Goodman Mfg SS-CE120 User Manual

PRODUCT SPECIFICATIONS
CE COMMERCIAL
SPLIT SYSTEM AIR CONDITIONER
Standard Features
Single-scroll compressor with crankcase heater
• Quiet operating top discharge
• Permanently lubricated condenser motor
• Copper tube/aluminum fi n coil
• Brass suction ball valve and liquid front-seating shut-off
• valve with sweat connections
Large-capacity liquid line fi lter dryer
• High- and low-pressure switches
• Contactor with lug connections
• Ground lug connection
• ETL Listed
50 HZ, 10-TON
NOMINAL COOLING CAPACITY:
120,000 BTU/H [35.2 KW]
Cabinet Features
Unique Goodman® sound control top design
• Steel louver coil guard protects the coil from
• damage and adds strength to unit
Bottom pan rails elevate unit above slab
• Heavy-gauge galvanized-steel cabinet
• Attractive Architectural Gray powder-paint fi nish with 500-
• hour salt-spray approval
When properly anchored, meets the 2001 Florida Building
• Code unit integrity requirements for hurricane-type winds
SS-CE120 www.goodmanmfg.com 11/06
Supersedes 10/06
P
RODUCT SPECIFICATIONS
NOMENCLATURE
CAA
Product Category Engineering
C Split System Major/ Minor Revisions
Unit Type
E Commercial Air Conditioner Electrical K Air Conditioner 1 208/230 V, 1 Phase, 60 Hz P Heat Pump 2 220/240 V, 1 Phase, 50 Hz
Nominal Capacity 4 460 V, 3 Phase, 60 Hz
018 1½ Tons 048 4 Tons 5 380/415 V, 3 Phase, 50 Hz 024 2 Tons 060 5 Tons 030 2½ Tons 090 7½ tons 036 3 Tons 120 10 Tons 042 3½ Tons
E
2
120
3,4,5 6
3
7,81
3 208/230 V, 3 Phase, 60 Hz
2 www.goodmanmfg.com SS-CE120
P
RODUCT SPECIFICATIONS
SPECIFICATIONS
Capacities CE120-5 Condenser Fan / Coil CE120-5
Nominal Cooling (BTU/h) 114,000 Horsepower - RPM 1-930
EER¹ 9.0 Fan Diameter/ # Fan Blades 26/3
Decibels 84 Outdoor Nominal CFM 4,400
Compressor Face Area (ft²) 29.4
RLA / LRA 17.2 / 118 Rows Deep/ Fins per Inch 1/22
Volts 380-420 Fin Type Ripple
Condenser Fan Motor Coil No. of Tubes 40
Horsepower / FLA 1 / 2 Coil Tube Diameter
Volts 380 Electrical Data Refrigeration System Voltage-Hz / Phase 380/415-50/3
Liquid Valve Size (“O.D.) Min. Circuit Ampacity² 23.6
Suction Valve Size (“O.D.) 1 Max. Overcurrent Protection³ 40 amps
Valve Type Sweat Min / Max Volts 342/456
Refrigerant Charge 32 Power Supply Conduit Size ½” or ¾”
Ship Weight (lbs-[kg]) 296 [134]
 Energy E ciency Ratio  Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.
PERFORMANCE RATINGS
Outdoor
Unit
CE120-5
 Energy E ciency Ratio  kWI = Compressor + Indoor Blower + Outdoor Fan Watts
Indoor Unit
Total BTU/h Sensible BTU/h EER¹ kWI²
AR-120-2 114,000 83,000 9.0 12.67
(2) CA*F4860*6* 114,000 83,000 9.0 12.67
Cooling Capacity
dBs
84
SS-CE120 www.goodmanmfg.com 3