•Refer to Service Manual RS6300008 for installation, operation, and troubleshooting information.
•All safety information must be followed as provided in the Service Manual.
•Refer to the appropriate Parts Catalog for part number information.
•Models listed on page 3.
•Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and
Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult
a tax professional if they have questions about the applicability of these credits.
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury due to improper
service procedures or services performed by an unqualified person.
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please
use these numbers when requesting service or parts information.
GPC1524M41 * *
BRAND:
G: Goodman
Bra nd or
Distinctions
Cooling/Heating
®
PRODUCT
TYPE:
Package
15 : 15 SE E R
PRODUCT
FAMILY:
C: Cooling
H: Heat P um p
PRODUCT
SERIES:
Ra ting
NOMINAL
CAPACITY:
24: 24,000 B TUH
30: 30,000 B TUH
36: 36,000 B TUH
42: 42,000 B TUH
48: 48,000 B TUH
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.
2
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
WARNING
HIGH VOLTAGE!
WARNING
WARNING
individuals meeting the requirements of an "entry level
technician" as specified by the Air-Conditioning, Heating,
and Refrigeration Institute (AHRI). Attempting to install
or repair this unit without such background may result
in product damage, personal injury or death.
Installation and repair of this unit
should be performed
ONLY by
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please
use these numbers when requesting service or parts information.
Models qualify for the 2009 and 2010 Federal Tax Credits
for Energy Efficiency**
**Note that these tax credits are subject to specific requirements set forth in the American
Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman
recommends that consumers consult a tax professional if they have questions about the
applicability of these credits.
WARNING
WARNING
WARNING
WARNING
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by
Goodman for use with this unit.
WARNING
WARNING
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
To prevent the risk of property
damage, personal injury, or death,
3
PRODUCT DESIGN
GPC Package Cooling Units are designed for outdoor installations only in either residential or light commercial applications and are available in 2, 2-1/2, 3, 3-1/2 and 4 ton sizes.
They are designed for 208/230 volt single phase applications.
The connecting ductwork (Supply and Return) can be connected for either horizontal or vertical airflow. In the vertical
application, a matching Roof Curb is recommended and a
horizontal duct cover kit is required.
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible location within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Section. Under no circumstances should the unit be operated
without return air filters.
A 3/4” PVC pipe is provided for removal of condensate water
from the indoor coil In order to provide proper condensate
flow, a drain trap is supplied and shipped loose inside the
unit for field installation. (Do not reduce the drain line size.)
Refrigerant flow control is achieved by use of restrictor orifices. GPC units use the FasTest Access Fitting System
with a saddle that is either soldered to the suction and liquid
lines or is fastened with a locking nut to the access fitting
box (core) and then screwed into the saddle. Do not re-
move the core from the saddle until the refrigerant
charge has been removed. Failure to do so could result in property damage or personal injury.
The single phase units use permanent split capacitor (PSC)
design compressors. Starting components are therefore not
required for these units. A low microfarad run capacitor assists the compressor to start and remains in the circuit during operation.
The outdoor fan motors are single phase capacitor type motors. GPC1524-48M41* units have X-13 indoor blower motors that are energized by a 24V signal from the thermostat
and are constant torque motors with very low power consumption. The X-13 features an integral control module.
Air for condensing (cooling cycle) is drawn through the outdoor coil by a propeller fan, and is discharged vertically out
the top of the unit. The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.
Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.
GPC15 models use Copeland Scroll Compressors. There
are a number of design characteristics which are different
from the traditional reciprocating compressor.
-Due to their design Scroll Compressors are inherently
more tolerant of liquid refrigerant. NOTE: Even though the
compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued floodback or flooded
start conditions may wash oil from the bearing surfaces
causing premature bearing failure.
-Scroll Compressors use white oil which is compatible
with 3GS oil which may be used if additional oil is required.
-Operating pressures and amp draws may differ from standard reciprocating compressors. This information may be
found in the "Cooling Performance Data" section.
Location and Clearances
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
48" MIN
12" MIN
36" MIN
(FOR
SERVICE)
.
12" MIN
3"
MIN
36" MIN
(FOR SERVICE)
Outside Slab Installation - Multi-positional (M)
NOTE: Roof overhang should be no more than 36" and
provisions made to deflect the warm discharge air out from the
overhang.
Minimum clearances are required to avoid air recirculation and
keep the unit operating at peak efficiency.
4
PRODUCT DESIGN
Roof Curb
Rooftop Installation - Multi-positional (M)
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: Roof Top installations), the installer must provide service platform for service person with rails or guards in accordance with local codes
or ordinances or in their absence with the latest edition of the
Uniform Mechanical Code Section 305.
NOTE: Unit can also use roof curb (and platform for leveling,
where necessary) to utilize bottom discharge.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION
DURING ALL RIGGING AND MOVING OPERATIONS.
TO FACILITATE LIFTING AND MOVING IF A CRANE
IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE
SLING.
IMPORTANT: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing
the unit.
Refer to Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with
the National Roofing Contractors Association Manual.
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
Heating kW Correction Factor
Supply Votage
Correction Factor
Multiply rated kW by correction factor to get actual kW
All wires and overcurrent protection devices are sized for use with electric heaters only and without
WARNING
WARNING
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
240230220210208
1.00.930.850.780.76
6
PRODUCT DIMENSIONS
GPC15[24-48]M41*
SUCTION/LIQUID
PRESSURE PORT
CONDENSATE
DRAIN
CONNECTION
3/4” NPT FEMALE
47
18 7/8
POWER
WIRE
ENTRANCE
4 1/8
2 1/8
6 ½
8
?
B
3
CONTROL
WIRE
ENTRANCE
1 3/8
51
?
16
5 ½
16
A
B
2 34
SUPPLY
RETURN
MEDIUM CHASSIS
GPC1524M41*
GPC1530M41*
GPC1536M41*
LARGE CHASSIS
GPC1542M41*
GPC1548M41*
BLOWER
ACCESS PANEL
7
PACKAGE COOLING SPECIFICATIONS
GPC15[24-48]M41A*
COOLING
CAPACITY
UNIT
ELECTRICAL
SPECIFICATION
COMPRESSOR
CONDENS E R
FAN MOTOR
CONDENS E R
FAN
CONDENS E R
COIL
EVAPORATOR
BLOWER
MOTOR
EVAPORATOR
BLOWER
EVAPORATOR
COIL
GENE RAL
INFORM ATION
COOLING CAPACITY, BTUH24,00028,00035,00040,00045,500
SEER / EER14.5 / 12. 014.5 / 12. 014.5 / 12. 014.5 / 12. 015.0 / 12.0
VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
AMPS15.817.520.122.224.2
MIN CIRCUIT AMP ACITY19.021.024.226.729.2
MAX OVERCURRENT PROTECTION3035404045
TYPESCROLLSCROLLSCROLLSCROLLSCROLL
RATED LOAD AMPS12.814.116.717.919.9
LOCKED ROTOR AMPS58.373.079.0112.0109.0
HORSEPOWER1/61/41/41/41/4
RPM81583783710751075
FULL LOAD AMPS1.11.51.51.41.4
LOCKED R OTOR AMPS1.73.03.02.92.9
BLADE DIAMETER (I NCHES)2222222222
NUMBER OF BLADES33333
FACE ARE A (SQ. F T.)12.3312.3312.3315.3815.38
NUMBER OF ROWS122 2 2
FINS PER INCH2416161616
HORSE PO WER - N O. O F S P EEDS1/2 - 51/2 - 51/2 - 53/4 - 53/4 - 5
FULL LOAD AMPS1.91.91.92.92.9
LOCKED ROTOR AMPS--------------MOTOR SPE ED TAP-COOLING X-13T2T2T2T2T2
RPM1,0501,0501,0501,0501,050
DIAMETER X WIDTH (INCHES)10 x 910 x 910 x 910 x 910 x 9
RATED SCFM COOLING8501,0501,1501,3501,350
MAX EXTERNAL STATIC PRESS ("w.c.)0.50.50.50.50.5
FACE AREA (SQ. FT.)4.524.524.526.176.17
NUMBER OF ROWS334 4 4
FINS PER INCH1616141414
FILTER SIZE *25 x 25 x 125 x 25 x 125 x 25 x 1(2) 20 x 20 x 1(2) 20 x 20 x 1
DRAIN SIZE (INCHES)3 /4"3/4"3/4"3/4"3/4"
EXPANSION DEVICE0.0570.0650.0680.0720.076
REFRIGERANT CHARGE R410A (OZS.)80100115140170
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
All wires and overcurrent protection devices are sized for use with electric heaters only and without
WARNING
WARNING
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
8
ACCESSORIES
ACCESSOR IE S - GP C/GPH* *** M M ODE LS
Part Num b e rD es c ri pt i o n
OT18-60AOutdoor Thermostat Kit w/Lockout Stat
OT/EHR18-60Emergency Heat Relay Kit
HKRElectric Heat Kit
PGC101/102/103Roof Curb
PEHH101/102Horizontal Economizer For Heat Pump, Small and Medium Chassis
PEHH103Horizontal Economizer For Heat Pump, Large Chassis
PEHC101/102Horizontal Economizer For A/C, Small and Medium Chassis
PEHC103Horizontal Economizer For A/C, Large Chassis
PGMDD101/102Manual 25% Fresh Air Damper Downflow Application, Small and Medium Chassis
PGMDD103Manual 25% F resh Air Damper Downflow Application, Large Chassis
PGMDH102Manual 25% F resh Air Damper Horizontal Application, Medium Chassis
PGMDH103Manual 25% F resh Air Damper Horizontal Application, Large Chassis
PGMDMD101/102Motorized 25% Fresh Air Damper Downflow Application,Small and Medium Chassis
PGMDMD103Motorized 25% Fresh Air Downflow Application, Large Chassis
PGMDMH102Motorized 25% Fresh Air Damper Horizontal Application, Medium Chassis
PGMDMH103Motorized 25% Fresh Air Damper Horizontal Application, Large Chassis
GPC13MED102Downflow Economizer For A/C, Medium Chassis
GPC13MED103Downflow Economizer For A/C, Large Chassis
GPH13MED102Downflow Economizer For Heat Pump, Medium Chassis
GPH13MED103Downflow Economizer For Heat Pump, Large Chas sis
GPH13MFR102Internal Filter Rack, Medium Chassis
GPH13MFR103Internal Filter Rack, Large Chassis
GPGHFR101-103External Horizontal Filter Rack for Goodman/Amana Gas/Electric and Multi-position Package Units All Chassis
SQRPG101/102Square to Round Adapter w/ 16" Round Dow nflow Application, Medium Chassis
SQRPG103Square to Round Adapter w/ 18" R ound Downflow Application, Large Chassis
SQRPGH101/102Square to Round Adapter w/ 16" Round Horizontal Application, Medium Chassis
SQRPGH103Square to Round Adapter w/ 18" Round Horizontal Application, Large Chassis
CDK36Flush Mount Concentric Duct Kit
CDK36515Flush Mount Concentric Duct Kit w/ Filter
CDK36530Step Down Concentric Duct Kit
CDK36535Step Down Concentric Duct Kit w/ Filter
CDK4872Flush Mount Concentric Duct Kit
CDK4872515Flush Mount Concentr ic Duct Kit w/ Filter
CDK4872530Step Down Concentric Duct Kit
CDK4872535Step Down Concentric Duct Kit w/ Filter
9
BLOWER PERFORMANCE DATA
Dry Coil Data
GPC15[24-48]M41A*
ModelSpeedVolts
T1 (G)
T2 / T3
GPC 1524M41*
T4 / T5
T1 (G)230
T2 / T3230
GPC1530M41*
T4 / T5230
T1 (G)
T2 / T3
230
230
230
230
230
E. S.P ( In . of H
0.10.20.30.40.50.60.70.8
CFM882808727649545---------
WATTS828692102108---------
CFM933873810733637584------
WATTS93103109120126135------
CFM10581012945896816723672---
WATTS124136142153168172179---
CFM893824752665575---------
WATTS8795101111115---------
CFM113210701011959889827733669
WATTS153162168179184195206208
CFM128712361165112310661012958857
WATTS211217228239244255265272
CFM852764711592545---------
WATTS8082859599---------
CFM12321190113110821023966889819
WATTS202214221229235246258264
O)
2
GPC 1536M41*
T4 / T5
T1 (G)230
T2 / T3230
GPC1542M41*
T4 / T5230
T1 (G)
T2 / T3
GPC 1548M41*
T4 / T5
NOTES:
• Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 0.1" H2O, for 2 row indoor coil; 0.2” H2O, for 3 row indoor coil;
and 0.3” H2O, for 4 row indoor coil.
• Data shown does not include filter pressure drop, approx. 0.08” H2O.
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON.
• Reduce airflow by 2% for 208V operation.
230
230
230
230
CFM126712131162112010581009932841
WATTS218226236245247260272275
CFM112310701025984942894839774
Watts162170182193204216229242
CFM14371390135413181281124312041165
Watts310317331342355366377389
CFM15281490145014101383134813121267
Watts372379391403416427439451
CFM1199113810851017957889820755
WATTS162173185193211219232245
CFM17991745169816581610156015221450
WATTS480493508521531545550547
CFM19211865181817801719166715791483
WATTS582585602625627621595569
10
BLOWER PERFORMANCE DATA
÷ CFM
130140150
FORMULAS
BTU OUTPUT = CFM x 1.08 x RISE
1.08
BTU OUTPUT
RISE =
100
2400 CFM
2200
2000
1800
1600
1400
1200
1100
1000
900
800
OUTPUT BTU/HR x 1000
BTU OUTPUT vs TEMPERATURE RISE CHART
700
600 CFM
30405060708090110120
100
90
80
70
60
50
40
30
20
10
TEMPERATURE RISE
11
COOLING PERFORMANCE DA TA
C OOLING OPERATION
GPC1524M41*
EXPANDED PERFORMANCE DATA
15102018151018171410
9.69.99.69.810.1 10.510.1 10.410.7 11.0
415433411442467487454489516538
25.627.4 21.8 22.424.326.1 20.2 20.822.5 24.1
0.610.39 0.94 0.840.630.41 0.95 0.850.64 0.41
18
23.6
0.81
Outdoor Ambient Temperature
Entering Indoor Wet Bulb Temperature
147157133141154164138146160170
2.072.15 2.03 2.092.172.26 2.12 2.182.27 2.36
9.3
393
135
1.99
16112019151119181410
9.59.89.59.710.0 10.410.0 10.310.6 10.9
24.826.6 21.2 21.823.625.3 19.6 20.221.8 23.4
0.580.38 0.89 0.800.610.39 0.90 0.810.61 0.39
22.9
0.77
411429407438463482450484511533
2.042.13 2.01 2.072.152.24 2.10 2.162.24 2.33
19
9.2
389
1.97
16112119161119181510
146155132140153163136145158168
22.924.6 19.5 20.121.823.4 18.1 18.620.2 21.6
134
21.2
9.39.69.39.59.810.19.810.010.3 10.7
399416395425449468436470496517
0.560.36 0.86 0.770.580.38 0.87 0.780.59 0.38
19
0.74
142151128136148158132141153163
1.982.06 1.95 2.002.092.17 2.04 2.092.17 2.26
9.0
378
130
1.91
12
65758595105115
MODE L: GPC 1524M41
Design Subcooling, 7 °F @ the liquid access fitt ing connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suct ion access fitting co n nec t ion .
HI PR24626 52 802922762973143283 1433835737335838 5407424403434458477445479506528
LO PR108115125133114121132141118126137146124132144154130139151161135143157167
MODE L: GPC1524M41
Desi gn Subcooling, 7 °F @ the liquid a ccess fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compre ssor sucti on access f ittin g connect ion.
HI PR22924726127225727729330529331533334 7333359379395375404426445415446471491
LO PR107114124132113120131139117125136145123131143152129137150160133142155165
MODE L: GPC1530M41
Desi gn Subcooling, 7 °F @ the liquid a ccess fitting connection AHRI 95 t est conditi ons. Design Superheat 5°F @ the compressor suction access fitting connec tion.
Desi gn Sub cool ing, 7 °F @ the liquid access fitting connection AHRI 95 test co nditions. Desig n Superheat 5°F @ the compressor suction access fit t ing connec tion.
HI PR23425 22 662782632832993122 9932234035534136 7387404383413436454424456481502
LO PR108115126134114122133141119126138147125133145154131139152162135144157167
MODE L: GPC1536M41
Desi gn Subcooling, 7 °F @ the liquid a ccess fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compre ssor sucti on access f ittin g connect ion.
Desi gn Sub cool ing, 7 °F @ the liquid access fitting connection AHRI 95 test co nditions. Desig n Superheat 5°F @ the compressor suction access fit t ing connec tion.
HI PR2352522672782632832993 1229932234035534136738740438441343645542445648250 2
LO PR108115125133114121132141118126138146124132144154130139151161135143157167
MODEL: GPC1548M41
Des ign Subc ooling, 7 °F @ the liquid access fitting connectio n AHRI 95 test conditions . D esign Superheat 5°F @ the comp ress or suction access fitting connection.
* Entering Ind oor Dry Bulb TemperatureNOTE: Shad ed area is AHRI Rating ConditionsKW = Total system power
High and low pressures are mea sured at the li quid and su c ti on acc ess fitti ngs .AMPS: Uni t amps (co mp.+ ev aporator + co ndens er fan mot o r s)
21
COOLING PERFORMANCE DA TA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
22
WIRING DIAGRAMS
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
HKR***
BK
BK
M2
BK
M1
BK
BK
BK
BK
BK
M1M2M3
M4
BK
BK
BK
BK
BK
BK
M1
M2
BK
M3
M4
M2
M1
BK
BK
BK
M1
M2
BK
M3
M4
M5
M6
M7
M8
BK
BK
BK
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
23
WIRING DIAGRAMS
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
-
2
8
0
2
GPC15[24-48]M41*
/
/
1
0
4
60
E
T
R
H
M
A
T
T
S
O
Y
R
GND
SEE NOTE 5
BR
YL
GR
RD
WH
PLF
BL
BK
PU
BL
PU
NOTE #3
3
240
BK
PU
TR
2
208
C
1
BL
L2
T2
RD
L1
C
YL
T1
BK
RD
BK
RD
24V
BL
RD
RD
GR
LVJB
RD
YL
G
GR
W1
WH
9
6
3
F
C
H
W2
BR
BR
8
5
2
RCCF
C
BL
RDYL
++
BK
BR
PU
7
41
SA (IF USED)
SEE NOTE 4
BL/PNK
RD
CONTROL
BL/PNK
BK
BOX
BK
BR
PU
YL
HPS
CR
S
208- 240/1/60 0140G0107 7 REV A
COMP
CM
WH
GR
YL
PU
BK
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
BL
GR
GR
L G N12 3
C
EM
4 5
SEE NOTE 2
24
WIRING DIAGRAMS
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
GPC15[24-48]M41*
FACTORY WIRING
LINE VOLTAGE
CONTACTOR
COMPONENT LEGEND
CCMCOMPEMGND
L2
FIELD WI RING
LOW VOLTAGE
OPTIONAL HIGH
CONDENSER MOT OR
COMPRESSOR
HIGH VOLTAGE
VOLTAGE
EV APO RATOR MOTOR
LOW VOLTAGE
WIRE CODE
BK BLACK
BL BLUE
BR BROWN
GR GREEN
OR ORANGE
PU PURPLE
RD RED
WH WHITE
YL YELLOW
BL/PNK BLUE/PINK STRIPE
EQUIPMENT GROUND
LOW VOLTAGE JUNCTION BOX
FEMALE PLUG / CO NNECTOR
RUN CAPACITOR FOR
COMPRESSOR A ND FA N
LVJB
PLF
RCCF SA
HIGH PRESSURE SWITCH
STA RT A SSIST
TRANSFORMER
TR HPS
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM
TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. STAR T ASSIST FA C TO R EQ UIP PED WH EN REQ UIRED .
5. USE COPPER CONDUCTORS ONLY.
LEADS FROM EM"2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE
ENERGIZED, THE HIGHER SPEED SETTING IS USED.
SEE NOTE #2
++ USE N.E.C. CLASS 2 WIRE
C
OF OVER CURRENT PROTECTION
SEE UNIT RATING PLATE FOR TYPE AND SIZE
208-240/1/60 0140G01077 REV A
C
CM
C
C
T2
208-240/1/60
SUPPLY VOLTAGE
L1
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
R
F
RCCF
NOTE #4
H
S
COMP
S.A.
C
T1
C
L
2
3
IF USED
NOTE #2
EM
N
G
1
TR
2
208-240
31
NOTE #3
24V
3
EM
2
1
456
HPS
W1 Y G C
THERMOSTAT
R W2