•Refer to Service Manual RS6300008 for installation, operation, and troubleshooting information.
•All safety information must be followed as provided in the Service Manual.
•Refer to the appropriate Parts Catalog for part number information.
•Models listed on page 3.
•Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and
Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult
a tax professional if they have questions about the applicability of these credits.
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury due to improper
service procedures or services performed by an unqualified person.
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please
use these numbers when requesting service or parts information.
GPC1524M41 * *
BRAND:
G: Goodman
Bra nd or
Distinctions
Cooling/Heating
®
PRODUCT
TYPE:
Package
15 : 15 SE E R
PRODUCT
FAMILY:
C: Cooling
H: Heat P um p
PRODUCT
SERIES:
Ra ting
NOMINAL
CAPACITY:
24: 24,000 B TUH
30: 30,000 B TUH
36: 36,000 B TUH
42: 42,000 B TUH
48: 48,000 B TUH
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.
2
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
WARNING
HIGH VOLTAGE!
WARNING
WARNING
individuals meeting the requirements of an "entry level
technician" as specified by the Air-Conditioning, Heating,
and Refrigeration Institute (AHRI). Attempting to install
or repair this unit without such background may result
in product damage, personal injury or death.
Installation and repair of this unit
should be performed
ONLY by
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please
use these numbers when requesting service or parts information.
Models qualify for the 2009 and 2010 Federal Tax Credits
for Energy Efficiency**
**Note that these tax credits are subject to specific requirements set forth in the American
Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman
recommends that consumers consult a tax professional if they have questions about the
applicability of these credits.
WARNING
WARNING
WARNING
WARNING
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by
Goodman for use with this unit.
WARNING
WARNING
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
To prevent the risk of property
damage, personal injury, or death,
3
PRODUCT DESIGN
GPC Package Cooling Units are designed for outdoor installations only in either residential or light commercial applications and are available in 2, 2-1/2, 3, 3-1/2 and 4 ton sizes.
They are designed for 208/230 volt single phase applications.
The connecting ductwork (Supply and Return) can be connected for either horizontal or vertical airflow. In the vertical
application, a matching Roof Curb is recommended and a
horizontal duct cover kit is required.
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible location within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Section. Under no circumstances should the unit be operated
without return air filters.
A 3/4” PVC pipe is provided for removal of condensate water
from the indoor coil In order to provide proper condensate
flow, a drain trap is supplied and shipped loose inside the
unit for field installation. (Do not reduce the drain line size.)
Refrigerant flow control is achieved by use of restrictor orifices. GPC units use the FasTest Access Fitting System
with a saddle that is either soldered to the suction and liquid
lines or is fastened with a locking nut to the access fitting
box (core) and then screwed into the saddle. Do not re-
move the core from the saddle until the refrigerant
charge has been removed. Failure to do so could result in property damage or personal injury.
The single phase units use permanent split capacitor (PSC)
design compressors. Starting components are therefore not
required for these units. A low microfarad run capacitor assists the compressor to start and remains in the circuit during operation.
The outdoor fan motors are single phase capacitor type motors. GPC1524-48M41* units have X-13 indoor blower motors that are energized by a 24V signal from the thermostat
and are constant torque motors with very low power consumption. The X-13 features an integral control module.
Air for condensing (cooling cycle) is drawn through the outdoor coil by a propeller fan, and is discharged vertically out
the top of the unit. The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.
Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.
GPC15 models use Copeland Scroll Compressors. There
are a number of design characteristics which are different
from the traditional reciprocating compressor.
-Due to their design Scroll Compressors are inherently
more tolerant of liquid refrigerant. NOTE: Even though the
compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued floodback or flooded
start conditions may wash oil from the bearing surfaces
causing premature bearing failure.
-Scroll Compressors use white oil which is compatible
with 3GS oil which may be used if additional oil is required.
-Operating pressures and amp draws may differ from standard reciprocating compressors. This information may be
found in the "Cooling Performance Data" section.
Location and Clearances
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
48" MIN
12" MIN
36" MIN
(FOR
SERVICE)
.
12" MIN
3"
MIN
36" MIN
(FOR SERVICE)
Outside Slab Installation - Multi-positional (M)
NOTE: Roof overhang should be no more than 36" and
provisions made to deflect the warm discharge air out from the
overhang.
Minimum clearances are required to avoid air recirculation and
keep the unit operating at peak efficiency.
4
PRODUCT DESIGN
Roof Curb
Rooftop Installation - Multi-positional (M)
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: Roof Top installations), the installer must provide service platform for service person with rails or guards in accordance with local codes
or ordinances or in their absence with the latest edition of the
Uniform Mechanical Code Section 305.
NOTE: Unit can also use roof curb (and platform for leveling,
where necessary) to utilize bottom discharge.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION
DURING ALL RIGGING AND MOVING OPERATIONS.
TO FACILITATE LIFTING AND MOVING IF A CRANE
IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE
SLING.
IMPORTANT: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing
the unit.
Refer to Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with
the National Roofing Contractors Association Manual.
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
Heating kW Correction Factor
Supply Votage
Correction Factor
Multiply rated kW by correction factor to get actual kW
All wires and overcurrent protection devices are sized for use with electric heaters only and without
WARNING
WARNING
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
240230220210208
1.00.930.850.780.76
6
PRODUCT DIMENSIONS
GPC15[24-48]M41*
SUCTION/LIQUID
PRESSURE PORT
CONDENSATE
DRAIN
CONNECTION
3/4” NPT FEMALE
47
18 7/8
POWER
WIRE
ENTRANCE
4 1/8
2 1/8
6 ½
8
?
B
3
CONTROL
WIRE
ENTRANCE
1 3/8
51
?
16
5 ½
16
A
B
2 34
SUPPLY
RETURN
MEDIUM CHASSIS
GPC1524M41*
GPC1530M41*
GPC1536M41*
LARGE CHASSIS
GPC1542M41*
GPC1548M41*
BLOWER
ACCESS PANEL
7
PACKAGE COOLING SPECIFICATIONS
GPC15[24-48]M41A*
COOLING
CAPACITY
UNIT
ELECTRICAL
SPECIFICATION
COMPRESSOR
CONDENS E R
FAN MOTOR
CONDENS E R
FAN
CONDENS E R
COIL
EVAPORATOR
BLOWER
MOTOR
EVAPORATOR
BLOWER
EVAPORATOR
COIL
GENE RAL
INFORM ATION
COOLING CAPACITY, BTUH24,00028,00035,00040,00045,500
SEER / EER14.5 / 12. 014.5 / 12. 014.5 / 12. 014.5 / 12. 015.0 / 12.0
VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
AMPS15.817.520.122.224.2
MIN CIRCUIT AMP ACITY19.021.024.226.729.2
MAX OVERCURRENT PROTECTION3035404045
TYPESCROLLSCROLLSCROLLSCROLLSCROLL
RATED LOAD AMPS12.814.116.717.919.9
LOCKED ROTOR AMPS58.373.079.0112.0109.0
HORSEPOWER1/61/41/41/41/4
RPM81583783710751075
FULL LOAD AMPS1.11.51.51.41.4
LOCKED R OTOR AMPS1.73.03.02.92.9
BLADE DIAMETER (I NCHES)2222222222
NUMBER OF BLADES33333
FACE ARE A (SQ. F T.)12.3312.3312.3315.3815.38
NUMBER OF ROWS122 2 2
FINS PER INCH2416161616
HORSE PO WER - N O. O F S P EEDS1/2 - 51/2 - 51/2 - 53/4 - 53/4 - 5
FULL LOAD AMPS1.91.91.92.92.9
LOCKED ROTOR AMPS--------------MOTOR SPE ED TAP-COOLING X-13T2T2T2T2T2
RPM1,0501,0501,0501,0501,050
DIAMETER X WIDTH (INCHES)10 x 910 x 910 x 910 x 910 x 9
RATED SCFM COOLING8501,0501,1501,3501,350
MAX EXTERNAL STATIC PRESS ("w.c.)0.50.50.50.50.5
FACE AREA (SQ. FT.)4.524.524.526.176.17
NUMBER OF ROWS334 4 4
FINS PER INCH1616141414
FILTER SIZE *25 x 25 x 125 x 25 x 125 x 25 x 1(2) 20 x 20 x 1(2) 20 x 20 x 1
DRAIN SIZE (INCHES)3 /4"3/4"3/4"3/4"3/4"
EXPANSION DEVICE0.0570.0650.0680.0720.076
REFRIGERANT CHARGE R410A (OZS.)80100115140170
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
All wires and overcurrent protection devices are sized for use with electric heaters only and without
WARNING
WARNING
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.