Goodman Mfg GSC140601A, GSC140481A, GSH140241A, GSH 14 SEER, GSC140421A User Manual

...
TECHNICAL INFORMATION MANUAL
GSH 14 SEER Remote Heat Pump
Refer to Service Manual RS6100004 for installation, op-
eration, and troubleshooting information.
All safety information must be followed as provided in the
Service Manual.
Models listed on page 3.
®
This manual is to be used by qualified HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person.
Copyright © 2006 Goodman Manufacturing Company, L.P.
RT6213004
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
G S H 14 036 1 A A
Brand Name
G: Goodman
(Standard Feature Set Models)
S: Goodman Deluxe
(High Feature Set Models)
Product Family
S: Split System
Product Type
C: Condenser R-22 X: Condenser R-410A H: Heat Pump R-22 Z: Heat Pump R-410A
SEER
SEER Rating
Minor Revision
A: Initial Release
Major Revision
A: Initial Release
Electrical
1: 208/230V/60Hz/1ph
3: 208/230V/60Hz/3ph 4: 460V/60Hz/3ph
Nominal Capacity
018: 1.5 tons 024: 2 tons 036: 3 tons 042: 3.5 tons 048: 4 tons 060: 5 tons
HIGH VOLTAGE!
WARNING
WARNING
WARNING
WARNING
GROUND MAY RESULT IN PRODUCT DAMAGE, PERSONAL INJURY OR DEATH.
2
DISCONNECT ALL POWER BEFORE SERVICING. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROP­ERTY DAMAGE, PERSONAL INJURY OR DEATH.
ONLY INDIVIDUALS MEETING THE REQUIREMENTS OF AN "ENTRY LEVEL TECHNICIAN" AS SPECIFIED BY THE AIR CONDITIONING AND REFRIGERATION INSTITUTE (ARI) MAY USE THIS INFORMATION. AT­TEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH BACK-
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
GSH140181A* GSH140241A* GSH140301A* GSH140361A* GSH140421A* GSH140481A* GSH140601A*
* Indicates minor revision & is not used for order entry or inventory management
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY,
WARNING
WARNING
WARNING
WARNING
HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES.
OR DEATH, DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASO­LINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
DO NOT CONNECT OR USE ANY DEVICE THAT IS NOT DESIGN CERTI­FIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR
3
PRODUCT DESIGN
GSH14 SEER split system heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications.
Air is drawn through the outdoor coil by a propeller fan, and is discharged vertically out the top of the unit. No additional restriction (ductwork) shall be applied.
The suction and liquid line connections are of the sweat type for field piping with refrigerant type copper. Non-back seating valves are factory installed to accept the field run copper. The total refrigerant charge for a normal installation is factory installed in the condensing unit. This charge is for the match­ing evaporator coil and a 15 foot refrigerant line set.
Systems should be properly sized by heat gain and loss calculations made according to methods of the Air Condi­tioning Contractors Association (ACCA) or equivalent. It is the contractors responsibility to ensure the system has ad­equate capacity to heat or cool the conditioned space.
GSH14 units use high-efficiency Copeland sors and there are a number of design characteristics which are different from the scroll compared to the traditional recip­rocating compressor.
Due to their design Scroll compressors are inherently more tolerant of liquid refrigerant.
GSH14 model heat pumps do not use a reversing relay to energize the reversing valve. The reversing valve is energized in the cooling cycle through the "O" terminal on the room thermostat.
This unit is for outdoor installation only. Refer to minimum figure for clearances from the sides of the unit to full walls and other objects.
NOTE: This unit cannot be completely enclosed. At least one side must be unrestricted.
These clearances will help avoid air recirculation. If installing two or more units at the same location, allow at least 24 inches between units. If only one side is restricted (for ex­ample, against the outside wall of a house), the unit may be placed as close as 8" to that one wall.
®
scroll compres-
DO NOT locate the unit:
* Directly under a vent termination for a gas appliance. * Within 3 feet of a clothes drier vent * Where the refreezing of defrost water would create
a hazard
* Where water may rise into the unit.
NOT
RECOMMENDED
B B B
AA
A
AA AAA
C
AA
AA
C
AA
CC
B
AA
OK!
OK!
OK!
Model Dimensions - W x D x H
GSH140181A* 29 x 29 x 34¼ GSH140241A* 29 x 29 x 38¼
OK!
OK!
OK!
GSH140301A* 29 x 29 x 38¼ GSH140361A* 35½ x 35½ x 38¼ GSC140421A* 35½ x 35½ x 38¼ GSC140481A* 35½ x 35½ x 38¼ GSC140601A* 35½ x 35½ x 38¼
4
HEAT PUMP SPECIFICATIONS GSH14[018-060]1A*
y
GSH140181A*
Cooling Capacity, BTUH 18,000 24,000 28,000 34,600 39,600 46,000 55,000 Compressor
R.L. Amps 9 10.9 12.2 13.4 16 18.3 19.8 L.R. Amps 41.0 54.0 63.0 73.0 88.0 109.0 137.0 Loss of Charge Pressure Switch
Open / Close 7 PSIG/25 PSIG 7 PSIG/25 PSIG 7 PSIG/25 PSIG 7 PSIG/25 PSIG 7PSIG/25 PSIG 7 PSIG/25 PSIG 7PSIG/25 PSIG
Condenser Fan Motor
Horsepower 1/12 1/6 1/6 1/4 1/4 1/4 1/4
F.L. Amps 0.6 1.1 1.1 1.5 1.5 1.5 1.5 Liquid Line, Inches O.D. 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" Suction Line, Inches O.D. 3/4" 3/4" 3/4" 7/8" 7/8" 7/8" 7/8" Refrigerant Charge 160 160 165 220 220 280 285 Power Supply 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
Minimum Circuit Ampacit
Maximum Overcurrent Device Electrical Conduit Size
Power Supply (Inches) 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4 Approximate Shipping Weight 199 207 207 242 242 266 280
(1)
Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
May use fuses or HACR type Circuit Breakers of the same size as noted.
(1)
(2)
11.8 14.7 16.3 18.3 21.5 27.8 27.3 20 20 20 30 30 40 40
GSH140241A*
GSH140301A*
GSH140361A*
GSH140421A*
GSH140481A*
GSH140601A*
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
5
COOLING PERFORMANCE DA TA GSH140181A*
COOLING OPERATION
EXPANDED PERFORMANCE DATA
1.53 1.58 1.51 1.54 1.59 1.64 1.56 1.59 1.64 1.70
1.48
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
0.60 0.39 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
0.79
5.8 6.0 5.8 6. 0 6.2 6.4 6.2 6.3 6.5 6.8
5.6
1.48 1.52 1.46 1.49 1.54 1.59 1.51 1.54 1.59 1.64
1.43
65 75 85 95 105 115
DT 21 19 16 11 21 19 16 11 21 19 16 11 21 19 16 11 21 19 16 11 19 18 15 10
MODEL: GSH140181A* / CA*F3131B6A*+TXV / MBR800**-1 Design Subcoo ling, 9 ±3 °F @ the liquid service valve, ARI 95 test conditions
MBh 17.6 18.3 20.0 - 17.2 17.9 19.6 - 16.8 17.4 19.1 - 16.4 17.0 18.6 - 15.6 16.2 17. 7 - 14.4 15.0 16.4 -
IDB*Airflow 596367715963677159636771596367715963677159636771
S/T 0.75 0 .62 0.43 - 0.77 0.65 0.45 - 0.79 0.66 0.46 - 0.82 0.68 0.47 - 0.85 0 .71 0.49 - 0.86 0.72 0.50 -
HI PR 140 151 159 - 157 169 179 - 179 193 20 4 - 204 220 232 - 229 247 261 - 254 273 288 -
AMPS 4.4 4.5 4.6 - 4.7 4.8 5.0 - 5.1 5.3 5.4 - 5.5 5.6 5.8 - 5.8 6.0 6.2 - 6.2 6.3 6.5 -
Delta T 18 1 6 1 2 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 1 2 - 17 15 11 -
675 KW 1.20 1.22 1.26 - 1.29 1.32 1.36 - 1.37 1.40 1.44 - 1.44 1.47 1.51 - 1.49 1.53 1 .58 - 1.55 1.58 1.63 -
S/T 0.71 0 .60 0.41 - 0.74 0.62 0.43 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0 .68 0.47 - 0.82 0.68 0.47 -
MBh 17.1 17.7 19. 4 - 16. 7 17.3 19.0 - 16.3 16. 9 18.5 - 15.9 16.5 18.1 - 15.1 15. 7 17.2 - 14.0 14.5 1 5. 9 -
LO PR 63 67 73 - 67 71 77 - 69 74 80 - 73 77 84 - 76 81 8 8 - 79 84 91 -
HI PR 139 150 158 - 156 168 177 - 177 191 20 2 - 202 217 230 - 227 245 258 - 251 270 285 -
AMPS 4.4 4.5 4.6 - 4.7 4.8 5.0 - 5.1 5.2 5.4 - 5.4 5.6 5.7 - 5.8 5.9 6.1 - 6.1 6.2 6.5 -
Delta T 19 1 6 1 2 - 19 16 12 - 19 16 12 - 19 17 13 - 19 16 1 2 - 18 15 12 -
70 600 KW 1.19 1.22 1.25 - 1.28 1.31 1.35 - 1.3 6 1.38 1.43 - 1.42 1.46 1.50 - 1.48 1.51 1.56 - 1.53 1.57 1.62 -
S/T 0.69 0 .57 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.44 - 0.78 0 .65 0.45 - 0.79 0.66 0.46 -
MBh 15.8 16.4 17. 9 - 15. 4 16.0 17.5 - 15.1 15. 6 17.1 - 14.7 15.2 16.7 - 14.0 14. 5 15.9 - 12.9 13.4 1 4. 7 -
LO PR 62 66 72 - 66 70 76 - 68 73 79 - 72 76 83 - 75 80 8 8 - 78 83 91 -
HI PR 135 145 153 - 151 163 172 - 172 185 19 5 - 196 211 223 - 220 237 250 - 244 262 277 -
AMPS 4.2 4.3 4.5 - 4.6 4.7 4.8 - 5.0 5.1 5.2 - 5.3 5.4 5.6 - 5.6 5.7 5.9 - 5.9 6.1 6.3 -
Delta T 19 1 6 1 2 - 19 17 13 - 19 17 13 - 19 17 13 - 19 17 1 3 - 18 15 12 -
LO PR 60 64 70 - 64 68 74 - 66 71 77 - 70 74 81 - 73 78 8 5 - 76 80 88 -
525 KW 1.16 1.19 1.22 - 1.25 1.28 1.31 - 1.3 2 1.35 1.39 - 1.39 1.42 1.46 - 1.45 1.48 1.52 - 1.50 1.53 1.58 -
S/T 0.850.760.570.370.880.790.600.380.900.810.610.390.930. 83 0.63 0.41 0.97 0.86 0.65 0.42 0.97 0.87 0.66 0.42
MBh 17.9 18.5 20.0 21.5 17.5 18. 0 19.5 21.0 17.1 17.6 19.1 20 .5 16.7 17.2 18.6 20.0 15.9 16.3 17.7 19.0 14.7 15.1 16.4 17.6
675 KW 1.211.231.271.311.301.331.371.411.381.411.451.501.45
HI PR 142 153 161 168 159 171 181 189 181 19 5 206 214 206 222 234 244 232 249 263 275 256 276 291 304
AMPS4.44.54.74.84.84.95.05.25.25.35.55.75.55. 7 5.8 6.1 5.9 6.0 6.2 6.4 6.2 6.4 6.6 6.8
LO PR 64 68 74 79 67 71 78 83 70 74 81 86 73 78 85 91 77 82 89 95 80 85 92 98
S/T 0.810.720.550.350.840.750.570.370.860.770.580.370.89
MBh 17.4 17.9 19.4 20.8 17.0 17. 5 19.0 20.3 16.6 17.1 18.5 19 .9 16.2 16.7 18.1 19.4 15.4 15.8 17.2 18.4 14.3 14.7 15.9 17.1
Delta T2220161122201711222017112220 17 11 22 20 16 11 20 19 15 11
75 600 KW 1.201.231.261.301.291.321.361.401.371.401.441.491.441.47 1.51 1.56 1.49 1.53 1.58 1.63 1.55 1.58 1.63 1.68
HI PR 140 151 160 166 158 170 179 187 179 19 3 204 212 204 220 232 242 230 247 261 272 254 273 288 301
AMPS4.44.54.64.84.74.85.05.25.15.35.45.65.5
LO PR 63 67 73 78 67 71 77 82 69 74 80 86 73 77 84 90 76 81 88 94 79 84 91 97
S/T 0.780.700.530.340.810.720.550.350.830.740.560.360.860. 77 0.58 0.37 0.89 0.80 0.60 0.39 0.90 0.80 0.61 0.39
MBh 16.1 16.5 17.9 19.2 15.7 16. 2 17.5 18.8 15.3 15.8 17.1 18 .3 15.0 15.4 16.7 17.9 14.2 14.6 15.8 17.0 13.2 13.5 14.7 15.7
Delta T2220171122201712222117122221 17 12 22 20 17 12 21 19 16 11
525 KW 1.171.201.231.271.261.291.321.371.331.361.411.451.40
HI PR 136 147 155 161 153 164 174 181 174 18 7 197 206 198 213 225 235 223 240 253 264 246 265 280 292
AMPS4.34.44.54.74.64.74.95.05.05.15.35.55.35. 5 5.6 5.8 5.7 5.8 6.0 6.2 6.0 6.1 6.3 6.6
LO PR 61 65 71 76 65 69 75 80 67 71 78 83 70 75 82 87 74 79 86 91 76 81 89 94
Shaded area is AR I Ratin g Co ndit ions IDB : En tering Ind oor Dry Bu lb T em pe ra ture KW = Tot al sys tem power AMPS=out door un it amps (comp. +fan)
6
COOLING PERFORMANCE DA TA GSH140181A*
COOLING OPERATION
EXPANDED PERFORMANCE DATA
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
65 75 85 95 105 115
S/T 0.930.870.710.530.970.910.740.551.000.930.760.561.000.960.780.581.001.000.810.611.001.000.820.61
MBh 18.3 18.7 19.9 21.3 17.8 18. 2 19.5 20.8 17.4 17.8 19.0 20.3 17.0 17.4 18.5 19.8 16.1 16.5 17.6 18.8 14.9 15.3 16.3 17.4
Delta T232219152322201624222016232320162222191620211814
HI PR 143 154 163 170 161 173 183 190 183 19 7 208 2 17 208 224 237 2 47 234 2 52 266 278 259 278 294 307
AMPS4.54.64.74.94.84.95.15.35.25.35.55.75.65.75.96.15.96.16.36.56.36.46.66.9
S/T 0.890.830.680.510.920.860.700.530.940.890.720.540.970.910.740.561.000.950.770.581.000.960.780.58
MBh 17.7 18.1 19.4 20.7 17.3 17. 7 18.9 20.2 16.9 17.3 18.5 19.7 16.5 16.8 18.0 19.2 15.7 16.0 17.1 18.3 14.5 14.8 15.8 16.9
LO PR 64 68 75 79 68 72 79 84 71 75 82 87 74 79 86 92 78 83 90 96 80 85 93 9 9
Delta T242320162423201624232016252421162423201622221915
HI PR 142 153 161 168 159 171 181 189 181 19 5 206 2 14 206 222 234 2 44 232 2 50 263 275 256 276 291 304
AMPS4.44.54.74.84.84.95.05.25.25.35.55.75.55.75.86.15.96.06.26.46.26.46.66.8
S/T 0.860.800.650.490.890.830.680.510.910.850.690.520.940.880.720.540.980.910.740.560.980.920.750.56
MBh 16.4 16.7 17.9 19.1 16.0 16. 3 17.4 18.6 15.6 15.9 17.0 18.2 15.2 15.6 16.6 17.8 14.5 14.8 15.8 16.9 13.4 13.7 14.6 15.6
LO PR 64 68 74 79 67 71 78 83 70 74 81 86 73 78 85 91 77 82 89 95 80 85 92 9 8
Delta T252420162524211725242117252421172524211623221915
HI PR 138 148 156 163 154 166 175 183 176 18 9 199 2 08 200 215 227 2 37 225 2 42 256 267 248 267 282 295
AMPS4.34.44.64.74.74.84.95.15.05.25.35.55.45.55.75.95.75.86.06.36.06.26.46.6
LO PR 62 66 72 76 65 69 76 81 68 72 79 84 71 76 83 88 75 79 87 92 77 82 90 9 5
S/T 0.980.940.850.691.000.980.880.711.001.000.900.731.001.000.930.761.001.000.970.791.001.000.980.79
MBh 18.6 18.9 19.8 21.2 18.1 18. 5 19.4 20.7 17.7 18.1 18.9 20.2 17.3 17.6 18.4 19.7 16.4 16.7 17.5 18.7 15.2 15.5 16.2 17.3
Delta T252423202525232024252320242423202223232021212219
HI PR 145 156 164 171 162 175 184 192 185 19 9 210 2 19 210 226 239 2 49 237 2 55 269 280 261 281 297 310
AMPS4.54.64.84.94.95.05.15.35.35.45.65.85.65.85.96.26.06.16.36.66.36.56.76.9
LO PR 65 69 75 80 69 73 80 85 71 76 83 88 75 80 87 93 78 83 91 97 81 86 94 100
S/T 0.930.900.810.660.970.930.840.680.990.950.860.701.000.990.890.721.001.000.920.751.001.000.930.76
MBh 18.0 18.4 19.3 20.5 17.6 18. 0 18.8 20.1 17.2 17.5 18.4 19.6 16.8 17.1 17.9 19.1 15.9 16.2 17.0 18.2 14.8 15.0 15.8 16.8
Delta T262524212626242126262421262624212425242123232219
HI PR 143 154 163 170 161 173 183 190 183 19 7 208 2 17 208 224 237 2 47 234 2 52 266 278 259 278 294 307
AMPS4.54.64.74.94.84.95.15.35.25.35.55.75.65.75.96.15.96.16.36.56.36.46.66.9
S/T 0.900.870.780.630.930.900.810.660.950.920.830.670.990.950.860.701.000.990.890.721.000.990.900.73
MBh 16.6 17.0 17.8 19.0 16.3 16. 6 17.4 18.5 15.9 16.2 16.9 18.1 15.5 15.8 16.5 17.6 14.7 15.0 15.7 16.8 13.6 13.9 14.5 15.5
LO PR 64 68 75 79 68 72 79 84 71 75 82 87 74 79 86 92 78 83 90 96 80 85 93 9 9
Delta T262624212626252127262521272625212626242124242320
HI PR 139 149 158 165 156 168 177 185 177 19 1 201 2 10 202 217 229 2 39 227 2 44 258 269 251 270 285 297
AMPS4.44.54.64.84.74.85.05.15.15.25.45.65.45.65.75.95.85.96.16.36.16.26.46.7
LO PR 62 66 72 77 66 70 76 81 68 73 79 85 72 76 83 89 75 80 87 93 78 83 90 9 6
MODEL: GSH140181A* / CA*F3131B6A*+TXV / MBR800**-1 Design Subcooling, 9 ±3 °F @ the liquid service valve, ARI 95 test conditions
IDB*Airflow 596367715963677159636771596367715963677159636771
675 KW 1.221.241.281.321.311.341.381.421.391.421.461.511.461.491.541.591.521.551.601.651.571.611.661.71
80 600 KW 1.211.231.271.311.301.331.371.411.381.411.451.501.451.481.531.581.511.541.591.641.561.591.641.70
525 KW 1.181.211.241.281.271.301.331.381.351.371.421.461.411.441.491.541.471.501.551.601.521.551.601.66
675 KW 1.231.251.291.331.321.351.391.431.401.431.481.521.471.501.551.601.531.561.621.671.581.621.671.73
525 KW 1.191.221.251.291.281.311.351.391.361.381.431.471.421.451.501.551.481.511.561.611.531.571.621.67
85 600 KW 1.221.241.281.321.311.341.381.421.391.421.461.511.461.491.541.591.521.551.601.651.571.611.661.71
Shaded area is AR I Ra tin g Co ndit i ons IDB : En te ring Ind oor Dry Bu l b Temperature KW=Tot al sy s tem power AMPS=outdoor un it amps (comp. +f an)
7
COOLING PERFORMANCE DA TA GSH140241A*
COOLING OPERATION
EXPANDED PERFORMANCE DATA
24.4 26.2 20.8 21.4 23.2 24.9 19.3 19.9 21.5 23.1
0.64 0.41 0.98 0.88 0.66 0.43 0.99 0.88 0.67 0.43
22.6
0.85
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
2.04 2.11 2.02 2.06 2.12 2.19 2.08 2.13 2.19 2.26
1.98
12.0 12.3 12.0 12.2 12.5 12.8 12.5 12.7 12.9 13.2
11.7
87 93 78 83 91 97 81 86 94 100
80
24.1 25.8 20.5 21.1 22.9 24.5 19.0 19.6 21.2 22.7
22.2
16 11 21 19 16 11 19 18 15 10
19
2.03 2.09 2.01 2.05 2.11 2.18 2.07 2.12 2.18 2.25
1.97
223 232 221 237 251 261 244 262 277 289
211
86 92 78 83 90 96 81 86 94 100
79
0.59 0.38 0.90 0.80 0.61 0.39 0.91 0.81 0.61 0.40
0.78
16 11 21 20 16 11 20 18 15 10
20
11.8 12.1 11.8 12.0 12.3 12.6 12.3 12.5 12.7 13.0
11.6
218 228 216 233 246 256 239 257 271 283
207
85 90 76 81 89 94 79 84 92 98
77
65 75 85 95 105 115
MODEL: GSH140241A* / CA*F3636B6A* +TXV / MBR800**1 Design Subcooling 9 ±3 °F @ the liquid service valve, ARI 95 test conditions
MBh 23.2 24.0 26.3 - 22.6 23.5 25.7 - 22.1 22.9 25.1 - 21.6 22.3 24.5 - 20.5 21.2 23.3 - 19.0 19.7 21.5 -
IDB*Airflow 596367715963677159636771596367715963677159636771
S/T 0.76 0.63 0.44 - 0.79 0.66 0.45 - 0.81 0.67 0.47 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.87 0.73 0.50 -
HI PR 134 145 153 - 151 162 171 - 172 185 195 - 195 210 222 - 220 237 250 - 243 261 276 -
AMPS 10.1 10.2 10.4 - 10.5 10.7 10.9 - 11.1 11.2 11.4 - 11.5 11.7 11.9 - 11.9 12.1 12.4 - 12.4 12.6 12.8 -
Delta T 17 15 11 - 17 15 11 - 17 1 5 11 - 17 15 11 - 17 15 11 - 16 14 10 -
950 KW 1.62 1.65 1.70 - 1.73 1.77 1.82 - 1.84 1.87 1.93 - 1.93 1.97 2.03 - 2.00 2.04 2.11 - 2.07 2.11 2.18 -
S/T 0.73 0.61 0.42 - 0.75 0.63 0.44 - 0.77 0.64 0.45 - 0.80 0.66 0.46 - 0.83 0.69 0.48 - 0.83 0.70 0.48 -
MBh 22.8 23.7 25.9 - 22.3 23.1 25.3 - 21.8 22.6 24.7 - 21.2 22.0 24.1 - 20.2 20.9 22.9 - 18.7 19.4 21.2 -
LO PR 64 68 75 - 68 72 79 - 71 75 82 - 74 79 86 - 78 83 90 - 80 85 9 3 -
HI PR 134 144 152 - 150 161 170 - 170 183 194 - 194 209 221 - 218 235 248 - 241 260 274 -
AMPS 10.1 10.2 10.4 - 10.5 10.6 10.8 - 11.0 11.2 11.4 - 11.5 11.6 11.9 - 11.9 12.1 12.3 - 12.3 12.5 12.8 -
Delta T 18 16 12 - 18 16 12 - 18 1 6 12 - 18 16 12 - 18 16 12 - 17 15 11 -
70 850 KW 1.61 1.64 1.69 - 1.73 1.76 1.81 - 1.83 1.86 1.92 - 1.92 1.95 2.01 - 1.99 2.03 2.10 - 2.06 2.10 2.16 -
S/T 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -
MBh 21.7 22.5 24.6 - 21.2 22.0 24.1 - 20.7 21.4 23.5 - 20.2 20.9 22.9 - 19.2 19.9 21.8 - 17.8 18.4 20.2 -
LO PR 64 68 74 - 67 72 78 - 70 75 81 - 74 78 85 - 77 82 90 - 80 85 9 3 -
Delta T 18 16 12 - 19 16 12 - 19 1 6 12 - 19 16 12 - 19 16 12 - 17 15 11 -
HI PR 131 141 149 - 147 158 167 - 167 180 190 - 190 205 216 - 214 230 243 - 236 254 269 -
AMPS 10.0 10.1 10.3 - 10.4 10.5 10.7 - 10.9 11.1 11.3 - 11.3 11.5 11.7 - 11.8 11.9 12.2 - 12.2 12.4 12.6 -
LO PR 63 67 73 - 66 70 77 - 69 73 80 - 72 77 84 - 76 80 88 - 78 83 9 1 -
750 KW 1.59 1.62 1.67 - 1.70 1.73 1.79 - 1.80 1.84 1.89 - 1.89 1.92 1.98 - 1.96 2.00 2.06 - 2.02 2.07 2.13 -
S/T 0.860.770.580.380.890.800.600.390.920.820.620.400.94
MBh 23.6 24.3 26.3 28.2 23.0 23.7 25.7 27.5 22.5 23.1 25.0 26.9 21.9
Delta T2018151020181510201815 102018 15 10 20 18 15 10 18 17 14 10
950 KW 1.631.661.711.761.751.781.841.891.851.891.952.011.94
HI PR 136 146 154 161 152 164 173 181 173 187 197 205 197 212 224 234 222 239 252 263 245 264 279 291
AMPS 10.2 10.3 10.5 10.7 10.6 10.7 10.9 11.2 11.1 11.3 11.5 11.8 11.6
LO PR 65 69 75 80 69 73 80 85 71 76 83 88 75
S/T 0.820.740.560.360.850.760.580.370.880.780.590.380.900.81 0.61 0.39 0.94 0.84 0.64 0.41 0.95 0.85 0.64 0.41
MBh 23.2 23.9 25.9 27.8 22.7 23.4 25.3 27.1 22.1 22.8 24.7 26.5 21.6
Delta T2119161121191611211916 1121
75 850 KW 1.621.661.701.751.741.771.831.881.841.881.942.001.93
HI PR 135 145 153 160 151 163 172 179 172 185 196 204 196
AMPS 10.1 10.2 10.4 10.6 10.6 10.7 10.9 11.1 11.1 11.2 11.5 11.7 11.5 11.7 11.9 12.2 12.0 12.2 12.4 12.7 12.4 12.6 12.9 13.2
LO PR 64 69 75 80 68 72 79 84 71 75 82 88 74
S/T 0.790.710.530.340.820.730.550.360.840.750.570.370.87
MBh 22.1 22.7 24.6 26.4 21.5 22.2 24.0 25.8 21.0 21.7 23.4 25.2 20.5 21.1 22.9 24.5 19.5 20.1 21.7 23.3 18.1 18.6 20.1 21.6
Delta T2120161122201611222016 1122
750 KW 1.601.631.681.731.711.751.801.851.811.851.911.961.901.94 2.00 2.06 1.98 2.02 2.08 2.14 2.04 2.08 2.15 2.22
HI PR 132 142 150 157 148 160 169 176 169 182 192 200 192
AMPS 10.0 10.1 10.3 10.5 10.5 10.6 10.8 11.0 11.0 11.1 11.3 11.6 11.4
LO PR 63 67 73 78 67 71 77 83 69 74 81 86 73
Shaded area is ACCA (TVA) condit ions IDB: Enteri ng Indoo r Dry Bulb Tem per ature KW=Total system power AMPS=out door uni t am p s (c omp.+fan)
8