STATUS CODES ....................................................................................................................................... 44
AIR FLOW DATA .................................................................................................................................... 45
Adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace.
To ensure proper installation and operation, thoroughly read
this manual for specifics pertaining to the installation and
application of this product.
Special Warning for Installation of Furnace or Air Handling Units in
Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide producing devices (such as an automobile, space
heater, ga s water heate r, etc.) should not be operat ed in enclosed areas
such as unventilated garages, utility rooms or parking areas because of
the danger of carbon monoxide (CO) poisoning resulting from the exhaust
emissions. If a furnace or air handler is installed in an enclosed area such
as a garage, utility room or parking area and a carbon monoxide producing
device is o perated therein, there must be adequate, direct outside
ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which
can occur if a carbon mono xide producing device continues to operat e in
the enclo sed area. Carb on monoxide emissions ca n be (re)circu lated
throughout the structure if the furnace or air handler is operating in any
mode.
CO can cause serious illness including permanent brain damage or death.
•This furnace is approved for Category I Venting only.
•Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in
locating the furnace.
SHIPPING I NSPECTION
All units are securely packed in shipping containers tested
according to International Safe Transit Association specifications. The carton must be checked upon arrival for external
damage. If damage is found, a request for inspection by carrier’s
agent must be made in writing immediately.
The furnace must be carefully inspected on arrival for damage
and bolts or screws which may have come loose in transit. In
the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible damage
to shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notified as soon
as possible - preferably within five days.
4. File the claim with the following support documents within
a nine month statute of limitations.
•Original or certified copy of the Bill of Lading, or
indemnity bond.
•Original paid freight bill or indemnity in lieu thereof.
•Original or certified copy of the invoice, showing trade
and other discounts or reductions.
•Copy of the inspection report issued by carrier’s
representative at the time damage is reported to carrier.
The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
Keep this literature in a safe place for future reference.
ELECTROSTATIC D ISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’s static electricity before touching unit.
An electrostatic discharge can adversely affect electrical components.
Use the following precautions during furnace installation and
servicing to protect the integrated control module from damage. By putting the furnace, the control, and the person at the
same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge.
This procedure is applicable to both installed and non-installed
(ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the
control prior to discharging your body’s electrostatic
charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnaces near the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting wiring
following the discharge process in step 2. Use caution
not to recharge your body with static electricity; (i.e., do
not move or shuffle your feet, do not touch ungrounded
objects, etc.). If you come in contact with an ungrounded
object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new
control from its container. Follow steps 1 through 3 if
installing the control on a furnace. Return any old or
new controls to their containers before touching any
ungrounded object.
TO T HE I NSTALLER
Before installing this unit, please read this manual thoroughly
to familiarize yourself with specific items which must be adhered to, including but not limited to: unit maximum external
static pressure, gas pressures, BTU input rating, proper electrical connections, circulating air temperature rise, minimum or
maximum CFM, and motor speed connections, and venting.
These furnaces are designed for Category I venting only.
IMPORTANT N OTETOTHE O WNER R EGARDING P RODUCT
WARRANTY
Complete warranty details and instructions are available from
your local dealer or at www.goodmanmfg.com and www.amanahac.com. Your warranty certificate is supplied as a separate
document with the unit installed by your contractor. Read the
limited warranty certificate carefully to determine what is and is
not covered and keep the warranty certificate in a safe place. If
you are unable to locate the warranty certificate please contact
your installing contractor or contact customer service (877-254-
4729) to obtain a copy.
To receive the Lifetime Heat Exchanger Limited Warranty, good
for as long as you own your home, and the 10-year Parts Limited Warranty, online registration must be completed within 60
days of installation. Online registration is not required in California or Quebec.
IMPORTANT: To register your Goodman brand unit, go to
www.goodmanmfg.com. Click on the word “Warranty” located
on the left side of the home page. Next, click on the word
“Product Registration” located on the left side of the Warranty
page and complete the forms in the manner indicated on the
Product Registration page.
To register your Amana brand unit, go to www.amana-hac.com.
Click on the word “Warranty” located on the top right of the
5
L
OCATION
R
EQUIREMENTS
AND
C
ONSIDERATIONS
home page. Next, click on the word “Product Registration”
located on the left side of the Warranty page and complete the
forms in the manner indicated on the Product Registration page.
Product limited warranty certificates for models currently in production can be viewed at
hac.com. If your model is not currently in production or does
not appear on the website, please contact your installing contractor or contact customer service at (877-254-4729) to obtain
a copy of your warranty certificate.
Each product overview page contains a Product Warranty link;
by clicking on it you will be able to view the limited warranty
coverage for that specific product. To view warranty registration
information, click on the Product Warranty text on the left navigation panel on the home page of each website. The Online
Product Registration pages are located in this same section.
This furnace is a part of the ComfortNet™ family of products.
The CTK01 ComfortNet thermostat kit allows this furnace to be
installed as part of a digitally communicating system. The
ComfortNet system provides automatic airflow configuration,
enhanced setup features, and enhanced diagnostics. It also
reduces the number of thermostat wires to a maximum of four.
It may be also installed as part of a “legacy” system using a
standard 24 VAC thermostat.
This product may also be installed with the ComfortNet thermostat and a non-ComfortNet compatible single stage air conditioning unit. However, this reduces the benefits of the
ComfortNet system as the enhancements will only apply to the
furnace.
•It must be installed per the installation instructions
provided and per local and national codes.
•It must be installed indoors in a building constructed
on site.
•It must be part of a ducted system and not used in a
free air delivery application.
•It must not be used as a “make-up” air unit.
•All other warranty exclusions and restrictions apply.
This furnace may be used as a construction site heater ONLY
if the following conditions are met:
•The vent system is permanently installed per these
installation instructions.
•A room thermostat is used to control the furnace. Fixed
jumpers that provide continuous heating CANNOT be
used.
•Return air ducts are provided and sealed to the furnace.
•A return air temperature range between 60ºF (16ºC)
and 80ºF (27ºC) is maintained.
•Air filters are installed in the system and maintained
during construction, replaced as appropriate during
construction, and upon completion of construction are
replaced.
•The input rate and temperature rise are set per the
furnace rating plate.
•100% outside air is provided for combustion air
requirements during construction. Temporary ducting
can be used.
NOTE: Do not connect the temporary duct directly to
the furnace. The duct must be sized for adequate
combustion and ventilation in accordance with the
latest edition of the National Fuel Gas Code NFPA 54/
ANSI Z223.1 orCAN/CSA B149.1 Installation Codes.
•The furnace heat exchanger, components, duct
system, air filters and evaporator coils are thoroughly
cleaned following final construction clean up.
•All furnace operating conditions (including ignition, input
rate, temperature rise and venting) are verified
according to these installation instructions.
P
RODUCT APPLICATION
This furnace is primarily designed for residential home-heating
applications. It is NOT designed or certified for use in mobile
homes, trailers or recreational vehicles. Neither is it designed
or certified for outdoor applications. The furnace must be installed indoors (i.e., attic space, crawl space, or garage area
provided the garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial commercial applications:
To ensure proper furnace operation, install, operate and
maintain the furnace in accordance with these installation and operation instructions, all local building codes
and ordinances. In their absence, follow the latest edition of
the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or
CAN/CSA B149 Installation Codes, local plumbing or waste
water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1)
can be obtained from any of the following:
American National Standards Institute
1430 Broadway
New York, NY 10018
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
A copy of the CAN/CSA B149 Installation Codes can also be
obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved method
or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Contractors of
America.
In the USA, this furnace MUST be installed in accordance with
the latest edition of the ANSI Z223.1 booklet entitled “National
Fuel Gas Code” (NFPA 54), and the requirements or codes of
the local utility or other authority having jurisdiction. In Canada,
this furnace must be installed in accordance with the current
CAN/CGA-B149.1 & 2 Gas Installation Codes, local plumbing
or waste water codes and other applicable codes. Additional
helpful publications available from the NFPA are, NFPA 90A Installation of Air Conditioning and Ventilating System and NFPA
90B - Warm Air Heating and Air Conditioning System.
All venting shall be in accordance with PART 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1, or applicable local building and/or air conditioning codes. These publications are available from:
National Fire Protection Association, Inc.
Batterymarch Park, Quincy, MA 02269
NOTE: Furnaces with NOx screens meet the California NOx
emission standards and California seasonal efficiency standards. ANNUAL inspections of the furnace and its vent system
is strongly recommended.
L
OCATION REQUIREMENTS AND CONSIDERATIONS
Your unit model type determines which installation procedures
must be used. For *MVC8 models, you must follow instructions for Horizontal Left, Horizontal Right or Upflow installations only. These furnaces are not approved for Downflow installations.
Downflow models *DVC8 ARE NOT APPROVED FOR HORI-ZONTAL OR UPFLOW INSTALLATIONS. For these models,
use only the instructions for downflow installation only.
Follow the instructions listed below when selecting a furnace
location. Refer also to the guidelines provided in Section V,
Combustion and Ventilation Air Requirements.
•Centrally locate the furnace with respect to the
proposed or existing air distribution system.
•Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.
•Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in
locating the furnace.
•Ensure adequate combustion air is available for the
furnace. Improper or insufficient combustion air can
expose building occupants to gas combustion products
that could include carbon monoxide. Refer to
Combustion and Ventilation Air Requirements section.
•The furnace must be level. If the furnace is to be set
on a floor that may become wet or damp at times, the
furnace should be supported above the floor on a
concrete base sized approximately 1-1/2" larger than
the base of the furnace.
•Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible
material. The only combustible material allowed is
wood.
•Exposure to contaminated combustion air will result
in safety and performance-related problems. Do not
install the furnace where the combustion air is exposed
to the following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
.
,
7
L
V
OCATION
R
EQUIREMENTS
AND
C
ONSIDERATIONS
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
•If the furnace is used in connection with a cooling unit,
install the furnace upstream or in parallel with the
cooling unit coil. Premature heat exchanger failure
will result if the cooling unit coil is placed ahead of the
furnace.
•If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)
above the floor. Protect the furnace from physical
damage by vehicles.
•If the furnace is installed horizontally, the furnace
access doors must be vertical so that the burners fire
horizontally into the heat exchanger. Do not install
the unit with the access doors on the “up/top” or “down/
bottom” side of the furnace.
•Do not connect this furnace to a chimney flue that
serves a separate appliance designed to burn solid
fuel.
•For counterflow installations, the air conditioning coil
must be downstream from the heat exchanger of the
furnace.
•Counterflow installation over a noncombustible floor.
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth and
level. A tight seal should be made between the furnace
base and floor by using a silicon rubber caulking
compound or cement grout.
•Counterflow installation over a combustible floor. If
installation over a combustible floor becomes
necessary, use an accessory subbase (see
Specification Sheet applicable to your model for details).
A special accessory subbase must be used for upright
counterflow unit installations over any combustible
material including wood. Follow the instructions with
the subbase for proper installations. Do not install the
furnace directly on carpeting, tile, or other combustible
material other than wood flooring. (NOTE: The subbase
will not be required if an air conditioning coil is installed
between the supply air opening on the furnace and the
floor.
ent Pipe Clearance to Combustibles6" using Single Wall Connector or 1"
using B-1 vent.
Top - 1"
Back - 0"
Side
Clearance - 1"
Front Clearance - 3"
•Adequate combustion/ventilation air must be supplied
to the closet.
•Furnace must be completely sealed to floor or base.
Combustion/ ventilation air supply pipes must
terminate 12" from top of closet and 12" from floor of
closet. DO NOT remove solid base plate for side
return.
•Return air ducts must be completely sealed to the
furnace and terminate outside the enclosure surfaces.
CLEARANCESAND A CCESSIBILITY
Unobstructed front clearance of 24" for servicing is recom-
mended.
VENT
B1-VENT SINGLE
1"6"1"3"0"1"
Top clearance for horizontal configuration - 1"
SIDESFRONTBACK
TOP
(PLENUM)
HORIZONTAL I NSTALLATION (*MVC8 MODELS O NLY)
Line contact to framing is permitted when installed in the horizontal configuration. Line contact is defined as the portion of
the cabinet that is formed by the intersection of the top and
side. ACCESSIBILITY CLEARANCE, WHERE GREATER,
SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE PROTECTION CLEARANCE. A gas-fired furnace for installation in
a residential garage must be installed so that the ignition source
and burners are located not less than eighteen inches (18")
above the floor and is protected or located to prevent physical
damage by vehicles. A gas furnace must not be installed directly on carpeting, tile, or other combustible materials other
than wood flooring.
FURNACE S USPENSION
If suspending the furnace from rafters or joist, use 3/8" threaded
rod and 2”x2”x3/8” angle iron as shown below. The length of
rod will depend on the application and the clearances necessary.
8
C
OMBUSTION
Suspended Furnace
& V
ENTILATION
C
ATEGORY
EXISTING F URNACE R EMOVAL
NOTE: When an existing furnace is removed from a venting
system serving other appliances, the venting system may be
too large to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the
American National Standard/National Standard of Canada
for Gas-Fired Central Furnaces ANSI Z21.47-Latest Edition, CSA-2.3-Latest Edition Section 1.23.1. The following
steps shall be followed with each appliance connected to the
venting system placed in operation, while any other appliances
connected to the venting system are not in operation:
a.Seal any unused openings in the venting system;
b.Inspect the venting system for proper size and
horizontal pitch, as required by the National Fuel Gas
Code, ANSI Z223.1 or the CAN/CSA B149 Installation
Codes and these instructions. Determine that there is
no blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition;
c.In so far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building. Turn on
clothes dryers and any appliance not connected to
the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they shall
operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers;
d.Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously;
e.Test for draft hood equipped appliance spillage at the
draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle;
f.After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas
burning appliance to their previous conditions of use;
I V
ENTING
g.If improper venting is observed during any of the above
tests, the common venting system must be corrected.
Corrections must be in accordance with the latest edition of
the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or CAN/
CSA B149 Installation Codes.
If resizing is required on any portion of the venting system, use
the appropriate table in Appendix G in the latest edition of the
National Fuel Gas Code ANSI Z223.1 and/or CAN/CSA B149
Installation Codes.
AIR R
EQUIREMENTS
THERMOSTAT L OCATION
In an area having good air circulation, locate the thermostat
about five feet high on a vibration-free inside wall. Do not install
the thermostat where it may be influenced by any of the following:
•Drafts, or dead spots behind doors, in corners, or under
cabinets.
•Hot or cold air from registers.
•Radiant heat from the sun.
•Light fixtures or other appliances.
•Radiant heat from a fireplace.
•Concealed hot or cold water pipes, or chimneys.
•Unconditioned areas behind the thermostat, such as
an outside wall.
HOT
COLD
Thermostat Influences
Consult the instructions packaged with the thermostat for mounting instructions and further precautions.
Improved construction and additional insulation in buildings have
reduced heat loss by reducing air infiltration and escape around
doors and windows. These changes have helped in reducing
.M
OSTHOMESREQUIREOUTSID EAIRBE
.
,
9
E
XTERIOR MASONRY CHIMNEYS
- C
ATEGORY
I F
URNACES
O
NLY
heating/cooling costs but have created a problem supplying
combustion and ventilation air for gas fired and other fuel burning appliances. Appliances that pull air out of the house (clothes
dryers, exhaust fans, fireplaces, etc.) increase the problem by
starving appliances for air.
House depressurization can cause back drafting or improper
combustion of gas-fired appliances, thereby exposing building
occupants to gas combustion products that could include carbon monoxide.
If this furnace is to be installed in the same space with other
gas appliances, such as a water heater, ensure there is an
adequate supply of combustion and ventilation air for the other
appliances. Refer to the latest edition of the National Fuel Gas
Code NFPA 54/ANSI Z223.1 or CAN/CSA B149 Installation
Codes or applicable provisions of the local building codes for
determining the combustion air requirements for the appliances.
This furnace must use indoor air for combustion. It cannot be
installed as a direct vent (i.e., sealed combustion) furnace.
Most homes will require outside air be supplied to the furnace
area by means of ventilation grilles or ducts connecting directly
to the outdoors or spaces open to the outdoors such as attics
or crawl spaces.
C
ATEGORY
I V
ENTING
(V
ERTICAL VENTING
)
MINIM UM VENT
MODEL
UPFLOW COUNTERFLOW
704 inch4 inch
904 inch4 inch
1155 inch4 inch
Under some conditions, larger vents than those shown above
may be required or allowed. When an existing furnace is re-moved from a venting system serving other appliances, the
venting system may be too large to properly vent the remaining
attached appliances.
Upflow or Horizontal units are shipped with the induced draft
blower discharging from the top of the furnace. (“Top” is as
viewed for an upflow installation.) The induced draft blower can
be rotated 90 degrees for Category I venting. For horizontal
installations, a four inch single wall pipe can be used to extend
the induced draft blower outlet 1/2” beyond the furnace cabinet.
THIS PRODUCT IS NOT DESIGNED FOR COUNTERCLOCKWISE INDUCED DRAFT BLOWER ROTATION.
Vent the furnace in accordance with the National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition. In Canada, vent
the furnace in accordance with the National Standard of Canada,
CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and
amendments.
Venting
WARNING
TO
PREVENTPOSSIBLEPERSONALINJURYORDEATHDUETO
ASPHYXIATION,THISFURNACEMUSTBECATEGORY
VENTUSINGCATEGORY
Category I Venting is venting at a non-positive pressure. A
furnace vented as Category I is considered a fan-assisted appliance and the vent system does not have to be “gas tight.”
NOTE: Single stage gas furnaces with induced draft blowers
draw products of combustion through a heat exchanger allowing, in some instances, common venting with natural draft appliances (i.e. water heaters). All installations must be vented in
accordance with National Fuel Gas Code NFPA 54/ANSI Z223.1
- latest edition. In Canada, the furnaces must be vented in accordance with the National Standard of Canada, CAN/CSA
B149.1 and CAN/CSA B149.2 - latest editions and amendments.
NOTE: The vertical height of the Category I venting system
must be at least as great as the horizontal length of the venting
system.
The minimum vent diameter for the Category I venting system
is as shown:
.
THIS FURNACE IS NOT DESIGN CERTIFIED TO BE HORIZONTALLY VENTED.
To rotate the induced draft blower clockwise, you will need to
purchase one (0270F01119) chimney transition bottom kit.
1. Disconnect electrical power from the furnace.
2. Disconnect the induced draft blower power leads, flue
pipe, and pressure switch tubing.
3. Remove the round cutout from the right side of the wrapper.
4. Remove and save the four screws that fasten the induced
draft blower to the flue collector box.
5. Remove and save the three screws that hold the chimney
assembly to the induced draft blower.
6. Remove and save the four screws that fasten the chimney
top to the chimney bottom.
7. Remove the chimney transition bottom from the transition
bottom kit.
8. Install the chimney top with the four screws retained
from step 6 onto the new chimney transition bottom from
the transition bottom kit.
9. Install chimney assembly with the three screws retained
from step 5 onto the induced draft blower.
10. Reinstall the induced draft blower rotating it 90 degrees
clockwise from the original upflow configuration using
the four screws retained in step 3. Ensure the gasket
located between the induced draft blower and the collector
box is rotated accordingly.
10
E
XTERIOR MASONRY CHIMNEYS
- C
ATEGORY
I F
URNACES
O
NLY
11. Reconnect the induced draft blower power leads. NOTE:
If the wires are not long enough, pull extra wire from the
wire bundle in the blower compartment.
12. Reconnect the flue pipe, and the pressure switch tubing.
Ensure that all wires and the pressure switch tubing is
at least one inch from the flue pipe, or any other hot
surface.
13. Restore power to furnace.
Counterflow units are shipped with the induced draft blower
discharging from the top of the furnace. (“Top” as viewed for a
counterflow installation.)
Vent the furnace in accordance with the National Fuel Gas
Code NFPA54/ANSI Z223.1-latest edition. In Canada, vent the
furnace in accordance with the national standard of Canada,
CAN/CSA B149.1 and CAN/CSA B149.2- latest editions and
amendments.
WARNING
N
EVERALLOWTHEPRODUCTSOFCOMBUSTION,INCLUDINGCARBO N
An exterior masonry chimney is defined as a “Masonry” chimney exposed to the outdoors on one or more sides below the
roof line.” The ability to use a clay lined masonry chimney
depends on a parameter not associated with interior chimneys.
This variable is the geographic location of the installation. Researchers have discovered that the winter design temperatures
have a direct impact on the suitability of this type of venting. In
most situations, the existing masonry chimneys will require a
properly sized metallic liner.
WARNING
Was h
Roof Line
Clay Tile Size: 8" x 8" x12"
(Each x 24" Length )
Attic Floor
1/2" to 1" Air Space
Second Floor
Throat
Damper
Breech
Fan Assisted
Clean Out
Typical Multiple Flue Clay Tile Chimney
Forced Air
Furnace
F.A .F. Ve nt
Connector
First Flo or
Water Heater
Vent Connect or
Natural Draft
Wate r Heat er
Basement Floor
CHECKLIST S UMMARY
This checklist serves as a summary of the items to be checked
before venting an 80+ furnace into a masonry chimney. In addition, we recommend that a qualified serviceman use this check-
)
list to perform a yearly inspection of the furnace venting system.
This checklist is only a summary. For detailed information on
each of the procedures mentioned, see the paragraph referenced with each item.
This inspection is based upon a draft topical report, “Masonry
Chimney Inspection and Relining”, issued by the Gas Research
Institute. While not yet finalized, we believe this report represents the best information on this subject which is currently
available.
If the chimney does not meet these termination requirements,
but all other requirements in the checklist can be met, it may
be possible for a mason to extend the chimney. If this will not
be practical, see Fix 1.
10' or Less
2' Min.
2' Min.
Wall or
Parapet
Chimney
10' or Less
2' Min.
Chimney
3' Min.
3' Min.
Liner in good
condition?
(Check 5)
Dilution air
available?
(Check 6)
Reline
(Fix 4)
Reline
(Fix 4)
Complete the
installation.
(Check 7)
CHECK 1 - PROPERCHIMNEYTERMINATION.
A masonry chimney used as a vent for gas fired equipment
must extend at least three feet above the highest point where it
passes through the roof. It must extend at least two feet higher
than any portion of a building within a horizontal distance of 10
feet. In addition, the chimney must terminate at least 3 feet
above any forced air inlet located within 10 feet. The chimney
must extend at least five feet above the highest connected equipment draft hood outlet or flue collar.
Termination 10 Feet Or Less From Ridge, Wall or Parapet
More than 10’
3’ Min.
NOTE:
No Height
above parapet
Wall or
Parapet
Ridge
Termination More Than 10 Feet From Ridge, Wall or Parapet
required when distance
from walls or parape t is
more than 10 feet.
More than 10’
Chimney
10’
2” Min.
Chimney
Height above any
roof surface within
10 feet horiz ontally.
3’ Min.
CHECK 2 - ANY S OLIDOR L IQUID F UEL A PPLIANCES V ENTED
THIS C HIMNEY C HANNEL
INTO
Solid fuel appliances include fireplaces, wood stoves, coal furnaces, and incinerators.
12
E
XTERIOR MASONRY CHIMNEYS
- C
ATEGORY
I F
URNACES
O
NLY
Liquid fuel appliances include oil furnaces, oil-fired boilers and
oil-fired water heaters.
Appliances which burn propane (sometimes referred to as LP
(liquefied petroleum)) gas are considered gas-fired appliances.
CHECK 3 - CHIMNEY C ROWN C ONDITION.
Damage from condensate usually shows up first in the crown.
If any of the following trouble signs are present, the condition of
the crown is not satisfactory:
a) Crown leaning
b) Bricks missing
c) Mortar missing
d) Tile liner cracked
e) No tile liner
f)Salt staining at mortar joints. (White stains, and mortar
becomes sandy and/or erodes.)
For problems a, b, or c, see Fix 3. If problems d, e, or f are
present, see Fix 4. IMPORTANT: It may be necessary to follow
both Fix 3 and Fix 4.
CHECK 4 - DEBRISIN C LEANOUT.
A cleanout (dropleg) must be present such that the upper edge
of the cleanout cover is at least 12 inches below the lower edge
of the lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked
by debris. If no cleanout is present, the chimney must be relined (Fix 4). Remove the cleanout cover, and examine the
cleanout for debris. If significant amounts of any of the following
are found:
•Fuel oil residue
•Bricks
•Mortar or sand
•Pieces of the tile liner
•Rusted pieces of the metallic liner - reline the chimney
(Fix 4).
CHECK 5 - LINER C ONDITION.
If a metal liner is present, it must be checked. It cannot be
assumed that all existing metal liners are correctly installed
and in good condition.
Remove the lowest existing vent connector, and examine the
inside of the elbow or tee at the base of the liner. A small amount
of soot may be considered acceptable, provided the installer
vacuums it away. If rusted pieces of the liner have collected
here, the metal liner must be removed and replaced (Fix 4).
Next, gently tap the inside of the liner with a Phillips screwdriver. If the screwdriver perforates the liner, or if the tapping
does not sound like metal hitting metal, the liner must be removed and replaced (Fix 4).
Remember that all appliances must be vented inside the liner.
Venting one appliance inside the liner and another appliance
outside the liner is not acceptable.
Next, use a flashlight and small mirror to sight up the liner. B
vent must be supported so as to not come into direct contact
with the chimney walls or tile liner. If it is not, it can probably be
rehung so as to be acceptable. A thimble or fire stop may be
helpful here.
Flexible liners should be hung straight or nearly straight. If it is
spiraled in the chimney and in good condition, it should be
rehung. To do this, break the top seal; pull up and cut off the
excess liner length, and refit the top seal. Use caution when
doing this, as the cut edges of flexible liners may be sharp.
The surfaces of the liner must be physically sound. If gaps or
holes are present, the metal liner must be removed and replaced (Fix 4). Finally, confirm that the metal liner is the correct size for the appliances to be installed. Use the GAMA
tables and rules.
If a metal liner is not present, a clay tile liner must be present,
or the chimney must be lined (Fix 4).
Use a flashlight and small mirror at the cleanout or vent connector to inspect the clay tile liner. If any of the following problems are present:
•Tile sections misaligned
•Tile sections missing
•Gaps between tile sections
•Signs of condensate drainage at the cleanout or vent
connectors
•Mortar protruding from between tile sections
•Use of sewer pipe or drainage pipe rather than an
approved fire clay tile reline the chimney (Fix 4).
Next, measure the size of the liner. It may be possible to do
this from the cleanout. The liner must be at least as large as
the minimum size established by the tables in National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the
National Standard of Canada, CAN/CSA B149.1 and CAN/CSA
B149.2 - latest editions and amendments. If the liner is too
small or too large, then the chimney must be relined (Fix 4).
CHECK 6 - DILUTION A IR.
If gas-fired appliances are to be vented into a clay tile liner, a
source of dilution air is required.
Dilution air cannot be obtained through:
•Induced draft appliances
•Natural draft appliances with vent dampers
Sufficient dilution air can ordinarily be obtained through the draft
hood of a natural draft appliance only if the appliance’s vent
connector does not include a vent damper. If dilution air will not
be available, the chimney must be relined (Fix 4).
CHECK 7 - COMPLETETHE I NSTALLATION.
If Checks 1 through 6 have been satisfactory, and the liner is an
acceptable size as determined by the tables in National Fuel
13
E
LECTRICAL
C
ONNECTIONS
Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the
National Standard of Canada, CAN/CSA B149.1 and CAN/CSA
B149.2 - latest editions and amendments, then the clay tile
liner can probably be used as a vent for the gas appliances.
However, the installer must keep in mind the following factors
which may render the tile liner unsuitable for use as a vent:
•Extremely cold weather
•Long vent connectors
•Masonry chimneys with no air gap between the liner
and the bricks. (In practice, this can be difficult to
detect.)
•Exterior chimneys (The tables in National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition and in the
National Standard of Canada, CAN/CSA B149.1 and
CAN/CSA B149.2 - latest editions and amendments
assume interior chimneys.)
If, in the judgment of the local gas utility, installer, and/or local
codes; one or more of the above factors is likely to present a
problem, the chimney must be relined (Fix 4).
FIX 1 - LINER T ERMINATION
Any cap or roof assembly used with a liner must be approved
by the liner manufacturer for such use. The liner and cap/roof
assembly must then terminate above the roof in accordance
with the manufacturer’s instructions.
In some cases, a shorter extension above the roof may be
possible with a liner than would be required with a masonry
chimney.
For further information on relining, see Fix 4.
FIX 2 -CHANGE V ENTING A RRANGEMENTS
If the masonry chimney has more than one channel, it may be
possible to vent the gas appliances into one channel and vent
the solid or liquid fuel appliance(s) into another channel(s). Do
not vent an 80+ Furnace inside of a metal liner with other appliances vented outside the liner.
Alternatively, the homeowner may agree to discontinue use of
the fireplace (solid fuel appliance). If so, the tile liner must be
cleaned to remove creosote buildup. The fireplace opening must
then be permanently sealed.
If oil-fired appliance(s) are being replaced by gas-fired
appliance(s), the tile liner must first be cleaned to remove the
fuel oil residue.
If none of the above options is practical, the furnace may need
to be vented vertically with a B Vent.
Under some conditions, a 90%+ furnace could be installed rather
than an 80% furnace. The 90%+ furnace can be vented horizontally or vertically through PVC pipe.
FIX 3 - REBUILDTHE C ROWN
If the chimney crown is damaged, a qualified mason must repair it in accordance with nationally recognized building codes
or standards. One such standard which may be referenced is
the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel
Burning Appliances, ANSI/NFPA 211.
FIX 4 - RELINING
Relining options include B vent and flexible liners.
If the chimney has diagonal offsets, B vent probably cannot be
used.
If B vent is to be used, it must be supported adequately. Supports (such as fire stops or thimbles) must be used to prevent
the B vent from coming into direct contact with the tile liner or
chimney walls. Direct contact would result in higher heat loss,
with an increased possibility of poor venting system performance.
It is not acceptable to vent one appliance inside the B vent and
other appliances outside. The excess space between the B
vent and the chimney walls must be covered at the top of the
chimney by a weatherproof, corrosion resistant flashing.
The B vent should then be topped with a listed vent cap. The
listed vent cap will, when installed per the manufacturer’s instructions, prevent problems due to rain, birds, or wind effects.
A B-vent installed as described in this section is considered to
be an enclosed vent system, and the sizing tables in National
Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in
the National Standard of Canada, CAN/CSA B149.1 and CAN/
CSA B149.2 - latest editions and amendments may be used.
If a flexible liner is to be used, it must be made of the proper
materials:
•For most residential applications, an aluminum liner
should be acceptable.
•If the combustion air supplied to the furnace will be
contaminated with compounds containing chlorine or
fluorine, a liner of AL 29-4C stainless steel should be
used. Common sources of chlorine and fluorine
compounds include indoor swimming pools and
chlorine bleaches, paint strippers, adhesives, paints,
varnishes, sealers, waxes (which are not yet dried)
and solvents used during construction and remodeling.
Various commercial and industrial processes may also
be sources of chlorine/fluorine compounds.
•Heavier gauge 300 and 400 series stainless steel liners
were developed for use with oil or solid fuel appliances.
They are not suitable for use with gas-fired appliances.
Flexible liners specifically intended and tested for gas
applications are listed in the UL “Gas and Oil
Equipment Directory”. (UL Standard 1777).
For sizing of flexible liners, see Note 22 and the tables in the
National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition
14
E
LECTRICAL
C
ONNECTIONS
and in the National Standard of Canada, CAN/CSA B149.1 and
CAN/CSA B149.2 - latest editions and amendments.
To install the liner, read and follow the liner manufacturer’s instructions and your local codes. Excess liner length should be
pulled out of the chimney and cut off. Use caution when doing
this, as the cut edges of flexible liners may be sharp. Do not
spiral excess liner inside of the chimney. Support the liner as
recommended by the liner manufacturer.
Some manufacturers of flexible liners offer an insulation sleeve
designed to be added to the liner before it is installed in the
chimney. (Poured insulation, either vermiculite or other materials, is no longer recommended.) Insulation will need to be added
to the flexible liner if:
•It is required by the liner manufacturer’s instructions.
•The previous liner was properly sized and installed,
and suffered from condensation damage.
•It is required by your local building codes.
Even if none of those three conditions exist which require additional liner insulation, the installer may wish to consider it if:
•The local climate is very cold.
•The chimney is very tall.
•The vent connectors used are very long or have a large
number of elbows.
•Local experience indicates that flexible liners installed
without insulation are likely to have condensation
problems.
Insulation must be selected and installed in accordance with
the liner manufacturer’s instructions.
Finally, cap the chimney and terminate the liner in accordance
with the liner manufacturer’s instructions.
E
LECTRICAL CONNECTIONS
WARNING
HIGHVOLTAGE!
TO
AVOIDTHERISKOFELECTRICALSHOCK,WIRINGTO
THEUNITMUSTBEPOLARIZEDANDGROUNDED
.
WARNING
HIGHVOLTAGE!
TO
AVOIDPERSONALINJURYORDEATHDUETO
ELECTRICALSHOCK,DISCONNECTELECTRICALPOWER
BEFORESERVICINGORCHANGINGANYELECTRICAL
WIRING
.
WARNING
HIGHVOLTAGE!
TO
AVOIDTHERISKOFINJURY,ELECTRICALSHOCKOR
DEATH,THEFURNACEMUSTBEELECTRICALLY
GROUNDEDINACCORDANCEWITHLOCALCODESORIN
THEIRABSENCE,WITHTHELATESTEDITIONOFTHE
ATIONALELECTRICCODE
N
.
WIRING H ARNESS
The wiring harness is an integral part of this furnace. Field
alteration to comply with electrical codes should not be required. Wires are color coded for identification purposes. Refer to the wiring diagram for wire routings. If any of the original
wire as supplied with the furnace must be replaced, it must be
replaced with wiring material having a temperature rating of at
least 105° C. Any replacement wiring must be a copper conductor.
115 VOLT L INE C ONNECTIONS
Before proceeding with electrical connections, ensure that the
supply voltage, frequency, and phase correspond to that specified on the unit rating plate. Power supply to the furnace must
be NEC Class 1, and must comply with all applicable codes.
The furnace must be electrically grounded in accordance with
local codes or, in their absence, with the latest edition of The
National Electric Code, ANSI NFPA 70 and/or The Canadian
Electric Code CSA C22.1.
Use a separate fused branch electrical circuit containing properly sized wire, and fuse or circuit breaker. The fuse or circuit
breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating plate. An electrical disconnect must be provided at the furnace location.
Connect hot, neutral, and ground wires as shown in the wiring
diagram located on the unit’s blower door.
Line polarity must be observed when making field connections.
Line voltage connections can be made through either the right
or left side panel. The furnace is shipped configured for a right
side electrical connection with the junction box located inside
the burner compartment (blower compartment for downflows).
To make electrical connections through the opposite side of
the furnace, the junction box must be relocated to the other
side of the burner (or blower) compartment prior to making
electrical connections. To relocate the junction box, follow the
steps shown below.
NOTE: Wire routing must not to interfere with circulator blower
operation, filter removal, or routine maintenance.
Line voltage connections can be made through either the right
or left side panel. The furnace is shipped configured for a right
side electrical connection. To make electrical connections
through the opposite side of the furnace, the junction box must
be relocated to the left side prior to making electrical connections. To relocate the junction box, perform the following steps.
2. Remove and save the screws holding the junction box to
the right side of the furnace.
3. Models that have the junction box located in the burner
or blower compartment will need to move the junction
box directly over.
4. Attach the junction box to the left side of the furnace,
using the screws removed in step 2.
5. Check the location of the wiring. Confirm that it will not
be damaged by heat from the burners or by the rotation
of the fan. Also confirm that wiring location will not
interfere with filter removal or other maintenance.
After the junction box is in the desired location, use washers to
connect field-supplied conduit to the junction box in accordance
with NEC and local codes. Connect hot, neutral, and ground
wires as shown in the furnace wiring diagram. The wires and
ground screw are located in the furnace junction box.
NOTE: In downflow applications the power leads should be
routed through the supplied wire tabs when locating junction
box to the left side.
Low voltage wires may be connected to the terminal strip.
IMPORTANT NOTE: To avoid possible equipment malfunction,
route the low voltage wires to avoid interference with filter removal or other maintenance.
WARNING
HIGHVOLTAGE!
TO
AVOIDTHERISKOFINJURY,ELECTRICALSHOCKOR
DEATH,THEFURNACEMUSTBEELECTRICALLY
GROUNDEDINACCORDANCEWITHLOCALCODESORIN
THEIRABSENCE,WITHTHELATESTEDITIONOFTHE
ATIONALELECTRICCODE
N
.
To ensure proper unit grounding, the ground wire should run
from the furnace ground screw located inside the furnace junction box all the way back to the electrical panel. NOTE: Do
not use gas piping as an electrical ground. To confirm proper
unit grounding, turn off the electrical power and perform the
following check.
1. Measure resistance between the neutral (white)
connection and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch
which interrupts unit voltage when the blower door is opened for
servicing. Do not defeat this switch.
As a two-stage non-communicating furnace, the furnace integrated control module provides terminals for both “W1” and “W2”,
and “Y1” and “Y2” thermostat connections. This allows the
furnace to support the following system applications: ‘TwoStage Heating Only’, ‘Two-Stage Heating with Single Stage Cooling’, and ‘Two-Stage Heating with Two-Stage Cooling’. Refer to
the following figures for proper connections to the integrated
control module.
Low voltage connections can be made through either the right
or left side panel. Thermostat wiring entrance holes are located
in the blower compartment. The following figure shows connections for a “heat/cool system”.
This furnace is equipped with a 40 VA transformer to facilitate
use with most cooling equipment. Consult the wiring diagram,
located on the blower compartment door, for further details of
115 Volt and 24 Volt wiring.
NOTE: For single stage cooling applications, a jumper must
be located between Y1 and Y2 at the furnace control in order
to achieve the desired single stage cooling airflow. Use of
ramping profiles and dehumidification features require a
jumper between Y1 and O and Y1 and DEHUM, respectively.
NOTE: Thermostat “R” required if outdoor unit is equipped
with a Comfort Alert™ module or if the out door unit is a part
of the ComfortNet™ family of equipment AND is wired as a
legacy system.
.
,
16
E
)
NOFF
LECTRICAL
C
ONNECTIONS
Thermostat
R
R
YC
Remote
Condensing Unit
(Single-Stage Cooling)
Single Stage Heating with Si ngle St age Cooling
To apply a single-stage Heating Thermostat,
NOTE:
the thermostat selector switch on the
Integrated Control Module be set on
single-stage.
R
R
YC
Remote
Condensing Unit
(Single-Stage Cooling)
Single Stage Heating with
Single Stage Cooling
Furnace Integrated
NEU
Dehumidistat
[Optional]
must
Thermostat
Two-Stage Heati ng
Single-Stage Cooling
Furnace Integrated
Control Module
NEU
Dehumidistat
[Optional]
Control Module
with
DIP switch to the desired ON/OFF position. Turn power back
on. Refer to the following figure.
Heat OFF Delay
DIP Switches
ONOFF
3
4
Thermostat
Stage Delay
S1
Move to the ON position
to select two-stage
thermostat or OFF to
select single stage
thermostat
Move to the ON position
to select Auto transition
delay or OFF for 5 minute
transition delay
24 VOLT D EHUMIDISTAT W IRING
The optional usage of a dehumidistat allows the furnace’s
circulator blower to operate at a slightly lower speed (85%
of desired speed) during a combined thermostat call for cooling and dehumidistat call for dehumidification. This can be
done through an independent dehumidistat or through a
thermostat’s DEHUM terminal (if available). This lower blower
speed enhances dehumidification of the conditioned air as
it passes through the AC coil. For proper function, a dehumidistat applied to this furnace must operate on 24 VAC
and utilize a switch which opens on humidity rise. Refer to
the “Thermostat Wiring Diagrams” figure for additional wiring details.
Two-Stage Heating with Single-Stage Cooling
Thermostat
Y2
Y2
Y2
Remote
Condensing Unit
(Two-Stage Cooling)
Two-Stage Heating with Two-Stage Cool ing
W1 W2
W1 W2
NEU
Two-Stage Heati ng
(
Two-Stage Cooling
Furnace Integrated
Dehumidistat
[Optional]
with
Control Module
Thermostat Wiring Diagrams
SINGLE-STAGE H EATING T HERMOSTAT A PPLICATION
A single-stage thermostat with only one heating stage may be
used to control this furnace. The application of a single-stage
thermostat offers a timed transition from low to high fire. The
furnace will run on low stage for a fixed period of time before
stepping up to high stage to satisfy the thermostat’s call for
heat. The delay period prior to stepping up can be set at either
a fixed 5 minute time delay or a load based variable time between 1 and 12 minutes (AUTO mode). If the AUTO mode is
selected, the control averages the cycle times of the previous
three cycles and uses the average to determine the time to
transition from low stage to high stage.
To use a single-stage thermostat, turn off power to the furnace,
move the thermostat selection DIP switch to the OFF position.
Set the desired transition time by setting the transition delay
To install/connect a dehumidistat:
1. Turn OFF power to furnace.
2. Secure the dehumidistat neutral wire (typically the
white lead) to the terminal marked “DEHUM” on the
furnace integrated control module.
3. Secure the dehumidistat hot wire (typically the black
lead) to the terminal marked “R” on the furnace
integrated control module.
4. Secure the dehumidistat ground wire (typically the
green lead) to the ground screw on the furnace junction
box. NOTE: Ground wire may not be present on all
dehumidistats.
5. Turn ON power to furnace.
To enable the dehumidify function on the integrated control
module, set the dehumidification ENABLE dipswitch from
OFF to ON.
Once the switch is set, the dehumidify function is enabled
during a combination call for cooling (T-Stat) and dehumidification (DEHUM-Stat).
O
9
10
S5
DEHUM
Unused
Move to the ON position
to enable dehumidification
FOSSIL F UEL A PPLICATIONS
This furnace can be used in conjunction with a heat pump in
a fossil fuel application. A fossil fuel application refers to a
combined gas furnace and heat pump installation which uses
an outdoor temperature sensor to determine the most cost
efficient means of heating (heat pump or gas furnace).
17
G
AS
S
UPPLY AND
P
IPING
A heat pump thermostat with three stages of heat is required to
properly use a two-stage furnace in conjunction with a heat
pump. Refer to the fossil fuel kit installation instructions for
additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit installation instructions. All furnace connections must be made to the
furnace two-stage integrated control module and the “FURNACE” terminal strip on the fossil fuel control board.
115 VOLT L INE C ONNECTIONOF A CCESSORIES ( H UMIDIFIER
E LECTRONIC A IR C LEANER)
AND
WARNING
HIGHVOLTAGE!
TO
AVOIDPERSONALINJURYORDEATHDUETO
ELECTRICALSHOCK,DISCONNECTELECTRICALPOWER
BEFORESERVICINGORCHANGINGANYELECTRICAL
WIRING
.
The furnace integrated control module is equipped with line
voltage accessory terminals for controlling power to an optional
field-supplied humidifier and/or electronic air cleaner.
The accessory load specifications are as follows:
Humidifier1.0 Amp maximum at 120 VAC
Electronic Air Cleaner1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any accessories. Follow the humidifier or air cleaner manufacturers’ instructions for locating, mounting, grounding, and controlling
these accessories. Accessory wiring connections are to be
made through the 1/4" quick connect terminals provided on the
furnace integrated control module. The humidifier and electronic air cleaner hot terminals are identified as HUM and EAC.
The humidifier and electronic air cleaner neutral terminals are
identified as NEUTRAL. All field wiring must conform to applicable codes. Connections should be made as shown.
to all local codes, and have a minimum temperature rating of
105°C. All line voltage wire splices must be made inside the
furnace junction box.
The integrated control module humidifier terminals (HUM) are
energized with 115 volts whenever the induced draft blower is
energized. The integrated control module electronic air cleaner
terminals (EAC) are energized with 115 volts whenever the circulator blower is energized.
24 VOLT H UMIDIFIER
A 5" long brown wire in the wire harness at the low fire pressure
switch provides 24 VAC humidifier control. This wire is powered any time the pressure switch is closed. To connect 24
VAC HUM, connect the 24 VAC line of the humidifier to the 5”
brown wire. The connection can be made by either stripping
the wire and using a wire nut or by using a field supplied quick
connect terminal. The wiring must conform to all local and
national codes. Connect the COM side of the humidifier to the
C terminal on the furnace control board (or to the COM side of
the 24 VAC transformer). Do not connect 115V humidifier to
these terminals.
GAS S
The furnace rating plate includes the approved furnace gas input rating and gas types. The furnace must be equipped to
operate on the type of gas applied. This includes any conversion kits required for alternate fuels and/or high altitude.
Inlet gas supply pressures must be maintained within the ranges
specified in the following table. The supply pressure must be
constant and available with all other household gas fired appliances operating. The minimum gas supply pressure must be
maintained to prevent unreliable ignition. The maximum must
not be exceeded to prevent unit overfiring.
If it is necessary for the installer to supply additional line voltage wiring to the inside of the furnace, the wiring must conform
NOTE: Adjusting the minimum supply pressure below the limits
in the above table could lead to unreliable ignition. Gas input to
the burners must not exceed the rated input shown on the
rating plate. Overfiring of the furnace can result in premature
heat exchanger failure. Gas pressures in excess of 13 inches
water column can also cause permanent damage to the gas
valve.
At all altitudes, the manifold pressure must be within 0.3 inches
w.c. of that listed in the Specification Sheet applicable to your
model for the fuel used. At all altitudes and with either fuel, the
18
C
IRCULATING
AIR
AND
F
ILTERS
air temperature rise must be within the range listed on the furnace nameplate. Should this appliance be converted to LP,
refer to the instructions included in the factory authorized LP
conversion kit.
HIGH A LTITUDE D ERATE
IMPORTANT NOTE: The furnace will naturally derate itself with
altitude. Do not attempt to increase the firing rate by changing
orifices or increasing the manifold pressure. This can cause
poor combustion and equipment failure.
High altitude installations may require both a pressure switch
and an orifice change. These changes are necessary to compensate for the natural reduction in the density of both the gas
fuel and the combustion air at higher altitude.
For installations above 7000 feet, please refer to your distributor for required kit(s).
Alti tudeKit
Gas
NaturalNone#433.5" w.c.1.9" w.c.None
0-7000
Propane
1
LPM-05* support s White-Rodgers 2-s tage val ve only
2
LPM-06* s upports Honeywell and White-Rodgers 2-st age valves
In Canada, gas furnaces are only c ertified to 4500 feet .
NOTE:
LPM-05*
LPM-06*
Ori fice
1
#5510.0" w.c.6.0" w.c .None
2
Ma ni fol d P ressur ePre ssure
High Stage Low Stage
Switch Change
Contact the distributor for a tabular listing of appropriate
manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure safe and
proper furnace operation. All conversions must be performed
by a qualified installer, or service agency.
This unit is configured for natural gas. The appropriate
manufacturer’s propane gas conversion kit, must be applied for
propane gas installations. Refer to the “Propane Gas and/or
High Altitude Installations” section for details.
Contact your distributor for a tabular listing of appropriate
manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure safe and
proper furnace operation. All conversions must be performed
by a qualified installer, or service agency.
When sizing a trunk line, be sure to include all appliances
which will operate simultaneously.
The gas piping supplying the furnace must be properly sized
based on the gas flow required, specific gravity of the gas, and
length of the run. The gas line installation must comply with
local codes, or in their absence, with the latest edition of the
National Fuel Gas Code, NFPA 54/ANSI Z223.1.
(Pressure 0.5 ps ig or less and pressure drop of 0.3" W.C.; Bas ed on
0.60 Specific Gravity Gas)
BTUH Furnac e Input
CFH =
Heating Value of Gas (BTU/Cubic Foot)
In Cubic Feet of Gas Per Hour (CFH)
To connect the furnace to the building’s gas piping, the installer
must supply a ground joint union, drip leg, manual shutoff valve,
and line and fittings to connect to gas valve. In some cases,
the installer may also need to supply a transition piece from 1/
2" pipe to a larger pipe size.
The following stipulations apply when connecting gas piping.
•Use black iron or steel pipe and fittings for the building
piping.
•Use pipe joint compound on male threads only. Pipe
joint compound must be resistant to the action of the
fuel used.
•Use ground joint unions.
•Install a drip leg to trap dirt and moisture before it can
enter the gas valve. The drip leg must be a minimum
of three inches long.
•Install a 1/8" NPT pipe plug fitting, accessible for test
gage connection, immediately upstream of the gas
supply connection to the furnace.
•Use two pipe wrenches when making connection to
the gas valve to keep it from turning. The orientation
of the gas valve on the manifold must be maintained
as shipped from the factory.
19
G
AS
S
UPPLY AND
P
IPING
•Install a manual shutoff valve between the gas meter
and unit within six feet of the unit. If a union is installed,
the union must be downstream of the manual shutoff
valve, between the shutoff valve and the furnace.
•Tighten all joints securely.
•Connect the furnace to the building piping by one of
the following methods:
– Rigid metallic pipe and fittings.
– Semi-rigid metallic tubing and metallic fittings.
Aluminum alloy tubing must not be used in exterior
locations.
– Use listed gas appliance connectors in accordance
with their instructions. Connectors must be fully in
the same room as the furnace.
– Protect connectors and semi-rigid tubing against
physical and thermal damage when installed.
Ensure aluminum-alloy tubing and connectors are
coated to protect against external corrosion when
in contact with masonry, plaster, or insulation, or
subjected to repeated wetting by liquids such as
water (except rain water), detergents, or sewage.
Location of Manual Valve
(Installed Ahead of
Ground Joint Pipe Union)
Height Required
By Local Code
Ground Joint Pipe Union
To Be Installed Ahead of
Drip Leg
Gas Valve
``
When the gas piping enters through the left side of the furnace,
the installer must supply the following fittings (starting from the
gas valve):
•90 degree elbow.
•Straight pipe to reach the exterior of the furnace.
•A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases,
the installer may also need to supply a transition piece
from 1/2 inch to another pipe size.
COUNTERFLOW I NSTALLATIONS
When the gas piping enters through the left side of the furnace,
the installer must supply a straight pipe and a 90 degree elbow
to reach the exterior of the furnace.
A ground joint union, drip leg and manual shutoff valve must
also be supplied by the installer. In most cases, the installer
may also need to supply a transition piece from ½” to another
pipe size. When the gas piping enters through the right side of
the furnace, the installer must supply the following fittings (starting at the gas valve):
•Close Nipple
•90 Degree Elbow
•Straight Pipe to Reach Exterior of Furnace.
GAS P IPING C HECKS
Before placing unit in operation, leak test the unit and gas connections.
When the gas piping enters through the right side of the furnace, the installer must supply the following fittings (starting
from the gas valve):
•Close nipple.
•90 degree elbows.
•Straight pipe to reach the exterior of the furnace .
A ground joint union, drip leg, and manual shutoff valve must
also be supplied by the installer. In some cases, the installer
may also need to supply a transition piece from 1/2" to another
pipe size.
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other
approved testing methods.
NOTE: Never exceed specified pressures for testing. Higher
pressure may damage the gas valve and cause subsequent
overfiring, resulting in heat exchanger failure.
Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system
with pressures in excess of 1/2 psig (3.48 kPa).
This unit must be isolated from the gas supply system by closing its manual shutoff valve before pressure testing of gas supply piping system with test pressures equal to or less than 1/2
psig (3.48 kPa).
A gas detecting warning system is the only reliable way to
detect a propane gas leak. Rust can reduce the level of odorant
in propane gas. Do not rely on your sense of smell. Contact a
local propane gas supplier about installing a gas detecting
warning system. If the presence of gas is suspected, follow
the instructions on Page 3 of this manual.
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters, NBFU Manual
58.
For satisfactory operation, propane gas pressure must be 10
inch WC at the furnace manifold with all gas appliances in
operation. Maintaining proper gas pressure depends on three
main factors:
1. Vaporization rate, depending on temperature of the liquid,
and “wetted surface” area of the container or containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size will
depend on length of pipe run and total load of all
appliances.
Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is available from
most regulator manufacturers and propane gas suppliers.
200 PSIG
Maximum
5 to 15 PSIG
(20 PSIG Max.)
Continuous
Second Stage
Regulator
11" W.C .
First Stag e
Regulator
Propane Gas Installation (Typ.)
PROPANE G AS P IPING C HARTS
Sizing Between First and Second S tage Regulator*
Maximum Propane Capacities listed are based on 2 psig pr essure drop at 10 psig setting .
Capacities in 1,000 BTU/hour.
Sizing Between Second S tage an d Applia nce Regu lator*
Maximum P ropane Capacities listed are base d on 2 psig pressure d rop at 10 psig setting.
Cap acities in 1,000 B TU/h our.
Since propane gas will quickly dissolve white lead and most
standard commercial compounds, special pipe dope must be
used. Shellac-based compounds resistant to the actions of
liquefied petroleum gases such as Gasolac®, Stalactic®,
Clyde’s® or John Crane® are satisfactory.
Refer to the following illustration for typical propane gas installations and piping.
C
IRCULATING AIR AND FILTERS
WARNING
N
EVERALLOWTHEPRODUCTSOFCOMBUSTION,INCLUDINGCARBO N
Duct systems and register sizes must be properly designed for
the CFM and external static pressure rating of the furnace.
Ductwork should be designed in accordance with the recommended methods of “Air Conditioning Contractors of America”
Manual D.
A duct system must be installed in accordance with Standards
of the National Board of Fire Underwriters for the Installation of
Air Conditioning, Warm Air Heating and Ventilating Systems.
Pamphlets No. 90A and 90B.
21
S
TART-UP PROCEDURE
AND
A
DJUSTMENT
A closed return duct system must be used, with the return duct
connected to the furnace. NOTE: Ductwork must never be
attached to the back of the furnace. For installations requiring
more than 1800 CFM, use a bottom return or two sided return.
Supply and return connections to the furnace may be made
with flexible joints to reduce noise transmission. To prevent the
blower from interfering with combustion air or draft when a central return is used, a connecting duct must be installed between the unit and the utility room wall. A room, closet, or
alcove must not be used as a return air chamber.
When the furnace is used in connection with a cooling unit, the
furnace should be installed in parallel with or on the upstream
side of the cooling unit to avoid condensation in the heating
element. With a parallel flow arrangement, the dampers or other
means used to control the flow of air must be adequate to
prevent chilled air from entering the furnace and, if manually
operated, must be equipped with means to prevent operation of
either unit unless the damper is in the full heat or cool position.
When the furnace is installed without a cooling coil, it is recommended that a removable access panel be provided in the
outlet air duct. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat
exchanger can be viewed for visual light inspection or such that
a sampling probe can be inserted into the airstream. The access panel must be made to prevent air leaks when the furnace
is in operation.
To determine total external duct static pressure, proceed as
follows;
1. With clean filters in the furnace, use a draft gauge (inclined
manometer) to measure the static pressure of the return
duct at the inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive
Pressure)
3. The difference between the two numbers is .4” w.c.
Example:
static reading from return duct = -.1" w.c.
static reading from supply duct = .3" w.c.
total external static pressure on this system = .4" w.c.
NOTE: Both readings may be taken simultaneously and read
directly on the manometer if so desired. If an air conditioner
coil or Electronic Air Cleaner is used in conjunction with the
furnace, the readings must also include theses components,
as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum listed
on the furnace rating plate, check for closed dampers, registers, undersized and/or oversized poorly laid out duct work.
When the furnace is heating, the temperature of the return air
entering the furnace must be between 55°F and 100°F.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing
the furnace, the return air shall also be handled by a duct sealed
to the furnace casing and terminating outside the space containing the furnace.
CHECKING D UCT S TATIC
Refer to your furnace rating plate for the maximum ESP (external duct static) rating.
Total external static refers to everything external to the furnace
cabinet. Cooling coils, filters, ducts, grilles, registers must all
be considered when reading your total external static pressure. The supply duct pressure must be read between the furnace and the cooling coil. This reading is usually taken by
removing the “A” shaped block off plate from the end on the
coil; drilling a test hole in it and reinstalling the block off plate.
Take a duct static reading at the test hole. Tape up the test
hole after your test is complete. The negative pressure must be
read between the filter and the furnace blower.
Too much external static pressure will result in insufficient air
that can cause excessive temperature rise. This can cause
limit switch tripping and heat exchanger failure.
Checking Static Pressure
(80% Furnace Shown, 90% Similar)
FILTERS - READ T HIS S ECTION B EFORE I NSTALLING T HE
RETURN A IR D UCTWORK
Filters must be used with this furnace. Discuss filter maintenance with the building owner. Filters do not ship with this
furnace, but must be provided by the installer. Filters must com-
22
S
TART-UP
P
ROCEDURE
AND
A
DJUSTMENT
ply with UL900 or CAN/ULCS111 standards. If the furnace is
installed without filters, the warranty will be voided.
NOTE: An undersized opening will cause reduced airflow. The
bottom return is set up as a knock out.
UPRIGHT I NSTALLATIONS
Depending on the installation and/or customer preference, differing filter arrangements can be applied. Filters can be installed in the central return register or a side panel external
filter rack kit (upflows), or the ductwork above a downflow furnace. As an alternative, a media air filter or electronic air cleaner
can be used as the primary filter.
CIRCULATION A IR F ILTERS
One of the most common causes of a problem in a forced air
heating system is a blocked or dirty filter. Circulating air filters
must be inspected monthly for dirt accumulation and replaced
if necessary. Failure to maintain clean filters can cause premature heat exchanger failure.
A new home may require more frequent replacement until all
construction dust and dirt is removed. Circulating air filters are
to be installed in the return air duct external to the furnace
cabinet.
M INIM UM FILTER SIZES for DISPOSABL E FILTERS
FURNACE INPUTFILTER SIZE
70M768 in
90M960 in
115M1022 in
DISPOSABLE NOMINA L 300 F.M . FACE VELOCITY
2
2
2
HORIZONTAL I NSTALLATIONS
Filters must be installed in either the central return register or
in the return air duct work.
S
TART-UP PROCEDURE AND ADJUSTMENT
Furnace must have a 115 VAC power supply properly connected
and grounded. Proper polarity must be maintained for correct
operation. In addition to the following start-up and adjustment
items, refer to further information in Operational Checks section.
HEAT A NTICIPATOR S ETTING
The heat anticipator in the room thermostat must be correctly
adjusted to obtain the proper number of cycles per hour and to
prevent “overshooting” of the setting. Set the heat anticipator
setting to 0.7 amps. Follow the thermostat manufacturer’s
instructions on how to adjust the heat anticipator setting.
FURNACE O PERATION
Purge gas lines of air prior to startup. Be sure not purge lines
into an enclosed burner compartment.
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other
approved method. Verify that all required kits (propane gas,
high altitude, etc.) have been appropriately installed.
FURNACE S TARTUP
1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by
hand.
5. Move the furnace gas valve manual control to the OFF
position.
6. Wait five minutes then smell for gas. Be sure check
near the floor as some types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow
the Safety Instructions on page 2 of this manual. If you
do not smell gas after five minutes, move the furnace
gas valve manual control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners are lit, set the thermostat to desired
temperature.
FURNACE S HUTDOWN
1. Set the thermostat to the lowest setting.
The integrated control will close the gas valve and
extinguish flame. Following a 15 second delay, the
induced draft blower will be de-energized. After a 120,
150, 180 or 210-second delay period (field selectable
delay OFF [90, 120, 150, 180] plus 30-second ramp
down), the circulator blower de-energizes.
2. Remove the burner compartment door and move the
furnace gas valve manual control to the OFF position.
3. Close the manual gas shutoff valve external to the furnace.
The line pressure supplied to the gas valve must be within the
range specified below. The supply pressure can be measured
at the gas valve inlet pressure boss or at a hose fitting installed
in the gas piping drip leg. The supply pressure must be measured with the burners operating. To measure the gas supply
pressure, use the following procedure.
23
S
TART-UP PROCEDURE
INLETOUTLET
AND
A
DJUSTMENT
Common
e
m
e
t
e
n
M
t
p
O
p
h
s
t
A
m
o
a
o
e
r
e
i
r
n
o
e
o
H
s
Terminal(C)
High Fire Coil
Terminal (HI)
Low Fire Coil
Terminal (LO)
Gas Valve On/Off
Selector Switch
White-Rodgers Model 36G54 (Two-Stage)
t
e
Open to
Atmosphere
a
M
n
o
m
Inlet
Pressure
Boss
e
t
e
r
a
M
r
n
o
m
e
e
o
H
s
Outlet
Pressure Boss
c
t
S
i
w
n
O
f
f
O
/
High Fire Regulator
e
r
g
i
h
F
i
H
i
n
a
l
T
e
m
r
h
o
i
C
I
(
)
H
Adjust
l
Common
Terminal(C)
o
C
a
T
e
r
White-Rodgers Model 36G54 Connected to Manometer
High Fire
Regulator
Vent
Gas Valve On/Off
Selector Switch
Regulator
Adjust
Low Fire
Regulator
Adjust
Honeywell Model VR9205 (Two-Stage)
Regulator
Vent
Low Fire
Regulator
Adjust
a
x
l
o
i
C
n
a
i
l
M
(
m
Inlet Pressure Tap
1/8 NPT
e
t
M
a
r
n
o
e
m
Outlet Pressure Tap
1/8 NPT
Honeywell Model VR9205 Connected to Manometer
1. Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.
2. Connect a calibrated water manometer (or appropriate
gas pressure gauge) at either the gas valve inlet pressure
l
i
)
boss or the gas piping drip leg. See Honeywell VR9205
gas valve figure or White-Rodgers 36G54 gas valve figure
for location of inlet pressure boss.
NOTE: If measuring gas pressure at the drip leg or Honeywell
VR9205 gas valve, a field-supplied hose barb fitting must be
installed prior to making the hose connection. If using the inlet
pressure boss on the White-Rodgers 36G54 gas valve, then
use the 36G Valve Pressure Check Kit, Goodman Part No.
0151K00000S.
3. Turn ON the gas supply and operate the furnace and all
other gas consuming appliances on the same gas supply
line.
4. Measure furnace gas supply pressure with burners firing.
Supply pressure must be within the range specified in
the Inlet Gas Supply Pressure table.
If supply pressure differs from table, make the necessary adjustments to pressure regulator, gas piping size, etc., and/or
consult with local gas utility.
5. Turn OFF gas to furnace at the manual shutoff valve and
disconnect manometer. Reinstall plug before turning on
gas to furnace.
6. Turn OFF any unnecessary gas appliances stated in
step 3.
24
S
.
TART-UP
P
ROCEDURE
AND
A
DJUSTMENT
Gas Line
Gas
Shutoff
Valve
Gas Line
To Furnace
Open To
Atmosphere
Drip Leg Cap
With Fitting
Manometer Hose
Manometer
Measuring Inlet Gas Pressure (Alt. Method)
GAS M ANIFOLD P RESSURE M EASUREMENTAND A DJUSTMENT
9. Close thermostat “R” and “W2” contacts to provide a
call for high stage heat.
10. Remove regulator cover screw from the high (HI) outlet
pressure regulator adjust tower and turn screw clockwise
to increase pressure or counterclockwise to decrease
pressure. Replace regulator cover screw.
11. Turn off all electrical power and gas supply to the system.
12. Remove the manometer hose from the hose barb fitting
or outlet pressure boss.
13. Replace outlet pressure tap:
a. Honeywell VR9205 valve: Remove the 1/8" NPT hose
barb fitting from the outlet pressure tap. Replace the
outlet pressure boss plug and seal with a high quality
thread sealer.
b. White-Rodgers 36G54 valve: Turn outlet pressure test
screw in to seal pressure port (clockwise, 7 in-lb
minimum).
14. Turn on electrical power and gas supply to the system.
15. Close thermostat contacts “R” and “W1/W2” to energize
the valve.
Using a leak detection solution or soap suds, check for leaks
at outlet pressure boss plug (Honeywell valve) or screw (WhiteRodgers valve). Bubbles forming indicate a leak. SHUT OFF
GAS AND REPAIR ALL LEAKS IMMEDIATELY!
NOTE: For gas to gas conversion, consult your dealer for
appropriate conversion.
Only small variations in gas pressure should be made by adjusting the gas valve pressure regulator. The manifold pressure
must be measured with the burners operating. To measure
and adjust the manifold pressure, use the following procedure.
1. Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.
2. Turn off all electrical power to the system.
3. Outlet pressure tap connections:
a. Honeywell VR9205 valve: Remove the outlet pressure
boss plug. Install an 1/8" NPT hose barb fitting into
the outlet pressure tap.
b. White-Rodgers 36G54 valve: Back outlet pressure test
screw (inlet/outlet pressure boss) out one turn
(counterclockwise, not more than one turn).
4. Attach a hose and manometer to the outlet pressure
barb fitting (Honeywell valve) or outlet pressure boss
(White-Rodgers valve).
5. Turn ON the gas supply.
6. Turn on power and close thermostat “R” and “W1”
contacts to provide a call for low stage heat.
7. Measure the gas manifold pressure with burners firing.
Adjust manifold pressure using the Manifold GasPressure table shown below.
8. Remove regulator cover screw from the low (LO) outlet
pressure regulator adjust tower and turn screw clockwise
to increase pressure or counterclockwise to decrease
pressure. Replace regulator cover screw.
Manifold Gas Pressure
Gas
NaturalLow Stage 1.6 - 2.2" w .c.1.9" w .c.
High Stage 3.2 - 3.8" w .c.3.5" w .c.
PropaneLow Stage 5.7 - 6.3" w .c .6.0" w .c.
High Stage 9.7 - 10.3" w .c
RangeNominal
10.0" w .c.
GAS I NPUT R ATE M EASUREMENT (NATURAL G AS O NLY)
The gas input rate to the furnace must never be greater than
that specified on the unit rating plate. To measure natural gas
input using the gas meter, use the following procedure.
1. Turn OFF the gas supply to all other gas-burning
appliances except the furnace.
2. While the furnace is operating, time and record one
complete revolution of the smallest gas meter dial.
3. Calculate the number of seconds per cubic foot (sec/ft3)
of gas being delivered to the furnace. If the dial is a one
cubic foot dial, divide the number of seconds recorded in
step 2 by one. If the dial is a two cubic foot dial, divide
the number of seconds recorded in step 2 by two.
25
S
TART-UP PROCEDURE
AND
A
DJUSTMENT
4. Calculate the furnace input in BTUs per hour (BTU/hr).
Input equals the sum of the installation’s gas heating
value and a conversion factor (hours to seconds) divided
by the number of seconds per cubic foot. The measured
input must not be greater than the input indicated on the
unit rating plate.
EXAMPLE:
Installation’s gas heating (HTG) value: 1,000 BTU/ft
3
(Obtained from gas supplier)
Installation’s seconds per cubic foot: 34 sec/ ft
3
Conversion Factor (hours to seconds): 3600 sec/hr
Input = (Htg. value x 3600) ÷ seconds per cubic foot
Input = (1,000 BTU/ft3 x 3600 sec/hr) ÷ 34 sec/ ft
3
Input = 106,000 BTU/hr
Minor changes to the input rate may be accomplished through
manifold pressure adjustments at the gas valve. Refer to Sec-
tion XIV, Startup Procedure and Adjustment - Gas Manifold
Pressure Measurement and Adjustment for details. NOTE:
The final manifold pressure cannot vary by more than ± 0.3”
w.c. from the specified setting. Consult your local gas supplier
if additional input rate adjustment is required.
5. Repeat steps 2 through 4 on high stage.
6. Turn ON gas to and relight all other appliances turned off
in step 1. Be certain that all appliances are functioning
properly and that all pilot burners are operating.
TEMPERATURE R ISE
Temperature rise must be within the range specified on the unit
rating plate. An incorrect temperature rise may result in condensing in or overheating of the heat exchanger. An airflow and
temperature rise table is provided in the Specification Sheet
applicable to your model. Determine and adjust temperature
rise as follows:
1. Operate furnace with burners firing for approximately ten
minutes. Ensure all registers are open and all duct
dampers are in their final (fully or partially open) position.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must
not be influenced by radiant heat by being able to “see”
the heat exchanger.
3. Subtract the return air temperature from the supply air
temperature to determine the air temperature rise. Allow
adequate time for thermometer readings to stabilize.
4. Adjust temperature rise by adjusting the circulator blower
speed. Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
Refer to Startup Procedure and Adjustment -CirculatorBlower Speeds for speed changing details.
This furnace is equipped with a multi-speed circulator blower.
This blower provides ease in adjusting blower speeds. The
Specification Sheet applicable to your model provides an airflow table, showing the relationship between airflow (CFM) and
external static pressure (E.S.P.), for the proper selection of
heating and cooling speeds. The heating blower speed is
shipped set at “B”, and the cooling blower speed is set at “D”.
These blower speeds should be adjusted by the installer to
match the installation requirements so as to provide the correct heating temperature rise and correct cooling CFM.
Use the dual 7-segment LED display adjacent to the dipswitches
to obtain the approximate airflow quantity. The airflow quantity
is displayed as a number on the display, rounded to the nearest 100 CFM. The display alternates airflow delivery indication
and the operating mode indication.
Example: The airflow being delivered is 1225 CFM. The display indicates 12. If the airflow being delivered is 1275, the
display indicates 13.
1. Determine the tonnage of the cooling system installed
with the furnace. If the cooling capacity is in BTU/hr divide
it by 12,000 to convert capacity to TONs.
Example: Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air flow for the cooling system.
Most cooling systems are designed to work with air flows
between 350 and 450 CFM per ton. Most manufacturers
recommend an air flow of about 400 CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
,
.
26
S
The cooling system manufacturer’s instructions must be
checked for required air flow. Any electronic air cleaners or
other devices may require specific air flows, consult installation instructions of those devices for requirements.
3. Knowing the furnace model, locate the high stage cooling
air flow charts in the Specification Sheet applicable to
your model. Look up the cooling air flow determined in
step 2 and find the required cooling speed and adjustment
setting.
Example: A *MVC80704BX furnace installed with a 2.5
ton air conditioning system. The air flow
needed is 1000 CFM. Looking at the cooling
speed chart for *MVC80704BX, find the air
flow closest to 1000 CFM. A cooling airflow
of 990 CFM can be attained by setting the
cooling speed to “C” and the adjustment to
“-” (minus).
4. Continuous fan speed is 30% of the furnace’s maximum
airflow capability.
Example: If the furnace’s maximum airflow capability
is 2000 CFM, the continuous fan speed will
be 0.30 x 2000 CFM = 600 CFM.
5. Locate the blower speed selection DIP switches on the
integrated control module. Select the desired “cooling”
speed tap by positioning switches 1 and 2 appropriately.
Select the desired “adjust” tap by positioning switches
3 and 4 appropriately. Refer to the following figure for
switch positions and their corresponding taps. Verify
CFM by noting the number displayed on the dual 7segment LED display.
6. The multi-speed circulator blower also offers several
custom ON/OFF ramping profiles. These profiles may
be used to enhance cooling performance and increase
comfort level. The ramping profiles are selected using
DIP switches 5 and 6. Refer to the following figure for
switch positions and their corresponding taps. Refer to
the bullet points below for a description of each ramping
profile. Verify CFM by noting the number displayed on
the dual 7-segment LED display.
Switch B ank: S4
Ramp ing
Profiles
A*O FFOFF
BONOFF
COFFON
DONON
(*Indicates factor y setting)
•Profile A provides only an OFF delay of one (1) minute
at 100% of the cooling demand airflow.
DIP Switch No.
56
TART-UP
OFF
P
ROCEDURE
100% CFM100% CFM
AND
A
DJUSTMENT
1 min
•Profile B ramps up to full cooling demand airflow by
first stepping up to 50% of the full demand for 30 seconds.
The motor then ramps to 100% of the required airflow. A
one (1) minute OFF delay at 100% of the cooling airflow
is provided.
OFF
50% CFM
1/2 min
100% CFM
100% CFM
1 min
•Profile C ramps up to 85% of the full cooling demand
airflow and operates there for approximately 7 1/2
minutes. The motor then steps up to the full demand
airflow. Profile C also has a one (1) minute 100% OFF
delay.
OFF
Swi tch Bank: S3
Cooling
Airflow
AOFFOFF
BONOFF
COFFON
D*ONON
(*Indicates factory setting)
Switch Bank: S3
Adjust Taps
Norma l*OFFOFF
10%O NOFF
-10%OFFON
NormalONON
(*Indicates factory se tting)
100% CFM
DIP Switch No .
12
DIP Switch No.
34
•Profile D ramps up to 50% of the demand for 1/2 minute,
then ramps to 85% of the full cooling demand airflow
and operates there for approximately 7 1/2 minutes. The
motor then steps up to the full demand airflow. Profile D
has a 1/2 minute at 50% airflow OFF delay.
OFF
OFF
OFF
OFF
OFF
27
S
TART-UP PROCEDURE
AND
A
DJUSTMENT
7. Select the heating speed for your model from the heating
speed chart in the Specification Sheet. The adjust setting
(already established by the cooling speed selection)
determines which set of speeds are available. The
selected speed must provide a temperature rise within
the rise range listed with the particular model.
Example: The *MVC80704BX is set for 990 CFM on
cooling, the “ADJUST” is set to “+” (plus).
The four heating speeds available are “A
Plus”, “B Plus”, “C Plus”, and “D Plus”. “A
Plus” has a rise of 38°F for both stages
which is within the 20-50°F rise range for
the *MVC80704BX . This setting will keep
electrical consumption to a minimum. Set
the “Heat” speed DIP switches to “A”.
Switch Bank: S4
Heating
Airflow
DIP Swi tch No.
78
AOFFOFF
B*ONOFF
COFFON
DONON
(*Indicates factory setting)
8. Select the desired “heating” speed tap by positioning
switches 7 and 8 appropriately. Refer to figure above.
Verify CFM by noting the number displayed on the dual
7-segment LED display.
In general lower heating speeds will: reduce electrical consumption, lower operating sound levels of the blower, and increase
the outlet air temperature delivered to the home. The speeds
available allow the blower performance to be optimized for the
particular homeowner’s needs.
BLOWER H EAT O FF D ELAY T IMINGS
The integrated control module provides a selectable heat off
delay function. The heat off delay period may be set to 90, 120,
150, 180 seconds using the DIP switches or jumper provided
on the control module. The delay is factory shipped at 150
seconds but may be changed to suit the installation requirements and/or homeowner preference. Refer to the following figures for switch positions and corresponding delay times.
(1) Select model and desired
high stage cooling airflow. Determine the corresponding tap
( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate
ON / OFF positions. ( 2) Select model and desired high stage
heating airflow. Determine the corresponding tap ( A, B, C, or
D ). Set dip switches 7 and 8 to the appropriate ON / OFF
positions. (3) Select the airflow adjustment factor taps A and
D are 1; Tap B is +10%; Tap C -10%. Set dip switches 3 and 4
to the appropriate ON / OFF positions.
To set Comfort Mode:
Select desired Comfort Mode profile
(see profiles above). Set switches 5 and 6 to the appropriate
ON / O FF positions.
Model Tap Low Stage High Stage Low Stage High Stage
Cool Cool Heat Heat
735
805
875
935
945
1015
1085
1155
1085
1155
1225
1260
875
945
1015
1085
1050
1120
1190
1260
1210
1225
1245
1260
1750
1800
*DVC80703BX*
*DVC80905CX*
*DVC81155CX*
*MVC80704BX*
*MVC80905CX*
*MVC81155CX*
A
390
B
C
D
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
520
650
780
A
520
B
715
910
1170
553
748
943
1203
390
520
715
910
520
715
910
1170
520
715
910
1175
600
800
1000
1200
800
1100
1400
1800
850
1150
1450
1850
600
800
1100
1400
800
1100
1400
1800
800
1100
1400
1800
NOTE: Airflow data shown applies to legacy mode operation only. For a fully communicating
system, please see the outdoor unit’s installation instructions for cooling and pump heating
airflow data. See ComfortNet™ System - Airflow Consideration section for details.
28
1050
1150
1250
1350
1350
1450
1550
1650
1550
1650
1750
1800
1250
1350
1450
1550
1500
1600
1700
1800
1725
1775
COMFORTNET™ SYSTEM
C
OMFORTNET
™ S
YSTEM
OVERVIEW
The ComfortNet system (or CT system) is a system that includes a ComfortNet compatible furnace and air conditioner or
heat pump with a CTK01AA thermostat. A valid ComfortNet
system could also be a compatible furnace, CTK01AA thermostat and non-compatible, single stage air conditioner. Any other
system configurations are considered invalid ComfortNet systems and must be connected as a traditional (or legacy) system (see Electrical Connections for wiring connections). The
table below compares the valid CT systems.
CT compatible
Fur nace
CT compatible
Fur nace
CT compatible
Fur nace
CT compatible
Air Conditi oner
CT compatible
Heat P u mp
Non-CT compatible
Single Stage
Air Conditi oner
Full CT sy stem
benefits and features
Full CT sy stem
benefits and features
CT sy stem
benefits and features
for furnace only
A ComfortNet heating/air conditioning system differs from a
legacy/traditional system in the manner in which the indoor
unit, outdoor unit and thermostat interact with one another. In
a traditional system, the thermostat sends commands to the
indoor and outdoor units via analog 24 VAC signals. It is a oneway communication path in that the indoor and outdoor units
typically do not return information to the thermostat.
On the other hand, the indoor unit, outdoor unit, and thermostat comprising a ComfortNet system “communicate” digitally
with one another. It is now a two-way communications path.
The thermostat still sends commands to the indoor and outdoor units. However, the thermostat may also request and
receive information from both the indoor and outdoor units. This
information may be displayed on the CT thermostat. The indoor and outdoor units also interact with one another. The
outdoor unit may send commands to or request information
from the indoor unit. This two-way digital communications between the thermostat and subsystems (indoor/outdoor unit) and
between subsystems is the key to unlocking the benefits and
features of the ComfortNet system.
Two-way digital communications is accomplished using only
two wires. The thermostat and subsystem controls are power
with 24 VAC. Thus, a maximum of 4 wires between the equipment and thermostat is all that is required to operate the system.
AIRFLOW CONSIDERATIONS
Airflow demands are managed differently in a fully communicating system than they are in a legacy wired system. The
system operating mode (as determined by the thermostat)
determines which unit calculates the system airflow demand. If the indoor unit is responsible for determining the
airflow demand, it calculates the demand and sends it to the
ECM motor. If the outdoor unit or thermostat is responsible
for determining the demand, it calculates the demand and
transmits the demand along with a fan request to the indoor
unit. The indoor unit then sends the demand to the ECM
motor. The table below lists the various ComfortNet systems, the operating mode, and airflow demand source.
Sys te m
Air Conditioner +
Fur nace
Hea t Pump +
Fur nace
Furnace + Non-
Comm 1s tg A ir
Conditioner
System
Operating Mode
CoolingAir Conditioner
HeatingFurnace
Continuous FanThermostat
CoolingHeat Pump
Hea t Pump He ating
Only
Auxiliary HeatingFurnace
Continuous FanThermostat
CoolingFurnace
HeatingFurnace
Continuous FanThermostat
Airflow De m and
Source
Hea t Pump
For example, assume the system is an air conditioner
matched with a furnace. With a call for low stage cooling,
the air conditioner will calculate the system’s low stage
cooling airflow demand. The air conditioner will then send a
fan request along with the low stage cooling airflow demand
to the furnace. Once received, the furnace will send the low
stage cooling airflow demand to the ECM motor. The ECM
motor then delivers the low stage cooling airflow. See the
applicable ComfortNet™ air conditioner or heat pump
installation manual for the airflow delivered during cooling or
heat pump heating.
In continuous fan mode, the CTK01AA thermostat provides
the airflow demand. The thermostat may be configured for a
low, medium, or high continuous fan speed. The low,
medium, and high fan speeds correspond to 25%, 50%, and
75%, respectively, of the furnaces’ maximum airflow capability. During continuous fan operation, the thermostat sends a
fan request along with the continuous fan demand to the
furnace. The furnace, in turn, sends the demand to the ECM
motor. The ECM motor delivers the requested continuous
fan airflow.
29
COMFORTNET™ SYSTEM
FOSSIL F UEL A PPLICATIONS
This furnace can be used in conjunction with a ComfortNet™ compatible heat pump in a fossil fuel application. A fossil fuel application refers to a combined gas furnace and heat pump installation
which uses an outdoor temperature sensor to determine the most
cost efficient means of heating (heat pump or gas furnace). When
used with the CTK01AA thermostat, the furnace/heat pump
system is automically configured as a fossil fuel system. The
balance point temperature may be adjusted via the CTK01AA
thermostat advanced user menus (see CTK01AA instructions
for additional information).
CTK01AA WIRING
NOTE: Refer to Electrical Connections for 115 volt line
connections to the furnace.
NOTE: A removable plug connector is provided with the control
to make thermostat wire connections. This plug may be
removed, wire connections made to the plug, and replaced. It
is strongly recommended that multiple wires into a single
terminal be twisted together prior to inserting into the plug
connector. Failure to do so may result in intermittent operation.
Typical 18 AWG thermostat wire may be used to wire the system components. One hundred (100) feet is the maximum
length of wire between indoor unit and outdoor unit, or between
indoor unit and thermostat. Wire runs over (100) feet require
larger gauge wire.
FOUR-WIRE I NDOORAND O UTDOOR W IRING
Typical ComfortNet™ wiring will consist of four wires between
the indoor unit and outdoor unit and between the indoor unit
and thermostat. The required wires are: (a) data lines, 1 and 2;
(b) thermostat “R” (24 VAC hot) and “C” (24 VAC common).
CTK01AA
12RC
Thermostat
Four wires are required between the indoor unit and thermostat.
NOTE: Use of the CTK01AA transformer is recommended if
installing a dual fuel/fossil fuel system. Failure to use the
transformer in the outdoor unit could result in over loading of
the furnace transformer.
CTK01AA
12RC
12RC
40VA Transformer (included in
CTK01AA kit)
208/230 VAC
System Wiring using Two-Wires between Furnace and AC/HP
and Four-Wires between Furnace and Thermostat
24 VAC
12
Thermostat
CT Compatible
Furnace Integrated
Control Module
RC
CT Compatible
AC/HP Integrated
Control Module
CT COMPATIBLE FURNACEWITH NON-CT COMPATIBLE SINGLE-
STAGE A IR C ONDITIONER
Four wires are required between the furnace and thermostat. Two
wires are required between the furnace control and single stage air
conditioner. For this system configuration, the “Y1” terminal on the
integrated furnace control becomes an output rather than an input.
The “Y1” connection to the outdoor unit is made using both 4position thermostat connectors in the CTK01AA kit. Remove the
red keying tabs from the on-board connector block and position
both 4-position connectors such that “1”, “2”, “R”, “C”, and “Y1”
positions are filled.
CTK01AA
Thermostat
12RC
4-Position Connectors
from CTK01AA
Thermostat Kit
12RC
12RC
System Wiring using Four-Wires
CT Compatible Furnace
Integrated Control Module
CT Compatible AC/HP
Integrated Control Module
TWO-WIRE O UTDOOR, FOUR-WIRE INDOOR W IRING
Two wires can be utilized between the indoor and outdoor units.
For this wiring scheme, only the data lines, 1 and 2, are needed
required between the indoor and outdoor units. A 40VA, 208/
230 VAC to 24VAC transformer must be installed in the outdoor unit to provide 24VAC power to the outdoor unit’s electronic control. The transformer is included with the CTK01AA
kit. See kit instructions for mounting and wiring instructions.
12RC
W1 W2 Y1 Y2
G
CY
System Wiring between Furnace and Non-CT Compatible
Single Stage Air Conditioner
O
Non-CT Compatible
Single Stage AC
CT Compatible
Furnace Integrated
Control Module
COMFORTNET S YSTEM A DVANCED F EATURES
The ComfortNet system permits access to additional system
information, advanced setup features, and advanced diagnostic/troubleshooting features. These advanced features are organized into a menu structure. The menus are accessed and
navigated as described in the following section.
30
COMFORTNET™ SYSTEM
ACCESSINGAND N AVIGATINGTHE A DVANCED F EATURES M ENUS
The advanced system features are accessed using the
ComfortNet thermostat. These advanced features are accessed
as follows:
•On the CT thermostat Home Screen Display, touch
the Menu key to display additional key choices.
•Touch and hold the Installer Config key for
approximately 3 seconds to enter the Thermostat
Options Configuration menu.
•Touch and hold the Installer Config key again for
approximately 3 seconds to enter the Advanced
Installer Configuration menu.
Set Time
Clean D isplay
Installer
Conf ig
Schedu le
Upon entering the advanced menus, the Advanced Fault Menu
is displayed. The display will change to the Fault Screen and
indicate any faults that may be present in the indoor or outdoor
equipment. If a fault is present, the Fault Screen will show the
equipment and an error code with a description of the fault.
Touch _ or + keys to view the fault status of any remaining
equipment. The text “NO FAULTS” will be scrolled if no errors
are present.
Run
Set
Schedule
the change is not accepted, the display will show “FAIL” then
revert to the Fault Screen.
Some parameters being displayed switch between the item
name and the item value. Touch the Hold key to momentarily
stop the display from switching.
To exit an equipment submenu and revert back to the equipment menus, touch the Menu key. Touch Menu again to revert
back to the Thermostat Options Menu. Touch the Run Sched-ule key to step out of all menus and back to the CT thermostat
Home Screen Display.
THERMOSTAT M ENU
If this furnace is installed with a CT compatible heat pump, the
system is recognized as a dual fuel system. The balance
point temperature should be set via the thermostat advanced
menu. Navigate to the THERMOSTAT menu. Press the IN-STALLER CONFIG key. Navigate to the SETUP menu and
press the INSTALLER CONFIG button. Navigate to dF BALPNT. Adjust the dual fuel system balance point using the back/
forward arrows.
DIAGNOSTICS
Accessing the furnace’s diagnostics menu provides ready access to the last six faults detected by the furnace. Faults are
stored most recent to least recent. Any consecutively repeated
fault is stored a maximum of three times. Example: A clogged
return air filter causes the furnace limit to trip repeatedly. The
control will only store this fault the first three consecutive times
the fault occurs. Navigate to the diagnostics menu as described
above in Accessing and Navigating the Advanced FeaturesMenus.
NOTE: It is highly recommended that the fault history be cleared
when performing maintenance or servicing the furnace.
Call for Service
Menu
Advanced
Run
Schedule
Call for Service
Menu
Advanced
Run
Schedule
Touch the + or _ to step through the list of installed equipment, including the thermostat. Touch the Installer Config
key to enter the submenus for the equipment displayed. The
text “WORKING” will be displayed in the scrolling display area
while the data is being retrieved. The first sub-menu is then
displayed. See tables below for listing of furnace submenus.
Touch the + or _ to step through the list of submenus and
view settings. If a setting can be adjusted, _ and + keys will
appear. Use the _ or + keys to adjust the setting to the
desired value. Touch the + or _ to step to the next item.
“WORKING” will appear as the settings are being updated.
“DONE” will appear to indicate the change was accepted. If
31
COMFORTNET™ SYSTEM
FURNACE A DVANCED F EATURES M ENUS
CONFIGURATION
Submenu ItemIndication (for Display Only; not User Modifiable)
Number of Heat Stages (HT STG)Displays the number of furnace heating stages
Input Rate (BTU/HR)Displays the furnace input rate in kBtu/hr
Motor HP (1/2, ¾, or 1 MTR HP)Displays the furnace indoor blower motor horsepower
DIAGNOSTICS
Submenu ItemIndication/User Modifiabl e OptionsComments
Fault 1 (FAULT #1)Most recent furnace faultFor display only
Fault 2 (FAULT #2)Next most recent furnace faultFor display only
Fault 3 (FAULT #3)Next most recent furnace faultFor display only
Fault 4 (FAULT #4)Next most recent furnace faultFor display only
Fault 5 (FAULT #5)Next most recent furnace faultFor display only
Fault 6 (FAULT #6)Least recent furnace faultFor display only
Clear Fault History (CLEAR)NO or YES
NOTE:
Consecutively repeated faults are shown a maximum of 3 times
Selecting “YES” clears the fault
history
IDENTIFICATION
Submenu ItemIndication (for Display Only; not User Modifiable)
Model Number (MOD NUM)Displays the furnace model number
Serial Number (SER NUM)Displays the furnace serial number (Optional)
Software (SOFTWARE)Displays the application software revision
SET-UP
Submenu ItemUser Modifiable OptionsCom ments
Heat Airflow Trim (HT TRM)-10% to +10% in 2% increments,
default is 0%
Heat ON Delay (HT ON5, 10, 15, 20, 25, or 30 seconds,
default is 30 seconds
Heat OFF Delay (HT OFF)30, 60, 90, 120, 150, or 180 seconds,
default is 150 seconds
Heat Airflow (HT ADJ)1, 2, 3, or 4Selects the nominal heating airflow (see
STATUS
Submenu ItemIndication (for Display Only; not User Modifiable)
Mode (MODE)Displays the current furnace operating mode
CFM (CFM)Displays the airflow for the current operating mode
Trims the heating airflow by the selected
amount.
Selects the indoor blower heat ON delay
Selects the indoor blower heat OFF delay
Startup Procedure and Adjustment –
Circulator Blower Speeds for addition
information)
32
COMFORTNET™ SYSTEM
NON-COMM (APPLIES ONLY TO A C T COMPATIBLE FURNACE MATCHED
WITH A NON-CT COMPATIBLE SINGLE STAGE AIR CONDITIONER)
Selects the airflow for the non-CT
compatible single stage AC unit
Cool Airflow Trim (CL TRM)-10% to +10% in 2% increments,
default is 0%
Selects the airflow trim amount for the nonCT compatible single stage AC unit
Cool Airflow Profile (CL PRFL)A, B, C, or D, default is ASelects the airflow profile for the non-CT
compatible single stage AC unit
Cool ON Delay (CL ON)5, 10, 20, or 30 seconds, default is
5 seconds
Cool OFF Delay (CL OFF)30, 60, 90, or 120 seconds, default
is 30 seconds
NETWORKTROUBLESHOOTING
Communications is achieved by taking the difference
between two dc signals. The signals and transmission lines
are referred to as “data 1” and “data 2”. Each transmission
line is biased to approximately 2.5Vdc. During data recep-
shoot the network may arise. The integrated furnace control
has some on-board tools that may be used to troubleshoot the
network. These tools are: red communications LED, green
receive (Rx) LED, and learn button.
•Red communications LED – Indicates the status of
tion/transmission, the data lines vary between +5V and
ground. (When data 1 is increasing towards +5V, data 2 is
decreasing towards ground and when data 1 is decreasing
•Green receive LED – Indicates network traffic. The
towards ground, data 2 is increasing towards +5V. Typically,
the data 1 line is approximately 2.6Vdc and the data 2
transmission line is approximately 2.3Vdc. The voltage
•Learn button – Used to reset the network. Depress
difference between data 1 and data 2 is typically 0.2 to 0.6
Vdc.
the network. The table below indicates the LED status
and the corresponding potential problem.
table below indicates the LED status and the
corresponding potential problem.
the button for approximately 2 seconds to reset the
network.
Selects the indoor blower ON delay for the
non-CT compatible s ingle stage AC unit
Selects the indoor blower OFF delay for the
non-CT compatible s ingle stage AC unit
The indoor control is equipped with a bank of three
dipswitches that provide biasing and termination functions for
the communications transmission lines. The outdoor control
in the CT compatible unit is equipped with a bank of two
dipswitches that provide termination functions for the communications transmission lines. Communications errors will
result if these switches are not correctly set. The table
below indicates the switch position for the bias and termination dipswitches along with the expected voltages. Note that
the ON position is the correct position for all bias and
termination dipswitches.
ONOFF
1
2
3
BIAS
BIAS
TERM
Indoor Unit BIAS and TERMINATION Dipswitches
The ComfortNet system is a fully communicating system, and
thus, constitutes a network. Occasionally the need to trouble-
SYSTEM T ROUBLESHOOTING
NOTE: Refer to the instructions accompanying the CT
compatible outdoor AC/HP unit for troubleshooting information.
Refer to the Troubleshooting Chart in the Appendix for a listing
of possible furnace error codes, possible causes and corrective actions.
33
O
PERATIONAL
C
HECKS
& S
AFETY
C
IRCUIT
D
ESCRIPTION
LED LED
Status
1 Flash
Red
Communications
LED
2 Flashes
1 Steady
Flash
Green Receive
LED
Rapid
Flashing
On Solid
Off
Off
Indication Possible Causes Corrective Action(s) Notes & Cautions
x Normal condition x None x None x None
x Communications
Failure
x Out-of-box reset x Control power up
x No power
x Communications
error
x No network found x Broken/ disconnected
x Normal network
traffic
x Data 1/ Data 2
miss-wire
x Communications
Failure
x Learn button
depressed
x No power to furnace
x Open fuse
x Communications error
data wire(s)
x Furnace is installed as
a legacy/ traditional
system
x Control is “talking” on
network as expected
x Data 1 and data 2
wires reversed at
furnace, thermostat,
or CT™ compatible
outdoor AC/HP
x Short between data 1
and data 2 wires
x Short between data 1
or data 2 wires and R
(24VAC) or C (24VAC
common)
x Depress Learn Button
x Verify that bus BIAS
and TERM
dipswitches are in the
ON position.
x None x None
x Check fuses and
circuit breakers;
replace/reset
x Replace blown fuse
x Check for shorts in
low voltage wiring in
furnace/system
x Reset network by
depressing learn
button
x Check data 1/ data 2
voltages
x Check
communications
wiring (data 1/ data 2
wires)
x Check wire
connections at
terminal block
x Verify furnace
installation type
(legacy/ traditional or
communicating)
x Check data 1/ data 2
voltages
x None x None
x Check
communications
wiring (data 1/ data 2
wires)
x Check wire
connections at
terminal block
x Check data 1/ data 2
voltages
x Depress once
quickly for a powerup reset
x Depress and hold
for 2 seconds for
an out-of-box reset
x Turn power OFF
prior to repair
x Turn power OFF
prior to repair
x Verify wires at
terminal blocks are
securely twisted
together prior to
inserting into
terminal block
x Verify data1 and
data voltages as
described above
x Turn power OFF
prior to repair
x Verify wires at
terminal blocks are
securely twisted
together prior to
inserting into
terminal block
x Verify data1 and
data voltages as
described above
N
ORMAL SEQUENCE OF OPERATION
POWER U P
The normal power up sequence is as follows:
•115 VAC power applied to furnace.
•Integrated control module performs internal checks.
88
•Integrated control module displays
88
8
8 on dual 7-segment
88
88
display LED’s.
•Integrated control module monitors safety circuits
continuously.
•Furnace awaits call from thermostat. Dual 7-segment
00
LED’s display
PP
0
P while awaiting call from thermostat.
00
PP
HEATING M ODE
The normal operational sequence in heating mode is as follows:
•R and W1 (or R and W1/W2) thermostat contacts close,
initiating a call for heat.
•Integrated control module performs safety circuit checks.
•Induced draft blower is energized on high speed for a 15-
second prepurge. Humidifier terminal is energized with
induced draft blower.
•Induced draft blower steps to low speed following
prepurge. Low stage pressure switch contacts are
closed.
•Igniter warm up begins upon step to low speed and
presence of closed low stage pressure switch contacts.
34
O
PERATIONAL
C
HECKS
& S
AFETY
C
IRCUIT
D
ESCRIPTION
•Gas valve opens at end of igniter warm up period, delivering
gas to burners and establishing flame.
•Integrated control module monitors flame presence. Gas
valve will remain open only if flame is detected.
•If the thermostat call is for low heat, gas valve and induced
draft blower will continue on low stage. If the call is for
high heat, the gas valve and induced draft blower will
change to high stage.
•Circulator blower is energized on heat speed following a
thirty (30) second blower on delay. The circulator blower
requires thirty seconds to ramp up to full speed.
Electronic air cleaner terminal is energized with circulator
blower.
•Furnace is now operating on the specified stage called
for by the two-stage thermostat.
•Furnace runs, integrated control module monitors safety
circuits continuously.
•If the two-stage thermostat changes the call from low
heat to high heat, the integrated control module will
immediately switch the induced draft blower, gas valve,
and circulator blower to their high stage settings.
•If the two-stage thermostat changes the call from high
heat to low heat, the control will immediately switch the
induced draft blower and gas valve to their low stage
settings. The circulator blower will remain on high
heating speed for thirty (30) seconds before switching to
the low heat circulating speed.
•R and W1 (or R and W1/W2) thermostat contacts open,
completing the call for heat.
•Gas valve closes, extinguishing flame.
•Induced draft blower is de-energized following a fifteen
second post purge. Humidifier terminals are de-energized.
•Circulator blower continues running for the selected heat
off delay period (90, 120, 150 or 180 seconds). The
speed run during this period depends on the last heat
call provided by the thermostat.
If the last call for heat was a call for low heat, the air
circulator motor will run on low heat speed for the duration
of the heat off delay period (90, 120, 150 or 180 seconds).
If the last call for heat was a call for high heat, the air
circulating motor will run on the high heating speed for
thirty (30) seconds and then switch to the low heating
speed for the balance of the heat off delay period (60,
90, 120 or 150 seconds).
•Circulator blower and electronic air cleaner terminal is
de-energized.
•Circulator blower ramps down to OFF during the 30
seconds following the heat off delay period.
•Furnace awaits next call from thermostat.
COOLING M ODE
The normal operational sequence in cooling mode is as follows:
•R and Y1/G or Y2/G thermostat contacts close, initiating
a call for cool.
•Integrated control module performs safety circuit checks.
•Outdoor fan and compressor are energized to their
appropriate speed.
•Circulator blower is energized on the appropriate cool
speed at the level and time determined by the selected
ramping profile. Electronic air cleaner terminal is
energized with circulator blower.
•Furnace circulator blower and outdoor cooling unit run
their appropriate speeds, integrated control module
monitors safety circuits continuously.
•R and Y1/G or Y2/G thermostat contacts open,
completing the call for cool.
•Outdoor fan and compressor are de-energized.
•Circulator blower continues running during a cool off delay
period. The OFF delay time and airflow level are
determined by the selected ramping profile.
•Electronic air cleaner terminal and circulator blower are
de-energized.
•Furnace awaits next call from thermostat.
FAN O NLY M ODE
The normal operational sequence in fan only mode is as follows:
•R and G thermostat contacts close, initiating a call for
fan.
•Integrated control module performs safety circuit checks.
•Circulator blower is energized on continuous fan speed
(30% of the furnace’s maximum airflow capability)
following a five (5) second delay. Electronic air cleaner
terminal is energized.
•Circulator blower runs, integrated control module
monitors safety circuits continuously.
•R and G thermostat contacts open, completing the call
for fan.
•Circulator blower is de-energized. Electronic air cleaner
terminal is de-energized.
•Furnace awaits next call from thermostat.
O
PERATIONAL CHECKS
The burner flames should be inspected with the burner compartment door installed. Flames should be stable, quiet, soft,
and blue (dust may cause orange tips but they must not be
yellow). Flames should extend directly outward from the burners without curling, floating, or lifting off. Flames must not
impinge on the sides of the heat exchanger firing tubes.
35
T
ROUBLESHOOTING
& M
AINTENANCE
FLAME S ENSOR
The flame sensor is a probe mounted to the burner/manifold
assembly which uses the principle of flame rectification to determine the presence or absence of flame.
T
ROUBLESHOOTING
ELECTROSTATIC D ISCHARGE (ESD) PRECAUTIONS
Burner Flame
S
AFETY CIRCUIT DESCRIPTION
A number of safety circuits are employed to ensure safe and
proper furnace operation. These circuits serve to control any
potential safety hazards and serve as inputs in the monitoring
and diagnosis of abnormal function. These circuits are continuously monitored during furnace operation by the integrated
control module.
INTEGRATED C ONTROL M ODULE
The integrated control module is an electronic device which, if
a potential safety concern is detected, will take the necessary
precautions and provide diagnostic information through an LED.
PRIMARY LIMIT
The primary limit control is located on the partition panel and
monitors heat exchanger compartment temperatures. It is a
normally-closed (electrically), automatic reset, temperature-activated sensor. The limit guards against overheating as a result
of insufficient conditioned air passing over the heat exchanger.
AUXILIARY L IMIT
The auxiliary limit controls are located on or near the circulator
blower and monitors blower compartment temperatures. They
are a normally-closed (electrically), auto-reset sensors. These
limits guard against overheating as a result of insufficient conditioned air passing over the heat exchanger.
ROLLOUT LIMIT
NOTE: Discharge body’s static electricity before touching unit.
An electrostatic discharge can adversely affect electrical
components.
Use the following precautions during furnace installation and
servicing to protect the integrated control module from damage. By putting the furnace, the control, and the person at the
same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge.
This procedure is applicable to both installed and uninstalled
(ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the
control prior to discharging your body’s electrostatic
charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnace away from the control. Any tools held in a
person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring
following the discharge process in step 2. Use caution
not to recharge your body with static electricity; (i.e., do
not move or shuffle your feet, do not touch ungrounded
objects, etc.). If you come in contact with an ungrounded
object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new
control from its container. Follow steps 1 through 3 if
installing the control on a furnace. Return any old or
new controls to their containers before touching any
ungrounded object.
DIAGNOSTIC C HART
The rollout limit controls are mounted on the burner/manifold
assembly and monitor the burner flame. They are normallyclosed (electrically), manual-reset sensors. These limits guard
against burner flames not being properly drawn into the heat
exchanger.
PRESSURE S WITCHES
The pressure switches are normally-open (closed during operation) negative air pressure-activated switches. They monitor the airflow (combustion air and flue products) through the
heat exchanger via pressure taps located on the induced draft
blower and the coil front cover. These switches guard against
insufficient airflow (combustion air and flue products) through
the heat exchanger and/or blocked condensate drain conditions.
WARNING
HIGHVOLTAGE!
TO
AVOIDPERSONALINJURYORDEATHDUETO
ELECTRICALSHOCK,DISCONNECTELECTRICALPOWER
BEFORE
Refer to the Troubleshooting Chart at the end of this manual for
assistance in determining the source of unit operational problems. The dual 7-segment LED display will display an error
code that may contain a letter and number. The error code may
be used to assist in troubleshooting the unit.
36
PERFORMINGANYSERVICEORMAINTENANCE
.
M
ISCELLANEOUS
FAULT R ECALL
The ignition control is equipped with a momentary push-button
switch that can be used to display the last six faults on the
dual 7-segment LED’s. The control must be in Standby Mode
(no thermostat inputs) to use the feature. Depress the switch
for approximately 2 seconds. Release the switch when the
LED’s are turned off. The last six faults will be displayed most
recent to least recent on the dual 7-segment LED’s.
NOTE: Consecutively repeated faults are stored a maximum of
three times. Example: A clogged return air filter causes the
furnace limit to trip repeatedly. The control will only store this
fault the first three consecutive times the fault occurs.
RESETTING F ROM L OCKOUT
Furnace lockout results when a furnace is unable to achieve
ignition after three attempts during a single call for heat. It is
00
EE
characterized by a non-functioning furnace and a
0 code dis-
E
00
EE
played on the dual 7-segment display. If the furnace is in “lockout”, it will (or can be) reset in any of the following ways.
1. Automatic reset. The integrated control module will
automatically reset itself and attempt to resume normal
operations following a one hour lockout period.
2. Manual power interruption. Interrupt 115 volt power to
the furnace.
3. Manual thermostat cycle. Lower the thermostat so that
there is no longer a call for heat for 1 -20 seconds then
reset to previous setting.
NOTE: If the condition which originally caused the lockout still
exists, the control will return to lockout. Refer to the DiagnosticChart for aid in determining the cause.
M
AINTENANCE
WARNING
TO
AVOIDELECTRICALSHOCK,INJURYORDEATH
DISCONNECTELECTRICALPOWERBEFOREPERFORMINGANY
MAINTENANCE
HANDLEWITHCARE
WITHBAREFINGERS,ROUGHHANDLINGORVIBRATION
COULDDAMAGETHEIGNITERRESULTINGINPREMATURE
FAILURE
HANDLETHEIGNITER
.IF
YOUMUSTHANDLETHEIGNITER
.T
OUCHINGTHEIGNITERELEMENT
.O
NLYAQUALIFIEDSERVICERSHOULDEVER
.
,
,
ANNUAL I NSPECTION
The furnace should be inspected by a qualified installer, or service agency at least once per year. This check should be performed at the beginning of the heating season. This will ensure
that all furnace components are in proper working order and
that the heating system functions appropriately. Pay particular
attention to the following items. Repair or service as necessary.
•Flue pipe system. Check for blockage and/or leakage.
Check the outside termination and the connections at
and internal to the furnace.
•Heat exchanger. Check for corrosion and/or buildup
within the heat exchanger passageways.
•Burners. Check for proper ignition, burner flame, and
flame sense.
•Drainage system. Check for blockage and/or leakage.
Check hose connections at and internal to furnace.
•Wiring. Check electrical connections for tightness and/
or corrosion. Check wires for damage.
Improper filter maintenance is the most common cause of inadequate heating or cooling performance. Filters should be
cleaned (permanent) or replaced (disposable) every two months
or as required. When replacing a filter, it must be replaced with
a filter of the same type and size.
FILTER REMOVAL
Depending on the installation, differing filter arrangements can
be applied. Filters can be installed in either the central return
register or a side panel external filter rack (upflow only). A
media air filter or electronic air cleaner can be used as an alternate filter. Follow the filter sizes given in the Recommended
Minimum Filter size table to ensure proper unit performance.
To remove filters from an external filter rack in an upright upflow
installation, follow the directions provided with external filter
rack kit.
HORIZONTAL UNIT FILTER REMOVAL
Filters in horizontal installations are located in the central return register or the ductwork near the furnace.
To remove:
1. Turn OFF electrical power to furnace.
2. Remove filter(s) from the central return register or
ductwork.
3. Replace filter(s) by reversing the procedure for removal.
4. Turn ON electrical power to furnace.
MEDIA AIR FILTEROR ELECTRONIC AIR CLEANER REMOVAL
Follow the manufacturer’s directions for service.
37
M
ISCELLANEOUS
BURNERS
Visually inspect the burner flames periodically during the heating season. Turn on the furnace at the thermostat and allow
several minutes for flames to stabilize, since any dislodged
dust will alter the flames normal appearance. Flames should
be stable, quiet, soft, and blue (dust may cause orange tips
but they must not be yellow). They should extend directly
outward from the burners without curling, floating, or lifting off.
Flames must not impinge on the sides of the heat exchanger
firing tubes.
INDUCED D RAFTAND C IRCULATOR B LOWERS
The bearings in the induced draft blower and circulator blower
motors are permanently lubricated by the manufacturer. No further lubrication is required. Check motor windings for accumulation of dust which may cause overheating. Clean as necessary.
FLAME S ENSOR (QUALIFIED S ERVICER O NLY)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the flame sensor. This coating acts
as an insulator causing a drop in the flame sense signal. If the
flame sense signal drops too low the furnace will not sense
flame and will lock out. The flame sensor should be carefully
cleaned by a qualified servicer using emery cloth or steel wool.
Following cleaning, the flame sense signal should be as indicated in the Specifications Sheet.
FLUE P ASSAGES (QUALIFIED S ERVICER O NLY)
The heat exchanger flue passageways should be inspected at
the beginning of each heating season. If necessary, clean the
passageways as outlined below.
1. Turn OFF the electrical power and gas supply to the
furnace.
2. Disconnect the gas line and remove the burner/ manifold
assembly by removing the screws securing the assembly
to the partition panel.
3. Disconnect the flue pipe system from the induced draft
blower.
4. Remove the induced draft blower and collector box cover.
5. Clean the primary heat exchanger tubes using a wire
brush attached to a length of high grade stainless steel
cable, such as drain cleanout cable. Attach a variable
speed reversible drill to the other end of the cable. Slowly
rotate the cable with the drill and insert it into one of the
heat exchanger tubes. While reversing the drill, work
the cable in and out several times to obtain sufficient
cleaning. Repeat for each tube.
6. Clean residue from furnace using a vacuum cleaner.
7. Replace the parts removed in the previous steps in
reverse order.
8. Turn on electrical power and gas to furnace. Check for
leaks and proper unit operation.
9. Severe heat exchanger fouling is an indication of an
operational problem. Perform the checks listed in
Startup Procedure and Adjustments to reduce the
chances of repeated fouling.
B
EFORE LEAVING AN INSTALLATION
•Cycle the furnace with the thermostat at least three
times. Verify cooling and fan only operation.
•Review the Owner’s Manual with the homeowner and
discuss proper furnace operation and maintenance.
•Leave literature packet near furnace.
R
EPAIR AND REPLACEMENT PARTS
•When ordering any of the listed functional parts, be sure
to provide the furnace model, manufacturing, and serial
numbers with the order.
•Although only functional parts are shown in the parts
list, all sheet metal parts, doors, etc. may be ordered by
description.
•Parts are available from your distributor.
Functional Parts List-
Gas ValveBlower Motor
Gas ManifoldBlower Wheel
Natural Gas OrificeBlower Mounting Bracket
Propane Gas OrificeBlower Cutoff
IgniterBlower Housing
Flame SensorInductor
Rollout Limit SwitchHeat Exchanger
Primary Limit SwitchAuxiliary Limit Switch
Pressure SwitchIntegrated Control Module
Induced Draft BlowerTransformer
Door Switch
38
T
OP
E0
E1
E2
ROUBLESHOOTING
C
HART
Notes & Cautions
repair.
module fuse with 3A
automotive fuse.
“Electrostatic Discharge”
section of manual.
x Turn power OFF prior to
x Replace integrated control
x Read precautions in
module with current
x Replace integrated control
replacement parts.
x Turn power OFF prior to
repair.
with care.
x Igniter is fragile, handle
emery cloth.
section for piping details.
x Sand flame sensor with
x See “Vent/Flue Pipe”
x Turn power OFF prior to
repair.
with correct replacement
part.
x Replace pressure switch
x Turn power OFF prior to
repair.
with correct replacement
part.
x Replace pressure switch
x Replace induced draft
blower with correct
replacement part.
Corrective Actions
interruption.
switch operation (hose, wiring,
contact operation). Correct if
necessary.
sensor if coated and/or oxidized.
proper length, elbows, and
termination.
furnace and integrated control
x Assure 115 and 24 volt power to
module.
fuse (3A). Replace if necessary.
and 24 volt circuits. Repair as
necessary.
x Check integrated control module
x Check for possible shorts in 115
module.
x Replace bad integrated control
x Locate and correct gas
x Check front cover pressure
x Replace or realign igniter.
x Check flame sense signal. Sand
x Check flue piping for blockage,
x Verify proper induced draft
blower performance.
x Replace low stage pressure
switch.
x Repair short in wiring.
Repair/replace if necessary.
piping for blockage, proper
length, elbows, and termination.
necessary.
performance. Correct as
necessary.
or contact motion.
x Inspect pressure switch hose.
x Inspect flue and/or inlet air
x Check drain system. Correct as
x Check induced draft blower
connection.
x Correct pressure switch set point
x Tighten or correct wiring
Possible Causes
may be no gas to burners, front
cover pressure switch stuck open,
bad igniter or igniter alignment,
improper orifices, or
coated/oxidized or improperly
connected flame sensor.
Cause may be interrupted gas
supply, lazy burner flames
(improper gas pressure or
restriction in flue and/or
combustion air piping), front
cover pressure switch opening, or
improper induced draft blower
performance.
contacts sticking.
door switch open or 24 volt wire
improperly connected or loose
x Blown fuse or circuit breaker
x Integrated control module has an
internal fault
x Manual disconnect switch OFF,
EE
x Normal operation x None x Normal operation
x Failure to establish flame. Cause
x Loss of flame after establishment.
wiring.
x Low stage pressure switch
x Shorts in pressure switch circuit
E1
pinched, or connected improperly.
blocked drain system or weak
induced draft blower.
or malfunctioning switch
contacts.
x Pressure switch hose blocked
x Blocked flue and/or inlet air pipe,
x Incorrect pressure switch set point
wiring.
x Loose or improperly connected
ComfortNet™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
& ComfortNet™ Thermostat)
Symptoms of Abnormal Operation (Legacy
FAULT
Message Code
INTERNAL
or no 24 volt power to
x No 115 power to furnace
None
x Furnace fails to operate
x Integrated control module LED display
integrated control
provides no signal.
module
x Blown fuse or circuit
x ComfortNet™ thermostat “Call for
PS1
CLOSED
switch circuit is closed at
x Low stage pressure
E1
start of heating cycle.
error code.
PS1 OPEN E2
switch circuit is not
closed.
x Low stage pressure
E2
error code.
breaker
None None
LOCKOUT E0
an excessive number of
module has an internal
fault
x Integrated control
x Normal operation
OP
ignition “retries” (3 total)
x Furnace lockout due to
E0
error code.
Service” icon illuminated.
Service” icon illuminated
x ComfortNet™ thermostat scrolls “Check
Furnace” message
x LED display indicates
provides E0
x Furnace fails to operate
x Integrated control module LED display
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
39
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
with no further furnace operation.
x Induced draft blower runs continuously
provides E1
x Integrated control module LED display
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
provides E2
x Integrated control module LED display
T
E3
E4
E5
E6
E7
ROUBLESHOOTING
Notes & Cautions
repair.
applicable to your model
for allowable rise range
x Turn power OFF prior to
and proper circulator
x See Specification Sheet
Corrective Actions
blockage. Clean filters or
remove obstruction.
and performance. Correct speed
x Check filters and ductwork for
or replace blower motor if
x Check circulator blower speed
C
HART
speed.
section for piping details.
x See "Vent/Flue Pipe"
necessary.
alignment.
for blockage, proper length,
elbows, and termination. Correct
as necessary.
proper performance. Replace if
x Check burners for proper
x Check flue and air inlet piping
necessary.
x Check induced draft blower for
connection.
x Tighten or correct wiring
repair.
x Turn power OFF prior to
in flame sensor wiring.
x Correct short at flame sensor or
x Check for lingering flame.
x Verify proper operation of gas
valve.
x Turn power OFF prior to
repair.
automotive type
repair.
emery cloth.
section for piping details.
gas pressure.
repair.
correct replacement part.
x Replace fuse with 3-amp
x Turn power OFF prior to
x Sand flame sensor with
x See "Vent/Flue Pipe"
x See rating plate for proper
x Turn power OFF prior to
voltage wiring
coated/oxidized.
x Sand flame sensor if
x Inspect for proper sensor
alignment.
blockage, proper length, elbows,
and termination.
x Check inlet air piping for
integrated control module to
rating plate. Adjust as needed.
x Check and correct wiring from
x Compare current gas pressure to
x Replace igniter with
igniter.
x Replace shorted igniter.
correct replacement part.
x Replace control with
wiring.
x Check and correct unit ground
control. Replace if necessary.
x Check igniter output from
Possible Causes
ComfortNet™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
E3
HIGH
Message Code
x Insufficient conditioned air over
x Primary limit or
E3
the heat exchanger. Blocked
filters, restrictive ductwork,
LIMIT
OPEN
auxiliary limit circuit is
open.
improper circulator blower speed,
x Rollout limit circuit is
or failed circulator blower motor.
x Flame rollout.
open.
x Misaligned burners, blocked flue
and/or air inlet pipe, or failed
induced draft blower.
wiring.
x Loose or improperly connected
circuit.
x Short to ground in flame sense
x Lingering burner flame.
x Slow closing gas valve.
E4
FLAME
IMPROPER
call for heat.
x Flame sensed with no
E4
x Short in low voltage wiring x Locate and correct short in low
Not
Displayed
Not
Displayed
x Open Fuse
E5
x Flame sensor is coated/oxidized.
E6
WEAK
x Flame sense micro amp
E6
positioned in burner flame.
x Flame sensor incorrectly
FLAME
signal is low
improper gas pressure or
combustion air.
x Lazy burner flame due to
x Improperly connected igniter.
E7
IGNITER
x Problem with igniter
x Shorted igniter.
FAULT
circuit.
E7
control module.
x Poor unit ground.
x Igniter relay fault on integrated
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
error code.
error code.
error code.
error code.
error code.
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
runs continuously. No furnace operation.
x Induced draft blower and circulator blower
furnace operation.
provides E3
x Circulator blower runs continuously. No
x Integrated control module LED display
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x No furnace operation.
provides E4
x Integrated control module LED display
“Battery Power”.
provides E5
x ComfortNet™ thermostat displays
x Integrated control module LED display
x Normal furnace operation.
provides
x Integrated control module LED display
x Furnace fails to operate.
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
provides E7
x Integrated control module LED display
40
T
E8
E9
EA
0
ROUBLESHOOTING
C
HART
Notes & Cautions
repair.
with correct replacement
x Turn power OFF prior to
part.
x Replace pressure switch
x Turn power OFF prior to
repair.
with correct replacement
part.
x Replace pressure switch
x Replace induced draft
blower with correct
replacement part.
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair
specific model.
BEFORE turning power
ON. Memory card may be
removed after data is
loaded.
removing memory card.
x Use memory card for the
x Insert memory card
x Turn power OFF before
x Error code will be cleared
once data is loaded.
Corrective Actions
switch.
x Replace high stage pressure
x Repair short in wiring
Repair/replace if necessary.
piping for blockage, proper
length, elbows, and termination.
Check drain system. Correct as
necessary.
performance. Correct as
necessary.
or contact motion.
connection.
correct polarity.
x Inspect pressure switch hose.
x Inspect flue and/or inlet air
x Check induced draft blower
x Correct pressure switch set point
x Tighten or correct wiring
necessary.
x Review wiring diagram to
x Verify proper ground. Correct if
x Check and correct wiring.
x Populate shared data set using
memory card.
Possible Causes
ComfortNet™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
Message Code
contacts sticking.
x High stage pressure switch
E8
PS2
CLOSED
switch circuit is closed at
x High stage pressure
E8
wiring.
x Shorts in pressure switch circuit
start of heating cycle.
operating.
x Induced draft blower is
x Furnace is operating on
pinched, or connected
improperly.
blocked drain system or weak
induced draft blower.
point or malfunctioning switch
contacts.
x Pressure switch hose blocked
x Blocked flue and/or inlet air pipe,
x Incorrect pressure switch set
PS2 OPEN E9
low stage only
switch circuit is not
closed.
operating.
x High stage pressure
low stage only
x Induced draft blower is
x Furnace is operating on
wiring.
x Loose or improperly connected
E9
x Polarity of 115 volt AC power to
EA
REVERSED
x Polarity of 115 volt AC
furnace or integrated module is
PLTY
is reversed
EA
revered.
x Poor unit ground
shared data.
x Furnace does not contain any
d0
DATA
NO NET
x Data not yet on network.
d0
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
furnace operates normally on low stage.
x Furnace fails to operate on high stage;
x Integrated control module LED display
error code.
provides
x Furnace fails to operate on high stage;
error code.
furnace operates normally on low stage.
provides
x Integrated control module LED display
error code.
error code.
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
41
provides d
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x Integrated control module LED display
provides
x Furnace fails to operate.
x Integrated control module LED display
T
4
0
1
2
3
ROUBLESHOOTING
Notes & Cautions
repair
specific model.
x Turn power OFF prior to
x Use memory card for the
x Insert memory card
Corrective Actions
for the specific model. Re-
populate data using correct
memory card if required.
x Verify shared data set is correct
BEFORE turning power
ON. Memory card may be
C
HART
removed after data is
loaded.
removing memory card.
x Turn power OFF before
x Error code will be cleared
once data is loaded.
repair
x Turn power OFF prior to
connection.
x Tighten or correct wiring
correct replacement part.
with correct replacement
x Replace inductor with
x Replace circulator motor
through inductor. Replace if
open or short circuit.
x Verify continuous circuit
x Check circulator blower motor.
repair
with correct replacement
part.
x Turn power OFF prior to
Replace if necessary.
x Tighten or correct wiring
part.
x Replace circulator motor
x Replace integrated control
connection.
Replace if necessary.
Replace if necessary.
x Check circulator blower motor.
x Check integrated control module.
module with correct
repair
replacement part.
x Turn power OFF prior to
horse power is the same
x Verify circulator blower motor
x Replace motor with correct
specified for the specific furnace
replacement part.
x Use memory card for the
model. Replace if necessary.
x Verify shared data set is correct
specific model
x Insert memory card
for the specific model. Re-
populate data using correct
BEFORE turning power
ON. Memory card may be
memory card if required.
removed after data is
loaded.
removing memory card.
x Turn power OFF before
x Error code will be cleared
once shared data and
motor horse power match.
x Turn power OFF prior to
x Check filters for blockage.
repair.
Clean filters or remove
obstruction.
Remove obstruction. Verify all
registers are fully open.
sized for system. Resize/replace
ductwork if necessary.
"Location Requirements &
Considerations" for furnace
x Check ductwork for blockage.
x Verify ductwork is appropriately
installation requirements.
x See "Product Description" and
Possible Causes
ComfortNet™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
x Shared data set on memory card
d4
Message Code
INVALID
x Invalid memory card
d4
has been rejected by integrated
control module
MC DATA
data.
circulator motor power leads or
circulator motor power leads
x Loose wiring connection at
b0
MOTOR
NOT RUN
is not running when it
should be running.
x Circulator blower motor
b0
disconnected.
wiring connection at inductor (3/4
x Open circuit in inductor or loose
circulator motor control leads.
Hp and 1 Hp models only).
x Loose wiring connection at
x Failed circulator blower motor.
b1
COMM
MOTOR
module has lost
communications with
x Integrated control
x Failed integrated control module.
circulator blower motor.
x Failed circulator blower motor.
b1
in furnace.
x Incorrect circulator blower motor
x Incorrect shared data set in
b2
MOTOR
MISMATCH
horse power in shared
data set does not match
x Circulator blower motor
b2
integrated control module.
circulator blower motor
x Blocked filters.
x Restrictive ductwork.
x Undersized ductwork.
x High ambient temperatures.
b3
LIMITS
MOTOR
horse power.
x Circulator blower motor
is operating in a power,
temperature, or speed
limiting condition.
b3
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
error code.
operation.
provides d
Service” icon illuminated.
x Operation different than expected or no
x Integrated control module LED display
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
error code.
provides b
Service” icon illuminated.
Furnace” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
x Integrated control module LED display
x Furnace fails to operate.
error code.
provides b
Service” icon illuminated.
Furnace” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
x Integrated control module LED display
x Furnace fails to operate.
error code.
provides b
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x Integrated control module LED display
x Furnace operates at reduced performance.
error code.
provides b
x Airflow delivered is less than expected.
x Integrated control module LED display
42
T
4
5
6
7
9
ROUBLESHOOTING
C
HART
Notes & Cautions
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair
x Replace motor with correct
replacement part.
replacement part.
x Replace wheel with correct
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair.
replacement part(s).
x Replace with correct
x Use memory card for the
repair.
specific model.
x Turn power OFF prior to
Corrective Actions
grills/registers, duct system, and
furnace air inlet/outlet for
blockages.
x Check filters, filter
obstructions. Remove and
repair/replace wheel/motor if
necessary.
shaft rotation and motor.
Replace motor if necessary.
line voltage to furnace is within
the range specified on the
furnace rating plate.
x Check circulator blower for
x Check circulator blower motor
x Check power to furnace. Verify
x See "Product Description" and
"Location Requirements &
Considerations" for furnace
installation requirements.
Verify control is populated with
correct shared data set. See data
errors above for details.
x Check integrated control module.
x Check for locked rotor condition
(see error code above for
details).
x Check filters for blockage.
Clean filters or remove
obstruction.
Remove obstruction. Verify all
registers are fully open.
sized for system. Resize/replace
x Check ductwork for blockage.
ductwork if necessary.
x Verify ductwork is appropriately
Possible Causes
ComfortNet™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
x Abnormal motor loading, sudden
b4
MOTOR
Message Code
x Circulator blower motor
change in speed or torque, sudden
TRIPS
senses a loss of rotor
b4
blockage of furnace air inlet or
outlet.
filters, very restrictive ductwork,
blockage of furnace air inlet or
outlet.
housing.
x High loading conditions, blocked
control.
senses high current.
x Circulator blower motor
bearings.
x Obstruction in circulator blower
x Seized circulator blower motor
b5
ROTOR
MTR LCKD
fails to start 10
consecutive times.
x Circulator blower motor
b5
x High AC line voltage to furnace.
x Failed circulator blower motor.
x Low AC line voltage to furnace.
x High ambient temperatures.
b6
VOLTS
MOTOR
shuts down for over or
under voltage condition.
x Circulator blower motor
x Circulator blower motor
shuts down due to over
temperature condition on
b6
power module.
module.
x Error with integrated control
x Motor has a locked rotor
b7
MOTOR
PARAMS
does not have enough
information to operate
x Circulator blower motor
b7
condition.
properly.
x Blocked filters.
x Restrictive ductwork.
x Undersized ductwork.
b9
LOW ID
AIRFLOW
consecutive times.
x Airflow is lower than
demanded.
x Motor fails to start 40
b9
Symptoms of Abnormal Operation
error code.
error code.
error code.
error code.
error code.
provides b
Service” icon illuminated.
(Legacy & ComfortNet™ Thermostat)
x Furnace fails to operate.
x Integrated control module LED display
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x Furnace fails to operate.
provides b
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
x Integrated control module LED display
Furnace” message.
x Furnace fails to operate.
provides b
Service” icon illuminated.
Furnace” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
x Integrated control module LED display
x Furnace fails to operate.
provides b
Service” icon illuminated.
x Integrated control module LED display
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls “Check
Furnace” message.
x Furnace operates at reduced performance
or operates on low stage when high stage is
expected.
provides b
x Integrated control module LED display
43
S
TATUS
C
ODES
INTERNAL CONTROL FAULT/NO POWER
NORMAL OPERATION
O P
LOCKOUT DUE TO EXCESSIVE RETRIES
E 0
LOW STAGE PRESSURE SWITCH STUCK C LOSED AT START OF HEATING CYCLE
E 1
LOW STAGE PRESSURE SWITCH STUCK OPEN
E 2
OPEN HIGH LIMIT SWITCH
E 3
FLAME DETECTED WHEN NO FLAME SHOULD BE PRESENT
E 4
OPEN FUSE
E 5
LOW FLAME SIGNAL
E 6
IGNITER FAULT OR IMPROPER GROUNDING
E 7
HIGH STAGE PRESSURE SWITCH STUCK CLOSED AT START OF HEATING CYCLE
E 8
HIGH STAGE PRESSURE SWITCH STUCK OPEN
E 9
REVERSED 115 VAC POLARITY
E A
DATA NOT YET ON N ETWORK
d 0
INVALID MEMORY CARD DATA
d 4
BLOWER MOTOR NOT RUNNING
b 0
BLOWER COMMUNICATION ERROR
b 1
BLOWER HP MIS-MATCH
b 2
BLOWER MOTOR OPERATING IN POWER, TEMPERATURE, OR SPEED LIMIT
(1) Select model and desired
high stage cooling airflow. Determine the corresponding tap
( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate
ON / OFF p ositions. ( 2) Select model and de sired high stage
heating airflow. Determine the corresponding tap ( A, B, C, or
D ). Set dip switches 7 and 8 to the appropriate ON / OFF
positions. (3) Select the airflow adjustment factor taps A and
D are 1; Tap B is +10%; Tap C -10%. Set dip switches 3 and 4
to the appropriate ON / OFF positions.
To set Comfort Mode:
Select desired Comfort Mode profile
(see profiles above). Set switches 5 and 6 to the appropriate
ON / O FF positions.
Model Tap Low Stage High Stage Low Stage High Stage
Cool Cool Heat Heat
390
520
650
780
520
715
910
1170
553
748
943
1203
390
520
715
910
520
715
910
1170
520
715
910
1175
600
800
1000
1200
800
1100
1400
1800
850
1150
1450
1850
600
800
1100
1400
800
1100
1400
1800
800
1100
1400
1800
735
805
875
935
945
1015
1085
1155
1085
1155
1225
1260
875
945
1015
1085
1050
1120
1190
1260
1210
1225
1245
1260
1750
1800
*DVC80703BX*
*DVC80905CX*
*DVC81155CX*
*MVC80704BX*
*MVC80905CX*
*MVC81155CX*
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
NOTE: Airflow data shown applies to legacy mode operation only. For a fully communicating system,
please see the outdoor unit’s installation instructions for cooling and pump heating airflow data. See
ComfortNet™ System - Airflow Consideration section for details.
1050
1150
1250
1350
1350
1450
1550
1650
1550
1650
1750
1800
1250
1350
1450
1550
1500
1600
1700
1800
1725
1775
DIP S
Sw itch
Ban k
WITCHES
Purpose
Heat O FF
Delay
S1
Thermostat
Setup
Bus BIA SBIASON*ON*------------------------
S2
S3
S4
---
TERMBus Termination------ON*---------------------
Cooling
Speed Tap
Adjust
Taps
Ramping
Prof iles
Heating
Speed Tap
DEHUMS5
Not applicable
Function
90 secondsOFFOFF------------------------
120 secondsONOFF------------------------
150 seconds*OFFON------------------------
180 secondsONON------------------------
1-Stage T-stat------OFF---------------------
2-Stage T-Stat------ON---------------------
5-Min Delay---------OFF------------------
Auto Delay---------ON------------------
AOFFOFF------------------------
BONOFF------------------------
COFFON------------------------
D*ONON------------------------
Normal*------OFFOFF------------------
10%------ONOFF------------------
-10%------OFFON------------------
Normal------ONON------------------
A*------------OFFOFF------------
B------------ONOFF------------
C------------OFFON------------
D------------ONON------------
A------------------OFFOFF------
B*------------------ONOFF------
C------------------OFFON------
D------------------ONON------
Disabled*------------------------OFFUnused
Enabled------------------------ONUnused
12345678910
(*Indicates factory setting)
DIP Sw itc h No.
45
A
A
A
A
*MVC8_AA W
2
1
BK
WH
.
MAY
UNIT
SO
THIS
DO
.
TO
DEATH
INSTALLING
AILURE
OR
. F
OR
INJURY
PRESENT
SERVICING
BE
MAY
PERSONAL
,
BEFORE
DAMAGE
SOURCES
POWER
ALL
POWER
PROPERTY
ULTIPLE
ISCONNECT
HI GH V OLTAGE !
D
CAUSE
M
WH
BK
WH
C
E
HAR
NOTES:
1. SET HEAT ANTICIPATOR ON RO
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE
USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE
FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH
WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT
LEAST 105°C. USE COPPER CONDUCTORS O NLY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFOR
N.E.C. AND LOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST
RECENT, DEPRESS SWITCH FOR MORE THAN 2 SECONDS W HILE
IN STANDBY (NO THERMOSTAT INPUTS)
0
1
WH
M
N
4
RD
WH
T
M
R
E
S
0
F
PU
R
B
U
NER COM
O
L
B
WERCOM
BK
RD
L
B
S
Y
G
K
B
2
1
CIRCULATOR
BLOWER
0
0
0
6
IRING
H
PM
3
2
1
24V
O
DEHUM
DIAGNOSTIC
LED'S
1
2
3
4
1
2
3
4
5
4
3
6
3
I
2
C
1
R
D
R
P
A
R
A
P
ERMOSTATCO
T
H
Y2
Y1
DIP S WI TCHES
OM THERMO
R
E
D
N
TM
E
TME
N
W1
W2
2ND ST G DLY
T-STAT
HEAT OFF
DELAY
UNUSED
DEHUM
HEAT
DELAY
DJUST
COOL
F
NEUTRAL
5
4
3
2
1
.
V
IAGRAM
C
O
N
YL
WH
PU
T
T
AUTO RESET
AUXILIARY
LIMIT CONTROL
E
N
CTION
S
N
2
G
R
C
SEE
NOTE 5
YL
OR
LINE
S
HUM
BK
WH
GR
PK
STAT AT 0. 7 AMP S.
A
TO
5
1
1
V
A
C
1
/
R
P
W
E
YL
24V HUM.
C
S
P
GND
P
CTI
O
O
R
T
C
E
T
ON DEV
JUNCTION BOX
K
B
NO
YL
WH
TO 115VAC/ 1
Ø /60 HZ POWER SUPPLY WITH
OVERCURRENT PROTE
P
L
Y
U
I
D
O
N
EVI
ICE
DISCONNECT
H
I
T
W
C
E
CHASSIS GROUND
BR
L
L
A
OR
YL
WH
YL
BL
WH
BK
BLOWER
COMPARTMENT
DOOR SWITCH
(OPEN WHEN
DOOR OPEN)
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
HI VOLTAGE (115
O
W
G
E
N
INTEGRAT
GN
INTEGRAT ED CONTROL MODULE
R
24V THERMOSTAT CONNECT IONS
Y1
W1
W2
Y2
G
O
M
U
E
H
D
24V HUM.
C
B
K
O
T
R
T
MIC
INTE GRATED CONTR OL M ODULE
V
F
G
T
A
L
H
E
I
O
IELD
JUNCTION
E
T
R
INTERNALTO
NTROL
ED CO
PLUG CONNEC TION
DOOR
SWITCH
INDUCTO
70kBTU,90 kBTU,
115 kBTU M ODEL S
ONLY
LIN
E
EAC
HUM
IGN
LINE
FUSE 3 A
D
TO+
V
TO
MICRO
O
R
O
V)
M
L
A
I
N
R COI
IND HI
IND LO
FS
TH (4)
C
HLO (10)
PSO (7)
PS1 (2)
P
S
2
HIGH FIRE
PRES S. SWT ICH
HLI (1)
MVL (13)
MVH (1 4)
MVC (8 )
GND (5)
TR (11)
N
G
D
V
+
DC
2
X
(
R
T
X
3
(
JUNCT ION BOX
L
INDOOR
IR
CIRCULATOR
BLWR
ELECTRONIC
IR CLEANER
ID
BLWR
HUMI DI FIER
HOT SURFACE
IGNITER
FLAME SENSOR
115 VAC
24 VAC
24V HUM.
NO
1
)
(
2
4
)
(
(
)
1
)
C
I
)
F
HUMID
I
I
E
R
EQUIPM ENT GND
FIELD SPLICE
SWITCH (TEMP.)
SWITCH (PRESS
O
PROT. D EVICE
R
NO
I
N
C
BLWR
V
C
R
D
O
O
AIR
T
U
L
FIELD G
I
C
R
E
GND
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
40 VA
TRANSFORMER
LOW FIRE P RESS.
SWITCH
C
GND
O
R
ND
I
R
T
N
E
G
.)
URR
E
T
N
GAS
VALVE
INTEGRATED CONTROL MODULE
PM
HI
C
RD
YL
PU
PU
RD
FUSE
4
2
1
V
3
A
YL
2
1
3
6
9
12
15
RD
4
5
RD
7
8
YL
10
11
RD
13
BR
14
B
L
WH
BL
BK
EAC
WH
B
K
GND
INDUCTOR COIL
70kBTU,90 kBTU,
115 kBTU M ODEL S
ONLY
COLOR CODES:
PK PINK
B
R
ROWN
B
WH WHITE
BL BLUE
GY GRAY
O
M T
RD RED
Y
L
E
Y
OROR
PU PURPLE
GN GREEN
BK BLACK
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
46
*MVC8_AB, *DVC8_AA W
A
A
A
ID BLOWER TWO-STAGE PRESSURE
SWITCH ASSEMB LY
HOT
SURFACE
IGNITER
2 CIRCUIT
2
1
CONNECTOR
BK
TWO STAGE
WH
GAS VALVE
(HONEY WELL)
.
MAY
UNIT
SO
THIS
DO
.
TO
DEATH
INSTALLING
AILURE
OR
. F
OR
WH
INJURY
PRESENT
SERVICING
BE
MAY
PERSONAL
,
BEFORE
DAMAGE
SOURCES
POWER
ALL
POWER
PROPERTY
ULTIPLE
ISCONNECT
HI GH V OLTAGE !
D
CAUSE
M
RD
BK
WH
BK
WH
WH
RD
ECM M TR
HARNESS
NOTES:
1. SET HEAT ANTICIPATOR ON ROOM TH ERMOSTAT AT 0 .7 AMPS.
2. MANUFACTUR ER'S SPECIFIED REPL ACEMENT PARTS MUST BE
USED WHE N SERVICING.
3. IF ANY OF THE ORIGI NAL W IRE AS SUPPLIED WITH THE
FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH
WIRI NG MATERIAL HAVING A TEMPE RATURE RATING OF AT
LEAST 105 C. U SE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERM ANENTLY GROUNDED AND CONFORM TO
N.E.C. AND LOCAL CODES .
5. TO RECALL THE LAST 6 FAU LTS, MOST RECENT TO LEAST
RECENT, DEPRESS SWITCH F OR MORE THAN 2 SECONDS WHILE
IN STANDBY (NO THERMOSTAT INPUTS)
LOW FIRE
PRESSURE
SWITCH
2
HI
3
BL
C
1
PM
MANUAL RESET ROLLOUT LIMIT
PU
AUTO RESET PRI MARY
3
2
1
CONTROLS
LIMIT CONTROL
WH
RD
BK
BURNER COMPARTMENT
BLOWER COMPARTMENT
24 V THER MOSTAT CONNECTIONS
W2
DEHUM
DIAGNOSTIC
LED'S
CONTROL
MODULE
1
2
3
4
1
2
3
4
5
BL
GY
4
BK
3
2
1
CIRCULATOR
BLOW ER
W1
Y2
Y1
O
INTEGRATED
T
2ND STG DLY
W
O
T-STAT
S
HEAT OFF
T
DELAY
G
DIP SWITCHES
E
UNUSED
DEHUM
4 CIRCUIT MOTOR
HEAT
CONNECTOR
DELAY
ADJUST
COOL
5 CIRC UIT CO NNECTO R
5
4
3
2
1
WH
BR
G
FS
NEUTRAL
PU
SEE
NOTE 5
BK
GR
PK
C
C
OR
NO
YL
GND
AUTO RESET
AUXILIARY
LIMIT CONTROL
1
R
2
3
6
9
12
15
YL
LINE
HUM
WH
YL
PU
2
5
8
11
14
GND
24V HU M.
RD
INDUCED
DRAFT
BLOWER
FUSE
YL
1
4
7
10
13
WH
BK
E
C
IRING
C
NO
PU
24 V
3 A
RD
RD
YL
RD
BR
BL
RD
BL
BK
INDUCTOR C OIL
70kBTU,90kBTU,
115kBTU MODELS
ONLY
COLOR CODE S:
PK PIN K
BR B ROWN
WH WHITE
BL BLUE
GY GRAY
RD RED
YL YELLOW
OR ORA NGE
PU PURPLE
GN GREEN
BK BL ACK
D
HIGH FIRE
PRESSURE
SWITCH
YL
RD
BR
WH
IAGRAM
JUNCTION BOX
YL
FLAME
SENSOR
OR
YL
GN
WH
YL
BL
24
VAC
11 5
VAC
40 VA
TRANSFORMER
WH
BK
BLOWER
COMPARTMENT
DOOR SWITC H
(OPEN WH EN
DOOR OPEN)
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
HI VOLTAGE (115V)
HI VOLTAGE FIELD
INTEGRATED CONTROL
BK
WH
DISCONNECT
TO 115VAC/ 1
OVERCURRENT PRO TECTION DEVICE
WARNING:
DISCONNECT POWER
BEFOR E SERVICI NG.
WIR ING TO U NIT
MUST BE PROPERLY
POLAR IZED AND
GROUNDED.
CHASSIS GROUND
DOOR
SWITCH
INDUCTOR COI L
70kBTU,90kBTU,
115kBTU MODELS
LINE
I
N
T
E
G
R
A
T
E
D
C
O
N
T
R
O
L
M
O
D
U
L
E
LINE
FUSE 3 A
R
Y1
2
4
V
T
H
E
R
W1
M
O
S
T
W2
T
C
O
TO
N
MICRO
Y2
N
E
C
T
G
I
O
N
S
O
DEHUM
2
4
V
H
U
M
C
.
BK
TO
R
TO
MICRO
INTEGRATED CONTROL MODULE
JUNCTION
TERMINAL
INTERNA L TO
PLUG CONNECTION
GND
L
N
Ø /60 HZ POWER SUPPLY WITH
GND
L
JUNCTION BOX
ONLY
EAC
HUM
IGN
FS
TO +VDC
INDOOR
AIR
CIRCULATOR
BLWR
ELECTRO NIC
AIR CLEAN ER
IND HI
ID
BLWR
IND LO
HUMIDIFI ER
HOT SURFACE
IGNITER
FLAME SENSO R
115 VAC
TH (4)
HLO (10)
PSO (7)
PS1 (2)
PS2 (12)
HIGH FIRE
PRESS. SWTICH
HLI (1 )
MVL (13)
MVH (14)
MVC ( 8)
GND ( 5)
TR (11)
GND ( 4)
+ VDC (1)
RX (2)
TX (3)
24 VAC
AUT O RESET AUXILI ARY LI MIT
CONTROLS
24V HUM.
NO
INDOOR
CIRCULATOR
HUMIDIFI ER
EQUIPMENT GND
FIELD SPLICE
SWIT CH (TEM P.)
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
TO
115 VAC/ 1
Ø /60 HZ
POWER SUPPLY WITH
OVERCURRENT
PROTECTION DEVICE
WARNING:DISCONNECT
POWER BEFORE
SERV ICING. WIRING
TO UNIT MUST BE
PROPERLY POLARIZED
AND GROUNDED.
N
DISCONNE CT
GND
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
40 VA
TRANSFORME R
AUTO RESET PRIMARY
LIMIT CONTROL
LOW FIRE PRESS.
SWITCH
C
NO
C
MANUAL RESET RO LLOUT
LIMIT CONTROLS
PM
HI
C
GAS
VALV E
GND
AIR
BLWR
FIELD GND
IGNITER
I
N
T
E
G
R
A
T
E
D
C
O
N
T
R
O
L
M
O
D
U
L
E
0140F00660 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.