valve. Consult your GormanRupp distributor, or contact the Gorman-Rupp
Company for selection of an Automatic Air Release
Valve to fit your application.
Allow an over-heated pump to cool before servicing. Do not remove plates,
covers, gauges, or fittings from an overheated pump. Liquid within the pump
can reach boiling temperatures, and vapor pressure within the pump can cause
parts being disengaged to be ejected
with great force. After the pump cools,
drain the liquid from the pump by removing the casing drain plug. Use caution when removing the plug to prevent
injury to personnel from hot liquid.
AUTOMATIC AIR RELEASE VALVE
When properly installed and correctly adjusted to
the specific hydraulic operating conditions of the
application, the Gorman-Rupp Automatic Air Release Valve will permit air to escape through the bypass line, and then close automatically when the
pump is fully primed and pumping at full capacity.
PAGE B − 5INSTALLATION
Page 12
OM−00711−0410 SERIES
Theory of Operation
Figures B−3 and B−4 show a cross-sectional view
of the Automatic Air Release Valve, and a corresponding description of operation.
Some leakage (1 to 5 gallons (3,8 to 18,9
Liters) per minute) will occur when the
valve is fully closed. Be sure the bypass
line is directed back to the wet well or
tank to prevent hazardous spills.
When the pump shuts down, the spring returns the
diaphragm to its original position. Any solids that
may have accumulated in the diaphragm chamber
settle to the bottom and are flushed out during the
next priming cycle.
NOTE
Figure B−3. Valve in Open Position
During the priming cycle, air from the pump casing
flows through the bypass line, and passes through
the Air Release Valve to the wet well (Figure B−3).
The valve will remain open if the pump does not
reach its designed capacity or head. Valve closing
pressure is dependent upon the discharge head of
the pump at full capacity. The range of the valve
closing pressure is established by the tension rate
of the spring as ordered from the factory. Valve closing pressure can be further adjusted to the exact
system requirements by moving the spring retaining pin up or down the plunger rod to increase or
decrease tension on the spring. Contact your Gorman-Rupp distributor or the Gorman-Rupp Company for information about an Automatic Air Release Valve for your specific application.
Air Release Valve Installation
The Automatic Air Release Valve must be inde-
Figure B−4. Valve in Closed Position
When the pump is fully primed, pressure resulting
from flow against the valve diaphragm compresses the spring and closes the valve (Figure
B−4). The valve will remain closed, reducing the
bypass of liquid to 1 to 5 gallons per minute, until
the pump loses its prime or stops.
PAGE B − 6INSTALLATION
pendently mounted in a horizontal position and
connected to the discharge line of the self-priming
centrifugal pump (see Figure B−5).
NOTE
If the Air Release Valve is to be installed on a staged
pump application, contact the factory for specific
installation instructions.
Page 13
10 SERIESOM−00711−04
INSTALL AIR RELEASE VALVE
IN HORIZONTAL POSITION
90_ LONG
RADIUS
ELBOW
BLEED LINE 1"
(25,4 MM) DIA. MIN.
(CUSTOMER FURNISHED) EXTEND 6"
(152 MM) BELOW
PUMP OFF LIQUID
LEVEL
SUPPORT
BRACKET
CLEAN-OUT
COVER
SUCTION
LINE
WET WELL
OR SUMP
DISCHARGE PIPE
DISCHARGE
CHECK VALVE
PUMP DISCHARGE
SELF-PRIMING
CENTRIFUGAL
PUMP
Figure B−5. Typical Automatic Air Release Valve Installation
The valve inlet line must be installed between the
pump discharge port and the non-pressurized side
of the discharge check valve. The valve inlet is at
the large end of the valve body, and is provided
with standard 1 inch NPT pipe threads.
The valve outlet is located at the opposite end of
the valve, and is also equipped with standard 1
inch NPT pipe threads. The outlet should be connected to a bleed line which slopes back to the wet
well or sump. The bleed line must be the same size
as the inlet piping, or larger. If piping is used for the
bleed line, avoid the use of elbows whenever possible.
NOTE
It is recommended that each Air Release Valve be
fitted with an independent bleeder line directed
back to the wet well. However, if multiple Air Release Valves are installed in a system, the bleeder
lines may be directed to a common manifold pipe.
Contact your Gorman-Rupp distributor or the Gorman-Rupp Company for information about installation of an Automatic Air Release Valve for your specific application.
ALIGNMENT
The alignment of the pump and its power source is
critical for trouble-free mechanical operation. In
either a flexible coupling or V-belt driven system,
the driver and pump must be mounted so that their
shafts are aligned with and parallel to each other. It
is imperative that alignment be checked after the
pump and piping are installed, and before operation.
NOTE
Check Rotation, Section C, before final alignment
of the pump.
When mounted at the Gorman-Rupp factory, driver
and pump are aligned before shipment. Misalignment will occur in transit and handling. Pumps
must be checked and realigned before operation.
Before checking alignment, tighten the foundation
bolts. The pump casing feet and/or pedestal feet,
and the driver mounting bolts should also be tightly
secured.
PAGE B − 7INSTALLATION
Page 14
OM−00711−0410 SERIES
When checking alignment, disconnect
the power source to ensure that the
pump will remain inoperative.
Adjusting the alignment in one direction
may alter the alignment in another direction. Check each procedure after altering
alignment.
Coupled Drives
When using couplings, the axis of the power
source must be aligned to the axis of the pump
shaft in both the horizontal and vertical planes.
Most couplings require a specific gap or clearance
between the driving and the driven shafts. Refer to
the coupling manufacturer’s service literature.
Align spider insert type couplings by using calipers
to measure the dimensions on the circumference
of the outer ends of the coupling hub every 90_.
The coupling is in alignment when the hub ends
are the same distance apart at all points (see Figure B−6).
Figure B−7. Alignment of V-Belt Driven
Pumps
Check parallel adjustment by laying a straightedge
across both coupling rims at the top, bottom, and
side. When the straightedge rests evenly on both
halves of the coupling, the coupling is in horizontal
parallel alignment. If the coupling is misaligned,
use a feeler gauge between the coupling and the
straightedge to measure the amount of misalignment.
V-Belt Drives
When using V-belt drives, the power source and
the pump must be parallel. Use a straightedge
along the sides of the pulleys to ensure that the pulleys are properly aligned (see Figure B−8). In drive
systems using two or more belts, make certain that
the belts are a matched set; unmatched sets will
cause accelerated belt wear.
Figure B−6. Alignment of V-Belt Driven
Pumps
Align non-spider type couplings by using a feeler
gauge or taper gauge between the coupling halves
every 90_. The coupling is in alignment when the
hubs are the same distance apart at all points (see
Figure B−7).
MISALIGNED:
SHAFTS
NOT PARALLEL
MISALIGNED:
SHAFTS
NOT IN LINE
ALIGNED: SHAFTS
PARALLEL AND
SHEAVES IN LINE
Figure B−8. Alignment of V-Belt Driven
Pumps
Tighten the belts in accordance with the belt manufacturer’s instructions. If the belts are too loose,
PAGE B − 8INSTALLATION
Page 15
10 SERIESOM−00711−04
they will slip; if the belts are too tight, there will be
excessive power loss and possible bearing failure.
Select pulleys that will match the proper speed ratio; overspeeding the pump may damage both
pump and power source.
Do not operate the pump without the
guard in place over the rotating parts.
Exposed rotating parts can catch clothing, fingers, or tools, causing severe injury to personnel.
PAGE B − 9INSTALLATION
Page 16
10 SERIES
OM−00711−04
OPERATION − SECTION C
Review all SAFETY information in Section A.
Follow the instructions on all tags, labels and
decals attached to the pump.
This pump is designed to handle corrosive liquids containing specified entrained solids, residues and slurries. Do
not attempt to pump volatile, or flammable liquids which may damage the
pump or endanger personnel as a result
of pump failure.
Pump speed and operating condition
points must be within the continuous performance range shown on the curve (see
Section E, Page 1).
PRIMING
not prime when dry. Extended operation of
a dry pump will destroy the seal assembly.
Add liquid to the pump casing when:
1. The pump is being put into service for the
first time.
2. The pump has not been used for a considerable length of time.
3. The liquid in the pump casing has evaporated.
Once the pump casing has been filled, the pump
will prime and reprime as necessary.
After filling the pump casing, reinstall
and tighten the fill plug. Do not attempt
to operate the pump unless all connecting piping is securely installed. Otherwise, liquid in the pump forced out under pressure could cause injury to personnel.
To fill the pump, remove the pump casing fill cover
or fill plug in the top of the casing, and add clean
liquid until the casing is filled. Replace the fill cover
or fill plug before operating the pump.
Install the pump and piping as described in IN-STALLATION. Make sure that the piping connections are tight, and that the pump is securely
mounted. Check that the pump is properly lubricated (see LUBRICATION in MAINTENANCEAND REPAIR).
This pump is self-priming, but the pump should
never be operated unless there is liquid in the
pump casing.
STARTING
Consult the operations manual furnished with the
power source.
Rotation
The correct direction of pump rotation is indicated
by an arrow on the pump body or accompanying
decals. If the pump is operated in the wrong direction, the impeller could become loosened from the
shaft and seriously damage the pump.
Never operate this pump unless there is
liquid in the pump casing. The pump will
OPERATIONPAGE C − 1
The pump must operate in the direction in-
Page 17
OM−00711−0410 SERIES
dicated by the arrow on the pump, or accompanying decals. Reverse rotation
could loosen the impeller and seriously
damage the pump.
Consult the operating manual furnished with the
pump power source before attempting to start the
power source.
If an electric motor is used to drive the pump, remove V-belts, couplings, or otherwise disconnect
the pump from the motor before checking motor
rotation. Operate the motor independently while
observing the direction of the motor shaft, or cooling fan.
If rotation is incorrect on a three-phase motor, have
a qualified electrician interchange any two of the
three phase wires to change direction. If rotation is
incorrect on a single-phase motor, consult the literature supplied with the motor for specific instructions.
OPERATION
Lines With a Bypass
slowly and guard against excessive shock pressure which could damage pipe ends, gaskets,
sprinkler heads, and any other fixtures connected
to the line. When the discharge line is completely
filled, adjust the throttling valve to the required flow
rate.
Leakage
No leakage should be visible at pump mating surfaces, or at pump connections or fittings. Keep all
line connections and fittings tight to maintain maximum pump efficiency.
Liquid Temperature And Overheating
The maximum liquid temperature for this pump is
160_ F (71_C). Do not apply it at a higher operating
temperature.
Overheating can occur if operated with the valves
in the suction or discharge lines closed. Operating
against closed valves could bring the liquid to a
boil, build pressure, and cause the pump to rupture or explode. If overheating occurs, stop the
pump and allow it to cool before servicing it. Refill
the pump casing with cool liquid.
If a Gorman-Rupp Automatic Air Release Valve has
been installed, the valve will automatically open to
allow the pump to prime, and automatically close
after priming is complete (see INSTALLATION for
Air Release Valve operation).
If the bypass line is open, air from the suction line
will be discharged through the bypass line back to
the wet well during the priming cycle. Liquid will
then continue to circulate through the bypass line
while the pump is in operation.
Lines Without a Bypass
Open all valves in the discharge line and start the
power source. Priming is indicated by a positive
reading on the discharge pressure gauge or by a
quieter operation. The pump may not prime immediately because the suction line must first fill with
liquid. If the pump fails to prime within five minutes,
stop it and check the suction line for leaks.
After the pump has been primed, partially close the
discharge line throttling valve in order to fill the line
Do not remove plates, covers, gauges,
pipe plugs, or fittings from an overheated pump. Vapor pressure within the
pump can cause parts being disengaged to be ejected with great force. Allow the pump to cool before servicing.
Strainer Check
If a suction strainer has been shipped with the
pump or installed by the user, check the strainer
regularly, and clean it as necessary. The strainer
should also be checked if pump flow rate begins to
drop. If a vacuum suction gauge has been installed, monitor and record the readings regularly
to detect strainer blockage.
Never introduce air or steam pressure into the
pump casing or piping to remove a blockage. This
could result in personal injury or damage to the
OPERATIONPAGE C − 2
Page 18
10 SERIES
OM−00711−04
equipment. If backflushing is absolutely necessary, liquid pressure must be limited to 50% of the
maximum permissible operating pressure shown
on the pump performance curve (see Section E,
Page 1).
Pump Vacuum Check
With the pump inoperative, install a vacuum gauge
in the system, using pipe dope on the threads.
Block the suction line and start the pump. At operating speed the pump should pull a vacuum of 20
inches (508,0 mm) or more of mercury. If it does
not, check for air leaks in the seal, gasket, or discharge valve.
Open the suction line, and read the vacuum gauge
with the pump primed and at operating speed.
Shut off the pump. The vacuum gauge reading will
immediately drop proportionate to static suction
lift, and should then stabilize. If the vacuum reading
falls off rapidly after stabilization, an air leak exists.
Before checking for the source of the leak, check
the point of installation of the vacuum gauge.
Cold Weather Preservation
In below freezing conditions, drain the pump to
prevent damage from freezing. Also, clean out any
solids by flushing with a hose. Operate the pump
for approximately one minute; this will remove any
remaining liquid that could freeze the pump rotating parts. If the pump will be idle for more than a
few hours, or if it has been pumping liquids containing a large amount of solids, drain the pump,
and flush it thoroughly with clean water. To prevent
large solids from clogging the drain port and preventing the pump from completely draining, insert
a rod or stiff wire in the drain port, and agitate the
liquid during the draining process. Clean out any
remaining solids by flushing with a hose.
BEARING TEMPERATURE CHECK
Bearings normally run at higher than ambient temperatures because of heat generated by friction.
Temperatures up to 160_F (71_C) are considered
normal for bearings, and they can operate safely to
at least 180_F (82_C).
STOPPING
Never halt the flow of liquid suddenly. If the liquid
being pumped is stopped abruptly, damaging
shock waves can be transmitted to the pump and
piping system. Close all connecting valves slowly.
If the application involves a high discharge
head, gradually close the discharge
throttling valve before stopping the pump.
After stopping the pump, disconnect the power
source or lock it out to ensure that the pump will remain inoperative.
Checking bearing temperatures by hand is inaccurate. Bearing temperatures can be measured accurately by placing a contact-type thermometer
against the housing. Record this temperature for
future reference.
A sudden increase in bearing temperatures is a
warning that the bearings are at the point of failing
to operate properly. Make certain that the bearing
lubricant is of the proper viscosity and at the correct level (see LUBRICATION in Section E). Bearing overheating can also be caused by shaft
misalignment and/or excessive vibration.
When pumps are first started, the bearings may
seem to run at temperatures above normal. Continued operation should bring the temperatures
down to normal levels.
OPERATIONPAGE C − 3
Page 19
TROUBLESHOOTING − SECTION D
Review all SAFETY information in Section A.
Before attempting to open or service the
pump:
1. Familiarize yourself with this manual.
2. Disconnect or lock out the power
source to ensure that the pump will
remain inoperative.
3. Allow the pump to completely cool if
overheated.
4. Check the temperature before opening any covers, plates, or plugs.
5. Close the suction and discharge
valves.
6. Vent the pump slowly and cautiously.
7. Drain the pump.
OM−00711−0410 SERIES
TROUBLEPOSSIBLE CAUSEPROBABLE REMEDY
PUMP FAILS TO
PRIME
PUMP STOPS OR
FAILS TO DELIVER
RATED FLOW OR
PRESSURE
Not enough liquid in casing.
Suction check valve contaminated or
damaged.
Air leak in suction line.Correct leak.
Lining of suction hose collapsed.Replace suction hose.
Leaking or worn seal or pump gasket.Check pump vacuum. Replace
Suction lift or discharge head too high.Check piping installation and install
Strainer clogged.Check strainer and clean if neces-
Air leak in suction line.Correct leak.
Lining of suction hose collapsed.Replace suction hose.
Suction intake not submerged at
proper level or sump too small.
Impeller or other wearing parts worn
or damaged.
Add liquid to casing. See
PRIMING.
Clean or replace check valve.
leaking or worn seal or gasket.
bypass line if needed. See INSTAL-LATION.
sary.
Check installation and correct
submergence as needed.
Replace worn or damaged parts.
Check that impeller is properly
centered and rotates freely.
TROUBLESHOOTINGPAGE D − 1
Page 20
OM−00711−0410 SERIES
TROUBLEPOSSIBLE CAUSEPROBABLE REMEDY
PUMP STOPS OR
FAILS TO DELIVER
RATED FLOW OR
PRESSURE (cont.)
PUMP REQUIRES
TOO MUCH
POWER
PUMP CLOGS
FREQUENTLY
Leaking or worn seal or pump gasket.Check pump vacuum. Replace
leaking or worn seal or gasket.
Free impeller of debris.Impeller clogged.
Pump speed too slow.Check driver output; check
belts
Pump running backwards.
Suction lift or discharge head too high.Check piping installation and install
Pump speed too high.Check driver output check that
Discharge head too low.
Discharge flow too slow.
Suction check valve or foot valve
clogged or binding.
or couplings for slippage.
Check direction of rotation and
correct by interchanging any two
motor leads at control box. (See
Pump Rotation, Section C).
bypass line if needed. See INSTAL-LATION.
sheaves or couplings are correctly
sized.
Adjust discharge
valve.
Dilute if possible.Liquid solution too thick.
Open discharge valve fully to increase flow rate, and run power
source at maximum governed
speed.
Clean valve.
EXCESSIVE NOISECavitation in pump.Reduce suction lift and/or friction
losses in suction line. Record vacuum and pressure gauge readings
and consult local representative or
factory.
Locate and eliminate source of air
bubble.
Secure mounting hardware.
parts.
Check bearing temperature regularly to monitor any increase.
Check for proper type and level of
lubricant.
Check piping installation for proper
support.
Align drive properly.
BEARINGS RUN
TOO HOT
Pumping entrained
air.
Pump or drive not securely mounted.
Impeller clogged or damaged.Clean out debris; replace damaged
Bearing temperature is high, but
within limits.
Low or incorrect lubricant.
Suction and discharge lines not properly supported.
Drive misaligned.
TROUBLESHOOTINGPAGE D − 2
Page 21
10 SERIESOM−00711−04
PUMP MAINTENANCE AND REPAIR - SECTION E
MAINTENANCE AND REPAIR OF THE WEARING PARTS OF THE PUMP WILL MAINTAIN PEAK OPERATING PERFORMANCE.
STANDARD PERFORMANCE FOR PUMP MODEL 16A22−B
Based on 70_ F (21_ C) clear water at sea level
with minimum suction lift. Since pump installations
are seldom identical, your performance may be different due to such factors as viscosity, specific
gravity, elevation, temperature, and impeller trim.
Contact the Gorman-Rupp Company to verify performance or part numbers.
Pump speed and operating condition
If your pump serial number is followed by an N",
your pump is NOT a standard production model.
MAINTENANCE & REPAIRPAGE E − 1
points must be within the continuous performance range shown on the curve.
Page 22
PARTS PAGE
10 SERIESOM−00711−04
SECTION DRAWING
Figure E−1. Pump Model 16A22−B
MAINTENANCE & REPAIRPAGE E − 2
Page 23
10 SERIESOM−00711−04
PARTS LIST
Pump Model 16A22−B
(From S/N 1068713 up)
If your pump serial number is followed by an N", your pump is NOT a standard production model. Contact
the Gorman-Rupp Company to verify part numbers.
CANADIAN SERIAL NO. .............................. AND UP
MAINTENANCE & REPAIRPAGE E − 3
Page 24
10 SERIESOM−00711−04
PUMP AND SEAL DISASSEMBLY
AND REASSEMBLY
Review all SAFETY information in Section A.
Follow the instructions on all tags, label and decals attached to the pump.
This pump requires little service due to its rugged,
minimum-maintenance design. However, if it becomes necessary to inspect or replace the wearing
parts, follow these instructions which are keyed to
the sectional view (see Figure E−1) and the accompanying parts list.
Before attempting to service the pump, disconnect
or lock out the power source to ensure that the
pump will remain inoperative. Close all valves in the
suction and discharge lines.
Suction Check Valve Removal and Disassembly
Before attempting to service the pump, remove the
pump casing drain plug (48) and drain the pump.
Clean and reinstall the drain plug.
To service the suction check valve assembly (68),
remove the suction piping. Remove the nuts (66)
securing the suction flange (64) and suction flange
gasket (63) to the check valve seat (62). Remove
the machine screws (67) securing check valve seat
(62) and check valve assembly (68) to the pump
casing (1). Separate the check valve assembly
from the check valve seat. Discard the suction
flange gasket (63) and check valve gasket (61).
Inspect the check valve parts for wear or damage.
If replacement is required, remove the hardware
(69 and 70), and separate the check valve gasket
(72), and weights (71 and 73).
If no further disassembly is required, see SuctionCheck Valve Installation.
For power source disassembly and repair, consult
the literature supplied with the power source, or
contact your local power source representative.
Before attempting to open or service the
pump:
1. Familiarize yourself with this manual.
2. Disconnect or lock out the power
source to ensure that the pump will
remain inoperative.
3. Allow the pump to completely cool
if overheated.
4. Check the temperature before
opening any covers, plates, or
plugs.
5. Close the suction and discharge
valves.
6. Vent the pump slowly and cautiously.
7. Drain the pump.
Back Cover Removal
The wear plate (47) is easily accessible and may be
serviced by removing the back cover assembly
(52). Loosen the clamp bar screw (59) and remove
the clamp bar (60). Pull the back cover and wear
plate from the pump casing. Remove the back cover gasket (51). Clean the mating surfaces of the
back cover plate and pump casing.
Inspect the wear plate and replace it if badly scored
or worn. To remove the wear plate, disengage the
hardware (57 and 58) securing it to the back cover.
If no further disassembly is required, see Back
Cover Installation.
Pump Casing Removal
To service the impeller or seal assembly, disconnect the discharge piping. Remove the hardware
securing the pump to the base. Disconnect the
power source. Tie and tag any leveling shims used
under the pump mounting feet to ease reassembly.
Remove the nuts (45), and using a suitable hoist
and sling of sufficient capacity separate the pump
casing (1) and gasket set (11) from the seal plate
MAINTENANCE & REPAIRPAGE E − 4
Page 25
OM−00711−0410 SERIES
(12) and pedestal (23). Clean the mating surfaces
of the seal plate and pump casing. Tie and tag the
gaskets, or measure and record their thickness for
ease of reassembly.
Impeller Removal
Before removing the impeller, remove the bottle oiler and piping (16, 17, 18 and 19). Remove the seal
drain plug (44) and drain the oil from the seal cavity
to prevent the oil from escaping when the impeller
is removed. Clean and reinstall the drain plug.
Immobilize the impeller by wedging a block wood
between the vanes. Remove the impeller capscrew and washer (49 and 50).
If removed, install the shaft key (29). Install a lathe
dog on the drive end of the shaft (21) with the V"
notch positioned over the shaft keyway.
With the impeller rotation still blocked, strike the
lathe dog sharply in a counterclockwise direction
(when facing the drive end of the shaft). The impeller may also be loosened by using a long piece of
heavy bar stock to pry against the arm of the lathe
dog in a counterclockwise direction (when facing
the drive end of the shaft) as shown in Figure 2.
Use caution not to damage the shaft or keyway.
When the impeller breaks loose, remove the lathe
dog and wood block and unscrew the impeller
from the shaft.
Unscrew the impeller from the shaft. Use caution
when removing the impeller; tension on the seal
spring will be released as the impeller is unscrewed.
Inspect the impeller and replace it if cracked or
badly worn. Slide the impeller adjusting shims (74)
off the impeller shaft. Tie and tag the shims or measure and record their thickness for ease of reassembly.
Seal Removal and Disassembly
Remove the spring centering washer and seal
spring. Slide the shaft sleeve (75) and rotating portion of the seal off the shaft as a single unit. Apply oil
to the sleeve and work it up under the bellows.
Slide the rotating portion of the seal off the shaft
sleeve. Use a stiff wire with a hooked end to remove the stationary element, seat and O-rings
from the seal plate. Slide the seal plate (12) and oil
seal (43) off the shaft. Use a suitable sized dowel
and press the oil from the seal plate.
NOTE
An alternate method of removing the seal assembly
is to slide the seal plate, shaft sleeve and seal assembly off the shaft as a single unit. Place the seal
plate on a flat surface with the impeller side down.
Using a suitable sized dowel, press the seal components from the seal plate. Press the oil seal from
the seal plate.
Inspect the seal plate and replace it if cracked or
badly worn.
If no further disassembly is required, see Seal
Reassembly and Installation.
Shaft and Bearing Removal and Disassembly
When the pump is properly operated and maintained, the pedestal should not require disassembly. Disassemble the shaft and bearings only
when there is evidence of wear or damage.
Counterclockwise
Lathe Dog Arm
Heavy
Bar Stock
Turn
V" Notch
Shaft Key
Impeller Shaft
Lathe Dog
Setscrew
Shaft and bearing disassembly in the field
Figure 2. Loosening Impeller
MAINTENANCE & REPAIRPAGE E − 5
is not recommended. These operations
Page 26
10 SERIESOM−00711−04
should be performed only in a properlyequipped shop by qualified personnel.
Remove the pedestal drain plug (35) and drain the
bearing lubricant. Clean and reinstall the drain
plug.
Remove the slinger ring (42).
Using snap ring pliers, remove the bearing retaining ring (27) from the pedestal bore.
Remove the machine screws and lockwashers (30
and 31) in the bearing retainer (32). Install two machine screws (#10−32 X 1" long) and using two
screwdrivers against the heads of the machine
screws pry the bearing retainer from the pedestal
bore.
NOTE
Do not use the machine screws to jack against the
ball bearings.
be replaced any time the shaft and bear-
ings are removed.
Clean the pedestal, shaft and all component parts
(except the bearings) with a soft cloth soaked in
cleaning solvent. Inspect the parts for wear or damage and replace as necessary.
Most cleaning solvents are toxic and
flammable. Use them only in a well ventilated area free from excessive heat,
sparks, and flame. Read and follow all
precautions printed on solvent containers.
Clean the bearings thoroughly in fresh cleaning
solvent. Dry the bearings with filtered compressed
air and coat with light oil.
Remove the bearing shim set (25); tie and tag the
shims or measure and record their thickness for
ease of reassembly.
Press the oil seal (28) from the bearing retainer,
and remove the bearing retainer O-ring (26) from
the pedestal bore.
Remove the hardware (40 and 41) and remove the
the bearing cap (38). Press the oil seal (36) from
the bearing cap. Remove the O-ring (37).
Place a block of wood against the drive end of the
shaft and tap the shaft (21) and assembled bearings (20 and 24) from the pedestal. Be careful not
to damage the shaft.
After removing the shaft and bearings, clean and
inspect the bearings in place as follows.
Bearings must be kept free of all dirt and
foreign material. Failure to do so will greatly shorten bearing life. Do not spin dry
bearings. This may scratch the balls or
races and cause premature bearing failure.
Rotate the bearings by hand to check for roughness or binding and inspect the bearing balls. If rotation is rough or the bearing balls are discolored,
replace the bearings.
The bearing tolerances provide a tight press fit
onto the shaft and a snug slip fit into the pedestal.
Replace the bearings, shaft, or pedestal if the
proper bearing fit is not achieved.
If bearing replacement is required, use a bearing
puller or an arbor (or hydraulic) press to remove
the bearings from the shaft.
To prevent damage during removal from
the shaft, it is recommended that bearings
be cleaned and inspected in place. It is
strongly recommended that the bearings
Shaft and Bearing Reassembly and Installation
Clean and inspect the bearings as indicated in
Shaft and Bearing Removal and Disassembly.
MAINTENANCE & REPAIRPAGE E − 6
Page 27
To prevent damage during removal from
the shaft, it is recommended that bearings
be cleaned and inspected in place. It is
strongly recommended that the bearings
be replaced any time the shaft and bear-
ings are removed.
Inspect the shaft for distortion, nicks or scratches,
or for thread damage on the impeller end. Dress
small nicks and burrs with a fine file or emery cloth.
Replace the shaft if defective.
The bearings may be heated to ease installation.
An induction heater, hot oil bath, electric oven, or
hot plate may be used to heat the bearings. Bearings should never be heated with a direct flame or
directly on a hot plate.
NOTE
If a hot oil bath is used to heat the bearings, both the
oil and the container must be absolutely clean. If
the oil has been previously used, it must be thor-oughly filtered.
Heat the bearings to a uniform temperature no
higher than 250_F (120_C), and slide the bearings
onto the shaft, one at a time, until they are fully
seated. This should be done quickly, in one continuous motion, to prevent the bearings from cooling and sticking on the shaft.
Use caution when handling hot bearings to prevent burns.
After the bearings have been installed and allowed
to cool, check to ensure that they have not moved
away from the shaft shoulders in shrinking. If
movement has occurred, use a suitable sized
sleeve and a press to reposition the bearings
against the shaft shoulders.
If heating the bearings is not practical, use a suitable sized sleeve and an arbor (or hydraulic) press
to install the bearings on the shaft until fully seated
OM−00711−0410 SERIES
against the shaft shoulders. Position the inboard
bearing on the shaft with the retaining ring facing
toward the impeller end of the shaft.
When installing the bearings onto the
shaft, never press or hit against the outer
race, balls, or ball cage. Press only on the
inner race.
Slide the shaft and assembled bearings into the
pedestal until the inboard bearing seats against
the pedestal bore.
When installing the shaft and bearings into
the bearing bore, push against the outer
race. Never hit the balls or ball cage.
Install the oil seal (36) in the bearing cap (38) with
the lip positioned as shown in Figure 1. Install the
bearing cap O-ring (37) in the bearing cap. Slide
the assembled bearing cap over the shaft and secure it to the pedestal (23) with the hardware (40
and 41). Be careful not to damage the oil seal lip.
Apply a light coating of soft grease on the bearing
retainer O-ring (26) and the O-ring groove. Install
the O-ring in the pedestal. Install the same thickness of bearing adjusting shim (25) as previously
removed.
Press the outboard oil seal (28) in the bearing retainer (32) with the lip positioned as shown in Figure E−1. Press the bearing retainer into the pedestal until it seats against the bearing. Be careful not
to damage the oil seal lip on the shaft keyway. Be
sure the machine screws and lockwashers (30 and
31) are fully screwed into the bearing retainer and
are positioned horizontally in line.
Using snap ring pliers, secure the bearing retainer
with the bearing retaining ring (27). Check the shaft
endplay.
NOTE
Shaft endplay should be between .002 and .010
inch (.05 to .25 mm). Add or remove bearing adjusting shims to achieve the correct endplay.
MAINTENANCE & REPAIRPAGE E − 7
Page 28
10 SERIESOM−00711−04
Lubricate the pedestal as indicated in LUBRICATION at the end of this section.
Seal Reassembly and Installation
Clean the seal cavity and shaft with a cloth soaked
in fresh cleaning solvent.
Most cleaning solvents are toxic and
flammable. Use them only in a well ventilated area free from excessive heat,
sparks, and flame. Read and follow all
precautions printed on solvent containers.
Inspect the impeller shaft for damage. Small
scratches or nicks may be removed with a fine file
or emery cloth. If excessive wear exists, the shaft
will have to be replaced.
The seal is not normally reused because wear patterns on the finished faces cannot be realigned
during reassembly. This could result in premature
failure. If necessary to reuse an old seal in an emer-
gency, carefully wash all metallic parts in fresh
cleaning solvent and allow to dry thoroughly.
Handle the seal parts with extreme care to prevent
damage. Be careful not to contaminate precision
finished faces; even fingerprints on the faces can
shorten seal life. If necessary, clean the faces with a
non-oil based solvent and a clean, lint-free tissue.
Wipe lightly in a concentric pattern to avoid
scratching the faces.
Inspect the seal components for wear, scoring,
grooves, and other damage that might cause leakage. Clean and polish the shaft sleeve (75), or replace it if there are nicks or cuts on either end. If any
components are worn, replace the complete seal;
never mix old and new seal parts.
If a replacement seal is being used, remove it from
the container and inspect the precision finished
faces to ensure that they are free of any foreign
matter.
To ease installation of the seal, lubricate the Orings, bellows and shaft sleeve with water or a very
small amount of oil, and apply a drop of light lubricating oil on the finished faces. Assemble the seal
as follows, (see Figure E−3).
MAINTENANCE & REPAIRPAGE E − 8
Page 29
OM−00711−0410 SERIES
SPRING CENTERING
WASHER
IMPELLER
SHIMS
IMPELLER
SPRING
BELLOWS
DRIVE BAND
RETAINER
ROTATING ELEMENT
SEAL PLATE
O-RINGS
SHAFT
SLEEVE
STATIONARY
SEAL SEAT
IMPELLER
SHAFT
OIL SEAL
STATIONARY
ELEMENT
Figure E−3. 12461B Seal Assembly
This seal is not designed for operation at
temperatures above 160_F (71_C). Do not
use at higher operating temperatures.
Install the slinger ring (42) on the shaft.
Place the seal plate on a flat surface with the impeller side up. Press the oil seal (43) into the seal plate
(12) with the lips positioned as shown in Figure
E−1.
Lightly lubricate the stationary seat O-rings with a
small amount of oil. Subassemble the stationary
element in the stationary seat with the chambered
side out. Press the stationary seat into the seal
plate until it bottoms against the seal plate bore. A
push tube cut from a length of plastic pipe would
aid this installation. The I.D. of the pipe should be
approximately the same diameter as the I.D. of the
seal spring.
Slide the seal plate over the shaft until fully seated
against the pedestal (23). Be careful not to damage the oil seal lip on the shaft threads.
Align the threaded seal lubricant hole in the seal
plate with the pedestal opening and temporarily
secure the seal plate using two capscrews and
nuts (1/2 UNC X 1-1/2 inch long, not supplied).
Slide the lubricated shaft sleeve (75) onto the shaft
and push it through the stationary seat and oil lip
seal. Be careful not to damage the oil seal lip.
Lightly lubricate the rotating subassembly (consisting of the rotating element, retainer and bellows) and press it onto the lubricated shaft sleeve.
Continue to push the subassembly until the seal
faces contact. Install the seal spring and the spring
centering washer.
After the impeller has been installed, reinstall the
bottle oiler and piping (16, 17, 18 and 19) and the
air vent and piping (13, 14 and 15) in the seal plate.
Lubricate the seal assembly as indicated in
LUBRICATION.
MAINTENANCE & REPAIRPAGE E − 9
Page 30
10 SERIESOM−00711−04
Impeller Installation And Adjustment
Inspect the impeller, and replace it if cracked or
badly worn. Install the same thickness of impeller
shims (74) as previously removed. Apply ‘NeverSeez’ or equivalent compound to the shaft threads
and screw the impeller onto the shaft until tight.
A clearance of .020 to .040 inch (0,51 to 1,02 mm)
between the impeller and the seal plate is necessary for maximum pump efficiency. Measure this
clearance and add or remove impeller shims until
this clearance is reached.
NOTE
Be sure the seal plate is tight against the pedestal
while measuring this clearance.
Apply a thin coat of ‘Never-Seez’ or equivalent
compound to the threads on the socket head capscrew (50) and install the capscrew and impeller
washer (49). Torque the impeller capscrew to 90 ft.
lbs. (1080 in. lbs. or 12,4 m. kg.)
After the face clearance has been set, tighten the
nuts (45) securing the pump casing to the pedestal.
Back Cover Installation
If the wear plate (47) was removed for replacement, secure it to the cover plate (53) using the attaching hardware (57 and 58). The wear plate must
be concentric to prevent binding when the back
cover is installed.
Clean any scales or debris from the contacting surfaces on the pump casing that might prevent a
good seal with the back cover. Replace the back
cover gasket (51) and slide the back cover assembly (52) into the pump casing. Be sure the wear
plate does not scrape against the impeller.
NOTE
To ease future disassembly, apply a film of grease
or ‘Never-Seez’ on the back cover shoulder, or any
surface that contacts the pump casing. This action
will reduce rust and scale build-up.
Pump Casing Installation
Remove the hardware temporarily securing the
seal plate to the pedestal. Install the same thickness of pump casing gaskets (11) as previously removed. Using a suitable hoist and sling, secure
the pump casing (1) to the seal plate (12) and pedestal (23) with the nuts (45). Do not fully tighten the
nuts at this time.
NOTE
It is recommended that the back cover be installed
now. The back cover assembly must be in place to
adjust the impeller face clearance.
A clearance of .008 to .015 inch (0,20 to 0,38 mm)
between the impeller and the wear plate (47) is also
recommended for maximum pump efficiency. Set
this clearance by adding or removing gaskets in
the pump casing gasket set (11) until the impeller
scrapes against the wear plate when the shaft is
turned. After the impeller scrapes, add approximately .008 inch (0,20 mm) of gaskets.
Secure the back cover assembly by installing the
clamp bar (60) and tightening the clamp bar screw
(59). Do not over-tighten the clamp bar screw; it
should be just tight enough to seal the back cover
shoulder.
Suction Check Valve Installation
Inspect the check valve components and replace
as required. Subassemble the check valve weights
(71 and 73) and check valve gasket (72) using the
attaching hardware (69 and 70).
Position the check valve assembly (68) in the
check valve seat (62) with the large weight toward
the inside of the pump casing. Install the check
valve seat gasket (61) and secure the valve seat to
the suction port with the machine screws (67).
NOTE
To ease future disassembly, apply a film of grease in
the valve seat slot for the check valve. This action
will help reduce rust and seizing.
Replace the suction flange gasket (63) and secure
the suction flange (64) with the nuts (66). Check
MAINTENANCE & REPAIRPAGE E − 10
Page 31
OM−00711−0410 SERIES
the operation of the check valve to ensure proper
seating and free movement.
Final Pump Assembly
Secure the pump to the base with the previously removed hardware. Be sure to reinstall any leveling
shims used under the pump mounting feet.
Install the shaft key (29) and secure the pump to
the power source with the previously removed
hardware. Be sure the pump and power source
are securely mounted to the base.
Install the suction and discharge lines and open all
valves. Make certain that all piping connections are
tight, properly supported and secure. Open all the
valves in the suction and discharge lines.
Be sure the pump and power source have been
properly lubricated, see LUBRICATION.
Bearings
The pedestal was fully lubricated when shipped
from the factory. Check the oil level regularly
through the sight gauge (33) and maintain it at the
middle of the gauge. When lubrication is required,
add SAE No. 30 non-detergent oil through the hole
for the air vent (22). Do not over-lubricate. Over-lubrication can cause the bearings to over-heat, resulting in premature bearing failure.
NOTE
The white reflector in the sight gauge must be positioned horizontally to provide proper drainage.
Under normal conditions, drain the pedestal once
each year and refill with clean oil to the middle of
the sight gauge. Change the oil more frequently if
the pump is operated continuously or installed in
an environment with rapid temperature change.
Remove the fill cover assembly (76) and fill the
pump casing with clean liquid. Reinstall the fill cover and tighten it.
Refer to OPERATION, Section C, before putting
the pump back into service.
LUBRICATION
Seal Assembly
Fill the bottle oiler (16) with SAE No. 30 non-detergent oil while venting the seal cavity at the air vent
(15). Check the oil level regularly and keep the
bottle oiler full.
Monitor the condition of the bearing lubricant regularly for evidence of rust or moisture condensation. This is especially important in areas where variable hot and
cold temperatures are common.
For cold weather operation, consult the factory or a
lubricant supplier for the recommended grade of
oil.
Power Source
Consult the literature supplied with the power
source, or contact your local power source representative.
MAINTENANCE & REPAIRPAGE E − 11
Page 32
For U.S. and International Warranty Information,
Please Visit www.grpumps.com/warranty
or call:
U.S.: 419−755−1280
International: +1−419−755−1352
For Canadian Warranty Information,
Please Visit www.grcanada.com/warranty
or call:
519−631−2870
THE GORMAN-RUPP COMPANY D MANSFIELD, OHIO
GORMAN-RUPP OF CANADA LIMITED D ST. THOMAS, ONTARIO, CANADA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.